This file contains engineering drawings and specifications for an Electric Vehicle Charging Station (EVCS) project at the California Department of Transportation (CDOT) District 3 facility located at 1001 N. Beale Road in Marysville, CA. The project involves installing infrastructure for six Level 2 dual-port EVCS charging stations intended for fleet and employee use only. The scope includes installing all electrical infrastructure for a "make ready" installation, including required wiring devices, saw cutting, trenching, backfilling, and restoration of affected surfaces. The drawings are dated July 2024 and have received State Fire Marshal approval.
The technical specifications detail a 120/208V electrical system with a new 225A panelboard (PB-EV) connected to the existing 400A main switchboard. The charging stations will be ChargePoint Level 2 CP6000 series pedestal chargers mounted on 24"x24"x24" concrete pads. The project includes detailed electrical, structural, and site work requirements, with specific details for conduit installation, bollards, signage, and surface markings. Notably, the actual EVCS charger procurement and installation is not included in the contractor's scope of work. The drawings indicate this is a designated fleet charging area not intended for public use.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 981_N_Beale_Plans.pdf | ||
| Bid_Package_Documents.pdf | ||
| Project_Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS © 2024 TomTom
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS
© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS
SITE MAP
VICINITY MAP
G0.0
NONE
CODES AND PREFERENCES SHEET INDEX
SYMBOLS AND ABBREVIATIONS
TITLE 19 CCR PUBLIC SAFETY, DIVISION 1, STATE FIRE MARSHAL REGULATIONS
TITLE 24 CCR, PART 1 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE
TITLE 24 CCR, PART 2 2022 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1 AND 2 (2021 IBC, AS AMENDED BY CA)
TITLE 24 CCR, PART 3 2022 CALIFORNIA ELECTRICAL CODE (CEC) (2020 NEC, AS AMENDED BY CA)
TITLE 24 CCR, PART 8 2022 CALIFORNIA HISTORICAL BUILDING CODE
TITLE 24 CCR, PART 9 2022 CALIFORNIA FIRE CODE (CFC) (2021 IFC, AS AMENDED BY CA)
TITLE 24 CCR, PART 10 2022 EXISTING BUILDING CODE
TITLE 24 CCR, PART 11 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CAL GREEN CODE)
TITLE 24 CCR, PART 12 2022 CALIFORNIA REFERENCED STANDARDS CODE (SEE ALSO TITLE 24 CCR-PART 2, CHAPTER 35 -
REFERENCE STANDARDS AND TITLE 24 CCR - PART 9, CHAPTER 47 - REFERENCED STANDARDS)
DRAWINGS
G0.0 TITLE SHEET
E0.0 ELECTRICAL NOTES
E1.0 SINGLE LINE DIAGRAM AND SCHEDULES
E2.0 ELECTRICAL SITE PLAN
E3.0 ELECTRICAL DETAILS
S1.0 STRUCTURAL DETAILS
EVCS DESCRIPTION SCOPE OF WORK
EXISTING EVCS SPACES NEW EVCS SPACES
(0) LEVEL 1
(0) LEVEL 2
(0) LEVEL 1
(0) LEVEL 2
(0) LEVEL 1
(6) LEVEL 2
FLEET WORKPLACE WORKPLACEFLEET
DISCONNECT SWITCH, NON-FUSIBLE, SEE PLANS FOR RATING
EXISTING TO BE REMOVED AND SALVAGED
EXISTING TO BE DEMOLISHED
NEW PLANS-FINAL LOCATION OF RELOCATED EQUIPMENT.
DEMO PLANS-EXISTING TO BE RELOCATED.
EXISTING TO REMAIN
(RS)
(D)
(RL)
(E)
ENCLOSED CIRCUIT BREAKER
GROUND FAULT PROTECTION
GREEN
GREEN
WHITE
WHITE
BLUE
RED
RED
BLACK
BLACK
240V
240Y/120V
POWER WIRE COLOR CODE
SYSTEM
208Y/120V
480Y/277V
PHASE A
BLACK
YELLOW
PHASE B
RED
BROWN
PHASE C
BLUE
ORANGE
NEUTRAL
WHITE
GRAY
GROUND
GREEN
GREEN
ELECTRICAL ABBREVIATIONS
INCOMING ELECTRIC SERVICE
GROUND
DISCONNECT SWITCH, FUSIBLE, SEE PLANS FOR RATING
FUSE
SWITCH
2S, 2W = 2 SPEED, 2 WINDING
RV=REDUCED VOLTAGE STARTING
FULL-VOLTAGE NON-REVERSING UNLESS NOTED
MAGNETIC MOTOR STARTER, NEMA SIZE INDICATED
MCP INDICATES MOTOR CIRCUIT PROTECTOR
3 POLE UNLESS NOTED
CIRCUIT BREAKER,
METERING
Y, SHEET WHERE DETAIL IS DRAWN
DETAIL CALL-OUT: X, DETAIL IDENTIFIER;
WITH EQUIPMENT
CONTROLLER/STARTER FURNISHED
+ 48" UON
+ 18" UON
FLOOR GRADE TO CENTERLINE OF DEVICE
INDICATES HEIGHT FROM FINISHED
SHEET NOTE, SEE NOTE INDICATED
SURFACE MOUNTED PANELBOARD-NEW, EXISTING
POWER DISTRIBUTION SWITCHBOARD
CONDUIT STUB-OUT AND CAPPED
CONDUIT BENDS AWAY FROM OBSERVER
CONDUIT BENDS TOWARD OBSERVER
BELOW GRADE, #4/0 UON
GROUNDING CONDUCTOR 30"
CURVE LINE INDICATES GROUND WIRE
WIRE SIZE OTHER THAN #12
GROUND WIRE
QUANTITY #12 WIRE CURVE LINE INDICATES
CONDUIT EXPOSED 3/4"C-2#12, 1#12G, UON
3/4"C-2#12, 1#12G, UON
CONDUIT UNDER GROUND
CEILING 3/4"C-2#12, 1#12G, UON
CONDUIT CONCEALED IN WALLS OR
PULLBOX
HAND HOLE, 11"Hx17"Lx12"D, UON
ELECTRICAL SYMBOLS - ONE LINE DIAGRAMELECTRICAL SYMBOLS - PLANS
JUNCTION BOX
SINGLE RECEPTACLE 120V, 20A GFCI TYPE
DUPLEX RECEPTACLE
EXISTING AREA LIGHT AND POLE
(AIP)
1"C-2#12, 1#12G
(U)(V"C-W#X,Y#Z)
EXAMPLE: (2)(3/4"C-2#12-1#12G) INDICATES TWO 3/4"
CONDUITS EACH WITH 2#12 AND 1#12G CONDUCTORS
ELECTRICAL SYMBOLS COMMON
SINGLE RUN OF RACEWAY AND CIRCUIT CONDUCTORS.
FIRST NUMBER IS RACEWAY SIZE.
THE FOLLOWING NUMBERS ARE THE CONDUCTOR
QUANTITIES AND SIZES.
A AMPERES
AMPERES INTERRUPTING CAPACITY, SYMMETRICAL
AMERICAN WIRE GAUGE
BARE COPPER
CONDUIT, CONDUCTOR
AICS
AWG
BC
C
CB CIRCUIT BREAKER
CKT CIRCUIT
CNTL CONTROL
CO CONDUIT ONLY
CT CURRENT TRANSFORMER
DTL DETAIL
DWG DRAWING
E EXISTING
G, GND GROUND
GFCI GROUND-FAULT CIRCUIT INTERRUPTER
HH HANDHOLE
JB JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATT
LTG LIGHTING
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
N NEUTRAL
NIC NOT IN CONTRACT
NO. NUMBER
P POLE
PB PUSH BUTTON, PULL BOX
PC PHOTO CELL
PH, Ø PHASE
PVC POLYVINYL CHLORIDE
REQ'D REQUIRED
SMUD SACRAMENTO MUNICIPAL UTILITY DISTRICT
SW SWITCH
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
W WATTS, WIRE
W/ WITH
WP WEATHERPROOF
XFMR TRANSFORMER
NTS NOT TO SCALE
FLUSH MOUNTED PANELBOARD
EXISTING TO BE REMOVED AND REPLACED WITH NEW(RP)
ABOVE FINISHED GRADEAFG
BOLLARD
NEW PLANS: EXISTING TO NEW
INTERCEPTION POINT:
EVCS ELECTRICAL VEHICLE SUPPLY EQUIPMENT
LB FITTING
TEE FITTING
A-1,3
G
#10
PB
J
X
Y
+18"
RV
MCP
30A
M
F
GFP
LFMC LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT
(#)# CONDUIT CALLOUT REFERENCE WITH NUMBER OF CONDUITS
SHOWN IN PARENTHESIS.
PROJECT
LOCATION
PROJECT
WORKING AREA
(6 EVCS SPACES)
ELECTRICAL VEHICLE SUPPLY EQUIPMENT (EVCS) INSTALLED ON THIS PROJECT WILL NOT BE AVAILABLE TO THE GENERAL PUBLIC, AND IS INTENDED FOR
USE BY A DESIGNATED VEHICLE OR EMPLOYEE. ELECTRIC VEHICLE CHARGER PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.
INSTALL AND ELECTRICALLY CONNECT EVCS INFRASTRUCTURE FOR MAKE READY INSTALLATION AS
SHOWN. CONTRACTOR TO PROVIDE AND INSTALL THE WIRING DEVICES INCLUDING ALL REQUIRED
ASSOCIATED ITEMS FOR A COMPLETE AND OPERATIONAL SYSTEM INCLUDING REQUIRED TESTING.
CONTRACTOR SHALL ALSO PROVIDE THE REQUIRED SAW CUTTING, TRENCHING, BACKFILLING AND
FINISHING OF THE AFFECTED LOT SURFACE AND RESTORE TO ORIGINAL CONDITION. EVCS CHARGER
PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.
NOTICE TO CONTRACTOR:
MUST ADHERE TO CFC CHAPTER 33. FIELD DEPUTY TO VERIFY.
(0) LEVEL 1
(0) LEVEL 2
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JACH SWH JSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
000000000013676
POWER TRANSFORMER
FEEDER DESIGNATION SEE
CONDUIT/CONDUCTOR TABLE FOR SIZE
TITLE SHEET
HOMERUN TO PANEL A,
CIRCUIT 1 AND 3
ABANDON IN PLACE. (D) ABOVE GROUND CONDUITS &
CONNECTORS DOWN TO 3" BELOW GROUND LEVEL.
REMOVE AND (D) CONDUCTORS IN UG CONDUITS.
PLUG UG CONDUITS AND ABANDON IN PLACE.
MULTIPLE RUNS OF RACEWAY AND CIRCUIT CONDUCTORS
U = # OF PARALLEL RUNS
V = CONDUIT SIZE
W = # OF PHASE/NEUTRAL CONDUCTORS IN EA. CONDUIT
X = PHASE/NEUTRAL CONDUCTOR SIZE
Y = #OF GROUND CONDUCTORS IN EACH CONDUIT
Z = GROUND CONDUCTOR SIZE
V2
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/24/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2186
DOT D3 - Electric Vehicle Supply Equipment - Marysville (2 Sites) PN: 000000000013676, Date: 2/21/2025
E0.0
N/A
ELECTRICAL NOTES
SPECIAL INSPECTIONS REQUIRED
CONCRETE CONSTRUCTION:
STEEL CONSTRUCTION:
GENERAL NOTES:
V2
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JACH SWH JSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
000000000013676
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
N/A
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/24/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2186
E1.0
N/A
SINGLE LINE DIAGRAM
AND SCHEDULES
120/208V MAIN SWITCHBOARD, NEMA 1 3Ø, 4W, 60HZ
(E) MSB
PB-EV
PANELBOARD, NEMA 3R
225A, 120/208V, 3Ø, 4W, 60HZ
400A BUS, 120/208V, 3Ø, 4W, 60HZ
SINGLE LINE DIAGRAM
400A 3P
EXIST.
LOAD
VOLTAGE DROP CALCULATION
1001 N BEALE RD, MARYSVILLE
1. OCCUPANCY CLASSIFICATION GROUP B
2. BUILDING CONSTRUCTION TYPE I
3. YEAR BUILT 1963
4. NUMBER OF STORIES 1
5. ACTUAL BUILDING HEIGHT 20'
6. BUILDING AREA IN SQUARE FEET (SPI) 4000'
7. PROJECT AREA IN SQUARE FEET (i.e. TENANT IMPROVEMENTS) N/A
8. ALLOWABLE AREA PER C.B.C. N/A
9. AREA AND OR HEIGHT INCREASES N/A
10. FIRE SPRINKLERED (YES OR NO)
TYPE: (WET, DRY, PRE-ACTION, DELUGE)
NO
11. FIRE ALARM (YES OR NO)
TYPE: (MANUAL, AUTOMATIC, ETC.)
NO
12. OTHER FIRE PROTECTION SYSTEMS IF ANY FIRE EXTINGUISHER
NOTES:
PB-EV PANEL SHALL BE USED FOR ONLY 208V, 1Ø EVCS CHARGING STATIONS.
ELECTRICAL ION METER, SCHNEIDER IEM3000 SERIES OR APPROVED EQUAL.
INSTALL A NEW CIRCUIT BREAKER MATCHING THE EXISTING BREAKER MANUFACTURER,
AND KAIC RATING ON EXISTING MAIN SWITCHBOARD (MSB).
CABLES SIZED FOR MAXIMUM CAPACITY OF CHARGER. CONDUITS SIZED UP 1" FOR FUTURE
PROOFING.
AN ARC-FLASH ASSESSMENT STUDY SHALL BE PERFORMED AND ADHERE TO NFPA70E
130.5.3 CONTRACTOR IS TO PROVIDE ARC-FLASH WARNING LABELS IN COMPLIANCE WITH
CEC 110.16. ARC-FLASH ASSESSMENT STUDY STUDY AND ARC-FLASH WARNING LABELS
SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEERING OF RECORD FOR REVIEW AND
APPROVAL.
CONTRACTOR TO VERIFY AND MATCH AIC RATING TO EXISTING MSB.
CONDUIT/ CABLE SCHEDULE
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JACH SWH JSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
000000000013676
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
V2
EXIST.
LOAD
EXIST.
LOAD
EXIST.
LOAD
225A 3P
PANEL SCHEDULE
SECTION POSITION DESCRIPTION
LOAD
HP kVA A
1 BLOCK HEATER
2 PANEL P
3 PB-EV 59.92 166.32
4 PANEL B
5 PANEL A
ESTIMATED LOAD MSB
TOTAL NEW CONNECTED LOAD 59.92 166.3
TOTAL DEMAND LOAD
AØ BØ CØ
(1) MAXIMUM DEMAND (BASED ON 1 YEAR OF UTILITY DATA)
(kVA) 14 14 14
(A) 116.67 116.67 116.67
(2) NEW CONNECTED LOAD
(kVA) 23.30 18.31 18.31
(A) 194.17 152.58 152.58
(3) TOTAL PROSPECTIVE LOAD
SUM OF (1) AND (2)
(kVA) 37.30 32.31 32.31
(A) 310. 8 269.3 269.3
(4) FEEDER EVALUATION (NEC 220.87)
MAXIMUM DEMAND AT 125% PLUS NEW LOAD
(4)=1.25x(1+2)
(kVA) 46.6 40.4 40.4
(A) 388.5 336.6 336.6
(E) MAIN SWITCHBOARD 'MSB'
VERTICAL BUS BRACING
MAIN FUSE RATING
MAIN BREAKER INTR. RATING
MAX FAULT AT MAIN BREAKER
FEEDER SIZE
VERTICAL BUS RATING 400A
VOLTS 120/208V, 3Ø, 4W 60HZ
XFMR CONFIGURATION
XFMR RATING
XFMR PRIMARY
XFMR SECONDARY
XFMR TEMP. RISE
XFMR IMPEDANCE
XFMR VOLTAGE
TAG XFMR TAG
ENCLOSURE TYPE NEMA 1 XFMR ENCLOSURE TYPE
LOCATION ELECTRICAL ROOM XFMR LOCATION
MSB
400A
225A
PROPOSED EV CHARGERS
PANEL LOAD SUMMARY
N/A
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/24/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2186
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
E2.0
1/16'=1'-0"
ELECTRICAL SITE PLAN
Know what's below.
before you dig.Call
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JACH SWH JSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
000000000013676
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
V2
D R A W
IN
G L
IM
IT
S
D R A W
IN
G L
IM
IT
S
DRAWING LIMITS
DRAWING LIMITS
(N) PB-EV
(E) 400A 120/208V
MSB
EVCS-1
PB-EV-1/3; 5/7
EVCS-2
PB-EV-9/11; 10/12
EVCS-3
PB-EV-2/4; 6/8
TYP.
EVCS DUAL PORT PEDESTAL (NIC)(TYP.)
NEW LEVEL 2 DUAL PORT EV CHARGERS
(TYP. 3)
(TYP.)
TYP.
TYP.
X3
X2
(TYP.)
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/24/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2186
E3.0
NONE
ELECTRICAL DETAILS
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
JACH SWH JSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
000000000013676
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
V2
2' -6
1'-0"
1'-0"
1' -6
FOR USEAGE IN LANDSCAPE
OR SIDEWALK AREAS
FLEET EVCS SIGNAGE
AUTHORIZED
FLEET
USE
ONLY
SCALE: NONE
6' -8
M
IN
. C
LE
AR
AN
C E
FR
O M T
H E
G R O U N D
5' -0
4' LONG WHEEL STOP
FINISHED GRADE ON FLOOR
RGS FLUSH CONDUIT PLUG
COUPLING, FLUSH
WITH FINISHED CONCRETE
COUPLING
PVC CONDUIT,
SEE DWG. FOR CONTINUATION
NOTES:
1. THIS STUB-UP IS ONLY TO BE USED FOR SPARES AND
FUTURE USE.
RGS PVC COATED FACTORY
MADE ELBOW
SCALE:
CONDUIT STUB-UP
NONE
SAW CUT, THEN PATCH TO
MATCH (E) SURFACE FINISH
FINISH SURFACE, AC PAVING
CONCRETE, GRASS, ETC.
RED WARNING TAPE
(ELECTRICAL)
SELECT BACKFILL
90% COMPACTION
CONDUIT, NUMBER AND SIZES
PER PLANS
SAND FILL
M
IN
3"
M
IN
NOTES:
1. WIDTH OF TRENCH WILL BE DETERMINED BY
THE SIZE OF CONDUITS, NUMBER OF
CONDUITS, AND CONFIGURATION.
3"
M
IN
SCALE:
CONDUIT TRENCH
NONE
INSTALL 1" ABOVE FINISHED GRADE IN
UNPAVED AND LANDSCAPE AREAS.
INSCRIBED BOLT ON COVER, CONCRETE OR
COMPOSITE, LETTERING PER SPECIFICATIONS.
INSTALL FLUSH WITH FINISHED
PAVED OR CONCRETE SURFACES.
ELECTRICAL CONCRETE
HANDHOLE OR PULL BOX,
CHRISTY N09 OR EQUAL
GRAVEL
CONDUIT PER PLANS
PROVIDE BUSHINGS OR END
BELLS ON ALL CONDUIT
SCALE:
HANDHOLES
NONE
STRIPING DETAIL PANELBOARD SUPPORT
3" GALVANIZED PIPE
P-1000
UNISTRUT
PANELBOARD
FINISHED GRADEFINISHED GRADE
1' -0
(M
IN
A D
JU
S T T
O B
O
LT
H O
LE
S
O F P
A N E
LB
O A R D
PANELBOARD
6" WIDER THAN
PANELBOARD
1' -6
(M
IN
3" M
IN
18" (MIN.)CONCRETE
EVSE PER PLAN
CROWN CONCRETE
4" DIA GALVANIZED STEEL
PIPE. PRIME AND PAINT
2 COATS INDUSTRIAL
YELLOW ENAMEL
SLOPE 1/2"
AGGREGATE BASE (TYP)
CONCRETE
4' -0
3' -0
3"
M
IN
1'-3"
PERMANENT BOLLARD
CONCRETE
CURB
EV
CHARGING
ONLY
EV
CHARGING
ONLY
PROPOSED OSHA
SAFTEY GREEN
14120 STRIPE
WHEELSTOP PER
PLAN
MIN. 12" HIGH WHITE LETTERS,
WITHIN 6" OF THE STALL
CENTERLINE AND ALIGNED AT THE
BOTTOM OF THE PARKING STALL
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/24/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2186
S1.0
NONE
V2
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
JACHSWHJSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
1 LEVEL 2 EVSE SERVICE PEDESTAL
NONE
FINISHED GRADE
24"W x 24"L x 24"D
4000 PSI
INSTALL FLUSH WITH
FINISHED PAVED OR
CONCRETE SURFACES.
INSTALL 4" ABOVE
FINISHED GRADE IN
UNPAVED AND
LANDSCAPING AREAS.
CHARGEPOINT LEVEL 2
CP6000 SERIES
PEDESTAL CHARGER
CONDUIT (SEE DETAIL 1, SHEET E3.0)
NATIVE SOIL
CONCRETE PAD
SECTION
3" COVER
(TYP.)
CONCRETE PAD
PLAN VIEW
CONDUIT
ENTRY
CONCRETE MOUNTING TEMPLATE
ENLARGED PLAN VIEW
CHARGEPOINT LEVEL 2 PEDESTAL CHARGER
ELEVATION VIEW
GENERAL NOTES:
STRUCTURAL DETAILS
1001 N. BEALE ROAD,
MARYSVILLE, CA 95901
State of California
Department of General Services
Real Estate Services Division
PROJECT MANAGEMENT AND DEVELOPMENT BRANCH
Architecture & Engineering Section
707 Third Street, Suite 4-105
West Sacramento, California 95605
ANN WATSON
Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV
05/08/24
100% WORKING DRAWINGS SFM
SUBMITTAL
JACHSWHJSV
EVCS LEVEL II
CA DOT DISTRICT 3
MARYSVILLE
DEPARTMENT OF
GENERAL SERVICES
0000000000000000000013676
07/02/24
100% WORKING DRAWINGS SFM
SUBMITTAL
DESIGN CRITERIA
DEVIATION / EXISTING CONDITIONS
SPECIAL INSPECTIONS
CONCRETE
STRUCTURAL GENERAL NOTES
5/8"Ø HILTI KWIK HUS-EZ SCREW
ANCHORS W/ 4" EMBED (TYP. 3)
2 - #5 @ 15" O.C. EA. WAY
TOP & BOTTOM
HILTI HILTI
HILTI
5/8"Ø HILTI KWIK HUS-EZ SCREW ANCHORS
W/ 4" EMBED (TYP. 3)
OFFICE OF THE STATE FIRE MARSHAL
shall be available on the project site at all times.
07/24/24
APPROVED FIRE AND PANIC ONLY
Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans
24-2186
| 0001 G0.0 Title Sheet |
| Sheets and Views |
| G0.0 |
| 0002 E0.0 Electrical Notes |
| Sheets and Views |
| E1.1 |
| 0003 E1.0 Single Line Diagram And Schedules |
| Sheets and Views |
| E1.0 |
| 0004 E2.0 Electrical Site Plan |
| Sheets and Views |
| E3.0 |
| 0005 E3.0 Electrical Details |
| Sheets and Views |
| E3.0 |
| 0006 S1.0 Structural Details |
| Sheets and Views |
| S1.0 |
File details come from the government source that posted it. Updated .