This document is a Statement of Work (SOW) for the Fixed CO2 Fire Suppression System Cylinder Hydro-Test / Recharge, Cylinder Valve Rebuild, and High-Pressure Hose Hydro-Test on the USCGC THETIS (WMEC 910) vessel. The SOW requires a Department of Transportation (DOT) approved hydro-static test facility to hydro-test 9 50lb CO2 bottles attached to the vessel's fixed CO2 systems, one-third at a time to maintain operational readiness. The bottles will be refilled and reinstalled with the ship's crew's assistance. Additionally, the hoses attached to the bottles must be hydro-tested and the valve assemblies rebuilt. The work must be performed between August 12-30. The contracting agency is the Department of Homeland Security US Coast Guard. The contracting officer's representative is ENS Robert Stankovich, and the requisitioner/approver is SK1 Elizabeth Haun.

View the file

Other files

File Type Posted
12a_Provisions and Clauses.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK

CGC THETIS (WMEC 910)

Fixed CO2 Fire Suppression System Cylinder Hydro-Test / Recharge, Cylinder Valve Rebuild, and High-Pressure Hose Hydro-Test

FSMS Requisi�on # 11510PR240000412

Descrip�on of Service:

Service must be provided by Department of Transporta�on (DOT) approved hydro-sta�c test facility. Hydro-test 09 50lb CO2 botles atached to the units various fixed CO2 systems. The botles be taken 03 at a �me to ensure that the installed systems remain opera�onal. Post hydro-test, the botles be refilled and returned to the unit with ships force assis�ng in the reinstalla�on. Addi�onally, request that the hoses atached to the botles be hydrotested in addi�on to rebuilding the valve assembly on the botles. Hoses must be renewed or tested at a pressure of 1,000 psi. At test pressure, the pressure must not drop at a rate greater than 150 psi per minute for a 2-minute period.

Period of Performance:

Actual date of service will be arranged by cuters DCA. Preferred POP AUG12-AUG30.

Cuter Homeport Loca�on:

USCGC THETIS (WMEC 910)

100 Trumbo Point Road Key West, FL 33040-6650