This is an Addendum (No. 02) for the Oscoda Area Schools Miscellaneous Renovation Phase 1 project, prepared by The Collaborative architectural firm for Oscoda Area Schools in Michigan. The addendum supplements and amends the original drawings and specifications for a renovation project at the high school, with a project number of 107348. The document includes clarifications on various technical aspects of the project, such as door hardware, electrical systems, stage lighting, and equipment installation. Key details include specifications for electrical circuits, conduit runs, lighting fixtures, and stage equipment, with precise instructions for contractors on installation, wiring, and equipment placement.
The addendum provides detailed technical guidance for electrical and stage infrastructure work, including circuit descriptions, receptacle locations, lighting fixture specifications, and conduit routing. Notable elements include a transfer fan (TF-251) installation in the storage room, extensive stage lighting and audio-visual system preparations, and specific electrical circuit configurations. The document indicates that the district is separately working with an AV contractor and that certain existing systems will be maintained or modified. The electrical plans show a comprehensive approach to renovating the auditorium and stage areas, with careful attention to power distribution, lighting control, and system integration.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
09/23/2025
ADDENDUM NO. 02
To the Drawings and Specifications for:
Oscoda Area Schools Miscellaneous Renovation Phase 1
107348
Oscoda Area Schools
Prepared By:
The Collaborative
Telephone: (419) 242-7405 Fax: (419) 242-7400
TO ALL BIDDERS:
This addendum supplements and amends the original drawings and specifications, and shall be taken into account in preparing proposals, and shall become a part of the contract documents. Receipt of this Addendum must be acknowledged in the Bid Form.
ADDENDUM NO. 002
GENERAL
Question 1: I am looking to clarify on the door schedule. It has removeable mullion, but no hardware. Is the bid to include hardware, or just doors and frame? If just doors and frame, what hardware will be on these to make sure correct prep is done. If bid is to have hardware, could you please provide list of what and basis of manufacture?
Answer 1: See attached for the door hardware spec sheet that was missing. Door 267B will have hardware set 1.0
Question 2: Will the seating that is being removed by others be completely removed from the space before commencement of the contract and for the duration of the project?
Answer 2: The seating will be removed by the district and will be gone for the duration of the contract.
Question 3: Is the asbestos report purely for information and not intended to imply any responsibility for abatement or handling under this contract?
Answer 3: Correct, we do not have any asbestos remediation as a part of this work but provided it purely for information.
Question 4: Is the TF-251 fan considered mechanical work as shown on the electrical plans and require a mechanical contractor and a mechanical permit or is this unit an electric device that will fall under the electrical permit?
Answer 4: The work for TF-251 is to be performed under the electrical contractor’s scope
Question 5: We were unable to attend the prebid meeting and would like to visit the site. Who do we contact for access?
Answer 5: You would have to reach out to Tony Brooks:
brookst@oscodaschools.org. School is currently in session so they may not be able to accommodate your request, but Tony will be able to schedule a time if they are free
Question 6: EC to only provide power feeds and empty raceways based on sheet E6.01?
Answer 6: Correct.
Question 7: Who is to provide AV equipment, cabling, AV devices, controller ETC?
Answer 7: The district is already working with an AV contractor and installer:
Eric Joseph erockcmu@gmail.com
Question 8: Is OHS currently working with AV contractor on system design and installation?
Answer 8: Yes, see question 7
Question 9: Is there access under stage?
Answer 9: Yes, the front of the stage can be opened to allow access underneath.
Question 10: All type D50I and D50 fixtures switched from LV switching shown on sheet E1.10?
Looks as if center and both outside rows appear to not have switching called out.
Answer 10: The center and both outside rows will be switched by the DMX system via circuit S-1. All exterior perimeter light labeled as existing are in an asbestos containing ceiling and are being left as is.
Question 11: Both Floor Boxes shown on sheet E1.10 to remain and reuse for new power/DMX control?
Answer 11: Provide new 4-gang floor pocket for quad power, (1) gang DMX and (1) gang XLR similar or equal to Ace Backstage Co. Incorporated model 122SLBK . Confirm dimensions for installation in stage floor.
Question 12: Is EC or others to provide ‘Quad Edison Receptacle Box”
Answer 12: The E.C. is to provide the Quad Edison Receptacle Boxes.
Question 13: Are “Edison Boxes” required if not provided by other or will metal 4sq with raised covers be adequate installation method?
Answer 13: ‘Quad Edison Receptacle Box” should just be a 4” square box with 2-duplex ( four receptacles) raised covers. Keynote wording has been updated to reflect this change.
CLARIFICATIONS:
• See attached hardware specs
DRAWINGS:
Electrical Drawings Drawing E1.10 Drawing E.01.1 Item E1: Revise drawing numbers to indicate phase.
Drawing ED1.10.1 Item E1: Add first electric batten.
Drawing E1.10.1 Item E1: Add first electric batten.
Item E2: Revise batten outlet location.
Item E3: Revise keynote 12.
ddewitt Pen
Drawing E6.01.1 Item E1: Revise electrical circuit schedule location 12 note.
END OF ADDENDUM #02 (04 Written Pages, 04 Drawings, 01 Specification Section)
NEW COMMUNITY CENTER (OSCODA AREA SCHOOLS) 107167
OSCODA, MI
DOOR HARDWARE SCHEDULE 080671 - 1
SECTION 080671 – DOOR HARDWARE SCHEDULE
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section references specification sections relating to commercial door hardware for the following:
1. Swinging doors.
2. Sliding Doors.
3. Other doors to the extent indicated.
B. Commercial door hardware includes, but is not necessarily limited to, the following:
1. Mechanical door hardware.
2. Electromechanical and access control door hardware.
3. Electromechanical and access control door hardware power supplies, back-ups and surge protection.
4. Automatic operators.
5. Cylinders specified for doors in other sections.
C. Related Sections:
1. Division 08 Section “Door Hardware”.
2. Division 08 Section “Automatic Door Operators”.
3. Division 28 Section “Access Control Hardware Devices”.
D. Codes and References: Comply with the version year adopted by the Authority Having
Jurisdiction.
1. ANSI A117.1 - Accessible and Usable Buildings and Facilities.
2. ICC/IBC - International Building Code.
3. NFPA 70 - National Electrical Code.
4. NFPA 80 - Fire Doors and Windows.
5. NFPA 101 - Life Safety Code.
6. NFPA 105 - Installation of Smoke Door Assemblies.
7. State Building Codes, Local Amendments.
DOOR HARDWARE SCHEDULE 080671 - 2
E. Standards: Reference Related Sections for requirements regarding compliance with applicable industry standards.
1.3 SUBMITTALS
A. Product Data: Manufacturer's product data sheets including installation details, material descriptions, dimensions of individual components and profiles, operational descriptions and finishes.
B. Door Hardware Schedule: Prepared by or under the supervision of supplier, detailing fabrication and assembly of door hardware, as well as procedures and diagrams. Coordinate the final Door
Hardware Schedule with doors, frames, and related work to ensure proper size, thickness, hand, function, and finish of door hardware.
1. Format: Comply with scheduling sequence and vertical format in DHI's "Sequence and
Format for the Hardware Schedule."
2. Organization: Organize the Door Hardware Schedule into door hardware sets indicating complete designations of every item required for each door or opening. Organize door hardware sets in same order as in the Door Hardware Sets at the end of Part 3. Submittals that do not follow the same format and order as the Door Hardware Sets will be rejected and subject to resubmission.
3. Content: Include the following information:
a. Type, style, function, size, label, hand, and finish of each door hardware item.
b. Manufacturer of each item.
c. Fastenings and other pertinent information.
d. Location of door hardware set, cross-referenced to Drawings, both on floor plans and in door and frame schedule.
e. Explanation of abbreviations, symbols, and codes contained in schedule.
f. Mounting locations for door hardware.
g. Door and frame sizes and materials.
4. Submittal Sequence: Submit the final Door Hardware Schedule at earliest possible date, particularly where approval of the Door Hardware Schedule must precede fabrication of other work that is critical in the Project construction schedule. Include Product Data, Samples, Shop Drawings of other work affected by door hardware, and other information essential to the coordinated review of the Door Hardware Schedule.
C. Keying Schedule: Prepared under the supervision of the Owner, separate schedule detailing final keying instructions for locksets and cylinders in writing. Include keying system explanation, door numbers, key set symbols, hardware set numbers and special instructions.
Owner to approve submitted keying schedule prior to the ordering of permanent cylinders.
D. Product Test Reports: Indicating compliance with cycle testing requirements, based on evaluation of comprehensive tests performed by manufacturer and witnessed by a qualified independent testing agency.
DOOR HARDWARE SCHEDULE 080671 - 3
E. Operating and Maintenance Manuals: Provide manufacturers operating and maintenance manuals for each item comprising the complete door hardware installation in quantity as required in Division 01, Closeout Submittals. The manual to include the name, address, and contact information of the manufacturers providing the hardware and their nearest service representatives. The final copies delivered after completion of the installation test to include "as built" modifications made during installation, checkout, and acceptance.
F. Warranties and Maintenance: Special warranties and maintenance agreements specified in the
Related Sections.
1.4 DELIVERY, STORAGE, AND HANDLING
A. Inventory door hardware on receipt and provide secure lock-up and shelving for door hardware delivered to Project site. Do not store electronic access control hardware, software or accessories at Project site without prior authorization.
B. Tag each item or package separately with identification related to the final Door Hardware
Schedule, and include basic installation instructions with each item or package.
C. Deliver, as applicable, permanent keys, cylinders, cores, access control credentials, software and related accessories directly to Owner via registered mail or overnight package service.
Instructions for delivery to the Owner shall be established at the "Keying Conference".
1.5 WARRANTY
A. General Warranty: Reference Division 01, General Requirements. Special warranties specified in this Article shall not deprive Owner of other rights Owner may have under other provisions of the Contract Documents and shall be in addition to, and run concurrent with, other warranties made by Contractor under requirements of the Contract Documents.
1.6 MAINTENANCE SERVICE
A. Maintenance Tools and Instructions: Furnish a complete set of specialized tools and maintenance instructions as needed for Owner's continued adjustment, maintenance, and removal and replacement of door hardware.
PART 2 - PRODUCTS
2.1 SCHEDULED DOOR HARDWARE
A. Refer to “PART 3 – EXECUTION” for required specification sections.
DOOR HARDWARE SCHEDULE 080671 - 4
PART 3 - EXECUTION
3.1 DOOR HARDWARE SETS
A. The door hardware sets represent the design intent and direction of the owner and architect.
They are a guideline only and should not be considered a detailed hardware schedule.
Discrepancies, conflicting hardware and missing items should be brought to the attention of the architect with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality.
1. Quantities listed are for each pair of doors, or for each single door.
2. The supplier is responsible for handing and sizing all products.
3. Where multiple options for a piece of hardware are given in a single line item, the supplier shall provide the appropriate application for the opening.
4. At existing openings with new hardware the supplier shall field inspect existing conditions prior to the submittal stage to verify the specified hardware will work as required. Provide alternate solutions and proposals as needed.
B. Products listed in the hardware sets shall be supplied by and in accordance with the requirements described in the specification section as noted for each item.
1. Section 08 71 00 – Door Hardware.
2. Section 08 71 13 – Automatic Door Operators.
3. Section 28 15 00 – Access Control Hardware Devices.
C. Manufacturer’s Abbreviations:
1. MK - McKinney
2. PE - Pemko
3. MR - Markar
4. SU - Securitron
5. RO - Rockwood
6. RU - Corbin Russwin
7. RI - RITE Door
8. AD - Adams Rite
9. SA - SARGENT
10. HS - HES
11. RF - Rixson
12. NO - Norton
13. HI - Hiawatha
14. OT - Other
15. YA - ASSA ABLOY ACCENTRA
DOOR HARDWARE SCHEDULE 080671 - 5
Hardware Sets
Set: 1.0
Doors: 267B
6 Hinge, Full Mortise TA2714 (NRP) US26D MK 087100
2 Flush Bolt 555 US26D RO 087100
1 Dust Proof Strike 570 US26D RO 087100
1 Storeroom Lock ML2057 NSA CT6SB 626 RU 087100
2 Surf Overhead Stop 10-336 630 RF 087100
2 Silencer 608-RKW RO 087100
END OF SECTION 080671
GENERAL DEMOLITION NOTES:
1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
EQUIPMENT SHALL BE COORDINATED WITH BUILDING STRUCTURE, EQUIPMENT
FURNISHED, ARCHITECTURAL DRAWINGS AND ALL OTHER TRADES PRIOR TO
DEMOLITION.
2. DEMOLITION SHALL BE APPROVED BY THE OWNER PRIOR TO COMMENCEMENT AND
SHALL BE PERFORMED UNDER REQUIREMENTS AND APPROVAL OF THE LOCAL CODE
JURISDICTIONS.
3. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN APPROVED
MANNER ANY SUCH WORK WHICH BECOMES DAMAGED. THIS INCLUDES BUT NOT
LIMITED TO CEILING PROJECTORS, POWER POLES, WIFI ACCESS POINTS AND SMOKE
DETECTORS.
4. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING
REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE DOCUMENTS OR
SHOWN NOT MATCHING FIELD CONDITIONS.
5. ELECTRICAL CONTRACTOR SHALL EXAMINE THE PROJECT DOCUMENTS AND VISIT THE
SITE AS THEY DEEM NECESSARY PRIOR TO SUBMITTING A BID. DO NOT RELY SOLELY
ON THE ELECTRICAL PLANS FOR ALL DEMOLITION REQUIREMENTS. REVIEW ALL
PROJECT DOCUMENTS PRIOR TO SUBMITTING A BID. IF A DEPARTURE FROM THE
DESIGN INTENT OF THE DOCUMENTS IS REQUIRED DUE TO THE ACTUAL FIELD
CONDITIONS OBSERVED BY THE CONTRACTOR, THE CONTRACTOR SHALL NOTIFY THE
ARCHITECT IN WRITING FOR RESOLUTION PRIOR TO SUBMITTING FINAL BID OR
ENTERING INTO A CONTRACT FOR CONSTRUCTION. FAILURE TO PROVIDE THE
ARCHITECT WITH NOTIFICATION SHALL RESULT IN THE CONTRACTOR BEING HELD
RESPONSIBLE TO COMPLETE ALL WORK TO MEET THE DESIGN INTENT WITH NO
ADDITIONAL COST BEING INCURRED BY THE OWNER.
6. THE DEMOLITION INFORMATION IS PROVIDED TO ASSIST WITH LABOR COSTS
ASSOCIATED WITH THE ELECTRICAL SYSTEMS REMOVAL. THE DEMOLITION
CONTRACTOR WILL REMOVE ELECTRICAL COMPONENTS AS NOTED, BUT NOT LIMITED
TO THE DRAWINGS.
7. VERIFY EXTENT OF DEMOLITION WORK WITH INFORMATION SHOWN IN THE DRAWINGS
AND WORK THAT IS NOT SHOWN AND MAY BE REQUIRED TO COMPLETE THE INTENDED
WORK.
8. ALL WORK SHALL COMPLY WITH REQUIRED LOCAL CODES. CONTRACTOR IS
RESPONSIBLE FOR OBTAINING REQUIRED PERMITS AND INSPECTIONS FOR ALL WORK
ASSOCIATED WITH THIS CONTRACT.
9. CONTRACTOR SHALL REPAIR ALL DISTURBED AREAS AS REQUIRED TO MATCH
SURROUNDING EXISTING FINISHES NOT DISTURBED.
10. IN EXISTING AREAS, RENOVATION AND DEMOLITION WORK SHALL BE ACCOMPLISHED
WITH MINIMAL DISRUPTION TO OPERATIONS. IF REQUIRED, THE OWNER RESERVES
THE RIGHT TO TEMPORARILY STOP WORK OF SPECIFIC CONSTRUCTION OPERATIONS
SHOULD THE OWNER IDENTIFY AN EMERGENCY OR DANGER EXISTS TO THE WELFARE
OF THE OCCUPANTS ON ACCOUNT OF SUCH WORK OR OPERATIONS.
11. CONTRACTOR SHALL REMOVE AND DISPOSE OF ALL MATERIAL IN A LEGAL MANNER NOT
SCHEDULED FOR REUSE UNDER THIS PROJECT.
12. CONFIRM WITH THE ARCHITECTS OFFICE AND/OR CONSTRUCTION MANAGER, PROJECT
SCHEDULES AND REVIEW THE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL
DRAWINGS PRIOR TO COMMENCING DEMOLITION.
13. USE CARE DURING THE DEMOLITION PHASE TO AVOID DAMAGE TO ANY GLAZED BLOCK,
TILE OR BRICK VENEERED WALLS THAT ARE TO REMAIN.
14. DEMOLITION CONTRACTORS ARE RESPONSIBLE TO CONFIRM ALL QUANTITIES AND
DEMOLITION REQUIRED. COMPLETE DEMOLITION IS NOT SHOWN ON THE DRAWINGS.
15. DISCONNECT, REMOVE AND/OR RELOCATE ALL ITEMS AS SHOWN. IF THERE ARE ANY
ITEMS THAT ARE TO REMAIN, THEY ARE SPECIFICALLY NOTED SO ON THE DRAWINGS.
16. WHERE CONDUITS OR NON-METALLIC SHEATHED CABLE ARE ROUTED CONCEALED IN
WALL CAVITIES OF WALL THAT ARE TO REMAIN, ABANDON THE CONDUIT AND/OR
CABLE. CUT BACK TO THE POINT OF CONCEALMENT INSIDE THE WALL OR CEILING
CAVITY. CUT AND REMOVE THE CONDUIT EXITING THE WALL CAVITY INTO THE CEILING
SPACE. DISCONNECT AND REMOVE FEEDS FROM ELECTRICAL PANEL. REMOVE ALL
SURFACE MOUNTED OUTLET BOXES ASSOCIATED WITH THE CONDUIT SYSTEMS.
17. DISCONNECT AND REMOVE ALL ELECTRICAL EQUIPMENT INCLUDING HANGERS, PULL
BOXES, SWITCHES, LIGHT FIXTURES, CONDUIT AND WIRING FROM THE POINT OF
CONCEALMENT TO THE EQUIPMENT. DISPOSE OF ALL ITEMS (SPECIAL ATTENTION TO
LAMPS) AS REQUIRED BY LAW.
18. ELECTRICAL CONTRACTOR SHALL TAKE CARE WHEN REMOVING ELECTRICAL SYSTEMS.
ALL WIRING THAT IS REQUIRED FOR POWER AND SPECIAL SYSTEMS ON OTHER FLOORS
SHALL BE MAINTAINED.
19. EXISTING LIGHT FIXTURES MAY BE UTILIZED FOR TEMPORARY LIGHTING, ALL
TEMPORARY SHALL REMAIN AFTER PROJECT IS DONE FOR OWNERS USE. ALL LIGHT
FIXTURES THAT ARE REMOVED SHALL BE DISPOSED OF IN A LAWFUL WAY.
20. OWNER HAS FIRST RIGHTS TO ITEMS REMOVED.
GENERAL SPECIFICATIONS:
1. EXECUTE THE WORK REQUIRED IN A MANNER EVIDENCE BY THE "BEST TRADE PRACTICES"
CONTRIBUTING TO EFFICIENCY OF OPERATION, MINIMUM MAINTENANCE, ACCESSIBILITY AND
AESTHETICS OF THE INSTALLATION.
2. MECHANICAL AND ELECTRICAL PLANS ARE DIAGRAMMATIC IN NATURE, INTENDED TO INDICATE DESIGN INTENT ONLY. CONTRACTOR IS RESPONSIBLE TO COORDINATE SPECIFIC LOCATIONS OF
ITEMS AND ADJUST AS REQUIRED TO ACCOMMODATE CODE REQUIREMENTS, MANUFACTURER'S
INSTALLATION REQUIREMENTS, AND THE WORK OF OTHER TRADES.
3. MECHANICAL AND ELECTRICAL INFORMATION IS PRESENTED ON A REFERENCED BACKGROUND
FLOOR PLAN. IN CASE OF CONFLICT BETWEEN BACKGROUND PLAN AND ARCHITECTURAL FLOOR
PLAN, ARCHITECTURAL FLOOR PLAN SHALL GOVERN.
4. RUN ALL PIPING, CONDUIT, ETC. CONCEALED IN WALLS WHENEVER POSSIBLE.
5. AVOID EXPOSED INSTALLATION UNLESS SPECIFICALLY REQUIRED (TYPICAL UNLESS NOTED
OTHERWISE ON DRAWINGS).
6. THE ENGINEER WILL NOT HAVE CONTROL OR CHARGE OF CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES, OR PROCEDURES. ENGINEER IS NOT RESPONSIBLE FOR SAFETY
PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK; AND WILL NOT BE RESPONSIBLE FOR CONTRACTOR'S FAILURE TO CARRY OUT THE WORK IN ACCORDANCE WITH THOSE DOCUMENTS
PREPARED BY THE ENGINEER.
7. ALL CONSTRUCTION SHALL BE DONE IN COMPLIANCE WITH CURRENT CODES, INCLUDING:
MICHIGAN BUILDING CODES, MICHIGAN PLUMBING CODE, MICHIGAN MECHANICAL CODE, NATIONAL ELECTRICAL CODE, MICHIGAN BUILDING REHABILITATION CODE (WHEN APPLICABLE), NFPA CODES, LIFE SAFETY CODE (WHEN APPLICABLE), AMERICANS WITH DISABILITIES ACT (A.D.A.) AND
MICHIGAN BARRIER FREE CODES, DEPARTMENT OF PUBLIC HEALTH CODES (WHEN APPLICABLE), AND ALL OTHER LOCAL, STATE, AND FEDERAL APPLICABLE CODES. CONTRACTOR SHALL UTILIZE
THE LATEST ADOPTED EDITIONS OF ALL CODES.
8. IF BIDDING CONTRACTOR WOULD LIKE TO SUBSTITUTE ANY SPECIFIED ELECTRICAL DEVICES, LIGHT FIXTURES, CONTROLLERS, PANELS, DISCONNECTS, VFD'S, ELEC. GEAR, ETC., THEY MUST PROVIDE SUBMITTAL TYPE DRAWINGS TO THE ENGINEER A MINIMUM OF 7 DAYS PRIOR TO BIDDING
THE PROJECT. IF THESE APPROVAL DRAWINGS ARE NOT SUBMITTED AND ACCEPTED, THE
SPECIFIED EQUIPMENT MUST BE USED - NO EXCEPTIONS.
9. EQUIPMENT AND MATERIALS SHALL BE U.L. APPROVED.
10. SECURE PERMITS AND INSPECTIONS REQUIRED BY STATE AND LOCAL LAWS AND ORDINANCES AND PAY ALL FEES AND EXPENSES IN CONNECTION THEREWITH AS A PART OF THEIR WORK UNDER THIS
CONTRACT.
11. UPON COMPLETION OF WORK, FURNISH OWNER CERTIFICATES OF FINAL INSPECTION AND
APPROVAL FROM AUTHORITIES HAVING JURISDICTION.
12. ALL CONDUCTORS SHALL BEAR IDENTIFICATION AS TO SIZE AND TYPE OF INSULATION, AND SHALL
BE EQUIPPED WITH WIRE MARKERS INDICATING THE CIRCUIT NUMBER, WIRE NUMBER AND/OR
PHASE LETTER.
13. IDENTIFY ELECTRICAL EQUIPMENT WITH THE NAME OF THE EQUIPMENT, THE EQUIPMENT
CONTROLLED OR THE SYSTEM INVOLVED. DISCONNECT SWITCHES AND MOTOR STARTERS SHALL
HAVE NAMEPLATES TO INDICATE THE EQUIPMENT THEY CONTROL. FOR NEW ELECTRICAL DEVICES AS NOTED ON RISER DIAGRAM, PROVIDE LAMINATED PLASTIC NAME PLATES WITH WHITE LETTERS.
14. EXISTING LIGHTING AND RE-USED RECEPTACLE PANELS SHALL HAVE NAMEPLATES DESIGNATING
THEIR NAMES AND VOLTAGE RATING, SUCH AS LP-A, 120/208 VOLT, 3 PHASE, 4 WIRE. THE
NAMEPLATES SHALL BE BLACK LAMINATED PLASTIC WITH WHITE CHARACTERS. THE CHARACTERS ON THE NAMEPLATES SHALL BE 1/4" HIGH, UNLESS OTHERWISE DIRECTED IN THE FIELD. THE
CHARACTERS SHALL BE ENGRAVED ON THE NAMEPLATES.
15. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH CONDITIONS OF WHICH WILL AFFECT THE WORK HE IS TO PERFORM. THE SUBMISSION OF A PROPOSAL BY THIS CONTRACTOR SHALL BE CONCLUSIVE EVIDENCE THAT THIS CONTRACTOR HAS VISITED THE SITE
AND HAS GIVEN PROPER CONSIDERATION AND EVALUATION OF THESE CONDITIONS IN THE
PREPARATION OF HIS PROPOSAL. NO ALLOWANCE SHALL SUBSEQUENTLY BE MADE IN HIS BEHALF FOR EXTRA EXPENSE INCURRED DUE TO FAILURE OR NEGLECT ON HIS PART TO MAKE THIS VISIT
AND EXAMINATION.
16. WHERE ACTIVE SEWERS, GAS, ELECTRIC, OR OTHER SERVICES ARE ENCOUNTERED DURING THE PERFORMANCE OF THIS CONTRACT, THE CONTRACTOR SHALL PROTECT, BRACE AND SUPPORT THEM
AS REQUIRED. DO NOT PREVENT, INTERRUPT OR DISTURB OPERATION OF EXISTING SERVICES
THAT ARE TO REMAIN. RELOCATE EXISTING SERVICES IF REQUIRED.
17. IN GENERAL, MOUNTING HEIGHTS ABOVE FINISHED FLOOR TO THE CENTERLINE OF BOXES AND EQUIPMENT SHALL BE AS PER AMERICANS WITH DISABILITIES ACT, AND MICHIGAN BARRIER FREE
CODES.
18. MAINTAIN A MINIMUM OF 3'-0" CLEAR IN FRONT OF ALL ELECTRICAL EQUIPMENT (DISCONNECT SWITCHES, LIGHTING AND APPLIANCE AND DISTRIBUTION PANELS) FOR SERVICING PER N.E.C.
19. ALL WORK TO CONFORM TO THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE AND LOCAL
REQUIREMENTS. ALSO REFERENCE ARCHITECTURAL AND KITCHEN DWG'S.
20. WIRING TO BE MINIMUM #12 (FOR RUNS OVER 100 FEET, MINIMUM #10). ALL WIRING TO BE
INSTALLED IN E.M.T. (THINWALL CONDUIT).
21. DEVICE PLATES FOR SWITCHES, RECEPTACLES, TELEPHONE, COMPUTER, ETC., SHALL MATCH EXISTING AS MANUFACTURED BY PASS AND SEYMOUR, HUBBELL, OR BRYANT. ALL DEVICES TO BE
SPECIFICATION GRADE. ANY OTHER COLOR OF DEVICES SHALLS BE CHOSEN BY
OWNER/ARCHITECT.
22. CONTRACTOR TO OBTAIN AND PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS.
23. ALL WORK AND MATERIALS SHALL BE GUARANTEED IN WRITING FOR (1) YEAR FROM PROJECT
COMPLETION.
24. WORK SHALL BE PERFORMED BY SKILLED MECHANICS WELL VERSED IN THEIR PARTICULAR TRADES.
25. RESPONSIBILITY FOR CARE AND PROTECTION OF ELECTRICAL WORK RESTS WITH THE
CONTRACTOR UNTIL IS HAS BEEN TESTED AND ACCEPTED.
26. CONTRACTOR IS TO CHECK DOOR SWINGS WITH ARCHITECTURAL PLANS AND MOUNT LIGHT
SWITCHES, CONTROLS, ETC., ACCORDINGLY.
27. ELECTRICAL DEVICES SHALL BE SQUARE D, SIEMENS, EATON, G.E. OR MATCH EXISTING.
28. DISCONNECT SWITCHES SHALL BE NEMA HEAVY DUTY, FUSIBLE OR NON-FUSIBLE AS NOTED ON
PLANS, WITH A NEMA 3R ENCLOSURE WHERE MOUNTED OUTDOORS.
29. THE NEUTRAL CONDUCTOR OF THE WIRING SYSTEM TOGETHER WITH THE CONDUIT SYSTEM AND
SERVICE EQUIPMENT SHALL BE GROUNDED AND SIZED PER NEC ARTICLE 250.
30. HOLES THROUGH WALLS OR PARTITIONS REQUIRED FOR ELECTRICAL WORK SHALL BE NEATLY CUT
TO SIZE. PENETRATIONS OF FIRE RATED ASSEMBLIES SHALL BE FIRE-STOPPED BY APPROVED
METHODS AND MATERIALS. NO BEAMS OR OTHER STRUCTURAL MEMBERS SHALL BE DRILLED,
BURNED, OR CUT.
31. LOCATIONS OF WIRING DEVICES SUCH AS LIGHT SWITCHES, DUPLEX RECEPTACLES, THERMOSTATS, ETC., SHALL BE COORDINATED WITH OTHER TRADES.
32. IN GENERAL, ALL MOTORS ARE FURNISHED AND INSTALLED UNDER THE MECHANICAL SECTION OF THE SPECIFICATIONS. ALL STARTERS, FUSED SWITCHES, SAFETY SWITCHES, INCLUDING ALL POWER
WIRING SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR.
33. OUTLET BOXES IN THE SAME WALL BUT SERVING DIFFERENT ROOMS SHALL BE AT LEAST 4" APART TO MINIMIZE NOISE TRANSMISSION. WHEN LOCATED ON FIRE WALLS, THEY SHALL BE 24" APART.
34. OCCUPANCY AND TOGGLE SWITCHES AS WELL AS RECEPTACLES SHALL BE SPECIFICATION GRADE, COLOR TO MATCH EXISTING.
35. LIGHTING AND CONTROL WIRING SHALL BE TESTED FOR SHORTS AND OPENS AND SHALL BE GIVEN
A COMPLETE OPERATIONAL TEST.
36. THE CONTRACTOR SHALL TEST ALL CIRCUITS AS SOON AS CONDUCTORS ARE INSTALLED AND MAKE FINAL TESTS WHEN ALL WORK IS COMPLETE. IF CIRCUITS ARE NOT PROPERLY CONTROLLED AND INSULATED AT TIME OF EACH FINAL TEST, THE NECESSARY REPAIRS AND TESTS SHALL BE MADE AT
THE CONTRACTORS EXPENSE.
37. NO DUCTWORK IS TO RUN ABOVE THE ELECTRICAL PANELS FOR 6' ABOVE THE PANELS PER 2017 N.E.C. KEEP PANEL AREAS CLEAR FOR 36" IN FRONT OF PANELS FROM FLOOR TO TOP OF PANELS FOR SERVICING PANELS PER N.E.C. COORDINATE LOCATIONS OF M.E.P. ITEMS WITH CONTRACTORS
PRIOR TO CONSTRUCTION TO ASSURE THAT CLEARANCES ARE MET. LACK OF COORDINATION
BETWEEN CONTRACTORS WILL NOT RESULT IN EXTRA MONEY AWARDED FOR RELOCATION OF
M.E.P. ITEMS.
38. ALL BUSSING AND WIRING TO BE COPPER. NO ALUMINUM IS ALLOWED ON THIS PROJECT.
39. CHECK FINAL LOCATIONS OF LIGHT FIXTURES AND CEILING ELECTRICAL ITEMS WITH GRILLES AND
REGISTERS, CAMERAS, FANS, SPRINKLER HEADS, ETC. COORDINATE WITH RESPECTIVE
CONTRACTORS PRIOR TO INSTALLATION. NO MONEY WILL BE AWARDED TO CONTRACTORS
HAVING TO RELOCATE ITEMS DUE TO LACK OF COORDINATION BETWEEN CONTRACTORS.
MECHANICAL AND ELECTRICAL PLANS SHOW SCHEMATIC LOCATIONS ONLY.
40. ANY DISCREPANCIES BETWEEN ARCHITECTURAL DRAWINGS AND ELECTRICAL DRAWINGS SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
41. CONTRACTOR SHALL MAINTAIN AND KEEP AN UP-TO-DATE SET OF DRAWINGS REFLECTING "AS
BUILT" CONDITIONS OF THEIR WORK. CONTRACTOR SHALL INDICATE EXACT DIMENSIONS AND
ELEVATIONS FOR ALL UNDERGROUND AND/OR CONCEALED WORK. UPON COMPLETION OF THIS
PROJECT, THE CONTRACTOR SHALL DELIVER TO THE CONSTRUCTION MANAGER OR GENERAL
CONTRACTOR THE AS-BUILT DRAWINGS.
42. THE WIRING METHOD(S) USED SHALL BE SUITABLE FOR THE INSTALLATION AND USE IN
CONFORMITY WITH THE PROVISIONS OF THE 2017 N.E.C. LISTED OR LABELED EQUIPMENT SHALL BE USED OR INSTALLED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING OR LABELING. REFER TO NEC, SECTION 110-3(a) AND (b).
43. ALL NEW ELECTRICAL DEVICES AND ASSOCIATED OUTLET BOXES SHALL BE FLUSH MOUNTED UNLESS NOTED OTHERWISE. ALL CONDUIT AND WIRING SHALL BE CONCEALED. SURFACE RACEWAY
AND ASSOCIATED BOXES SHALL ONLY BE PERMITTED WHERE NOTED, AND SHALL BE DISCUSSED
WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION.
44. THE MAIN SERVICE DISCONNECTS SHALL BE IDENTIFIED AS THE MAIN SERVICE DISCONNECTION
MEANS PER N.E.C. 2017, ARTICLE 230-70B.
45. FLASH PROTECTION WARNING SHALL BE PROVIDED AT ALL ELECTRICAL PANELS PER NEC 2017, SECTION 110.16
46. FIRST CLASS WORKABLE SYSTEMS SHALL BE PROVIDED BY THE CONTRACTOR. IF, IN THE OPINION
OF THE CONTRACTOR, CHANGES IN THE DRAWINGS OR SPECIFICATIONS ARE REQUIRED TO
PRODUCE FIRST-CLASS WORKABLE SYSTEMS, CONTRACTOR SHALL REQUEST AN INTERPRETATION
FROM THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK. IT THE CONTRACTOR
FAILS TO MAKE SUCH A REQUEST, NO EXCUSE WILL THEREAFTER BE ENTERTAINED FOR FAILURE TO
PROVIDE FIRST-CLASS WORKABLE SYSTEMS.
47. SHOP DRAWINGS ARE TO BE THOROUGHLY CHECKED (AND NOTED SO ON FRONT COVER) BY THE
CONTRACTOR PRIOR TO SUBMITTING THEM TO THE ARCHITECT/ENGINEER. REVIEW BY THE
ENGINEER, SHALL NOT BE CONSTRUED AS A COMPLETE CHECK, BUT ONLY THAT THE GENERAL
METHOD OF CONSTRUCTION AND DETAILING IS SATISFACTORY. REVIEW SHALL NOT RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS WHICH MAY EXIST. SHOP DRAWINGS ARE TO BE
SUBMITTED VIA INTERNET IN PDF FORM. NO HARD COPIES WILL BE ACCEPTED.
48. CONNECT ALL EMERGENCY AND EXIT BATTERY PACKS TO NEARBY LIGHTING CIRCUITS, AHEAD OF
SWITCHES PER N.E.C. SO EMERGENCY/EXIT LIGHTS OPERATE ON LOSS OF POWER.
49. MANUALS: PER ASHRAE 2013, 90.1 STANDARDS, CONSTRUCTION DOCUMENTS SHALL REQUIRE
THAT AN OPERATING MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING
OWNER. THE MANUALS SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:
A. SUBMITTAL DATA FOR ALL ELECTRICAL EQUIPMENT CLEARLY STATING EQUIPMENT RATING , EXACTLY WHAT MODELS, ACCESSORIES, OPTIONS ARE INSTALLED.
B. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY
IDENTIFIED.
C. NAMES AND ADDRESSES AND PHONE NUMBERS/EMAIL ADDRESSES FOR AT LEAST ONE
QUALIFIED SERVICE AGENCY FOR EACH PIECE OF EQUIPMENT.
D. A COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
MEP CONSULTING ENGINEER
OWNER JOB NO.
SHEET NO.
TC JOB NO.
PROJECT TITLE
FED
B C
Bn
A
G
N
SHEET TITLE
KEY PLAN
PR
EL
IM
IN
AR
Y
NOT
FO
R C
ONST
RUCT
IO
N
491 E. WRIGHT AVE.
SHEPHERD, MI 48883
(PH) 989-567-1100
info@KTSEngineeringGroup.com
E0.01.1
GENERAL
ELECTRICAL
NOTES, SYMBOLS
& ABBREVIATIONS
KTS PROJECT NO. 25-0275
3550 E River Road Oscoda, Michigan 48750
Oscoda High School Misc Renovation
107348
Oscoda Area Schools
" INCHES
# NUMBER
' FEET
1P 1 POLE (2P, 3P, 4P, ETC.)
@ AT
A AMPERE
ABOVE CEILING ACLG
ACT ABOVE COUNTER
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFCI ARC FAULT COMBINATION CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUA-STAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BF BOTTLE FILLER
BLDG BUILDING
BMS BUILDING MANAEMENT SYSTEM
C CONDUIT
C CENTER LINE
CAB CABINET
CAT CATALOG
CAT6 CATEGORY 6 CABLING
CATV CABLE TELEVISION
CB CIR UIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CL CONNECTED LOAD
COF COFFEE MAKER
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION, CONTINUOUS
CONTR CONTRACTOR
CP CIRCULATING PUMP
CT CURRENT TRANSOFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCUITING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DL DEMAND LOAD
DN DOWN
DPR DAMPER
DS DISCONNECT SWITCH
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPLOSION PROOF
F FLOOR
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABP FIRE ALARM BOOSTER SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FASP FIRE ALARM SLAVE PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FU FUSE
FUDS FUSED DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP GYPSUM BOARD
HOA HAND-OFF-AUTO SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING & AIR CONDITIONING
I/W INTERLOCK WITH
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT- AMPERE RECTIVE
KW KILOWATT
KWC KILOWATT CONNECTED
KWD KILOWATT DEMAND
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LP LIGHTNING PEOTECTION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
M/C MOMENTARY CONTACT
MAGS MAGNETIC STARTER
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELEC MFGR'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
P PLATE
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
SP SPARE
SPEC SPECIFICATION
SPKR SPEAKER
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STA STATION
STBY STANDBY
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SWL SWITCH WITH LIGHTS
SYM SYMMETRICAL
SYS SYSTEM
T-STAT THERMOSTAT
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UCR UNDER COUNTER REFRIGERATOR
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VOL VOLUME
W WATT
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WH WATER HEATER
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
℄ CENTER LINE
∠ ANGLE
▲ DELTA
ABBREVIATIONS:
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF
LIGHT FIXTURES.
2. LIGHT FIXTURES SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE AND IN
ACCORDANCE WITH N.E.C. AND LOCAL REQUIREMENTS.
3. CONTRACTOR SHALL FIELD VERIFY EXACT MOUNTING OF ALL EXIT LIGHTS PRIOR
TO ORDERING.
4. EMERGENCY LIGHT FIXTURES SHALL BE CONTROLLED WITH NORMAL ROOM OR
AREA LIGHTING VIA 924 INC. EMERGENCY CONTROL MODULE.
5. PROVIDE ALL BRANCH CIRCUIT WIRING REVISIONS AND CONNECTIONS REQUIRED
TO ACCOMMODATE LIGHTING REVISIONS INDICATED OR SPECIFIED.
6. PROVIDE AN UNSWITCHED HOT TO ALL EMERGENCY BATTERY PACKS AND EXIT
SIGNS. CONNECT TO THE SAME CIRCUIT AS THE NORMAL LIGHTING SERVING THE
SURROUNDING AREA AHEAD OF ANY SWITCHING/CONTROLS.
7. ALL BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR AND
GROUND CONDUCTOR. PROVIDE ADDITIONAL NEUTRAL CONDUCTOR WHERE
REQUIRED.
8. MC CABLE MAY ONLY BE USED FOR FINAL CONNECTION TO LIGHT FIXTURES 6'-0"
LENGTH MAX. BRANCH CIRCUIT HOME RUNS SHALL BE IN EMT.
9. CONDUITS LOCATED IN FINISHED AREAS MUST BE RECESSED IN WALLS OR
LOCATED ABOVE FINISH CEILINGS. SURFACE MOUNTED CONDUIT WILL NOT BE
ALLOWED UNLESS NOTED OTHERWISE.
10. JUNCTION BOXES SERVING BRANCH CIRCUIT WIRING SHALL BE LABELED WITH
CIRCUITS BEING SERVED. USE INDELIBLE MARKER ON BOX COVER.
11. PROVIDE LABELS ON NEW LIGHT SWITCHES WITH CIRCUIT NUMBER AND PANEL
DESIGNATION LOCATED IN AREA AFFECTED BY NEW SCOPE OF WORK.
12. REUSE BRANCH CIRCUITS MADE AVAILABLE FROM DEMOLITION. EXISTING
LIGHTING CIRCUITS SHALL BE EXTENDED TO NEW LIGHTING FIXTURES AND ROOM
CONTROLLERS (POWER PACKS). IDENTIFY UN-USED LIGHTING CIRCUITS AND
REMOVE COMPLETE TO ELECTRICAL PANEL.
13. CIRCUIT NUMBERS INDICATED ON PLAN DO NOT INDICATE ACTUAL CIRCUIT
BREAKERS POLE POSITION IN PANEL, BUT REPRESENT ITEMS GROUPED ON SAME
CIRCUIT.
14. PROVIDE AS-BUILT DRAWINGS INDICATING ALL ACTUAL LIGHTING CIRCUITS.
15. FIELD VERIFY ALL PANELS AND EXISTING CIRCUITING SERVING EXISTING AND
NEW LIGHT FIXTURES.
16. PROVIDE NEW TYPE WRITTEN PANEL LEGENDS FOR ALL PANELS AFFECTED BY
NEW SCOPE OF WORK.
17. VERIFY DEVICE & COVERPLATE COLORS WITH ARCHITECT PRIOR TO THE START
OF CONSTRUCTION.
18. LIGHT SWITCHES ON THIS PLAN SHALL BE NEW, UNLESS OTHERWISE NOTED.
19. WHERE MULTIPLE SWITCHES ARE GROUPED TOGETHER, PROVIDE A SINGLE
SHARED COVERPLATE.
20. FOR LIGHTING CONTROL AND OCCUPANCY SENSOR REQUIREMENTS, REFER TO
SPECIFICATIONS.
21. OCCUPANCY SENSORS AND POWER PACKS SHALL BE RATED FOR THE LOAD
INDICATED TO BE SERVED. PROVIDE MULTIPLE POWER PACKS WHERE REQUIRED.
22. MAINTAIN MANUFACTURER RECOMMENDED SPACING BETWEEN OCCUPANCY
SENSORS AND HVAC DEFFUSERS AND FANS. ADJUST LOCATIONS AS REQUIRED.
23. UNLESS NOTED OTHERWISE, CONDUCTORS SHALL BE #12 AWG MINIMUM.
24. SEE ORIGINAL BUILDING DRAWINGS FOR EXISTING CIRCUIT LOCATIONS.
25. PROVIDE BLANK COVERPLATE FOR UN-USED WALL SWITCH BOXES.
26. PROVIDE UPDATED TYPE WRITTEN PANEL DIRECTORIES REFLECTING CIRCUIT
CHANGES.
27. LIQUID TIGHT FLEXIBLE CONDUIT MAY ONLY BE USED FOR FINAL CONNECTION TO
MOTORIZED EQUIPMENT 6'-0" LENGTH MAXIMUM.
28. EXTERIOR CONDUITS SHALL BE RIGID GALVANIZED STEEL (RGS) CONDUIT.
29. WHERE UNGROUNDED CONDUCTORS ARE INCREASED IN SIZE FROM THE MINIMUM
SIZE THAT HAS SUFFICIENT AMPACITY FOR THE INTENDED INSTALLATION, WIRE-
TYPE EQUIPMENT GROUNDING CONDUCTORS, WHERE INSTALLED, SHALL BE
INCREASED IN SIZE PROPORTIONATELY ACCORDING TO THE CIRCULAR MIL AREA
OF THE UNGROUNDED CONDUCTORS PER NEC 250.122(B).
30. ROOF PENETRATIONS SERVING MECHANICAL EQUIPMENT SHALL BE ROUTED THRU
THE EQUIPMENT CURB AND COORDINATED WITH MECHANICAL TRADES.
GENERAL NOTES:
NEW
EXISTING
DEMOLISHED
PHASE LINE TYPES
ELECTRICAL SHEET INDEX:
E0.01.1 GENERAL ELECTRICAL NOTES, SYMBOLS & ABBREVIATIONS
ED1.10.1 FIRST FLOOR DEMOLITION PLAN - UNIT A
E1.10.1 FIRST FLOOR PLAN - UNIT A
E5.01.1 ELECTRICAL DETAILS
E6.01.1 ELECTRICAL SCHEDULES
E7.01.1 ELECTRICAL ONE LINE DIAGRAM
ELECTRICAL FIXTURE LEGEND
DISCONNECT SWITCH, NON-FUSED, HEAVY DUTY, HP-RATED - ASSUME 30
AMP SWITCH UNO ON ONE LINE DIAGRAM OR FLOOR PLANS.
DUPLEX RECEPTACLE AT 18" AFF
QUAD RECEPTACLE AT 46" AFF
SIMPLEX RECEPTACLE, NEMA CONFIGURATION AS NOTED
DATA LEGEND
PROVIDE CONDUIT, EMPTY BOX AND PULL ROPE
09.12.2025 DESIGN DEVELOPMENT
09.23.2025 ADDENDUM 01
OS
OS
OS
OS
OS
OS
OS
OS
s s
D
B
A
A C E H
Aa
Aa
F
F
I
IK
D O
W N
D O
W N
CORRIDOR
A-21
LOBBY
STAGE
VEST
AUDITORIUM
CORRIDOR
A-20
ST
ENSEMBLE
CHORAL RM
CORR
602a
PR
PR
PR
PR
PR
PR
BAND RM
M DRESSING
273 W DRESSING
PASSAGE
A-4
44444
4 4 4 4 4
4 4 4 4 444
4 4 4 4
4 4444
4 4 4 4 4
MAINTAIN 400A-3P DISCONNECT SWITCH
MAINTAIN CIRCUIT FOR REUSE.
PREP FOR EXTENSION TO NEW
ELECTRICAL PANEL AT STAGE RIGHT.
REMOVE DIMMER PANEL "S"
INCLUDING WIRING AND CONDUIT
TO DISCONNECT SWITCH.
REMOVE BORDER LIGHTING
INCLUDING CIRCUITS TO
DIMMING PANEL "S"
REMOVE BORDER AND
CYCLORAMA LIGHTING
INCLUDING CIRCUITS TO
DIMMING PANEL "S"
REMOVE SPOT LIGHTING INCLUDING
CIRCUITS TO DIMMER PANEL "S"
AUDITORIUM
1 1
6 6
2 2
4 4
14-2
F-2
A-2
D-2
G-2
B-2
F-3
I
H-2 K
Aa
E-2C-2
27-2
H-3
A-3
27-3
MEP CONSULTING ENGINEER
OWNER JOB NO.
SHEET NO.
TC JOB NO.
PROJECT TITLE
FED
B C
Bn
A
G
N
SHEET TITLE
KEY PLAN
PR
EL
IM
IN
AR
Y
NOT
FO
R C
ONST
RUCT
IO
N
491 E. WRIGHT AVE.
SHEPHERD, MI 48883
(PH) 989-567-1100
info@KTSEngineeringGroup.com
ED1.10.1
FIRST FLOOR
DEMOLITION PLAN
- UNIT A
KTS PROJECT NO. 25-0275
3550 E River Road Oscoda, Michigan 48750
Oscoda High School Misc Renovation
107348
Oscoda Area Schools
KEY NOTES:
1 EQUIPMENT TO REMAIN TO REMAIN IN PLACE.
2 DISCONNECT AND REMOVE 120 VAC LIGHT SWITCH AND WIRING FROM LIGHT
SWITCH TO FIRST ACTIVE CEILING JUNCTION BOX. PREP FOR INSTALLATION
OF NEW LIGHTING SWITCH AND LOW VOLTAGE WIRING IN SAME LOCATION.
4 DISCONNECT AND REMOVE LIGHT FIXTURE. MAINTAIN EXISTING CIRCUIT AND
PREP FOR NEW LIGHT FIXTURE IN SAME LOCATION.
6 DISCONNECT AND REMOVE INCLUDING WIRING AND CONDUIT TO SOURCE.
1/8" = 1'-0"ED1.10.1
FIRST FLOOR DEMOLITION PLAN - UNIT A1
09.12.2025 DESIGN DEVELOPMENT
B
OS
OS
OS
OS
OS
OS
OS
OS
OS OS OS
OS OS OS
OS OS OS
D
B
A
A C E H
Aa
Aa
F
F
I
IK
B
D O
W N
D O
W N
B
2 3
DOC
L42 L42 L42
(2) 1 1/4"C
ROUTE (2) CONDUITS
DOWN TO BELOW
PLATFORM
S- 9
S- 17 S- 17 S- 17
S- 11
S- 75
TOP FACE CLG S- 75
TOP FACE CLG
S- 75S- 75
S- 75
TF-251
S-75
D50I
D50I D50 D50 D50 D50 D50 D50 D50I
D50ID50D50ID50D50I
D50I D50 D50I D50 D50I
D50I D50 D50I D50 D50I
D50ID50D50ID50D50I
D50I D50 D50I D50 D50I
D50ID50D50ID50
D50I
PR
ST
PR
CHORAL RM
ENSEMBLE
PR
PR
PR
PR
BAND RM
M DRESSING
273 W DRESSING
CORR
602a
PASSAGE
A-4
CORRIDOR
A-21
LOBBY
STAGE
VEST
AUDITORIUM
CORRIDOR
A-20
MAIN STAGE RACK
XH
XH
XH
S-2 S-3 S-4
S-1
XH
XH
S-5 S-6
S-7
S
3 3
12 13 14 15
4 11
28 33
S-
,5
L6 -2
0R
S- 8, L6
-2 0R
3RD ELECTRIC
2ND ELECTRIC
4TH ELECTRIC
5TH ELECTRIC
S-
,2
L6 -2
0R
S-
,4
L6 -2
0R
S-
,4
L6 -2
0R S-
,3
L6
-2 0R
S-
,2
L6 -2
0R S-
,1
L6
-2 0R
6 7
8 9 10
30 31
S- 48
ABOVE APRON ABOVE APRON
S- 50 S- 52
F.F.F.F.
S- 29,31 L6-20R
S- 37,39 L6-20R
E1.10.1
XH XH
STAGE RT. DMX
(2) 1 1/4"C
(2
/4 "C
(2
/4 "C
(1
"C
"C
JUNCTION
BOX (TYP.)
S-
S-
S-
S- 33 S- 35
S- 41 S- 43
S-
S-
S- 19
HOUSE LIGHTING
CONTROLLER
S- 21
S-
S-
S-
S-
S-
S-
S-
S-
S-
S-
S-
TV TV
F. F.
S-
VERIFY DOWNLIGHT
SIZE PRIOR TO
ORDERING. (TYP.)
ENLARGE EXISTING
OPENING TO
FIT NEW RACEWAY.
LIGHTING &
POWER BATTEN (TYP.)
PAINT CONDUIT
TO MATCH
WALL SURFACE
(TYP.)
35 35
X-PNL.
EXTEND EXISTING 400A CIRCUIT FROM
DISCONNECT SWITCH TO NEW PANEL S
LV LV
LVLV
S-
1ST ELECTRIC
TF-251
INSTALL TRANSFER FAN IN STORAGE ROOM CEILING.
INSTALL RIGID METAL DUCT FROM DISCHARGE OF FAN
ABOVE LID OF STORAGE ROOM AND TURN HORIZONTALLY
TOWARD CENTER OF STORAGE. INSTALL DUCTWORK
SUCH THAT IT IS NOT VISIBLE FROM AUDITORIUM FLOOR
DOOR TO BE UNDERCUT
FOR AIR TRANSFER.
SEE ARCHITECTURAL
MEP CONSULTING ENGINEER
OWNER JOB NO.
SHEET NO.
TC JOB NO.
PROJECT TITLE
FED
B C
Bn
A
G
N
SHEET TITLE
KEY PLAN
PR
EL
IM
IN
AR
Y
NOT
FO
R C
ONST
RUCT
IO
N
491 E. WRIGHT AVE.
SHEPHERD, MI 48883
(PH) 989-567-1100
info@KTSEngineeringGroup.com
E1.10.1
FIRST FLOOR PLAN
- UNIT A
KTS PROJECT NO. 25-0275
3550 E River Road Oscoda, Michigan 48750
Oscoda High School Misc Renovation
107348
Oscoda Area Schools
ACCEPTABLE MANUFACTURERS: GREENHECK, COOK, BROAN, PANASONIC.
COMMENTS:
1. PROVIDE WITH STANDARD DESIGNER GRILLE.
2. PROVIDE WITH FACTORY MOUNTED DISCONNECT.
3. PROVIDE WITH ELECTRONICALLY COMMUTATED MOTOR WITH SPEED ADJUSTMENT. SPEED CONTROL TO BE USED FOR BALANCING PURPOSES.
TRANSFER FAN SCHEDULE
TAG
BASIS OF DESIGN
CFM E.S.P.
(in-wg)
FAN SPEED (RPM)
DRIVE TYPE SONES
ELECTRICAL DATA DISCONNECT BY
VFD CONTROL COMMENTS
MANUFACTURER
MODEL Fan RPM Max Fan
RPM
MOTOR POWER VOLTAGE M.T.C. E.T.C.
TF-251 Greenheck SP-LP0810W 100 0.10 894 894 Direct 1.5 4.06 W 120V / 1Ø X CONTINUOUS OPERATION 1, 2, 3
1/4" = 1'-0"E1.10.1
ENLARGED PLAN2
1/8" = 1'-0"E1.10.1
FIRST FLOOR PLAN - UNIT A1
KEY NOTES:
1 A-1: 120V/20A AUXILLARY CIRCUIT WITH RECEPTACLES SIDE OF WORK DESK.
2 C-1: 120V/20A CIRCUIT WITH 3 QUAD RECEPTACLE BOXES UNDER WORK DESK
EVENLY SPACED.
3 A-3: 120V/20A AUXILLARY CIRCUIT WITH RECEPTACLES SIDE OF WORK DESK.
4 L-1: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-2: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
5 L-3: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE.
6 L-4: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
7 L-5: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
8 L-6: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE.
9 L-7: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
10 L-8: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
11 L-9: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-10: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
12 L-11: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-12: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX. ELECTRIC BOXES ARE CLAMPED TO
THE BATTEN FOR ALL FLOWN LINE SETS, REFER TO THE EQUIPMENT DIAGRAM
FOR PLACEMENT. MOVE POWER CABLES OFF OF THE PIPE FOR INSTRUMENT
CLAMPS, PROVIDE BLACK VELCRO TO KEEP ALL CABLING AGAINST THE PIPE.
USE STANDARD PRACTICES FOR POWER/DATA DISTRIBUTION TO THE LINE
SETS, ALLOWING FOR ADJUSTMENT OF +/- 2' UP OR DOWN.
13 L-13: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
14 L-14: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-15: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
15 L-16: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
16 L-17: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-18 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
17 L-19: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
18 L-20: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-21: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
19 L-22: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
20 L-23: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-24: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
21 L-25: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
22 L-26: 208-240V/20A CIRCUIT WITH 1 TWISTLOCK RECEPTACLE, L-27: 120V/20A
CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
23 L-28: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
24 C-2: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX. PROVIDE SHELF 2'
WIDE BY 1' DEEP (10'-0" A.F.F.) FOR THE DMX DISTRIBUTORS.
25 A-3: 120V/20A AUXILLARY CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
26 A-4: 120V/20A AUXILLARY CIRCUIT WITH 1 QUAD RECEPTACLE BOX.
27 C-3: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX, ALSO ANOTHER
2-GANG BOX WITH 1 SWITCH CONTROLLING A DUPLEX RECEPTACLE. MOUNT
MAIN STAGE A/V RACK 5'-0" A.F.F.
28 V-1: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX FRONT SIDE AND 1
QUAD RECEPTACLE BOX BACK SIDE FOR TV.
29 S-1: 120V/20A CIRCUIT WITH 1 DUPLEX RECEPTACLE FOR MAIN SPEAKER
POWER. MOUNT TO WALL.
30 S-2: 120V/20A CIRCUIT WITH 1 QUAD RECESSED RECEPTACLE IN 4-GANG
FLOOR BOX (OTHER 2 GANG ARE FOR XLR AND DMX). LOCATED IN EXISTING
4-GANG FLOOR POCKET WHICH WILL HAVE POWER, XLR, AND DMX CIRCUITS
FOR VARIOUS EQUIPMENT.
31 S-3: 120V/20A CIRCUIT WITH 1 QUAD RECESSED RECEPTACLE IN 4-GANG
FLOOR BOX (OTHER 2 GANG ARE FOR XLR AND DMX). LOCATED IN EXISTING
4-GANG FLOOR POCKET WHICH WILL HAVE POWER, XLR, AND DMX CIRCUITS
FOR VARIOUS EQUIPMENT.
32 S-1: 120V/20A CIRCUIT WITH 1 DUPLEX RECEPTACLE FOR MAIN SPEAKER
POWER. MOUNT TO WALL.
33 V-2: 120V/20A CIRCUIT WITH 1 QUAD RECEPTACLE BOX FRONT SIDE AND 1
QUAD EDISON RECEPTACLE BOX BACK SIDE FOR TV.
34 LOCATE ON TOP FACE OF CEILING.
35 CONNECT TO EXISTING CIRCUIT.
1/4" = 1'-0"E1.10.1
MECHANICAL PLAN3
08.15.2025 CONSTRUCTION
ELECTRICAL CIRCUIT SCHEDULE
CIRCUIT LEGEND:
A: AUXILIARY CIRCUIT
PANEL LABELLING MUST IDENTIFY ALL LIGHTING
CIRCUITS AND ALL SOUND CIRCUITS CLEARLY FOR
SYSTEM STARTUP AND SHUTDOWN ON A REGULAR
BASIS. HOUSE LIGHTING CIRCUITS ARE INCLUDED IN
THE ELECTRICAL PANEL.
C: CONTROL SYSTEMS CIRCUIT
L: LIGHTING SYSTEM CIRCUIT
S: SOUND SYSTEM CIRCUIT
V: VIDEO SYSTEM CIRCUIT
LOC. DESCRIPTION CIRCUITS EST. AMPS. NOTES
CONTROL BOOTH HOUSE
RIGHT
A-1: 120V/20A AUXILLARY CIRCUIT
WITH RECEPTACLES BOTH SIDES OF
CONTROL DESK SPACED NORMALLY.
CONTROL BOOTH UNDER
DESK, MAIN BOOTH
CONTROL RACK
C-1: 120V/20A CIRCUIT WITH 3 QUAD
RECEPTACLE BOXES UNDER DESK
EVENLY SPACED
CONTROL BOOTH HOUSE
LEFT
A-2: 120V/20A AUXILLARY CIRCUIT
WITH RECEPTACLES BOTH SIDES OF
CONTROL DESK SPACED NORMALLY.
HOUSE RIGHT LIGHTING
LADDER
L-1: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-2:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
4.13 & 5
HOUSE 1 ELECTRIC (AUD.
COVE)
L-3: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE
10.34
HOUSE 1 ELECTRIC (AUD.
COVE)
L-4: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
9.17
HOUSE 1 ELECTRIC (AUD.
COVE)
L-5: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
6.25
HOUSE 1 ELECTRIC (AUD.
COVE)
L-6: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE
9.3
HOUSE 1 ELECTRIC (AUD.
COVE)
L-7: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
6.25
HOUSE 1 ELECTRIC (AUD.
COVE)
L-8: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
9.17
HOUSE LEFT LIGHTING
LADDER
L-9: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-10:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
4.13
12 FIRST ELECTRIC
L-11: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-12:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
12.55 & 6.25
ELECTRIC BOXES ARE CLAMPED TO THE BATTEN
FOR ALL FLOWN LINE SETS, REFER TO THE
DIAGRAM FOR PLACEMENT. ALSO, POWER
CABLES MUST BE ABLE TO BE MOVED OFF THE
PIPE FOR INSTRUMENT CLAMPS, PROVIDE
BLACK VELCRO TO KEEP ALL CABLING AGAINST
THE PIPE. USE STANDARD PRACTICES FOR
POWER/DATA DISTRIBUTION TO THE LINE
SETS, ALLOWING FOR ADJUSTMENT OF +/- 2'
UP OR DOWN.
13 FIRST ELECTRIC
L-13: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
5.8
14 FIRST ELECTRIC
L-14: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-15:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
11.51 & 6.25
15 FIRST ELECTRIC
L-16: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
5.8
16 SECOND ELECTRIC
L-17: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-18:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
12.69 & 6.24
17 SECOND ELECTRIC
L-19: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
4.16
18 THIRD ELECTRIC
L-20: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-21:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
13.72 & 4.16
19 THIRD ELECTRIC
L-22: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
2.08
20 FOURTH ELECTRIC
L-23: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-24:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
12.69 & 4.16
21 FOURTH ELECTRIC
L-25: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
2.08
22 FIFTH ELECTRIC
L-26: 208-240V/20A CIRCUIT WITH 1
TWISTLOCK RECEPTACLE, L-27:
120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
15.87
23 FIFTH ELECTRIC
L-28: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
STAGE RIGHT DMX
DISTRIBUTION (10' AFF),
HOUSE LIGHT
CONTROL/(DIMMERS),
BREAKERS/POWER
DISTRIBUTION
C-2: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX
PROVIDE SHELF 2' WIDE BY 1' DEEP (10' AFF)
FOR THE DMX DISTRIBUTORS.
STAGE LEFT PROSCENIUM
BACK WALL (16" AFF)
A-3: 120V/20A AUXILLARY CIRCUIT
WITH 1 QUAD RECEPTACLE BOX
STAGE RIGHT PROSCENIUM
BACK WALL (16" AFF)
A-4: 120V/20A AUXILLARY CIRCUIT
WITH 1 QUAD RECEPTACLE BOX
STAGE RIGHT WING,
MAIN
STAGE RACK (5' AFF)
C-3: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX, ALSO ANOTHER
2-GANG BOX WITH 1 SWITCH
CONTROLLING A DUPLEX RECEPTACLE
MAIN STAGE RACK FOR CONTROL AND SOUND
SYSTEM
STAGE LEFT PROSCENIUM
FRONT/BACK WALL (10' AFF,
6' OUT FROM PROSCENUIM)
V-1: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX FRONT SIDE AND 1
QUAD RECEPTACLE BOX BACK SIDE
FOR TVS
THIS IS 10' ABOVE STAGE FINISH HEIGHT AND
6' OUT FROM THE PROSCENUIM EDGE ON BOTH
SIDES OF THE WALL FOR TVS ON BOTH SIDES
OF THE WALL - AUDIENCE TVS AND ACTOR TV
MONITORS
STAGE LEFT CEILING ABOVE
APRON
S-1: 120V/20A CIRCUIT WITH 1
DUPLEX RECEPTACLE FOR MAIN
SPEAKER POWER
30 STAGE LEFT APRON
S-2: 120V/20A CIRCUIT WITH 1 QUAD
RECESSED RECEPTACLE IN 4-GANG
FLOOR BOX (OTHER 2 GANG ARE FOR
XLR AND DMX)
LOCATED IN A 4-GANG FLOOR POCKET WHICH
WILL HAVE POWER, XLR, AND DMX CIRCUITS
FOR VARIUS EQUIPMENT
31 STAGE RIGHT APRON
S-3: 120V/20A CIRCUIT WITH 1 QUAD
RECESSED RECEPTACLE IN 4-GANG
FLOOR BOX (OTHER 2 GANG ARE FOR
XLR AND DMX)
LOCATED IN A 4-GANG FLOOR POCKET WHICH
WILL HAVE POWER, XLR, AND DMX CIRCUITS
FOR VARIUS EQUIPMENT
STAGE RIGHT CEILING
ABOVE APRON
S-1: 120V/20A CIRCUIT WITH 1
DUPLEX RECEPTACLE FOR MAIN
SPEAKER POWER
NOTE THIS IS THE SAME CIRCUIT AS IN
LOCATION 29
STAGE RIGHT PROSCENIUM
FRONT/BACK WALL (10' AFF,
6' OUT FROM PROSCENUIM)
V-2: 120V/20A CIRCUIT WITH 1 QUAD
RECEPTACLE BOX FRONT SIDE AND 1
QUAD RECEPTACLE BOX BACK SIDE
FOR TVS
THIS IS 10' ABOVE STAGE FINISH HEIGHT AND
6' OUT FROM THE PROSCENUIM EDGE ON BOTH
SIDES OF THE WALL FOR TVS ON BOTH SIDES
OF THE WALL - AUDIENCE TVS AND ACTOR TV
MONITORS
CONDUIT SCHEDULE
RUN# LOCATION 1 LOCATION 2 DESCRIPTION/TABLES CONDUIT NOTES
1 #2 #27
PRIMARY TRUNK FOR CONTROL
SYSTEMS, 2X OM3 10G FIBER
WITH LC ENDS, 8 X CAT6
REQUIRES 1X 2" UNBROKEN CONDUIT
WITH PULL STRING, AND 1X JUNCTION
BOX 16"X16"X8" AT LOCATION #27
JUNCTION BOX AT #27 ABOUT 5' AFF
AND WILL BE A COMMON JUNCTION
POINT FOR OTHER RUNS
2 #27
#33 (BACK
SIDE)
PRIMARY DATA DISTRIBUTION ON
STAGE, 31 X CAT6, 12 X AUDIO
MIC CABLE
REQUIRES 2X 2" UNBROKEN CONDUIT
WITH PULL STRING, AND 1X JUNCTION
BOX 16"X16"X8" AT LOCATION #33
(BACK SIDE)
JUNCTION BOX AT #33 (BACK SIDE)
ABOUT 10' AFF ON THE BACK SIDE
(STAGE SIDE) OF PROSCENIUM WALL
AND WILL BE A COMMON JUNCTION
POINT FOR OTHER RUNS
#33 (BACK
SIDE)
#28 (BACK
SIDE)
DISTRIBUTION TO STAGE LEFT,
24 X CAT6, 9 X AUDIO MIC CABLE
REQUIRES 2X 2" UNBROKEN CONDUIT
WITH PULL STRING, AND 1X JUNCTION
BOX 16"X16"X8" AT LOCATION…