This is a Scope of Work outline for Halifax Health, a healthcare facility located in Orange City, Florida, detailing the replacement of a 25-ton air handling unit (AHU) at Halifax Health West Volusia Care Center. The project requires a turnkey, all-inclusive proposal for the complete removal and disposal of the existing unit and installation of a like-for-like replacement system. The scope includes demolition, rigging, installation, commissioning, and startup of the new unit, with acceptable manufacturers being York (basis of design Model XTI-60x72) or Trane. Additional work encompasses replacement of the electric duct heater and thermostats, necessary duct modifications, test and balance services (pre and post), crane and rigging services, and all associated electrical, plumbing, and low voltage work. The new system must utilize R454b refrigerant and include temporary cooling solutions during installation.

The project is located at Halifax Health Hospice Care Center, 1625 Veterans Memorial Parkway, Orange City, Florida 32763, and requires strict infection control measures as it is an active healthcare environment. All contractors must pass background checks and be badged prior to site access. The scope includes reuse of existing electrical disconnects if functional, outdoor air louvers, and duct smoke detectors, while requiring removal and replacement of existing refrigerant piping, condensing units, filter driers, and the air handling unit itself. Cleanliness standards are emphasized as imperative given the healthcare setting. The project timeline indicates an anticipated scope completion date of April 8, 2026, though no specific bid due date, award date, or contract term information is provided in this outline document.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WVCC AHU Replacement

Outline of Scope of work:

4/8/2026

The intent of this project is to replace a 25-ton air handling unit at Halifax Health West Volusia

Care Center for a like-for-like system.

Contractor shall provide a turnkey all-inclusive proposal/bid not limited to the following:

Complete demo and disposal of existing unit, installation, rigging, commissioning and startup of new replacement unit, any necessary accessories, replacement of electric duct heater, replacement of thermostats, necessary duct modifications, ICRA, controls associated plumbing, electrical, and low voltage work for new equipment fit and function, patch and paint etc.

Contractor must include:

- Removal and disposal of existing

- Like for like 25-ton AHU system (York or Trane accepted alternatives) o Basis of Design:

York AHU – Model #: XTI-60x72

JCI OD Split System- Model #: KC300C00A2GEE1

*Aluminum fin, copper tubing, stainless steel drain pan

- Electric Duct Heaters

- Thermostats

- Test and Balance (Pre and Post)

- System Start up

- Crane, Hoist and Rigging

- Refrigerant: R454b

- Spot coolers/ Temporary Air

See attached reference schematic and reference map for additional details

Cleanliness is imperative, and area must be treated with the highest level of infection control as this is an active healthcare environment. All contractors onsite must pass a background check and be badged.

AREA OF WORK

Halifax Health - Hospice Care Center Orange City 1625 Veterans Memorial Pkwy, Orange City, FL 32763

ELECTRICAL

DISCONNECTS, EXISTING

TO REMAIN

ELECTRICAL DISCONNECT, REUSE IF FUNCTIONAL

EXISTING CONDENSING

UNITS TO REMAIN

EXISTING FIRE SERVICE ENTRANCE/RISER

EXISTING REFRIGERANT PIPING (3 PIPES),

REMOVE AND REPLACE WITH NEW

EXISTING DRYWELL

SD

SD

REVISE EXISTING

CONDENSATE PIPING

AS REQUIRED

EXISTING RETURN DUCT

SMOKE DETECTOR TO REMAIN

EXISTING SUPPLY DUCT

SMOKE DETECTOR TO REMAIN

REMOVE EXISTING CONDENSING UNIT, SPRING

ISOLATORS, DISCONNECT AND MAKE SAFE

ELECTRICAL, CONTROLS AND PLUMBING.

INSTALL NEW CONDENSING UNIT ON EXISTING

CONCRETE PAD WITH WAFFLE ISOLATION PADS

REMOVE EXISTING REFRIGERANT FILTER DRIER,

REPLACE IF NEW SYSTEM DESIGN REQUIRES IT

REUSE EXISTING OUTDOOR AIR LOUVER

(42"x56"), BLANK-OFF PLATES, AND MANUAL

OUTDOOR AIR VOLUME DAMPER

REMOVE EXISTING AIR

HANDLING UNT, SPRING

ISOLATORS, DUCT REHEAT

COIL, REFRIGERANT PIPING.

DISCONNECT AND MAKE SAFE

ELECTRICAL AND WIRING.

Halifax Health - Hospice Care Center Orange City 1625 Veterans Memorial Pkwy, Orange City, FL 32763

ELECTRICAL DISCONNECT,

REUSE IF FUNCTIONAL

EXISTING

SUPPLY DUCT

E X

IS

T

IN

G

R E

T U

R N

D U

C T

WVCC AHU Replacement Scope Outline (2)
Halifax 25T AHU - Design Development (3)