1001_N_Beale_Plans.pdf

PDF 6 MB Posted

Attached to
Project 13676. DOT D3 EVSE. Contract 24-240975
Solicitation number
0000034394
Issued by
Yuba County, Yuba City, California

About this file

This file contains engineering drawings and specifications for an Electric Vehicle Charging Station (EVCS) project at the California Department of Transportation (CDOT) District 3 facility located at 1001 N. Beale Road in Marysville, CA. The project involves installing infrastructure for six Level 2 dual-port EVCS charging stations intended for fleet and employee use only. The scope includes installing all electrical infrastructure for a "make ready" installation, including required wiring devices, saw cutting, trenching, backfilling, and restoration of affected surfaces. The drawings are dated July 2024 and have received State Fire Marshal approval.

The technical specifications detail a 120/208V electrical system with a new 225A panelboard (PB-EV) connected to the existing 400A main switchboard. The charging stations will be ChargePoint Level 2 CP6000 series pedestal chargers mounted on 24"x24"x24" concrete pads. The project includes detailed electrical, structural, and site work requirements, with specific details for conduit installation, bollards, signage, and surface markings. Notably, the actual EVCS charger procurement and installation is not included in the contractor's scope of work. The drawings indicate this is a designated fleet charging area not intended for public use.

View the file

Other files

File Type Posted
981_N_Beale_Plans.pdf PDF
Bid_Package_Documents.pdf PDF
Project_Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS © 2024 TomTom

© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS

© 2024 Microsoft Corporation © 2024 Maxar ©CNES (2024) Distribution Airbus DS

SITE MAP

VICINITY MAP

G0.0

NONE

CODES AND PREFERENCES SHEET INDEX

SYMBOLS AND ABBREVIATIONS

TITLE 19 CCR PUBLIC SAFETY, DIVISION 1, STATE FIRE MARSHAL REGULATIONS

TITLE 24 CCR, PART 1 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE

TITLE 24 CCR, PART 2 2022 CALIFORNIA BUILDING CODE (CBC), VOLUMES 1 AND 2 (2021 IBC, AS AMENDED BY CA)

TITLE 24 CCR, PART 3 2022 CALIFORNIA ELECTRICAL CODE (CEC) (2020 NEC, AS AMENDED BY CA)

TITLE 24 CCR, PART 8 2022 CALIFORNIA HISTORICAL BUILDING CODE

TITLE 24 CCR, PART 9 2022 CALIFORNIA FIRE CODE (CFC) (2021 IFC, AS AMENDED BY CA)

TITLE 24 CCR, PART 10 2022 EXISTING BUILDING CODE

TITLE 24 CCR, PART 11 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CAL GREEN CODE)

TITLE 24 CCR, PART 12 2022 CALIFORNIA REFERENCED STANDARDS CODE (SEE ALSO TITLE 24 CCR-PART 2, CHAPTER 35 -

REFERENCE STANDARDS AND TITLE 24 CCR - PART 9, CHAPTER 47 - REFERENCED STANDARDS)

DRAWINGS

G0.0 TITLE SHEET

E0.0 ELECTRICAL NOTES

E1.0 SINGLE LINE DIAGRAM AND SCHEDULES

E2.0 ELECTRICAL SITE PLAN

E3.0 ELECTRICAL DETAILS

S1.0 STRUCTURAL DETAILS

EVCS DESCRIPTION SCOPE OF WORK

EXISTING EVCS SPACES NEW EVCS SPACES

(0) LEVEL 1

(0) LEVEL 2

(0) LEVEL 1

(0) LEVEL 2

(0) LEVEL 1

(6) LEVEL 2

FLEET WORKPLACE WORKPLACEFLEET

DISCONNECT SWITCH, NON-FUSIBLE, SEE PLANS FOR RATING

EXISTING TO BE REMOVED AND SALVAGED

EXISTING TO BE DEMOLISHED

NEW PLANS-FINAL LOCATION OF RELOCATED EQUIPMENT.

DEMO PLANS-EXISTING TO BE RELOCATED.

EXISTING TO REMAIN

(RS)

(D)

(RL)

(E)

ENCLOSED CIRCUIT BREAKER

GROUND FAULT PROTECTION

GREEN

GREEN

WHITE

WHITE

BLUE

RED

RED

BLACK

BLACK

240V

240Y/120V

POWER WIRE COLOR CODE

SYSTEM

208Y/120V

480Y/277V

PHASE A

BLACK

YELLOW

PHASE B

RED

BROWN

PHASE C

BLUE

ORANGE

NEUTRAL

WHITE

GRAY

GROUND

GREEN

GREEN

ELECTRICAL ABBREVIATIONS

INCOMING ELECTRIC SERVICE

GROUND

DISCONNECT SWITCH, FUSIBLE, SEE PLANS FOR RATING

FUSE

SWITCH

2S, 2W = 2 SPEED, 2 WINDING

RV=REDUCED VOLTAGE STARTING

FULL-VOLTAGE NON-REVERSING UNLESS NOTED

MAGNETIC MOTOR STARTER, NEMA SIZE INDICATED

MCP INDICATES MOTOR CIRCUIT PROTECTOR

3 POLE UNLESS NOTED

CIRCUIT BREAKER,

METERING

Y, SHEET WHERE DETAIL IS DRAWN

DETAIL CALL-OUT: X, DETAIL IDENTIFIER;

WITH EQUIPMENT

CONTROLLER/STARTER FURNISHED

+ 48" UON

+ 18" UON

FLOOR GRADE TO CENTERLINE OF DEVICE

INDICATES HEIGHT FROM FINISHED

SHEET NOTE, SEE NOTE INDICATED

SURFACE MOUNTED PANELBOARD-NEW, EXISTING

POWER DISTRIBUTION SWITCHBOARD

CONDUIT STUB-OUT AND CAPPED

CONDUIT BENDS AWAY FROM OBSERVER

CONDUIT BENDS TOWARD OBSERVER

BELOW GRADE, #4/0 UON

GROUNDING CONDUCTOR 30"

CURVE LINE INDICATES GROUND WIRE

WIRE SIZE OTHER THAN #12

GROUND WIRE

QUANTITY #12 WIRE CURVE LINE INDICATES

CONDUIT EXPOSED 3/4"C-2#12, 1#12G, UON

3/4"C-2#12, 1#12G, UON

CONDUIT UNDER GROUND

CEILING 3/4"C-2#12, 1#12G, UON

CONDUIT CONCEALED IN WALLS OR

PULLBOX

HAND HOLE, 11"Hx17"Lx12"D, UON

ELECTRICAL SYMBOLS - ONE LINE DIAGRAMELECTRICAL SYMBOLS - PLANS

JUNCTION BOX

SINGLE RECEPTACLE 120V, 20A GFCI TYPE

DUPLEX RECEPTACLE

EXISTING AREA LIGHT AND POLE

(AIP)

1"C-2#12, 1#12G

(U)(V"C-W#X,Y#Z)

EXAMPLE: (2)(3/4"C-2#12-1#12G) INDICATES TWO 3/4"

CONDUITS EACH WITH 2#12 AND 1#12G CONDUCTORS

ELECTRICAL SYMBOLS COMMON

SINGLE RUN OF RACEWAY AND CIRCUIT CONDUCTORS.

FIRST NUMBER IS RACEWAY SIZE.

THE FOLLOWING NUMBERS ARE THE CONDUCTOR

QUANTITIES AND SIZES.

A AMPERES

AMPERES INTERRUPTING CAPACITY, SYMMETRICAL

AMERICAN WIRE GAUGE

BARE COPPER

CONDUIT, CONDUCTOR

AICS

AWG

BC

C

CB CIRCUIT BREAKER

CKT CIRCUIT

CNTL CONTROL

CO CONDUIT ONLY

CT CURRENT TRANSFORMER

DTL DETAIL

DWG DRAWING

E EXISTING

G, GND GROUND

GFCI GROUND-FAULT CIRCUIT INTERRUPTER

HH HANDHOLE

JB JUNCTION BOX

KCMIL THOUSAND CIRCULAR MILS

KVA KILOVOLT-AMPERES

KW KILOWATT

LTG LIGHTING

MAX MAXIMUM

MCC MOTOR CONTROL CENTER

MIN MINIMUM

MLO MAIN LUGS ONLY

MTD MOUNTED

N NEUTRAL

NIC NOT IN CONTRACT

NO. NUMBER

P POLE

PB PUSH BUTTON, PULL BOX

PC PHOTO CELL

PH, Ø PHASE

PVC POLYVINYL CHLORIDE

REQ'D REQUIRED

SMUD SACRAMENTO MUNICIPAL UTILITY DISTRICT

SW SWITCH

TYP TYPICAL

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

V VOLT

W WATTS, WIRE

W/ WITH

WP WEATHERPROOF

XFMR TRANSFORMER

NTS NOT TO SCALE

FLUSH MOUNTED PANELBOARD

EXISTING TO BE REMOVED AND REPLACED WITH NEW(RP)

ABOVE FINISHED GRADEAFG

BOLLARD

NEW PLANS: EXISTING TO NEW

INTERCEPTION POINT:

EVCS ELECTRICAL VEHICLE SUPPLY EQUIPMENT

LB FITTING

TEE FITTING

A-1,3

G

#10

PB

J

X

Y

+18"

RV

MCP

30A

M

F

GFP

LFMC LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT

(#)# CONDUIT CALLOUT REFERENCE WITH NUMBER OF CONDUITS

SHOWN IN PARENTHESIS.

PROJECT

LOCATION

PROJECT

WORKING AREA

(6 EVCS SPACES)

ELECTRICAL VEHICLE SUPPLY EQUIPMENT (EVCS) INSTALLED ON THIS PROJECT WILL NOT BE AVAILABLE TO THE GENERAL PUBLIC, AND IS INTENDED FOR

USE BY A DESIGNATED VEHICLE OR EMPLOYEE. ELECTRIC VEHICLE CHARGER PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.

INSTALL AND ELECTRICALLY CONNECT EVCS INFRASTRUCTURE FOR MAKE READY INSTALLATION AS

SHOWN. CONTRACTOR TO PROVIDE AND INSTALL THE WIRING DEVICES INCLUDING ALL REQUIRED

ASSOCIATED ITEMS FOR A COMPLETE AND OPERATIONAL SYSTEM INCLUDING REQUIRED TESTING.

CONTRACTOR SHALL ALSO PROVIDE THE REQUIRED SAW CUTTING, TRENCHING, BACKFILLING AND

FINISHING OF THE AFFECTED LOT SURFACE AND RESTORE TO ORIGINAL CONDITION. EVCS CHARGER

PROCUREMENT AND INSTALLATION IS NOT IN THE CONTRACTORS SCOPE.

NOTICE TO CONTRACTOR:

MUST ADHERE TO CFC CHAPTER 33. FIELD DEPUTY TO VERIFY.

(0) LEVEL 1

(0) LEVEL 2

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

JACH SWH JSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

000000000013676

POWER TRANSFORMER

FEEDER DESIGNATION SEE

CONDUIT/CONDUCTOR TABLE FOR SIZE

TITLE SHEET

HOMERUN TO PANEL A,

CIRCUIT 1 AND 3

ABANDON IN PLACE. (D) ABOVE GROUND CONDUITS &

CONNECTORS DOWN TO 3" BELOW GROUND LEVEL.

REMOVE AND (D) CONDUCTORS IN UG CONDUITS.

PLUG UG CONDUITS AND ABANDON IN PLACE.

MULTIPLE RUNS OF RACEWAY AND CIRCUIT CONDUCTORS

U = # OF PARALLEL RUNS

V = CONDUIT SIZE

W = # OF PHASE/NEUTRAL CONDUCTORS IN EA. CONDUIT

X = PHASE/NEUTRAL CONDUCTOR SIZE

Y = #OF GROUND CONDUCTORS IN EACH CONDUIT

Z = GROUND CONDUCTOR SIZE

V2

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/24/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2186

DOT D3 - Electric Vehicle Supply Equipment - Marysville (2 Sites) PN: 000000000013676, Date: 2/21/2025

E0.0

N/A

ELECTRICAL NOTES

SPECIAL INSPECTIONS REQUIRED

CONCRETE CONSTRUCTION:

STEEL CONSTRUCTION:

GENERAL NOTES:

V2

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

JACH SWH JSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

000000000013676

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

N/A

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/24/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2186

E1.0

N/A

SINGLE LINE DIAGRAM

AND SCHEDULES

120/208V MAIN SWITCHBOARD, NEMA 1 3Ø, 4W, 60HZ

(E) MSB

PB-EV

PANELBOARD, NEMA 3R

225A, 120/208V, 3Ø, 4W, 60HZ

400A BUS, 120/208V, 3Ø, 4W, 60HZ

SINGLE LINE DIAGRAM

400A 3P

EXIST.

LOAD

VOLTAGE DROP CALCULATION

1001 N BEALE RD, MARYSVILLE

1. OCCUPANCY CLASSIFICATION GROUP B

2. BUILDING CONSTRUCTION TYPE I

3. YEAR BUILT 1963

4. NUMBER OF STORIES 1

5. ACTUAL BUILDING HEIGHT 20'

6. BUILDING AREA IN SQUARE FEET (SPI) 4000'

7. PROJECT AREA IN SQUARE FEET (i.e. TENANT IMPROVEMENTS) N/A

8. ALLOWABLE AREA PER C.B.C. N/A

9. AREA AND OR HEIGHT INCREASES N/A

10. FIRE SPRINKLERED (YES OR NO)

TYPE: (WET, DRY, PRE-ACTION, DELUGE)

NO

11. FIRE ALARM (YES OR NO)

TYPE: (MANUAL, AUTOMATIC, ETC.)

NO

12. OTHER FIRE PROTECTION SYSTEMS IF ANY FIRE EXTINGUISHER

NOTES:

PB-EV PANEL SHALL BE USED FOR ONLY 208V, 1Ø EVCS CHARGING STATIONS.

ELECTRICAL ION METER, SCHNEIDER IEM3000 SERIES OR APPROVED EQUAL.

INSTALL A NEW CIRCUIT BREAKER MATCHING THE EXISTING BREAKER MANUFACTURER,

AND KAIC RATING ON EXISTING MAIN SWITCHBOARD (MSB).

CABLES SIZED FOR MAXIMUM CAPACITY OF CHARGER. CONDUITS SIZED UP 1" FOR FUTURE

PROOFING.

AN ARC-FLASH ASSESSMENT STUDY SHALL BE PERFORMED AND ADHERE TO NFPA70E

130.5.3 CONTRACTOR IS TO PROVIDE ARC-FLASH WARNING LABELS IN COMPLIANCE WITH

CEC 110.16. ARC-FLASH ASSESSMENT STUDY STUDY AND ARC-FLASH WARNING LABELS

SHALL BE SUBMITTED TO THE ELECTRICAL ENGINEERING OF RECORD FOR REVIEW AND

APPROVAL.

CONTRACTOR TO VERIFY AND MATCH AIC RATING TO EXISTING MSB.

CONDUIT/ CABLE SCHEDULE

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

JACH SWH JSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

000000000013676

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

V2

EXIST.

LOAD

EXIST.

LOAD

EXIST.

LOAD

225A 3P

PANEL SCHEDULE

SECTION POSITION DESCRIPTION

LOAD

HP kVA A

1 BLOCK HEATER

2 PANEL P

3 PB-EV 59.92 166.32

4 PANEL B

5 PANEL A

ESTIMATED LOAD MSB

TOTAL NEW CONNECTED LOAD 59.92 166.3

TOTAL DEMAND LOAD

AØ BØ CØ

(1) MAXIMUM DEMAND (BASED ON 1 YEAR OF UTILITY DATA)

(kVA) 14 14 14

(A) 116.67 116.67 116.67

(2) NEW CONNECTED LOAD

(kVA) 23.30 18.31 18.31

(A) 194.17 152.58 152.58

(3) TOTAL PROSPECTIVE LOAD

SUM OF (1) AND (2)

(kVA) 37.30 32.31 32.31

(A) 310. 8 269.3 269.3

(4) FEEDER EVALUATION (NEC 220.87)

MAXIMUM DEMAND AT 125% PLUS NEW LOAD

(4)=1.25x(1+2)

(kVA) 46.6 40.4 40.4

(A) 388.5 336.6 336.6

(E) MAIN SWITCHBOARD 'MSB'

VERTICAL BUS BRACING

MAIN FUSE RATING

MAIN BREAKER INTR. RATING

MAX FAULT AT MAIN BREAKER

FEEDER SIZE

VERTICAL BUS RATING 400A

VOLTS 120/208V, 3Ø, 4W 60HZ

XFMR CONFIGURATION

XFMR RATING

XFMR PRIMARY

XFMR SECONDARY

XFMR TEMP. RISE

XFMR IMPEDANCE

XFMR VOLTAGE

TAG XFMR TAG

ENCLOSURE TYPE NEMA 1 XFMR ENCLOSURE TYPE

LOCATION ELECTRICAL ROOM XFMR LOCATION

MSB

400A

225A

PROPOSED EV CHARGERS

PANEL LOAD SUMMARY

N/A

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/24/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2186

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHARGING

ONLY

EV

CHARGING

ONLY

E2.0

1/16'=1'-0"

ELECTRICAL SITE PLAN

Know what's below.

before you dig.Call

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

JACH SWH JSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

000000000013676

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

V2

D R A W

IN

G L

IM

IT

S

D R A W

IN

G L

IM

IT

S

DRAWING LIMITS

DRAWING LIMITS

(N) PB-EV

(E) 400A 120/208V

MSB

EVCS-1

PB-EV-1/3; 5/7

EVCS-2

PB-EV-9/11; 10/12

EVCS-3

PB-EV-2/4; 6/8

TYP.

EVCS DUAL PORT PEDESTAL (NIC)(TYP.)

NEW LEVEL 2 DUAL PORT EV CHARGERS

(TYP. 3)

(TYP.)

TYP.

TYP.

X3

X2

(TYP.)

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/24/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2186

E3.0

NONE

ELECTRICAL DETAILS

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

JACH SWH JSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

000000000013676

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

V2

2' -6

1'-0"

1'-0"

1' -6

FOR USEAGE IN LANDSCAPE

OR SIDEWALK AREAS

FLEET EVCS SIGNAGE

AUTHORIZED

FLEET

USE

ONLY

SCALE: NONE

6' -8

M

IN

. C

LE

AR

AN

C E

FR

O M T

H E

G R O U N D

5' -0

4' LONG WHEEL STOP

FINISHED GRADE ON FLOOR

RGS FLUSH CONDUIT PLUG

COUPLING, FLUSH

WITH FINISHED CONCRETE

COUPLING

PVC CONDUIT,

SEE DWG. FOR CONTINUATION

NOTES:

1. THIS STUB-UP IS ONLY TO BE USED FOR SPARES AND

FUTURE USE.

RGS PVC COATED FACTORY

MADE ELBOW

SCALE:

CONDUIT STUB-UP

NONE

SAW CUT, THEN PATCH TO

MATCH (E) SURFACE FINISH

FINISH SURFACE, AC PAVING

CONCRETE, GRASS, ETC.

RED WARNING TAPE

(ELECTRICAL)

SELECT BACKFILL

90% COMPACTION

CONDUIT, NUMBER AND SIZES

PER PLANS

SAND FILL

M

IN

3"

M

IN

NOTES:

1. WIDTH OF TRENCH WILL BE DETERMINED BY

THE SIZE OF CONDUITS, NUMBER OF

CONDUITS, AND CONFIGURATION.

3"

M

IN

SCALE:

CONDUIT TRENCH

NONE

INSTALL 1" ABOVE FINISHED GRADE IN

UNPAVED AND LANDSCAPE AREAS.

INSCRIBED BOLT ON COVER, CONCRETE OR

COMPOSITE, LETTERING PER SPECIFICATIONS.

INSTALL FLUSH WITH FINISHED

PAVED OR CONCRETE SURFACES.

ELECTRICAL CONCRETE

HANDHOLE OR PULL BOX,

CHRISTY N09 OR EQUAL

GRAVEL

CONDUIT PER PLANS

PROVIDE BUSHINGS OR END

BELLS ON ALL CONDUIT

SCALE:

HANDHOLES

NONE

STRIPING DETAIL PANELBOARD SUPPORT

3" GALVANIZED PIPE

P-1000

UNISTRUT

PANELBOARD

FINISHED GRADEFINISHED GRADE

1' -0

(M

IN

A D

JU

S T T

O B

O

LT

H O

LE

S

O F P

A N E

LB

O A R D

PANELBOARD

6" WIDER THAN

PANELBOARD

1' -6

(M

IN

3" M

IN

18" (MIN.)CONCRETE

EVSE PER PLAN

CROWN CONCRETE

4" DIA GALVANIZED STEEL

PIPE. PRIME AND PAINT

2 COATS INDUSTRIAL

YELLOW ENAMEL

SLOPE 1/2"

AGGREGATE BASE (TYP)

CONCRETE

4' -0

3' -0

3"

M

IN

1'-3"

PERMANENT BOLLARD

CONCRETE

CURB

EV

CHARGING

ONLY

EV

CHARGING

ONLY

PROPOSED OSHA

SAFTEY GREEN

14120 STRIPE

WHEELSTOP PER

PLAN

MIN. 12" HIGH WHITE LETTERS,

WITHIN 6" OF THE STALL

CENTERLINE AND ALIGNED AT THE

BOTTOM OF THE PARKING STALL

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/24/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2186

S1.0

NONE

V2

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

JACHSWHJSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

1 LEVEL 2 EVSE SERVICE PEDESTAL

NONE

FINISHED GRADE

24"W x 24"L x 24"D

4000 PSI

INSTALL FLUSH WITH

FINISHED PAVED OR

CONCRETE SURFACES.

INSTALL 4" ABOVE

FINISHED GRADE IN

UNPAVED AND

LANDSCAPING AREAS.

CHARGEPOINT LEVEL 2

CP6000 SERIES

PEDESTAL CHARGER

CONDUIT (SEE DETAIL 1, SHEET E3.0)

NATIVE SOIL

CONCRETE PAD

SECTION

3" COVER

(TYP.)

CONCRETE PAD

PLAN VIEW

CONDUIT

ENTRY

CONCRETE MOUNTING TEMPLATE

ENLARGED PLAN VIEW

CHARGEPOINT LEVEL 2 PEDESTAL CHARGER

ELEVATION VIEW

GENERAL NOTES:

STRUCTURAL DETAILS

1001 N. BEALE ROAD,

MARYSVILLE, CA 95901

State of California

Department of General Services

Real Estate Services Division

PROJECT MANAGEMENT AND DEVELOPMENT BRANCH

Architecture & Engineering Section

707 Third Street, Suite 4-105

West Sacramento, California 95605

ANN WATSON

Phone 279 782-3872 Fax 916 376-6216 ann.watson@DGS.CA.GOV

05/08/24

100% WORKING DRAWINGS SFM

SUBMITTAL

JACHSWHJSV

EVCS LEVEL II

CA DOT DISTRICT 3

MARYSVILLE

DEPARTMENT OF

GENERAL SERVICES

0000000000000000000013676

07/02/24

100% WORKING DRAWINGS SFM

SUBMITTAL

DESIGN CRITERIA

DEVIATION / EXISTING CONDITIONS

SPECIAL INSPECTIONS

CONCRETE

STRUCTURAL GENERAL NOTES

5/8"Ø HILTI KWIK HUS-EZ SCREW

ANCHORS W/ 4" EMBED (TYP. 3)

2 - #5 @ 15" O.C. EA. WAY

TOP & BOTTOM

HILTI HILTI

HILTI

5/8"Ø HILTI KWIK HUS-EZ SCREW ANCHORS

W/ 4" EMBED (TYP. 3)

OFFICE OF THE STATE FIRE MARSHAL

shall be available on the project site at all times.

07/24/24

APPROVED FIRE AND PANIC ONLY

Approval of this plan does not authorize or approve any omission or deviation from applicable regulations. Final approval is subject to field inspection. One set of approved plans

24-2186

0001 G0.0 Title Sheet
Sheets and Views
G0.0
0002 E0.0 Electrical Notes
Sheets and Views
E1.1
0003 E1.0 Single Line Diagram And Schedules
Sheets and Views
E1.0
0004 E2.0 Electrical Site Plan
Sheets and Views
E3.0
0005 E3.0 Electrical Details
Sheets and Views
E3.0
0006 S1.0 Structural Details
Sheets and Views
S1.0

File details come from the government source that posted it. Updated .