These are as-built architectural and engineering drawings for replacing the air conditioning (A/C) system in Building 104 at Fort Buckner, Okinawa, Japan, dated November 18, 2014. The comprehensive set of technical drawings includes detailed plans for electrical, mechanical, and structural systems, specifically focusing on the replacement of the existing HVAC infrastructure. The drawings cover multiple aspects of the project, including floor plans, roof plans, electrical and power system layouts, lighting and grounding system designs, mechanical equipment specifications, and detailed installation instructions for various components such as air handling units, ductwork, electrical panels, and support structures.
The drawings provide intricate technical specifications for the complete A/C system replacement, including equipment schedules, wiring diagrams, conduit and cable routing, transformer and switchgear details, and precise measurements for installation. They document the as-built condition of the facility after the renovation, capturing the exact configuration of the new HVAC system, electrical infrastructure, and associated building modifications. The documents are prepared by AEC-Saber and include detailed technical annotations, legends, and notes to guide installation and understanding of the complex mechanical and electrical systems within Building 104.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
6 A/C-SPLIT TYPE (OUTDOOR EQP#4) 9511 3170
TYPE: SURFACE MTD, BOTTOM FED
BUS SIZE: 800A
LOC: SWITCH GEAR ROOMMIN KAIC:
CKT
NO.
LOAD DESCRIPTION
5 A/C-SPLIT TYPE (OUTDOOR EQP#4) 9511 3170 3170
PANEL "AC"
TOTAL A
SYSTEM: 208/120V
CONNECTED LOAD (VA) CIRCUIT BREAKER
REMARKS
B C P AF AT
1 A/C-SINGLE PACKAGE EQP#1 28496 9499 9499 9499 3 100 100
2 A/C-SINGLE PACKAGE EQP#2 42222 14074 14074 3
15091 3 2253 A/C-CRAC INDOOR UNIT EQP#3A 45273 15091 15091
4 A/C-CRAC OUTDOOR UNIT EQP#3B 1585
14074
4755 1585 30
TOTAL 224355 74785 74785 74785 MAIN : 3P - 800AF -800AT
3 100
3170 3 100 50 3170 3170 3 100 50
7 A/C-SPLIT TYPE (OUTDOOR EQP#4) 9511 3170 3170 3170 3 100 50
8 A/C-SPLIT TYPE (OUTDOOR EQP#4) 9511 3170 3170 3170 3 100 50
9 A/C-SPLIT TYPE (OUTDOOR EQP#4) 9511 3170 3170 3170 3 100 50
10 SPARE 793 264 264 264 3 100 20
11 SPARE 793 264 264 264 3 100 20
12 SPARE 793 264 264 264 3 100 20
13 SPARE 793 264 264 264 3 100 20
14 SPARE 793 264 264 264 3 100 20
15 A/C-SPLIT TYPE (OUTDOOR EQP#5) 7133 2378 2378 2378 3 100 40
16 A/C-SPLIT TYPE (OUTDOOR EQP#5) 7133 2378 2378 2378 3 100 40
17 SPARE 396 132 132 132 3 100 20
18 SPARE 396 132 132 132 3 100 20
19 A/C-SPLIT TYPE (OUTDOOR EQP#7) 2053 684 684 684 3 100 20
20 SPARE 396 132 132 132 3 100 20
21 SPARE 20175 6725 6725 6725 3 100 70
22 SPARE 14409 4803 4803 4803 3 100 50
* PROVIDE NEW CIRCUIT BREAKER
MAIN : 3P-100AF-70ATTOTAL 18863 6533 6165 6165
3 100 20 *
8 SPACE
1 100 20
7 SPLIT A/C UNIT 3099 1033 1033 1033
3 100 20 *
6 EMERGENCY LIGHTING 132 132
1 100 20
5 SPARE 3000 1000 1000 1000
3 100 60
4 WALL VENTILATOR 132 132
1 100 20
3 SPARE 9000 3000 3000 3000
3 100 15
2 LIGHTING 500 500
1 SPARE 3000 1000 1000 1000
TOTAL A B C P AF AT
CKT
NO.
LOAD DESCRIPTION
CONNECTED LOAD (VA) CIRCUIT BREAKER
REMARKS
MODIFIED PANEL "PMA" TYPE: SURFACE MTD, BOTTOM FED
SYSTEM: 208/120V BUS SIZE:
MIN KAIC: 10KAIC LOC: HV SWITCH GEAR ROOM
| 6. As-built drawings-2014_2008_2006_1962 |
| 00_7218_COMBINED |
| 01_AF8-(TO+ACM-1117) TS-1 Model (1) |
| 02_AF8-(TO+ACM-1117) A-1 Model (1) |
| 03_AF8-(TO+ACM-1117) A-2 Model (1) |
| 04_AF8-(TO+ACM-1117) M-1 Model (1) |
| 05_AF8-(TO+ACM-1117) M-2 Model (1) |
| 06_AF8-(TO+ACM-1117) M-3 Model (1) |
| 07_AF8-(TO+ACM-1117) E-1 Model (1) |
| 08_AF8-(TO+ACM-1117) E-2 Model (1) |
| 09_AF8-(TO+ACM-1117) E-3 Model (1) |
| 10_AF8-(TO+ACM-1117) E-4 Model (1) |
| GBS_B104BC_2008 |
| Light_B104BC_2006 |
| Power Building B104_1962_ Ft Buckner |
| B104-1 |
| B104-2 |
| B104-3 |
| B104-4 |
| B104-5 |
| B104-6 |
| B104-7 |
| B104-8 |
| B104-9 |
| B104-10 |
| B104-11 |
Repair and upgrade power system(Civil)
File details come from the government source that posted it. Updated .