107348_25.09.23_Oscoda Area Schools Miscellaneous Renovation Phase 1_Addendum 02.pdf

PDF 1 MB Posted

Attached to
HS Auditorium Renovation
Solicitation number
RFP-OAS-250000002977-5
Issued by
Huron County, North Muskegon City, Michigan

About this file

This is an Addendum (No. 02) for the Oscoda Area Schools Miscellaneous Renovation Phase 1 project, prepared by The Collaborative architectural firm for Oscoda Area Schools in Michigan. The addendum supplements and amends the original drawings and specifications for a renovation project at the high school, with a project number of 107348. The document includes clarifications on various technical aspects of the project, such as door hardware, electrical systems, stage lighting, and equipment installation. Key details include specifications for electrical circuits, conduit runs, lighting fixtures, and stage equipment, with precise instructions for contractors on installation, wiring, and equipment placement.

The addendum provides detailed technical guidance for electrical and stage infrastructure work, including circuit descriptions, receptacle locations, lighting fixture specifications, and conduit routing. Notable elements include a transfer fan (TF-251) installation in the storage room, extensive stage lighting and audio-visual system preparations, and specific electrical circuit configurations. The document indicates that the district is separately working with an AV contractor and that certain existing systems will be maintained or modified. The electrical plans show a comprehensive approach to renovating the auditorium and stage areas, with careful attention to power distribution, lighting control, and system integration.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09/23/2025

ADDENDUM NO. 02

To the Drawings and Specifications for:

Oscoda Area Schools Miscellaneous Renovation Phase 1

107348

Oscoda Area Schools

Prepared By:

The Collaborative

Telephone: (419) 242-7405 Fax: (419) 242-7400

TO ALL BIDDERS:

This addendum supplements and amends the original drawings and specifications, and shall be taken into account in preparing proposals, and shall become a part of the contract documents. Receipt of this Addendum must be acknowledged in the Bid Form.

ADDENDUM NO. 002

GENERAL

Question 1: I am looking to clarify on the door schedule. It has removeable mullion, but no hardware. Is the bid to include hardware, or just doors and frame? If just doors and frame, what hardware will be on these to make sure correct prep is done. If bid is to have hardware, could you please provide list of what and basis of manufacture?

Answer 1: See attached for the door hardware spec sheet that was missing. Door 267B will have hardware set 1.0

Question 2: Will the seating that is being removed by others be completely removed from the space before commencement of the contract and for the duration of the project?

Answer 2: The seating will be removed by the district and will be gone for the duration of the contract.

Question 3: Is the asbestos report purely for information and not intended to imply any responsibility for abatement or handling under this contract?

Answer 3: Correct, we do not have any asbestos remediation as a part of this work but provided it purely for information.

Question 4: Is the TF-251 fan considered mechanical work as shown on the electrical plans and require a mechanical contractor and a mechanical permit or is this unit an electric device that will fall under the electrical permit?

Answer 4: The work for TF-251 is to be performed under the electrical contractor’s scope

Question 5: We were unable to attend the prebid meeting and would like to visit the site. Who do we contact for access?

Answer 5: You would have to reach out to Tony Brooks:

brookst@oscodaschools.org. School is currently in session so they may not be able to accommodate your request, but Tony will be able to schedule a time if they are free

Question 6: EC to only provide power feeds and empty raceways based on sheet E6.01?

Answer 6: Correct.

Question 7: Who is to provide AV equipment, cabling, AV devices, controller ETC?

Answer 7: The district is already working with an AV contractor and installer:

Eric Joseph erockcmu@gmail.com

Question 8: Is OHS currently working with AV contractor on system design and installation?

Answer 8: Yes, see question 7

Question 9: Is there access under stage?

Answer 9: Yes, the front of the stage can be opened to allow access underneath.

Question 10: All type D50I and D50 fixtures switched from LV switching shown on sheet E1.10?

Looks as if center and both outside rows appear to not have switching called out.

Answer 10: The center and both outside rows will be switched by the DMX system via circuit S-1. All exterior perimeter light labeled as existing are in an asbestos containing ceiling and are being left as is.

Question 11: Both Floor Boxes shown on sheet E1.10 to remain and reuse for new power/DMX control?

Answer 11: Provide new 4-gang floor pocket for quad power, (1) gang DMX and (1) gang XLR similar or equal to Ace Backstage Co. Incorporated model 122SLBK . Confirm dimensions for installation in stage floor.

Question 12: Is EC or others to provide ‘Quad Edison Receptacle Box”

Answer 12: The E.C. is to provide the Quad Edison Receptacle Boxes.

Question 13: Are “Edison Boxes” required if not provided by other or will metal 4sq with raised covers be adequate installation method?

Answer 13: ‘Quad Edison Receptacle Box” should just be a 4” square box with 2-duplex ( four receptacles) raised covers. Keynote wording has been updated to reflect this change.

CLARIFICATIONS:

• See attached hardware specs

DRAWINGS:

Electrical Drawings Drawing E1.10 Drawing E.01.1 Item E1: Revise drawing numbers to indicate phase.

Drawing ED1.10.1 Item E1: Add first electric batten.

Drawing E1.10.1 Item E1: Add first electric batten.

Item E2: Revise batten outlet location.

Item E3: Revise keynote 12.

ddewitt Pen

Drawing E6.01.1 Item E1: Revise electrical circuit schedule location 12 note.

END OF ADDENDUM #02 (04 Written Pages, 04 Drawings, 01 Specification Section)

NEW COMMUNITY CENTER (OSCODA AREA SCHOOLS) 107167

OSCODA, MI

DOOR HARDWARE SCHEDULE 080671 - 1

SECTION 080671 – DOOR HARDWARE SCHEDULE

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary

Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section references specification sections relating to commercial door hardware for the following:

1. Swinging doors.

2. Sliding Doors.

3. Other doors to the extent indicated.

B. Commercial door hardware includes, but is not necessarily limited to, the following:

1. Mechanical door hardware.

2. Electromechanical and access control door hardware.

3. Electromechanical and access control door hardware power supplies, back-ups and surge protection.

4. Automatic operators.

5. Cylinders specified for doors in other sections.

C. Related Sections:

1. Division 08 Section “Door Hardware”.

2. Division 08 Section “Automatic Door Operators”.

3. Division 28 Section “Access Control Hardware Devices”.

D. Codes and References: Comply with the version year adopted by the Authority Having

Jurisdiction.

1. ANSI A117.1 - Accessible and Usable Buildings and Facilities.

2. ICC/IBC - International Building Code.

3. NFPA 70 - National Electrical Code.

4. NFPA 80 - Fire Doors and Windows.

5. NFPA 101 - Life Safety Code.

6. NFPA 105 - Installation of Smoke Door Assemblies.

7. State Building Codes, Local Amendments.

DOOR HARDWARE SCHEDULE 080671 - 2

E. Standards: Reference Related Sections for requirements regarding compliance with applicable industry standards.

1.3 SUBMITTALS

A. Product Data: Manufacturer's product data sheets including installation details, material descriptions, dimensions of individual components and profiles, operational descriptions and finishes.

B. Door Hardware Schedule: Prepared by or under the supervision of supplier, detailing fabrication and assembly of door hardware, as well as procedures and diagrams. Coordinate the final Door

Hardware Schedule with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.

1. Format: Comply with scheduling sequence and vertical format in DHI's "Sequence and

Format for the Hardware Schedule."

2. Organization: Organize the Door Hardware Schedule into door hardware sets indicating complete designations of every item required for each door or opening. Organize door hardware sets in same order as in the Door Hardware Sets at the end of Part 3. Submittals that do not follow the same format and order as the Door Hardware Sets will be rejected and subject to resubmission.

3. Content: Include the following information:

a. Type, style, function, size, label, hand, and finish of each door hardware item.

b. Manufacturer of each item.

c. Fastenings and other pertinent information.

d. Location of door hardware set, cross-referenced to Drawings, both on floor plans and in door and frame schedule.

e. Explanation of abbreviations, symbols, and codes contained in schedule.

f. Mounting locations for door hardware.

g. Door and frame sizes and materials.

4. Submittal Sequence: Submit the final Door Hardware Schedule at earliest possible date, particularly where approval of the Door Hardware Schedule must precede fabrication of other work that is critical in the Project construction schedule. Include Product Data, Samples, Shop Drawings of other work affected by door hardware, and other information essential to the coordinated review of the Door Hardware Schedule.

C. Keying Schedule: Prepared under the supervision of the Owner, separate schedule detailing final keying instructions for locksets and cylinders in writing. Include keying system explanation, door numbers, key set symbols, hardware set numbers and special instructions.

Owner to approve submitted keying schedule prior to the ordering of permanent cylinders.

D. Product Test Reports: Indicating compliance with cycle testing requirements, based on evaluation of comprehensive tests performed by manufacturer and witnessed by a qualified independent testing agency.

DOOR HARDWARE SCHEDULE 080671 - 3

E. Operating and Maintenance Manuals: Provide manufacturers operating and maintenance manuals for each item comprising the complete door hardware installation in quantity as required in Division 01, Closeout Submittals. The manual to include the name, address, and contact information of the manufacturers providing the hardware and their nearest service representatives. The final copies delivered after completion of the installation test to include "as built" modifications made during installation, checkout, and acceptance.

F. Warranties and Maintenance: Special warranties and maintenance agreements specified in the

Related Sections.

1.4 DELIVERY, STORAGE, AND HANDLING

A. Inventory door hardware on receipt and provide secure lock-up and shelving for door hardware delivered to Project site. Do not store electronic access control hardware, software or accessories at Project site without prior authorization.

B. Tag each item or package separately with identification related to the final Door Hardware

Schedule, and include basic installation instructions with each item or package.

C. Deliver, as applicable, permanent keys, cylinders, cores, access control credentials, software and related accessories directly to Owner via registered mail or overnight package service.

Instructions for delivery to the Owner shall be established at the "Keying Conference".

1.5 WARRANTY

A. General Warranty: Reference Division 01, General Requirements. Special warranties specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.

1.6 MAINTENANCE SERVICE

A. Maintenance Tools and Instructions: Furnish a complete set of specialized tools and maintenance instructions as needed for Owner's continued adjustment, maintenance, and removal and replacement of door hardware.

PART 2 - PRODUCTS

2.1 SCHEDULED DOOR HARDWARE

A. Refer to “PART 3 – EXECUTION” for required specification sections.

DOOR HARDWARE SCHEDULE 080671 - 4

PART 3 - EXECUTION

3.1 DOOR HARDWARE SETS

A. The door hardware sets represent the design intent and direction of the owner and architect.

They are a guideline only and should not be considered a detailed hardware schedule.

Discrepancies, conflicting hardware and missing items should be brought to the attention of the architect with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality.

1. Quantities listed are for each pair of doors, or for each single door.

2. The supplier is responsible for handing and sizing all products.

3. Where multiple options for a piece of hardware are given in a single line item, the supplier shall provide the appropriate application for the opening.

4. At existing openings with new hardware the supplier shall field inspect existing conditions prior to the submittal stage to verify the specified hardware will work as required. Provide alternate solutions and proposals as needed.

B. Products listed in the hardware sets shall be supplied by and in accordance with the requirements described in the specification section as noted for each item.

1. Section 08 71 00 – Door Hardware.

2. Section 08 71 13 – Automatic Door Operators.

3. Section 28 15 00 – Access Control Hardware Devices.

C. Manufacturer’s Abbreviations:

1. MK - McKinney

2. PE - Pemko

3. MR - Markar

4. SU - Securitron

5. RO - Rockwood

6. RU - Corbin Russwin

7. RI - RITE Door

8. AD - Adams Rite

9. SA - SARGENT

10. HS - HES

11. RF - Rixson

12. NO - Norton

13. HI - Hiawatha

14. OT - Other

15. YA - ASSA ABLOY ACCENTRA

DOOR HARDWARE SCHEDULE 080671 - 5

Hardware Sets

Set: 1.0

Doors: 267B

6 Hinge, Full Mortise TA2714 (NRP) US26D MK 087100

2 Flush Bolt 555 US26D RO 087100

1 Dust Proof Strike 570 US26D RO 087100

1 Storeroom Lock ML2057 NSA CT6SB 626 RU 087100

2 Surf Overhead Stop 10-336 630 RF 087100

2 Silencer 608-RKW RO 087100

END OF SECTION 080671

GENERAL DEMOLITION NOTES:

1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING

EQUIPMENT SHALL BE COORDINATED WITH BUILDING STRUCTURE, EQUIPMENT

FURNISHED, ARCHITECTURAL DRAWINGS AND ALL OTHER TRADES PRIOR TO

DEMOLITION.

2. DEMOLITION SHALL BE APPROVED BY THE OWNER PRIOR TO COMMENCEMENT AND

SHALL BE PERFORMED UNDER REQUIREMENTS AND APPROVAL OF THE LOCAL CODE

JURISDICTIONS.

3. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN APPROVED

MANNER ANY SUCH WORK WHICH BECOMES DAMAGED. THIS INCLUDES BUT NOT

LIMITED TO CEILING PROJECTORS, POWER POLES, WIFI ACCESS POINTS AND SMOKE

DETECTORS.

4. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING

REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE DOCUMENTS OR

SHOWN NOT MATCHING FIELD CONDITIONS.

5. ELECTRICAL CONTRACTOR SHALL EXAMINE THE PROJECT DOCUMENTS AND VISIT THE

SITE AS THEY DEEM NECESSARY PRIOR TO SUBMITTING A BID. DO NOT RELY SOLELY

ON THE ELECTRICAL PLANS FOR ALL DEMOLITION REQUIREMENTS. REVIEW ALL

PROJECT DOCUMENTS PRIOR TO SUBMITTING A BID. IF A DEPARTURE FROM THE

DESIGN INTENT OF THE DOCUMENTS IS REQUIRED DUE TO THE ACTUAL FIELD

CONDITIONS OBSERVED BY THE CONTRACTOR, THE CONTRACTOR SHALL NOTIFY THE

ARCHITECT IN WRITING FOR RESOLUTION PRIOR TO SUBMITTING FINAL BID OR

ENTERING INTO A CONTRACT FOR CONSTRUCTION. FAILURE TO PROVIDE THE

ARCHITECT WITH NOTIFICATION SHALL RESULT IN THE CONTRACTOR BEING HELD

RESPONSIBLE TO COMPLETE ALL WORK TO MEET THE DESIGN INTENT WITH NO

ADDITIONAL COST BEING INCURRED BY THE OWNER.

6. THE DEMOLITION INFORMATION IS PROVIDED TO ASSIST WITH LABOR COSTS

ASSOCIATED WITH THE ELECTRICAL SYSTEMS REMOVAL. THE DEMOLITION

CONTRACTOR WILL REMOVE ELECTRICAL COMPONENTS AS NOTED, BUT NOT LIMITED

TO THE DRAWINGS.

7. VERIFY EXTENT OF DEMOLITION WORK WITH INFORMATION SHOWN IN THE DRAWINGS

AND WORK THAT IS NOT SHOWN AND MAY BE REQUIRED TO COMPLETE THE INTENDED

WORK.

8. ALL WORK SHALL COMPLY WITH REQUIRED LOCAL CODES. CONTRACTOR IS

RESPONSIBLE FOR OBTAINING REQUIRED PERMITS AND INSPECTIONS FOR ALL WORK

ASSOCIATED WITH THIS CONTRACT.

9. CONTRACTOR SHALL REPAIR ALL DISTURBED AREAS AS REQUIRED TO MATCH

SURROUNDING EXISTING FINISHES NOT DISTURBED.

10. IN EXISTING AREAS, RENOVATION AND DEMOLITION WORK SHALL BE ACCOMPLISHED

WITH MINIMAL DISRUPTION TO OPERATIONS. IF REQUIRED, THE OWNER RESERVES

THE RIGHT TO TEMPORARILY STOP WORK OF SPECIFIC CONSTRUCTION OPERATIONS

SHOULD THE OWNER IDENTIFY AN EMERGENCY OR DANGER EXISTS TO THE WELFARE

OF THE OCCUPANTS ON ACCOUNT OF SUCH WORK OR OPERATIONS.

11. CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL MATERIAL IN A LEGAL MANNER NOT

SCHEDULED FOR REUSE UNDER THIS PROJECT.

12. CONFIRM WITH THE ARCHITECTS OFFICE AND/OR CONSTRUCTION MANAGER, PROJECT

SCHEDULES AND REVIEW THE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL

DRAWINGS PRIOR TO COMMENCING DEMOLITION.

13. USE CARE DURING THE DEMOLITION PHASE TO AVOID DAMAGE TO ANY GLAZED BLOCK,

TILE OR BRICK VENEERED WALLS THAT ARE TO REMAIN.

14. DEMOLITION CONTRACTORS ARE RESPONSIBLE TO CONFIRM ALL QUANTITIES AND

DEMOLITION REQUIRED. COMPLETE DEMOLITION IS NOT SHOWN ON THE DRAWINGS.

15. DISCONNECT, REMOVE AND/OR RELOCATE ALL ITEMS AS SHOWN. IF THERE ARE ANY

ITEMS THAT ARE TO REMAIN, THEY ARE SPECIFICALLY NOTED SO ON THE DRAWINGS.

16. WHERE CONDUITS OR NON-METALLIC SHEATHED CABLE ARE ROUTED CONCEALED IN

WALL CAVITIES OF WALL THAT ARE TO REMAIN, ABANDON THE CONDUIT AND/OR

CABLE. CUT BACK TO THE POINT OF CONCEALMENT INSIDE THE WALL OR CEILING

CAVITY. CUT AND REMOVE THE CONDUIT EXITING THE WALL CAVITY INTO THE CEILING

SPACE. DISCONNECT AND REMOVE FEEDS FROM ELECTRICAL PANEL. REMOVE ALL

SURFACE MOUNTED OUTLET BOXES ASSOCIATED WITH THE CONDUIT SYSTEMS.

17. DISCONNECT AND REMOVE ALL ELECTRICAL EQUIPMENT INCLUDING HANGERS, PULL

BOXES, SWITCHES, LIGHT FIXTURES, CONDUIT AND WIRING FROM THE POINT OF

CONCEALMENT TO THE EQUIPMENT. DISPOSE OF ALL ITEMS (SPECIAL ATTENTION TO

LAMPS) AS REQUIRED BY LAW.

18. ELECTRICAL CONTRACTOR SHALL TAKE CARE WHEN REMOVING ELECTRICAL SYSTEMS.

ALL WIRING THAT IS REQUIRED FOR POWER AND SPECIAL SYSTEMS ON OTHER FLOORS

SHALL BE MAINTAINED.

19. EXISTING LIGHT FIXTURES MAY BE UTILIZED FOR TEMPORARY LIGHTING, ALL

TEMPORARY SHALL REMAIN AFTER PROJECT IS DONE FOR OWNERS USE. ALL LIGHT

FIXTURES THAT ARE REMOVED SHALL BE DISPOSED OF IN A LAWFUL WAY.

20. OWNER HAS FIRST RIGHTS TO ITEMS REMOVED.

GENERAL SPECIFICATIONS:

1. EXECUTE THE WORK REQUIRED IN A MANNER EVIDENCE BY THE "BEST TRADE PRACTICES"

CONTRIBUTING TO EFFICIENCY OF OPERATION, MINIMUM MAINTENANCE, ACCESSIBILITY AND

AESTHETICS OF THE INSTALLATION.

2. MECHANICAL AND ELECTRICAL PLANS ARE DIAGRAMMATIC IN NATURE, INTENDED TO INDICATE DESIGN INTENT ONLY. CONTRACTOR IS RESPONSIBLE TO COORDINATE SPECIFIC LOCATIONS OF

ITEMS AND ADJUST AS REQUIRED TO ACCOMMODATE CODE REQUIREMENTS, MANUFACTURER'S

INSTALLATION REQUIREMENTS, AND THE WORK OF OTHER TRADES.

3. MECHANICAL AND ELECTRICAL INFORMATION IS PRESENTED ON A REFERENCED BACKGROUND

FLOOR PLAN. IN CASE OF CONFLICT BETWEEN BACKGROUND PLAN AND ARCHITECTURAL FLOOR

PLAN, ARCHITECTURAL FLOOR PLAN SHALL GOVERN.

4. RUN ALL PIPING, CONDUIT, ETC. CONCEALED IN WALLS WHENEVER POSSIBLE.

5. AVOID EXPOSED INSTALLATION UNLESS SPECIFICALLY REQUIRED (TYPICAL UNLESS NOTED

OTHERWISE ON DRAWINGS).

6. THE ENGINEER WILL NOT HAVE CONTROL OR CHARGE OF CONSTRUCTION MEANS, METHODS,

TECHNIQUES, SEQUENCES, OR PROCEDURES. ENGINEER IS NOT RESPONSIBLE FOR SAFETY

PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK; AND WILL NOT BE RESPONSIBLE FOR CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THOSE DOCUMENTS

PREPARED BY THE ENGINEER.

7. ALL CONSTRUCTION SHALL BE DONE IN COMPLIANCE WITH CURRENT CODES, INCLUDING:

MICHIGAN BUILDING CODES, MICHIGAN PLUMBING CODE, MICHIGAN MECHANICAL CODE, NATIONAL ELECTRICAL CODE, MICHIGAN BUILDING REHABILITATION CODE (WHEN APPLICABLE), NFPA CODES, LIFE SAFETY CODE (WHEN APPLICABLE), AMERICANS WITH DISABILITIES ACT (A.D.A.) AND

MICHIGAN BARRIER FREE CODES, DEPARTMENT OF PUBLIC HEALTH CODES (WHEN APPLICABLE), AND ALL OTHER LOCAL, STATE, AND FEDERAL APPLICABLE CODES. CONTRACTOR SHALL UTILIZE

THE LATEST ADOPTED EDITIONS OF ALL CODES.

8. IF BIDDING CONTRACTOR WOULD LIKE TO SUBSTITUTE ANY SPECIFIED ELECTRICAL DEVICES, LIGHT FIXTURES, CONTROLLERS, PANELS, DISCONNECTS, VFD'S, ELEC. GEAR, ETC., THEY MUST PROVIDE SUBMITTAL TYPE DRAWINGS TO THE ENGINEER A MINIMUM OF 7 DAYS PRIOR TO BIDDING

THE PROJECT. IF THESE APPROVAL DRAWINGS ARE NOT SUBMITTED AND ACCEPTED, THE

SPECIFIED EQUIPMENT MUST BE USED - NO EXCEPTIONS.

9. EQUIPMENT AND MATERIALS SHALL BE U.L. APPROVED.

10. SECURE PERMITS AND INSPECTIONS REQUIRED BY STATE AND LOCAL LAWS AND ORDINANCES AND PAY ALL FEES AND EXPENSES IN CONNECTION THEREWITH AS A PART OF THEIR WORK UNDER THIS

CONTRACT.

11. UPON COMPLETION OF WORK, FURNISH OWNER CERTIFICATES OF FINAL INSPECTION AND

APPROVAL FROM AUTHORITIES HAVING JURISDICTION.

12. ALL CONDUCTORS SHALL BEAR IDENTIFICATION AS TO SIZE AND TYPE OF INSULATION, AND SHALL

BE EQUIPPED WITH WIRE MARKERS INDICATING THE CIRCUIT NUMBER, WIRE NUMBER AND/OR

PHASE LETTER.

13. IDENTIFY ELECTRICAL EQUIPMENT WITH THE NAME OF THE EQUIPMENT, THE EQUIPMENT

CONTROLLED OR THE SYSTEM INVOLVED. DISCONNECT SWITCHES AND MOTOR STARTERS SHALL

HAVE NAMEPLATES TO INDICATE THE EQUIPMENT THEY CONTROL. FOR NEW ELECTRICAL DEVICES AS NOTED ON RISER DIAGRAM, PROVIDE LAMINATED PLASTIC NAME PLATES WITH WHITE LETTERS.

14. EXISTING LIGHTING AND RE-USED RECEPTACLE PANELS SHALL HAVE NAMEPLATES DESIGNATING

THEIR NAMES AND VOLTAGE RATING, SUCH AS LP-A, 120/208 VOLT, 3 PHASE, 4 WIRE. THE

NAMEPLATES SHALL BE BLACK LAMINATED PLASTIC WITH WHITE CHARACTERS. THE CHARACTERS ON THE NAMEPLATES SHALL BE 1/4" HIGH, UNLESS OTHERWISE DIRECTED IN THE FIELD. THE

CHARACTERS SHALL BE ENGRAVED ON THE NAMEPLATES.

15. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH CONDITIONS OF WHICH WILL AFFECT THE WORK HE IS TO PERFORM. THE SUBMISSION OF A PROPOSAL BY THIS CONTRACTOR SHALL BE CONCLUSIVE EVIDENCE THAT THIS CONTRACTOR HAS VISITED THE SITE

AND HAS GIVEN PROPER CONSIDERATION AND EVALUATION OF THESE CONDITIONS IN THE

PREPARATION OF HIS PROPOSAL. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE IN HIS BEHALF FOR EXTRA EXPENSE INCURRED DUE TO FAILURE OR NEGLECT ON HIS PART TO MAKE THIS VISIT

AND EXAMINATION.

16. WHERE ACTIVE SEWERS, GAS, ELECTRIC, OR OTHER SERVICES ARE ENCOUNTERED DURING THE PERFORMANCE OF THIS CONTRACT, THE CONTRACTOR SHALL PROTECT, BRACE AND SUPPORT THEM

AS REQUIRED. DO NOT PREVENT, INTERRUPT OR DISTURB OPERATION OF EXISTING SERVICES

THAT ARE TO REMAIN. RELOCATE EXISTING SERVICES IF REQUIRED.

17. IN GENERAL, MOUNTING HEIGHTS ABOVE FINISHED FLOOR TO THE CENTERLINE OF BOXES AND EQUIPMENT SHALL BE AS PER AMERICANS WITH DISABILITIES ACT, AND MICHIGAN BARRIER FREE

CODES.

18. MAINTAIN A MINIMUM OF 3'-0" CLEAR IN FRONT OF ALL ELECTRICAL EQUIPMENT (DISCONNECT SWITCHES, LIGHTING AND APPLIANCE AND DISTRIBUTION PANELS) FOR SERVICING PER N.E.C.

19. ALL WORK TO CONFORM TO THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AND LOCAL

REQUIREMENTS. ALSO REFERENCE ARCHITECTURAL AND KITCHEN DWG'S.

20. WIRING TO BE MINIMUM #12 (FOR RUNS OVER 100 FEET, MINIMUM #10). ALL WIRING TO BE

INSTALLED IN E.M.T. (THINWALL CONDUIT).

21. DEVICE PLATES FOR SWITCHES, RECEPTACLES, TELEPHONE, COMPUTER, ETC., SHALL MATCH EXISTING AS MANUFACTURED BY PASS AND SEYMOUR, HUBBELL, OR BRYANT. ALL DEVICES TO BE

SPECIFICATION GRADE. ANY OTHER COLOR OF DEVICES SHALLS BE CHOSEN BY

OWNER/ARCHITECT.

22. CONTRACTOR TO OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS.

23. ALL WORK AND MATERIALS SHALL BE GUARANTEED IN WRITING FOR (1) YEAR FROM PROJECT

COMPLETION.

24. WORK SHALL BE PERFORMED BY SKILLED MECHANICS WELL VERSED IN THEIR PARTICULAR TRADES.

25. RESPONSIBILITY FOR CARE AND PROTECTION OF ELECTRICAL WORK RESTS WITH THE

CONTRACTOR UNTIL IS HAS BEEN TESTED AND ACCEPTED.

26. CONTRACTOR IS TO CHECK DOOR SWINGS WITH ARCHITECTURAL PLANS AND MOUNT LIGHT

SWITCHES, CONTROLS, ETC., ACCORDINGLY.

27. ELECTRICAL DEVICES SHALL BE SQUARE D, SIEMENS, EATON, G.E. OR MATCH EXISTING.

28. DISCONNECT SWITCHES SHALL BE NEMA HEAVY DUTY, FUSIBLE OR NON-FUSIBLE AS NOTED ON

PLANS, WITH A NEMA 3R ENCLOSURE WHERE MOUNTED OUTDOORS.

29. THE NEUTRAL CONDUCTOR OF THE WIRING SYSTEM TOGETHER WITH THE CONDUIT SYSTEM AND

SERVICE EQUIPMENT SHALL BE GROUNDED AND SIZED PER NEC ARTICLE 250.

30. HOLES THROUGH WALLS OR PARTITIONS REQUIRED FOR ELECTRICAL WORK SHALL BE NEATLY CUT

TO SIZE. PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRE-STOPPED BY APPROVED

METHODS AND MATERIALS. NO BEAMS OR OTHER STRUCTURAL MEMBERS SHALL BE DRILLED,

BURNED, OR CUT.

31. LOCATIONS OF WIRING DEVICES SUCH AS LIGHT SWITCHES, DUPLEX RECEPTACLES, THERMOSTATS, ETC., SHALL BE COORDINATED WITH OTHER TRADES.

32. IN GENERAL, ALL MOTORS ARE FURNISHED AND INSTALLED UNDER THE MECHANICAL SECTION OF THE SPECIFICATIONS. ALL STARTERS, FUSED SWITCHES, SAFETY SWITCHES, INCLUDING ALL POWER

WIRING SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR.

33. OUTLET BOXES IN THE SAME WALL BUT SERVING DIFFERENT ROOMS SHALL BE AT LEAST 4" APART TO MINIMIZE NOISE TRANSMISSION. WHEN LOCATED ON FIRE WALLS, THEY SHALL BE 24" APART.

34. OCCUPANCY AND TOGGLE SWITCHES AS WELL AS RECEPTACLES SHALL BE SPECIFICATION GRADE, COLOR TO MATCH EXISTING.

35. LIGHTING AND CONTROL WIRING SHALL BE TESTED FOR SHORTS AND OPENS AND SHALL BE GIVEN

A COMPLETE OPERATIONAL TEST.

36. THE CONTRACTOR SHALL TEST ALL CIRCUITS AS SOON AS CONDUCTORS ARE INSTALLED AND MAKE FINAL TESTS WHEN ALL WORK IS COMPLETE. IF CIRCUITS ARE NOT PROPERLY CONTROLLED AND INSULATED AT TIME OF EACH FINAL TEST, THE NECESSARY REPAIRS AND TESTS SHALL BE MADE AT

THE CONTRACTORS EXPENSE.

37. NO DUCTWORK IS TO RUN ABOVE THE ELECTRICAL PANELS FOR 6' ABOVE THE PANELS PER 2017 N.E.C. KEEP PANEL AREAS CLEAR FOR 36" IN FRONT OF PANELS FROM FLOOR TO TOP OF PANELS FOR SERVICING PANELS PER N.E.C. COORDINATE LOCATIONS OF M.E.P. ITEMS WITH CONTRACTORS

PRIOR TO CONSTRUCTION TO ASSURE THAT CLEARANCES ARE MET. LACK OF COORDINATION

BETWEEN CONTRACTORS WILL NOT RESULT IN EXTRA MONEY AWARDED FOR RELOCATION OF

M.E.P. ITEMS.

38. ALL BUSSING AND WIRING TO BE COPPER. NO ALUMINUM IS ALLOWED ON THIS PROJECT.

39. CHECK FINAL LOCATIONS OF LIGHT FIXTURES AND CEILING ELECTRICAL ITEMS WITH GRILLES AND

REGISTERS, CAMERAS, FANS, SPRINKLER HEADS, ETC. COORDINATE WITH RESPECTIVE

CONTRACTORS PRIOR TO INSTALLATION. NO MONEY WILL BE AWARDED TO CONTRACTORS

HAVING TO RELOCATE ITEMS DUE TO LACK OF COORDINATION BETWEEN CONTRACTORS.

MECHANICAL AND ELECTRICAL PLANS SHOW SCHEMATIC LOCATIONS ONLY.

40. ANY DISCREPANCIES BETWEEN ARCHITECTURAL DRAWINGS AND ELECTRICAL DRAWINGS SHALL BE

BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.

41. CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF DRAWINGS REFLECTING "AS

BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT DIMENSIONS AND

ELEVATIONS FOR ALL UNDERGROUND AND/OR CONCEALED WORK. UPON COMPLETION OF THIS

PROJECT, THE CONTRACTOR SHALL DELIVER TO THE CONSTRUCTION MANAGER OR GENERAL

CONTRACTOR THE AS-BUILT DRAWINGS.

42. THE WIRING METHOD(S) USED SHALL BE SUITABLE FOR THE INSTALLATION AND USE IN

CONFORMITY WITH THE PROVISIONS OF THE 2017 N.E.C. LISTED OR LABELED EQUIPMENT SHALL BE USED OR INSTALLED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING OR LABELING. REFER TO NEC, SECTION 110-3(a) AND (b).

43. ALL NEW ELECTRICAL DEVICES AND ASSOCIATED OUTLET BOXES SHALL BE FLUSH MOUNTED UNLESS NOTED OTHERWISE. ALL CONDUIT AND WIRING SHALL BE CONCEALED. SURFACE RACEWAY

AND ASSOCIATED BOXES SHALL ONLY BE PERMITTED WHERE NOTED, AND SHALL BE DISCUSSED

WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION.

44. THE MAIN SERVICE DISCONNECTS SHALL BE IDENTIFIED AS THE MAIN SERVICE DISCONNECTION

MEANS PER N.E.C. 2017, ARTICLE 230-70B.

45. FLASH PROTECTION WARNING SHALL BE PROVIDED AT ALL ELECTRICAL PANELS PER NEC 2017, SECTION 110.16

46. FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN THE OPINION

OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS ARE REQUIRED TO

PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR SHALL REQUEST AN INTERPRETATION

FROM THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK. IT THE CONTRACTOR

FAILS TO MAKE SUCH A REQUEST, NO EXCUSE WILL THEREAFTER BE ENTERTAINED FOR FAILURE TO

PROVIDE FIRST-CLASS WORKABLE SYSTEMS.

47. SHOP DRAWINGS ARE TO BE THOROUGHLY CHECKED (AND NOTED SO ON FRONT COVER) BY THE

CONTRACTOR PRIOR TO SUBMITTING THEM TO THE ARCHITECT/ENGINEER. REVIEW BY THE

ENGINEER, SHALL NOT BE CONSTRUED AS A COMPLETE CHECK, BUT ONLY THAT THE GENERAL

METHOD OF CONSTRUCTION AND DETAILING IS SATISFACTORY. REVIEW SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS WHICH MAY EXIST. SHOP DRAWINGS ARE TO BE

SUBMITTED VIA INTERNET IN PDF FORM. NO HARD COPIES WILL BE ACCEPTED.

48. CONNECT ALL EMERGENCY AND EXIT BATTERY PACKS TO NEARBY LIGHTING CIRCUITS, AHEAD OF

SWITCHES PER N.E.C. SO EMERGENCY/EXIT LIGHTS OPERATE ON LOSS OF POWER.

49. MANUALS: PER ASHRAE 2013, 90.1 STANDARDS, CONSTRUCTION DOCUMENTS SHALL REQUIRE

THAT AN OPERATING MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING

OWNER. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:

A. SUBMITTAL DATA FOR ALL ELECTRICAL EQUIPMENT CLEARLY STATING EQUIPMENT RATING , EXACTLY WHAT MODELS, ACCESSORIES, OPTIONS ARE INSTALLED.

B. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT

REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY

IDENTIFIED.

C. NAMES AND ADDRESSES AND PHONE NUMBERS/EMAIL ADDRESSES FOR AT LEAST ONE

QUALIFIED SERVICE AGENCY FOR EACH PIECE OF EQUIPMENT.

D. A COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.

MEP CONSULTING ENGINEER

OWNER JOB NO.

SHEET NO.

TC JOB NO.

PROJECT TITLE

FED

B C

Bn

A

G

N

SHEET TITLE

KEY PLAN

PR

EL

IM

IN

AR

Y

NOT

FO

R C

ONST

RUCT

IO

N

491 E. WRIGHT AVE.

SHEPHERD, MI 48883

(PH) 989-567-1100

info@KTSEngineeringGroup.com

E0.01.1

GENERAL

ELECTRICAL

NOTES, SYMBOLS

& ABBREVIATIONS

KTS PROJECT NO. 25-0275

3550 E River Road Oscoda, Michigan 48750

Oscoda High School Misc Renovation

107348

Oscoda Area Schools

" INCHES

# NUMBER

' FEET

1P 1 POLE (2P, 3P, 4P, ETC.)

@ AT

A AMPERE

ABOVE CEILING ACLG

ACT ABOVE COUNTER

ADO AUTOMATIC DOOR OPENER

AF AMP FRAME

AFCI ARC FAULT COMBINATION CIRCUIT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUA-STAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BF BOTTLE FILLER

BLDG BUILDING

BMS BUILDING MANAEMENT SYSTEM

C CONDUIT

C CENTER LINE

CAB CABINET

CAT CATALOG

CAT6 CATEGORY 6 CABLING

CATV CABLE TELEVISION

CB CIR UIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CL CONNECTED LOAD

COF COFFEE MAKER

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION, CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CT CURRENT TRANSOFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCUITING PUMP

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DL DEMAND LOAD

DN DOWN

DPR DAMPER

DS DISCONNECT SWITCH

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXP EXPLOSION PROOF

F FLOOR

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABP FIRE ALARM BOOSTER SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FASP FIRE ALARM SLAVE PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FU FUSE

FUDS FUSED DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP GYPSUM BOARD

HOA HAND-OFF-AUTO SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING & AIR CONDITIONING

I/W INTERLOCK WITH

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT- AMPERE RECTIVE

KW KILOWATT

KWC KILOWATT CONNECTED

KWD KILOWATT DEMAND

KWH KILOWATT HOUR

LOC LOCATE OR LOCATION

LP LIGHTNING PEOTECTION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

M/C MOMENTARY CONTACT

MAGS MAGNETIC STARTER

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MSP MOTOR STARTER PANELBOARD

MT MOUNT

MT.C EMPTY CONDUIT

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELEC MFGR'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OH OVERHEAD

OL OVERLOADS

P PLATE

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

S/N SOLID NEUTRAL

S/S STOP/START PUSHBUTTONS

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

SP SPARE

SPEC SPECIFICATION

SPKR SPEAKER

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STA STATION

STBY STANDBY

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SWL SWITCH WITH LIGHTS

SYM SYMMETRICAL

SYS SYSTEM

T-STAT THERMOSTAT

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UCR UNDER COUNTER REFRIGERATOR

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV UNIT VENTILATOR

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

VOL VOLUME

W WATT

W/ WITH

W/O WITHOUT

WG WIRE GUARD

WH WATER HEATER

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

℄ CENTER LINE

∠ ANGLE

▲ DELTA

ABBREVIATIONS:

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF

LIGHT FIXTURES.

2. LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND IN

ACCORDANCE WITH N.E.C. AND LOCAL REQUIREMENTS.

3. CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING OF ALL EXIT LIGHTS PRIOR

TO ORDERING.

4. EMERGENCY LIGHT FIXTURES SHALL BE CONTROLLED WITH NORMAL ROOM OR

AREA LIGHTING VIA 924 INC. EMERGENCY CONTROL MODULE.

5. PROVIDE ALL BRANCH CIRCUIT WIRING REVISIONS AND CONNECTIONS REQUIRED

TO ACCOMMODATE LIGHTING REVISIONS INDICATED OR SPECIFIED.

6. PROVIDE AN UNSWITCHED HOT TO ALL EMERGENCY BATTERY PACKS AND EXIT

SIGNS. CONNECT TO THE SAME CIRCUIT AS THE NORMAL LIGHTING SERVING THE

SURROUNDING AREA AHEAD OF ANY SWITCHING/CONTROLS.

7. ALL BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR AND

GROUND CONDUCTOR. PROVIDE ADDITIONAL NEUTRAL CONDUCTOR WHERE

REQUIRED.

8. MC CABLE MAY ONLY BE USED FOR FINAL CONNECTION TO LIGHT FIXTURES 6'-0"

LENGTH MAX. BRANCH CIRCUIT HOME RUNS SHALL BE IN EMT.

9. CONDUITS LOCATED IN FINISHED AREAS MUST BE RECESSED IN WALLS OR

LOCATED ABOVE FINISH CEILINGS. SURFACE MOUNTED CONDUIT WILL NOT BE

ALLOWED UNLESS NOTED OTHERWISE.

10. JUNCTION BOXES SERVING BRANCH CIRCUIT WIRING SHALL BE LABELED WITH

CIRCUITS BEING SERVED. USE INDELIBLE MARKER ON BOX COVER.

11. PROVIDE LABELS ON NEW LIGHT SWITCHES WITH CIRCUIT NUMBER AND PANEL

DESIGNATION LOCATED IN AREA AFFECTED BY NEW SCOPE OF WORK.

12. REUSE BRANCH CIRCUITS MADE AVAILABLE FROM DEMOLITION. EXISTING

LIGHTING CIRCUITS SHALL BE EXTENDED TO NEW LIGHTING FIXTURES AND ROOM

CONTROLLERS (POWER PACKS). IDENTIFY UN-USED LIGHTING CIRCUITS AND

REMOVE COMPLETE TO ELECTRICAL PANEL.

13. CIRCUIT NUMBERS INDICATED ON PLAN DO NOT INDICATE ACTUAL CIRCUIT

BREAKERS POLE POSITION IN PANEL, BUT REPRESENT ITEMS GROUPED ON SAME

CIRCUIT.

14. PROVIDE AS-BUILT DRAWINGS INDICATING ALL ACTUAL LIGHTING CIRCUITS.

15. FIELD VERIFY ALL PANELS AND EXISTING CIRCUITING SERVING EXISTING AND

NEW LIGHT FIXTURES.

16. PROVIDE NEW TYPE WRITTEN PANEL LEGENDS FOR ALL PANELS AFFECTED BY

NEW SCOPE OF WORK.

17. VERIFY DEVICE & COVERPLATE COLORS WITH ARCHITECT PRIOR TO THE START

OF CONSTRUCTION.

18. LIGHT SWITCHES ON THIS PLAN SHALL BE NEW, UNLESS OTHERWISE NOTED.

19. WHERE MULTIPLE SWITCHES ARE GROUPED TOGETHER, PROVIDE A SINGLE

SHARED COVERPLATE.

20. FOR LIGHTING CONTROL AND OCCUPANCY SENSOR REQUIREMENTS, REFER TO

SPECIFICATIONS.

21. OCCUPANCY SENSORS AND POWER PACKS SHALL BE RATED FOR THE LOAD

INDICATED TO BE SERVED. PROVIDE MULTIPLE POWER PACKS WHERE REQUIRED.

22. MAINTAIN MANUFACTURER RECOMMENDED SPACING BETWEEN OCCUPANCY

SENSORS AND HVAC DEFFUSERS AND FANS. ADJUST LOCATIONS AS REQUIRED.

23. UNLESS NOTED OTHERWISE, CONDUCTORS SHALL BE #12 AWG MINIMUM.

24. SEE ORIGINAL BUILDING DRAWINGS FOR EXISTING CIRCUIT LOCATIONS.

25. PROVIDE BLANK COVERPLATE FOR UN-USED WALL SWITCH BOXES.

26. PROVIDE UPDATED TYPE WRITTEN PANEL DIRECTORIES REFLECTING CIRCUIT

CHANGES.

27. LIQUID TIGHT FLEXIBLE CONDUIT MAY ONLY BE USED FOR FINAL CONNECTION TO

MOTORIZED EQUIPMENT 6'-0" LENGTH MAXIMUM.

28. EXTERIOR CONDUITS SHALL BE RIGID GALVANIZED STEEL (RGS) CONDUIT.

29. WHERE UNGROUNDED CONDUCTORS ARE INCREASED IN SIZE FROM THE MINIMUM

SIZE THAT HAS SUFFICIENT AMPACITY FOR THE INTENDED INSTALLATION, WIRE-

TYPE EQUIPMENT GROUNDING CONDUCTORS, WHERE INSTALLED, SHALL BE

INCREASED IN SIZE PROPORTIONATELY ACCORDING TO THE CIRCULAR MIL AREA

OF THE UNGROUNDED CONDUCTORS PER NEC 250.122(B).

30. ROOF PENETRATIONS SERVING MECHANICAL EQUIPMENT SHALL BE ROUTED THRU

THE EQUIPMENT CURB AND COORDINATED WITH MECHANICAL TRADES.

GENERAL NOTES:

NEW

EXISTING

DEMOLISHED

PHASE LINE TYPES

ELECTRICAL SHEET INDEX:

E0.01.1 GENERAL ELECTRICAL NOTES, SYMBOLS & ABBREVIATIONS

ED1.10.1 FIRST FLOOR DEMOLITION PLAN - UNIT A

E1.10.1 FIRST FLOOR PLAN - UNIT A

E5.01.1 ELECTRICAL DETAILS

E6.01.1 ELECTRICAL SCHEDULES

E7.01.1 ELECTRICAL ONE LINE DIAGRAM

ELECTRICAL FIXTURE LEGEND

DISCONNECT SWITCH, NON-FUSED, HEAVY DUTY, HP-RATED - ASSUME 30

AMP SWITCH UNO ON ONE LINE DIAGRAM OR FLOOR PLANS.

DUPLEX RECEPTACLE AT 18" AFF

QUAD RECEPTACLE AT 46" AFF

SIMPLEX RECEPTACLE, NEMA CONFIGURATION AS NOTED

DATA LEGEND

PROVIDE CONDUIT, EMPTY BOX AND PULL ROPE

09.12.2025 DESIGN DEVELOPMENT

09.23.2025 ADDENDUM 01

OS

OS

OS

OS

OS

OS

OS

OS

s s

D

B

A

A C E H

Aa

Aa

F

F

I

IK

D O

W N

D O

W N

CORRIDOR

A-21

LOBBY

STAGE

VEST

AUDITORIUM

CORRIDOR

A-20

ST

ENSEMBLE

CHORAL RM

CORR

602a

PR

PR

PR

PR

PR

PR

BAND RM

M DRESSING

273 W DRESSING

PASSAGE

A-4

44444

4 4 4 4 4

4 4 4 4 444

4 4 4 4

4 4444

4 4 4 4 4

MAINTAIN 400A-3P DISCONNECT SWITCH

MAINTAIN CIRCUIT FOR REUSE.

PREP FOR EXTENSION TO NEW

ELECTRICAL PANEL AT STAGE RIGHT.

REMOVE DIMMER PANEL "S"

INCLUDING WIRING AND CONDUIT

TO DISCONNECT SWITCH.

REMOVE BORDER LIGHTING

INCLUDING CIRCUITS TO

DIMMING PANEL "S"

REMOVE BORDER AND

CYCLORAMA LIGHTING

INCLUDING CIRCUITS TO

DIMMING PANEL "S"

REMOVE SPOT LIGHTING INCLUDING

CIRCUITS TO DIMMER PANEL "S"

AUDITORIUM

1 1

6 6

2 2

4 4

14-2

F-2

A-2

D-2

G-2

B-2

F-3

I

H-2 K

Aa

E-2C-2

27-2

H-3

A-3

27-3

MEP CONSULTING ENGINEER

OWNER JOB NO.

SHEET NO.

TC JOB NO.

PROJECT TITLE

FED

B C

Bn

A

G

N

SHEET TITLE

KEY PLAN

PR

EL

IM

IN

AR

Y

NOT

FO

R C

ONST

RUCT

IO

N

491 E. WRIGHT AVE.

SHEPHERD, MI 48883

(PH) 989-567-1100

info@KTSEngineeringGroup.com

ED1.10.1

FIRST FLOOR

DEMOLITION PLAN

- UNIT A

KTS PROJECT NO. 25-0275

3550 E River Road Oscoda, Michigan 48750

Oscoda High School Misc Renovation

107348

Oscoda Area Schools

KEY NOTES:

1 EQUIPMENT TO REMAIN TO REMAIN IN PLACE.

2 DISCONNECT AND REMOVE 120 VAC LIGHT SWITCH AND WIRING FROM LIGHT

SWITCH TO FIRST ACTIVE CEILING JUNCTION BOX. PREP FOR INSTALLATION

OF NEW LIGHTING SWITCH AND LOW VOLTAGE WIRING IN SAME LOCATION.

4 DISCONNECT AND REMOVE LIGHT FIXTURE. MAINTAIN EXISTING CIRCUIT AND

PREP FOR NEW LIGHT FIXTURE IN SAME LOCATION.

6 DISCONNECT AND REMOVE INCLUDING WIRING AND CONDUIT TO SOURCE.

1/8" = 1'-0"ED1.10.1

FIRST FLOOR DEMOLITION PLAN - UNIT A1

09.12.2025 DESIGN DEVELOPMENT

B

OS

OS

OS

OS

OS

OS

OS

OS

OS OS OS

OS OS OS

OS OS OS

D

B

A

A C E H

Aa

Aa

F

F

I

IK

B

D O

W N

D O

W N

B

2 3

DOC

L42 L42 L42

(2) 1 1/4"C

ROUTE (2) CONDUITS

DOWN TO BELOW

PLATFORM

S- 9

S- 17 S- 17 S- 17

S- 11

S- 75

TOP FACE CLG S- 75

TOP FACE CLG

S- 75S- 75

S- 75

TF-251

S-75

D50I

D50I D50 D50 D50 D50 D50 D50 D50I

D50ID50D50ID50D50I

D50I D50 D50I D50 D50I

D50I D50 D50I D50 D50I

D50ID50D50ID50D50I

D50I D50 D50I D50 D50I

D50ID50D50ID50

D50I

PR

ST

PR

CHORAL RM

ENSEMBLE

PR

PR

PR

PR

BAND RM

M DRESSING

273 W DRESSING

CORR

602a

PASSAGE

A-4

CORRIDOR

A-21

LOBBY

STAGE

VEST

AUDITORIUM

CORRIDOR

A-20

MAIN STAGE RACK

XH

XH

XH

S-2 S-3 S-4

S-1

XH

XH

S-5 S-6

S-7

S

3 3

12 13 14 15

4 11

28 33

S-

,5

L6 -2

0R

S- 8, L6

-2 0R

3RD ELECTRIC

2ND ELECTRIC

4TH ELECTRIC

5TH ELECTRIC

S-

,2

L6 -2

0R

S-

,4

L6 -2

0R

S-

,4

L6 -2

0R S-

,3

L6

-2 0R

S-

,2

L6 -2

0R S-

,1

L6

-2 0R

6 7

8 9 10

30 31

S- 48

ABOVE APRON ABOVE APRON

S- 50 S- 52

F.F.F.F.

S- 29,31 L6-20R

S- 37,39 L6-20R

E1.10.1

XH XH

STAGE RT. DMX

(2) 1 1/4"C

(2

/4 "C

(2

/4 "C

(1

"C

"C

JUNCTION

BOX (TYP.)

S-

S-

S-

S- 33 S- 35

S- 41 S- 43

S-

S-

S- 19

HOUSE LIGHTING

CONTROLLER

S- 21

S-

S-

S-

S-

S-

S-

S-

S-

S-

S-

S-

TV TV

F. F.

S-

VERIFY DOWNLIGHT

SIZE PRIOR TO

ORDERING. (TYP.)

ENLARGE EXISTING

OPENING TO

FIT NEW RACEWAY.

LIGHTING &

POWER BATTEN (TYP.)

PAINT CONDUIT

TO MATCH

WALL SURFACE

(TYP.)

35 35

X-PNL.

EXTEND EXISTING 400A CIRCUIT FROM

DISCONNECT SWITCH TO NEW PANEL S

LV LV

LVLV

S-

1ST ELECTRIC

TF-251

INSTALL TRANSFER FAN IN STORAGE ROOM CEILING.

INSTALL RIGID METAL DUCT FROM DISCHARGE OF FAN

ABOVE LID OF STORAGE ROOM AND TURN HORIZONTALLY

TOWARD CENTER OF STORAGE. INSTALL DUCTWORK

SUCH THAT IT IS NOT VISIBLE FROM AUDITORIUM FLOOR

DOOR TO BE UNDERCUT

FOR AIR TRANSFER.

SEE ARCHITECTURAL

MEP CONSULTING ENGINEER

OWNER JOB NO.

SHEET NO.

TC JOB NO.

PROJECT TITLE

FED

B C

Bn

A

G

N

SHEET TITLE

KEY PLAN

PR

EL

IM

IN

AR

Y

NOT

FO

R C

ONST

RUCT

IO

N

491 E. WRIGHT AVE.

SHEPHERD, MI 48883

(PH) 989-567-1100

info@KTSEngineeringGroup.com

E1.10.1

FIRST FLOOR PLAN

- UNIT A

KTS PROJECT NO. 25-0275

3550 E River Road Oscoda, Michigan 48750

Oscoda High School Misc Renovation

107348

Oscoda Area Schools

ACCEPTABLE MANUFACTURERS: GREENHECK, COOK, BROAN, PANASONIC.

COMMENTS:

1. PROVIDE WITH STANDARD DESIGNER GRILLE.

2. PROVIDE WITH FACTORY MOUNTED DISCONNECT.

3. PROVIDE WITH ELECTRONICALLY COMMUTATED MOTOR WITH SPEED ADJUSTMENT. SPEED CONTROL TO BE USED FOR BALANCING PURPOSES.

TRANSFER FAN SCHEDULE

TAG

BASIS OF DESIGN

CFM E.S.P.

(in-wg)

FAN SPEED (RPM)

DRIVE TYPE SONES

ELECTRICAL DATA DISCONNECT BY

VFD CONTROL COMMENTS

MANUFACTURER

MODEL Fan RPM Max Fan

RPM

MOTOR POWER VOLTAGE M.T.C. E.T.C.

TF-251 Greenheck SP-LP0810W 100 0.10 894 894 Direct 1.5 4.06 W 120V / 1Ø X CONTINUOUS OPERATION 1, 2, 3

1/4" = 1'-0"E1.10.1

ENLARGED PLAN2

1/8" = 1'-0"E1.10.1

FIRST FLOOR PLAN - UNIT A1

KEY NOTES:

1 A-1: 120V/20A AUXILLARY CIRCUIT WITH RECEPTACLES SIDE OF WORK DESK.

2 C-1: 120V/20A CIRCUIT WITH 3 QUAD RECEPTACLE BOXES UNDER WORK DESK

EVENLY SPACED.

3 A-3: 120V/20A AUXILLARY CIRCUIT WITH RECEPTACLES SIDE OF WORK DESK.

4 L-1: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-2: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

5 L-3: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE.

6 L-4: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

7 L-5: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

8 L-6: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE.

9 L-7: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

10 L-8: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

11 L-9: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-10: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

12 L-11: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-12: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX. ELECTRIC BOXES ARE CLAMPED TO

THE BATTEN FOR ALL FLOWN LINE SETS, REFER TO THE EQUIPMENT DIAGRAM

FOR PLACEMENT. MOVE POWER CABLES OFF OF THE PIPE FOR INSTRUMENT

CLAMPS, PROVIDE BLACK VELCRO TO KEEP ALL CABLING AGAINST THE PIPE.

USE STANDARD PRACTICES FOR POWER/DATA DISTRIBUTION TO THE LINE

SETS, ALLOWING FOR ADJUSTMENT OF +/- 2' UP OR DOWN.

13 L-13: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

14 L-14: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-15: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

15 L-16: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

16 L-17: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-18 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

17 L-19: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

18 L-20: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-21: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

19 L-22: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

20 L-23: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-24: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

21 L-25: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

22 L-26: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-27: 120V/20A

CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

23 L-28: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

24 C-2: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX. PROVIDE SHELF 2'

WIDE BY 1' DEEP (10'-0" A.F.F.) FOR THE DMX DISTRIBUTORS.

25 A-3: 120V/20A AUXILLARY CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

26 A-4: 120V/20A AUXILLARY CIRCUIT WITH 1 QUAD RECEPTACLE BOX.

27 C-3: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX, ALSO ANOTHER

2-GANG BOX WITH 1 SWITCH CONTROLLING A DUPLEX RECEPTACLE. MOUNT

MAIN STAGE A/V RACK 5'-0" A.F.F.

28 V-1: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX FRONT SIDE AND 1

QUAD RECEPTACLE BOX BACK SIDE FOR TV.

29 S-1: 120V/20A CIRCUIT WITH 1 DUPLEX RECEPTACLE FOR MAIN SPEAKER

POWER. MOUNT TO WALL.

30 S-2: 120V/20A CIRCUIT WITH 1 QUAD RECESSED RECEPTACLE IN 4-GANG

FLOOR BOX (OTHER 2 GANG ARE FOR XLR AND DMX). LOCATED IN EXISTING

4-GANG FLOOR POCKET WHICH WILL HAVE POWER, XLR, AND DMX CIRCUITS

FOR VARIOUS EQUIPMENT.

31 S-3: 120V/20A CIRCUIT WITH 1 QUAD RECESSED RECEPTACLE IN 4-GANG

FLOOR BOX (OTHER 2 GANG ARE FOR XLR AND DMX). LOCATED IN EXISTING

4-GANG FLOOR POCKET WHICH WILL HAVE POWER, XLR, AND DMX CIRCUITS

FOR VARIOUS EQUIPMENT.

32 S-1: 120V/20A CIRCUIT WITH 1 DUPLEX RECEPTACLE FOR MAIN SPEAKER

POWER. MOUNT TO WALL.

33 V-2: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX FRONT SIDE AND 1

QUAD EDISON RECEPTACLE BOX BACK SIDE FOR TV.

34 LOCATE ON TOP FACE OF CEILING.

35 CONNECT TO EXISTING CIRCUIT.

1/4" = 1'-0"E1.10.1

MECHANICAL PLAN3

08.15.2025 CONSTRUCTION

ELECTRICAL CIRCUIT SCHEDULE

CIRCUIT LEGEND:

A: AUXILIARY CIRCUIT

PANEL LABELLING MUST IDENTIFY ALL LIGHTING

CIRCUITS AND ALL SOUND CIRCUITS CLEARLY FOR

SYSTEM STARTUP AND SHUTDOWN ON A REGULAR

BASIS. HOUSE LIGHTING CIRCUITS ARE INCLUDED IN

THE ELECTRICAL PANEL.

C: CONTROL SYSTEMS CIRCUIT

L: LIGHTING SYSTEM CIRCUIT

S: SOUND SYSTEM CIRCUIT

V: VIDEO SYSTEM CIRCUIT

LOC. DESCRIPTION CIRCUITS EST. AMPS. NOTES

CONTROL BOOTH HOUSE

RIGHT

A-1: 120V/20A AUXILLARY CIRCUIT

WITH RECEPTACLES BOTH SIDES OF

CONTROL DESK SPACED NORMALLY.

CONTROL BOOTH UNDER

DESK, MAIN BOOTH

CONTROL RACK

C-1: 120V/20A CIRCUIT WITH 3 QUAD

RECEPTACLE BOXES UNDER DESK

EVENLY SPACED

CONTROL BOOTH HOUSE

LEFT

A-2: 120V/20A AUXILLARY CIRCUIT

WITH RECEPTACLES BOTH SIDES OF

CONTROL DESK SPACED NORMALLY.

HOUSE RIGHT LIGHTING

LADDER

L-1: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-2:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

4.13 & 5

HOUSE 1 ELECTRIC (AUD.

COVE)

L-3: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE

10.34

HOUSE 1 ELECTRIC (AUD.

COVE)

L-4: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

9.17

HOUSE 1 ELECTRIC (AUD.

COVE)

L-5: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

6.25

HOUSE 1 ELECTRIC (AUD.

COVE)

L-6: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE

9.3

HOUSE 1 ELECTRIC (AUD.

COVE)

L-7: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

6.25

HOUSE 1 ELECTRIC (AUD.

COVE)

L-8: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

9.17

HOUSE LEFT LIGHTING

LADDER

L-9: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-10:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

4.13

12 FIRST ELECTRIC

L-11: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-12:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

12.55 & 6.25

ELECTRIC BOXES ARE CLAMPED TO THE BATTEN

FOR ALL FLOWN LINE SETS, REFER TO THE

DIAGRAM FOR PLACEMENT. ALSO, POWER

CABLES MUST BE ABLE TO BE MOVED OFF THE

PIPE FOR INSTRUMENT CLAMPS, PROVIDE

BLACK VELCRO TO KEEP ALL CABLING AGAINST

THE PIPE. USE STANDARD PRACTICES FOR

POWER/DATA DISTRIBUTION TO THE LINE

SETS, ALLOWING FOR ADJUSTMENT OF +/- 2'

UP OR DOWN.

13 FIRST ELECTRIC

L-13: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

5.8

14 FIRST ELECTRIC

L-14: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-15:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

11.51 & 6.25

15 FIRST ELECTRIC

L-16: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

5.8

16 SECOND ELECTRIC

L-17: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-18:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

12.69 & 6.24

17 SECOND ELECTRIC

L-19: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

4.16

18 THIRD ELECTRIC

L-20: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-21:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

13.72 & 4.16

19 THIRD ELECTRIC

L-22: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

2.08

20 FOURTH ELECTRIC

L-23: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-24:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

12.69 & 4.16

21 FOURTH ELECTRIC

L-25: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

2.08

22 FIFTH ELECTRIC

L-26: 208-240V/20A CIRCUIT WITH 1

TWISTLOCK RECEPTACLE, L-27:

120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

15.87

23 FIFTH ELECTRIC

L-28: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

STAGE RIGHT DMX

DISTRIBUTION (10' AFF),

HOUSE LIGHT

CONTROL/(DIMMERS),

BREAKERS/POWER

DISTRIBUTION

C-2: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX

PROVIDE SHELF 2' WIDE BY 1' DEEP (10' AFF)

FOR THE DMX DISTRIBUTORS.

STAGE LEFT PROSCENIUM

BACK WALL (16" AFF)

A-3: 120V/20A AUXILLARY CIRCUIT

WITH 1 QUAD RECEPTACLE BOX

STAGE RIGHT PROSCENIUM

BACK WALL (16" AFF)

A-4: 120V/20A AUXILLARY CIRCUIT

WITH 1 QUAD RECEPTACLE BOX

STAGE RIGHT WING,

MAIN

STAGE RACK (5' AFF)

C-3: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX, ALSO ANOTHER

2-GANG BOX WITH 1 SWITCH

CONTROLLING A DUPLEX RECEPTACLE

MAIN STAGE RACK FOR CONTROL AND SOUND

SYSTEM

STAGE LEFT PROSCENIUM

FRONT/BACK WALL (10' AFF,

6' OUT FROM PROSCENUIM)

V-1: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX FRONT SIDE AND 1

QUAD RECEPTACLE BOX BACK SIDE

FOR TVS

THIS IS 10' ABOVE STAGE FINISH HEIGHT AND

6' OUT FROM THE PROSCENUIM EDGE ON BOTH

SIDES OF THE WALL FOR TVS ON BOTH SIDES

OF THE WALL - AUDIENCE TVS AND ACTOR TV

MONITORS

STAGE LEFT CEILING ABOVE

APRON

S-1: 120V/20A CIRCUIT WITH 1

DUPLEX RECEPTACLE FOR MAIN

SPEAKER POWER

30 STAGE LEFT APRON

S-2: 120V/20A CIRCUIT WITH 1 QUAD

RECESSED RECEPTACLE IN 4-GANG

FLOOR BOX (OTHER 2 GANG ARE FOR

XLR AND DMX)

LOCATED IN A 4-GANG FLOOR POCKET WHICH

WILL HAVE POWER, XLR, AND DMX CIRCUITS

FOR VARIUS EQUIPMENT

31 STAGE RIGHT APRON

S-3: 120V/20A CIRCUIT WITH 1 QUAD

RECESSED RECEPTACLE IN 4-GANG

FLOOR BOX (OTHER 2 GANG ARE FOR

XLR AND DMX)

LOCATED IN A 4-GANG FLOOR POCKET WHICH

WILL HAVE POWER, XLR, AND DMX CIRCUITS

FOR VARIUS EQUIPMENT

STAGE RIGHT CEILING

ABOVE APRON

S-1: 120V/20A CIRCUIT WITH 1

DUPLEX RECEPTACLE FOR MAIN

SPEAKER POWER

NOTE THIS IS THE SAME CIRCUIT AS IN

LOCATION 29

STAGE RIGHT PROSCENIUM

FRONT/BACK WALL (10' AFF,

6' OUT FROM PROSCENUIM)

V-2: 120V/20A CIRCUIT WITH 1 QUAD

RECEPTACLE BOX FRONT SIDE AND 1

QUAD RECEPTACLE BOX BACK SIDE

FOR TVS

THIS IS 10' ABOVE STAGE FINISH HEIGHT AND

6' OUT FROM THE PROSCENUIM EDGE ON BOTH

SIDES OF THE WALL FOR TVS ON BOTH SIDES

OF THE WALL - AUDIENCE TVS AND ACTOR TV

MONITORS

CONDUIT SCHEDULE

RUN# LOCATION 1 LOCATION 2 DESCRIPTION/TABLES CONDUIT NOTES

1 #2 #27

PRIMARY TRUNK FOR CONTROL

SYSTEMS, 2X OM3 10G FIBER

WITH LC ENDS, 8 X CAT6

REQUIRES 1X 2" UNBROKEN CONDUIT

WITH PULL STRING, AND 1X JUNCTION

BOX 16"X16"X8" AT LOCATION #27

JUNCTION BOX AT #27 ABOUT 5' AFF

AND WILL BE A COMMON JUNCTION

POINT FOR OTHER RUNS

2 #27

#33 (BACK

SIDE)

PRIMARY DATA DISTRIBUTION ON

STAGE, 31 X CAT6, 12 X AUDIO

MIC CABLE

REQUIRES 2X 2" UNBROKEN CONDUIT

WITH PULL STRING, AND 1X JUNCTION

BOX 16"X16"X8" AT LOCATION #33

(BACK SIDE)

JUNCTION BOX AT #33 (BACK SIDE)

ABOUT 10' AFF ON THE BACK SIDE

(STAGE SIDE) OF PROSCENIUM WALL

AND WILL BE A COMMON JUNCTION

POINT FOR OTHER RUNS

#33 (BACK

SIDE)

#28 (BACK

SIDE)

DISTRIBUTION TO STAGE LEFT,

24 X CAT6, 9 X AUDIO MIC CABLE

REQUIRES 2X 2" UNBROKEN CONDUIT

WITH PULL STRING, AND 1X JUNCTION

BOX 16"X16"X8" AT LOCATION…