11.24.2020 GPPSS-Structured Cabling RFP-App B-Maire.pdf

PDF 819 KB Posted

Attached to
Structured Cabling
Solicitation number
RFP GPPS 210000000334 2
Issued by
Wayne County, Grand Rapids City, Michigan

About this file

This is a design development document prepared by Plante Moran for the Grosse Pointe Public School System's Maire Elementary School renovations project located in Grosse Pointe, Michigan (Project 2019-026). The document contains detailed floor plans for the first, second, and third floors of the facility, dated July 20, 2020, and depicts the planned installation of classroom technology infrastructure including interactive flat panels, wireless access points, audio/visual cabling, audio enhancement speakers, and general data systems throughout the school. The plans identify specific classroom locations and technology placement points across multiple instructional spaces, including standard classrooms, special education rooms, kindergarten classrooms, music rooms, library facilities, and administrative offices. The document indicates the structured cabling work is being pursued through an RFP (Request for Proposals) process, with the project encompassing technology upgrades across all three floors of the elementary school building.

The technical specifications outlined in the document establish requirements for infrastructure installation, including provisions for dedicated equipment racks with specific electrical receptacle configurations (one L5-30R and four 5-20R receptacles per rack at 120V), horizontal and vertical pathway conduits (four 4-inch trade-size conduits for horizontal pathways and riser systems), grounding busbars mounted at six inches above finished floor, and fire-treated plywood backboards measuring three-quarter inch thick and eight feet high. The document specifies environmental control requirements maintaining room temperatures between 64°F and 75°F with relative humidity between 37 and 55 percent non-condensing, with dedicated air conditioning units required. No pricing information, contract award dates, response deadlines, or funding sources are specified in this design development document.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Grosse Pointe Public School System Maire Elementary – Classroom Technology

Prepared by Plante Moran

Legend:

Interactive Flat Panel

General Data

Wireless AP

AV Cabling

Audio Enhancement Speakers

Teacher location T

A

D

W

SCALE: 1/8" = 1'-0"

5/8" ABUSE RESISTANT GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD

AT 16" O.C. (WALL THICKNESS = 4 7/8" - NOMINAL 5")

EXTERIOR WALLS TO BE 4" NOMINAL BRICK ON CONCRETE BLOCK WALL

WITH 2" RIGID CAVITY INSULATION

C.M.U. PARTITION AS DIMENSIONED

FLOOR PLAN LEGEND

INDICATES BATT SOUND ATTENUATION INSULATION

FLOOR PLAN NOTES

ALL INTERIOR PARTITIONS SHOWN SHADED SHALL EXTEND UP TO UNDERSIDE OF

FLOOR/ROOF DECK.

PATCH ALL HOLES FROM REMOVED ITEMS SUCH AS, BUT NOT LIMITED TO

THERMOSTATS, NAIL HOLES, WALL MOUNTED CASEWORK, ETC.

INFILL EXISTING EXTERIOR LOUVERS OPENINGS WITH NEW BRICK TO MATCH

EXISTING. TOOTH-IN TO MATCH COURSING - TYPICAL.

COORDINATE EXACT LOCATION FOR NEW CASEWORK IN FIELD.

1.

2.

3.

4.

SHADING INDICATES PARTITIONS TO EXTEND TO UNDERSIDE OF

FLOOR/ROOF DECK UNLESS OTHERWISE INDICATED.

STUDY

ROOM

NORTH

STAIRWELL

SECURE

VESTIBULE

MAIN

OFFICE

PRINCIPAL

OFFICE

CLINIC

WORK RM

REST RM

CORRIDOR

ELEVATOR

LOBBY

ELEVATOR

ELEVATOR

MACH. RM.

STORAGE

KINDERGARTEN

CLASSROOM

KINDERGARTEN

CLASSROOM

COAT

ROOM

WORK

ROOM

COAT

ROOM

WORK

ROOM

CLASSROOM

CLASSROOM

CLASSROOM

ASD

CLASSROOM

YOUNG FIVES

CLASSROOM

STUDY

ROOM

BOY'S

RESTROOM

GIRL'S

RESTROOM

J.C.

J.C.

KILN

STORAGE

RECEIVING

ROOM

GYMNASIUM

RESTROOM

RESTROOM

STAGE

GARAGE

GYM

OFFICE

RESTROOM

RESTROOM

BOILER

ROOM

117 KITCHEN

STORAGE

KITCHEN

RESTROOM

ELEVATOR

EAST

VESTIBULE

GYM

VESTIBULE

WEST

VESTIBULE

WEST

STAIR

EAST

STAIR

CORRIDOR

STAIR

B

A

1 1 1 1

1 1

1 1

1 1

1 1

A2.01

FIRST FLOOR PLAN

CPM

CPM

PAC

KEY PLAN

07/20/2020 DESIGN DEVELOPMENT

GROSSE POINTE

PUBLIC SCHOOLS

MAIRE ES

RENOVATIONS

GROSSE POINTE

MICHIGAN

2019-026

T T

T

TT T

T

2D2D

2D2D

4D4D

4D4D

2D2D

2D2D

2D2D

2D2D

D

D

3D3D

3D3D 3 D

D

2D2D

DD

2D2D

2W2W

2W2W

2W2W

2W2W

2W2W

2W2W 2W2W

2W2W

2W2W2W2W2W2W

AA

AA AA AA

AA

3D3D

AA

3D3D

3D3D 3D3D 3D3D

4D4D

2D2D

2D2D

DD

DEMARC

(basement)

DD

Phone line from Demarc to Main Office. Coordinate location with Owner.

Prepared by Plante Moran

Legend:

Interactive Flat Panel

General Data

Wireless AP

AV Cabling

Audio Enhancement Speakers

Teacher location T

A

D

W

STUDY

ROOM

CONFERENCE

CORRIDOR

ELEVATOR

LOBBY

ELEVATOR

ELEVATOR

MACH. RM.

LRC

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

SENSORY

ROOM

BOY'S

RESTROOM

GIRL'S

RESTROOM

J.C.

J.C.

UPPER

GYMNASIUM

CLASSROOM

CLASSROOM

CLASSROOM

MUSIC

UPPER

STAGE

BALCONY

NORTH

STAIR

EAST

STAIR

WEST

STAIR

SCALE: 1/8" = 1'-0"

5/8" ABUSE RESISTANT GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD

AT 16" O.C. (WALL THICKNESS = 4 7/8" - NOMINAL 5")

EXTERIOR WALLS TO BE 4" NOMINAL BRICK ON CONCRETE BLOCK WALL

WITH 2" RIGID CAVITY INSULATION

C.M.U. PARTITION AS DIMENSIONED

FLOOR PLAN LEGEND

INDICATES BATT SOUND ATTENUATION INSULATION

FLOOR PLAN NOTES

ALL INTERIOR PARTITIONS SHOWN SHADED SHALL EXTEND UP TO UNDERSIDE OF

FLOOR/ROOF DECK.

PATCH ALL HOLES FROM REMOVED ITEMS SUCH AS, BUT NOT LIMITED TO

THERMOSTATS, NAIL HOLES, WALL MOUNTED CASEWORK, ETC.

INFILL EXISTING EXTERIOR LOUVERS OPENINGS WITH NEW BRICK TO MATCH

EXISTING. TOOTH-IN TO MATCH COURSING - TYPICAL.

COORDINATE EXACT LOCATION FOR NEW CASEWORK IN FIELD.

1.

2.

3.

4.

SHADING INDICATES PARTITIONS TO EXTEND TO UNDERSIDE OF

FLOOR/ROOF DECK UNLESS OTHERWISE INDICATED.

D C

A2.02

SECOND FLOOR PLAN

CPM

CPM

PAC

KEY PLAN

07/20/2020 DESIGN DEVELOPMENT

GROSSE POINTE

PUBLIC SCHOOLS

MAIRE ES

RENOVATIONS

GROSSE POINTE

MICHIGAN

2019-026

T

T

T T

T T

T T T

T

2W2W

AA

3D3D

AA

2W2W

3D3D

2W2W

2W2W

2W2W2W2W2W2W

2W2W 2W2W

2W2W 2W2W

2W2W

2W2W

D

D

DD

3D3D

AA

3D3D 3D3D

3D3D

AA

AAAA

3D3D

3D3D3D3D

AA AA AA

AA

3D3D

AA

AA

2D2D

2D2D

3D3D

Prepared by Plante Moran

Legend:

Interactive Flat Panel

General Data

Wireless AP

AV Cabling

Audio Enhancement Speakers

Teacher location T

A

D

W

LIBRARY

OFFICE

STORAGE

COPY

ROOM

STUDY

ROOM

NORTH

STAIRWELL

CLASSROOM

BOY'S

RESTROOM

GIRL'S

RESTROOM

STORAGE

RESTRM.

WEST

STAIR

STORAGE

MAINT.

ELEVATOR

LOBBY

ELEVATOR

129 CORRIDOR

CORRIDOR

SCALE: 1/8" = 1'-0"

5/8" ABUSE RESISTANT GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD

AT 16" O.C. (WALL THICKNESS = 4 7/8" - NOMINAL 5")

EXTERIOR WALLS TO BE 4" NOMINAL BRICK ON CONCRETE BLOCK WALL

WITH 2" RIGID CAVITY INSULATION

C.M.U. PARTITION AS DIMENSIONED

FLOOR PLAN LEGEND

INDICATES BATT SOUND ATTENUATION INSULATION

FLOOR PLAN NOTES

ALL INTERIOR PARTITIONS SHOWN SHADED SHALL EXTEND UP TO UNDERSIDE OF

FLOOR/ROOF DECK.

PATCH ALL HOLES FROM REMOVED ITEMS SUCH AS, BUT NOT LIMITED TO

THERMOSTATS, NAIL HOLES, WALL MOUNTED CASEWORK, ETC.

INFILL EXISTING EXTERIOR LOUVERS OPENINGS WITH NEW BRICK TO MATCH

EXISTING. TOOTH-IN TO MATCH COURSING - TYPICAL.

COORDINATE EXACT LOCATION FOR NEW CASEWORK IN FIELD.

1.

2.

3.

4.

SHADING INDICATES PARTITIONS TO EXTEND TO UNDERSIDE OF

FLOOR/ROOF DECK UNLESS OTHERWISE INDICATED.

A2.03

THIRD FLOOR PLAN

CPM

CPM

PAC

KEY PLAN

07/20/2020 DESIGN DEVELOPMENT

GROSSE POINTE

PUBLIC SCHOOLS

MAIRE ES

RENOVATIONS

GROSSE POINTE

MICHIGAN

2019-026

4" Slv

TG

B

General Notes:

1. Suspended ceilings are not required or desired.

2. The space should be environmentally controlled to maintain a room temperature range of 64F to 75F (18°C to 24°C) with a relative humidity level between 37% to 55% non-condensing.

Space should have a dedicated A/C unit.

3. Grounding busbars shall be provided and grounded to the main building ground. Mount and secure to backboard at 6" AFF.

Detailed Notes:

1. 1 x L5-30R and 4 x 5-20R per equipment rack, 120V. Receptacles should be mounted on the backboard.

2. Four 4" conduits should be provided for horizontal pathway from the hallway.

3. Four 4" trade-size conduits should be provided for a vertical riser at the floor and ceiling of the MDF providing pathways for the first and second floor. The conduits should extend a minimum of 1" AFF. Conduits on third floor should extend to above ceiling.

4. 3/4" A/C fire treated plywood backboards to be installed, 8’ high (or as high as feasible, mounted so the bottom is 6" AFF, painted with two coats of fire retardant white paint.

x

2W2W

2D2D

AA

2D2D 2D2D

4D4D

2D2D

2W2W

2W2W

2D2D 2D2D

2D2D

AA

2D 2D2D

2W2W

MDF

Alex.Dietrich Rectangle

File details come from the government source that posted it. Updated .