100-CD---DRAWINGS---692-22-102-VAWC-Renovate-Specialty-Care.pdf
PDF 12 MB Posted
- Solicitation number
- 36C26026R0021
About this file
These are construction documents for a renovation project at the White City VA Medical Center in White City, Oregon. The project involves renovating Building 211A Specialty Care, which is approximately 2,100 square feet, to address infrastructure facility condition deficiencies and improve utility infrastructure resiliency and capacity. The comprehensive set of architectural, mechanical, electrical, plumbing, and fire protection drawings covers demolition, new construction, equipment specifications, and system modifications. Key elements include renovating exam rooms, clinical support spaces, corridors, and associated infrastructure, with work involving architectural updates, mechanical system replacements, electrical system modifications, and upgrades to medical gas, plumbing, and fire protection systems. The project number is 692-22-102, and the documents are dated August 15, 2025, with the design by Spees Design Build from Kent, Washington.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26026R0021.docx | DOCX document | |
| 100-CD---SPECIFICATIONS---692-22-102-VAWC-Renovate-Specialty-Care.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. STE 203
KENT, WA 98032
PHONE: (206) 590-2118
DESIGN TEAM
ELECTRICAL
SPEES DESIGN BUILD
PLUMBING
SPEES DESIGN BUILD
MECHANICAL
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. STE 203
KENT, WA 98032
PHONE: (206) 590-2118
23830 PACIFIC HIGHWAY S. STE 203
KENT, WA 98032
PHONE: (206) 590-2118
23830 PACIFIC HIGHWAY S. STE 203
KENT, WA 98032
PHONE: (206) 590-2118
FIRE PROTECTION
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. STE 203
KENT, WA 98032
PHONE: (206) 590-2118
PROJECT INFORMATION
STATE:
COUNTY:
JURISTICTION:
OWNER:
CODE ANALYSIS
PROJECT DESCRIPTION
THE PROPOSED DESIGN SHALL ALTER,
MODIFY AND PARTIALLY RENOVATE BUIDLING
211A FOR SPECIALTY CARE TO ADDRESS
INFRASTRUCTURE FACILITY CONDITION
DEFICIENCIES/IMPROVE UTILITY
INFRASTRUCTURE RESILIENCY/CAPACITY.
APPLICABLE BUILDING
B211A
APPLICABLE CLINIC
SPECIALTY CARE
APPROX SQUARE FEET IN SCOPE
2,100 SF
OREGON
JACKSON
WHITE CITY
GOV, VETERANS AFFAIRS
GENERAL NOTES
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO DRAWINGS &
SPECIFICATIONS.
2. SPECIFICATIONS SHALL SUPERSEDE DRAWINGS IN THE CASE OF ANY CONFLICTING INFORMATION.
BRING TO THE AWARENESS OF AND VERIFY WITH VA COR PRIOR TO PROCEEDING.
3. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT
IMMEDIATELY TO THE ATTENTION OF THE COR.
4. ALL WORK SHALL BE PERFORMED WITH A HIGH-LEVEL OF WORKMANSHIP.
5. THE CONTRACTOR SHALL VERIFY ALL PRODUCT TYPES AND QUANTITIES DURING SITE WALK
THROUGH, PRIOR TO PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
6. THE CONTRACTOR SHALL VERIFY AND COORDINATE WITH ALL INSTALLERS TO ENSURE COMPLIANCE
WITH THE CONTRACT DOCUMENTS.
211A
BUILDING WITHIN SCOPE OF THIS PROJECT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
G-001
COVER & DRAWING INDEX
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
RENOVATE B211A SPECIALTY CARE
PROJECT #: 692-22-102
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OREGON
1" = 100'-0"
FACILITY SITE PLAN - COVER
1/4" = 1'-0"
LOCATION PLAN
WHITE CITY VA MEDICAL CENTER,
WHITE CITY, OR
TRUE
NORTH
TRUE
NORTH
DRAWING INDEX
PAGE # SHEET # SHEET NAME
MECHANICAL
24 OF 45 M-001 MECHANICAL GENERAL NOTES
25 OF 45 M-002 MECHANICAL ABBREVIATIONS & LEGENDS
26 OF 45 MD101 DEMOLITION FLOOR PLAN - MECHANICAL DUCTWORK LAYOUT
27 OF 45 MD102 DEMOLITION FLOOR PLAN - MECHANICAL PIPING LAYOUT
28 OF 45 M-101 FLOOR PLAN - MECHANICAL DUCTWORK LAYOUT
29 OF 45 M-102 REFLECTED CEILING PLAN
30 OF 45 MP101 FLOOR PLAN - MECHANICAL PIPING LAYOUT
31 OF 45 M-501 MECHANICAL DETAILS
32 OF 45 M-601 MECHANICAL EQUIPMENT SCHEDULES
ELECTRICAL
33 OF 45 E-001 ABBREVIATION, GENERAL NOTES, AND SHEET INDEX
34 OF 45 E-002 ELECTRICAL LEGENDS
35 OF 45 ED101 OVERALL LIGHTING DEMOLITION PLAN
36 OF 45 ED102 OVERALL POWER AND SPECIAL SYSTEMS DEMOLITION PLAN
37 OF 45 EL101 OVERALL LIGHTING PLAN
38 OF 45 EP101 OVERALL POWER PLAN
39 OF 45 ET101 OVERALL SPECIAL SYSTEMS PLAN
40 OF 45 E-501 ELECTRICAL DETAILS
41 OF 45 E-502 ELECTRICAL DETAILS
43 OF 45 E-601 BUILDING 211A PARTIAL ONE-LINE DIAGRAM
44 OF 45 E-701 ELECTRICAL PANEL SCHEDULES
45 OF 45 E-702 ELECTRICAL GENERAL SCHEDULES
DRAWING INDEX
PAGE # SHEET # SHEET NAME
GENERAL
01 OF 45 G-001 COVER & DRAWING INDEX
02 OF 45 GS101 FACILITY SITE PLAN
ARCHITECTURAL
03 OF 45 A-001 ARCHITECTURAL SYMBOLS & ABBREVIATIONS
04 OF 45 AS101 ICRA PLAN
05 OF 45 AS201 FIRE AND LIFE SAFETY
06 OF 45 AD101 OVERALL DEMO FLOOR PLAN
07 OF 45 AD102 OVERALL DEMO REFLECTED CEILING PLAN
08 OF 45 AE101 OVERALL FLOOR PLAN
09 OF 45 AC101 OVERALL REFLECTED CEILING PLAN
10 OF 45 AE421a EXAM ROOM 124 - ENLARGED FLOOR PLAN AND INTERIOR ELEVATIONS
11 OF 45 AE421b EXAM ROOM 125 & 126 - ENLARGED FLOOR PLAN AND INTERIOR ELEVATIONS
12 OF 45 A-501 DETAILS
13 OF 45 A-510 INTERIOR SLIDING DOOR DETAILS
14 OF 45 A-601 SCHEDULES, DETAILS, DOOR TYPES & DETAILS
15 OF 45 AW001 SIGNAGE MESSAGE SCHEDULE, IN-04.02, IN-07.02
FIRE
16 OF 45 FX001 FIRE PROTECTION GENERAL NOTES, ABBREVIATIONS & LEGENDS.
17 OF 45 FX101 REFLECTED CEILING PLAN
PLUMBING
18 OF 45 P-001 PLUMBING GENERAL NOTES, ABBREVIATIONS, LEGENDS & SCHEDULE
19 OF 45 PD100 DEMOLITION FLOOR PLAN - PLUMBING FOUNDATION LAYOUT
20 OF 45 PD101 DEMOLITION FLOOR PLAN - PLUMBING LAYOUT
21 OF 45 PD102 DEMOLITION FLOOR PLAN - MEDICAL GAS LAYOUT
22 OF 45 P-100 FLOOR PLAN - PLUMBING FOUNDATION LAYOUT
23 OF 45 P-101 FLOOR PLAN - PLUMBING LAYOUT
Revisions: Date: 1 OF 45
211A
TRUE
NORTH
VA WHITE CITY MEDICAL CENTER
OREGON
1. COORDINATE CONTRACTOR STAGING AREA WITH VA COR
AT THE PRE-CONSTRUCTION MEETING. THIS INCLUDES,
BUT IS NOT LIMITED TO, AREAS TO BE USED FOR
MATERIAL STORAGE, ACCESS FOR MATERIAL DELIVERIES
AND TRANSPORTATION ROUTES TO THE PROJECT AREA.
2. DO NOT STORE PRODUCTS, MATERIALS, TOOLS,
EQUIPMENT, VEHICLES, OR ANY OTHER NON-PERMITTED
ITEMS ON MEDICAL CENTER PROPERTY UNLESS GIVEN
PRIOR APPROVAL BY THE VA COR.
3. A LIMITED AMOUNT OF SUPPLIES MAY BE STORED IN THE
CONSTRUCTION AREA AS LONG AS SAFETY AND
CLEANLINESS ARE NOT COMPROMISED. VA COR HAS
AUTHORITY TO REQUEST RELOCATION OF ANY AND
ALL STORED ITEMS TO A DIFFERENT LOCATION.
4. VERIFY CONTRACTOR STAGING AREA AND MATERIAL /
PRODUCT DELIVERY LOCATION WITH VA COR, PRIOR TO
BRINGING OR DELIVERING ITEMS TO THE MEDICAL
CENTER.
BUILDING WITHIN THE SCOPE OF THIS
PROJECT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
GS101
FACILITY SITE PLAN
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
1" = 50'-0"
FACILITY SITE PLAN
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
TRUE
NORTH
Revisions: Date: 2 OF 45
AB
ABA
AC(T)
ACM
ACW
ADA
ADJ
A/E
AF
AFF
AGG
ALT
ALUM
APPROX
ARCH
ASPH
A/V
BARR
BATH
BB
BLDG
BLK
BLKG
BLW
BM
BMTU
BO
BOC
BOS
BRC
BRKT
BRNG
BTM
BTWN
CAB
CC
CD
CJ
CLG
CLR
CMU
CO
COL
COMP
CONC
CONN
CONST
CONT
COORD
COR
CORR
CS
CT
CTR
CV
AND
ANGLE
AT
CENTERLINE
DEGREES
NUMBER
ANCHOR BOLT
ARCHITECTURAL BARRIERS ACT
ACOUSTICAL CEILING (TILE)
ASBESTOS CONTAINING MATERIAL
ACOUSTICAL WALL
AMERICANS W/ DISABILITIES ACT
ADJACENT
ARCHITECT/ENGINEER
ACCESS FLOOR
ABOVE FINISH FLOOR
AGGREGATE
ALTERNATE
ALUMINUM
APPROXIMATELY
ARCHITECT(URAL)
ASPHALT
AUDIO / VIDEO
BARRIER
BATHROOM
BACKER BOARD
BUILDING
BLOCK
BLOCKING
BELOW
BEAM
BONE MARROW TRANSPLANT UNIT
BOTTOM OF
BOTTOM OF CURB
BOTTOM OF SLAB
BRACE, BRACING
BRACKET
BEARING
BOTTOM
BETWEEN
CABINET
CONTRACTOR FURN, CONTRACTOR INST
CONSTRUCTION/CONTRACT DOCUMENTS
CONTROL JOINT
CEILING
CLEAR(ANCE)
CONCRETE MASONRY UNIT
CONTRACTING OFFICER
COLUMN
COMPOSITION
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
CONTRACTING OFFICER REPRESENTATIVE
CORRIDOR
CONCRETE SEALER
CERAMIC TILE
CENTER
CONTRACTOR FURNISHED, VA INSTALLED
HDR
HDWE
HM
HORZ
HPDL
HR
HT
HVAC
ICRA
ID
ILSM
INCL
INST
INSUL
INT
JT
KV
LAM
LAV
LCM
LT
MAT
MAX
MDF
MECH
MEP
MFR
MIN
MISC
MOD
MTL
N N/A
NEG
NO.
NOM
NTS
O.C.
OPNG
OPP
OPT
OVHD
P
PCONC
PCRA
PL
PLAM
PLY(WD)
PNL
PR
PRFB
PS
PT
PTN(S)
PVMT
QTY
HEADER
HARDWARE
HOLLOW METAL
HORIZONTAL
HIGH PRESSURE DECORATIVE LAM
HOUR
HEIGHT
HEATING, VENTILATION & AIR CONDITIONING
INFECTIOUS CONTROL RISK ASSESSMENT
INSIDE DIAMETER OR DIM
INTERIM LIFE SAFETY MEASURES
INCLUDE(D,ING)
INSTALL
INSULATION
INTERIOR
JOINT
KILOVOLT
LAMINATE(D)
LAVATORY
LEAD CONTAINING MATERIAL(S)
LIGHT
MATERIAL(S)
MAXIMUM
MEDIUM-DENSITY FIBREBOARD
MECHANIC(AL)
MECHANICAL, ELECTRICAL, PLUMBING
MANUFACTURE(R)
MINIMUM
MISCELLANEOUS
MODIFIED
METAL
NORTH
NOT APPLICABLE
NEGATIVE
NUMBER
NOMINAL
NOT TO SCALE
ON CENTER(S)
OPENING
OPPOSITE
OPTION(AL)
OVERHEAD
PAINT
PRECAST CONCRETE
PRE-CONSTRUCTION RISK ASSESSMENT
PLATE
PLASTIC LAMINATE
PLYWOOD
PANEL
PAIR
PREFABRICATED
PLASTIC
PRESSURE TREATED
PARTITION(S)
PAVEMENT
QUANTITY
RAD
RCP
REF
REINF
REP
REQ(s,(')D)
RESIL
REV
RF
RM
RMV
RO
S
SCHED
SD
SECT
SF
SFRM
SHG
SHT(G)
SIM
SM
SOW
SPEC
SQ
SS
ST
STDG
STL
STOR
STRUCT
SUSP
SV
SYS
TEMP
T&G
THK
THRESH
TOC
TOS
TPH
TRANS
TS
TYP
UON
VA
VAR
VB
VC
VERT
VIF
VV
W W/
WD
WDW
WGHT
W/O
WP
WR
RADIUS
REFLECTED CEILING PLAN
REFERENCE
REINFORCE(D,ING)
REPRESENTATIVE
REQUIRE(D,S,MENT(S))
RESILIENT
REVERSE
RADIO FREQUENCY / ROOF
ROOM
REMOVE
ROUGH OPENING
SOUTH
SCHEDULE
SCHEMATIC DESIGN
SECTION
SQUARE FEET
SPRAY APPLIED FIRE-RESISTIVE MATERIAL
SHINGLES
SHEET (SHEATHING)
SIMILAR
SEAM
SCOPE OF WORK
SPECIFICATION
SQUARE
STAINLESS STEEL
STAIN
STANDING
STEEL
STORAGE
STRUCTURAL
SUSPENDED
SHEET VINYL
SYSTEM
TEMPORARY
TONGUE AND GROOVE
THICK(NESS)
THRESHOLD
TABLE OF CONTENTS
TOP OF SLAB
TOILET PAPER HOLDER
TRANSITION
TUBE STEEL
TYPICAL
UNLESS OTHERWISE NOTED
VETERANS AFFAIRS
VARIES
VAPOR BARRIER
VA FURNISHED, CONTRACTOR INSTALLED
VERTICAL
VERIFY IN FIELD
VA FURNISHED, VA INSTALLED
WEST
WITH
WOOD
WINDOW
WEIGHT
WITHOUT
WATERPROOF(ING)
WATER RESISTANT
DBL
DC
DD
DEMO
DEPT
DG
DIA
DIM
DWN
DR
DTL
DWG
E
EA
EJ
ELEC
ELEV
ENG
EOC
EOP
EPDM
EQ
EQUIP
ES
ETS
EX(IST)
EXP
EXT
FA
FD
FE(C)
FF
FFB
FFL
FIN
FLASH
FLR
FLRSNT
FNDN
FOC
FOF
FOS
FP
FR
FRM
FT
FTG
FUR
FURN
GA
GALV
GE
G(W)B
GC
GL
GLB
GMU
GOV(T)
GYP
DOUBLE
DIRECT CURRENT
DESIGN DEVELOPMENT
DEMOLISH(ION)
DEPARTMENT
DESIGN GUIDE
DIAMETER
DIMENSION
DOWN
DOOR
DETAIL
DRAWING(S)
EAST
EACH
EXPANSION JOINT
ELECTRIC(AL)
ELEVATION OR ELEVATOR
ENGINEER(ING)
EDGE OF CURB
EDGE OF PAVEMENT
ETHYLENE PROPYLENE DIENE TERPOLYMER
EQUAL
EQUIPMENT
EACH SIDE
EXPOSED TO STRUCTURE
EXISTING
EXPANSION
EXTERIOR
FIRE ALARM
FLOOR DRAIN
FIRE EXTINGUISHER (CABINET)
FACTORY FINISH
FINISH FLOOR BREAK
FINISH FLOOR LINE
FINISH(ED)
FLASHING
FLOOR(ING)
FLORESCENT
FOUNDATION
FACE OF CONCRETE
FACE OF FINISH
FACE OF STUDS
FIRE PROOF
FIRE RATED
FRAME
FOOT, FEET
FOOTING
FURRING
FURNISHED
GAGE, GAUGE
GALVANIZED
GENERAL ELECTRIC
GYPSUM (WALL) BOARD
GENERAL CONTRACTOR
GRID LINE
GLUE LAMINATED BEAM
GLASS MASONRY UNIT
GOVERNMENT
GYPSUM BOARD
A101
1 TYP
101.1
A-101
SIM
EXTERIOR ELEVATION
INTERIOR ELEVATION
BUILDING SECTION FLAG
WALL SECTION FLAG
CALLOUT FLAG
VERTICAL GRID LINE
HORIZONTAL GRID LINE
TRUE NORTH ARROW
PROJECT NORTH ARROW
(TRUE NORTH DASHED)
ELEVATION MARKER
KEY NOTE
ROOM TAG (SF OPTIONAL)
CEILING HEIGHT TAG
ROOM NAME
150 SF
A
A-101
SIM
01A
TRUE
NORTH
W1
A-101
PROJECT
NORTH
WALL TAG
FLOOR TAG
ROOF TAG
DOOR TAG
WINDOW TAG
SPECIALTY EQUIPMENT TAG
SIGNAGE TAG
SIGNAGE KEY NOTE
(AW SHEETS ONLY)
SIGNAGE MATERIAL TAG
(AW SHEETS ONLY)
EXISTING TO REMAIN
NEW CONSTRUCTION
TO DEMOLISH
HIDDEN ABOVE OR BELOW
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
NEW DOOR
1 HR FIRE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
FIRE EXTINGUISHER CABINET
AREA OF WORK / AREA SHOWN
CONSTRUCTION ZONE, ( - - )
PRESSURE
ANTE ROOM, ( - ) PRESSURE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
PATH OF TRAVEL
EMERGENCY EGRESS PATHWAY
SEISMIC JOINT
BATT INSULATION
RIGID INSULATION
GYPSUM BOARD, TYPE X
ACOUSTICAL CEILING TILE, 2' x 2'
CONCRETE
STEEL
PLYWOOD, FIRE RATED
EARTH
SUPPLY GRILLE PER MECHANICAL
(SIZE & PROPORTIONS MAY VARY)
RETURN GRILLE PER MECHANICAL
(SIZE & PROPORTIONS MAY VARY)
LIGHTING PER ELECTRICAL
(SIZE & PROPORTIONS MAY VARY)
A-101
A01
D88
A5175SOAP DISH
IN-04.02-01
AFF
GYP ON MTL STUD
9' - 0"
FEC
F-1
R-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-001
ARCHITECTURAL SYMBOLS &
ABBREVIATIONS
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AK
CONSTRUCTION
DOCUMENTS
SYMBOLS ABBREVIATIONS
GENERAL NOTES
APPLICABLE PUBLICATIONS
1. ALL WORK DONE BY THE CONTRACTOR OR SUB-CONTRACTORS SHALL BE PERFORMED WITH
A HIGH LEVEL OF WORKMANSHIP.
2. MAINTAIN A SAFE, CLEAN CONSTRUCTION ZONE AT ALL TIMES.
3. DO NOT SCALE DRAWINGS.
4. DIMENSIONS ARE NOT ADJUSTABLE UNLESS NOTED WITH A +/- SYMBOL. ONLY NORMAL
INDUSTRY STANDARD TOLERANCES ARE ACCEPTABLE DEVIATIONS FROM DIMENSIONS
INDICATED.
5. ALL DIMENSIONS NOTED AS CLEAR SHALL MAINTAIN THE FULL SPACE INDICATED WITHOUT
ENCROACHMENTS.
6. FURNISH ALL MATERIALS & PRODUCTS TO COMPLY WITH THE CONTRACT DOCUMENTS.
7. ALL VERTICAL HEIGHTS INDICATED ARE FROM THE FINISH FLOOR ELEVATION, UON.
8. ANY AND ALL WALL MOUNTED EQUIPMENT SHALL HAVE BLOCKING IN WALL BEHIND, THIS
INCLUDES BACKING FOR WALL MOUNTED DOOR STOPS. ENSURE THAT ALL REQUIRED
BACKING IS INSTALLED IN WALLS PRIOR TO INSTALLING DRYWALL.
9. IN TOILET ROOMS PROVIDE STAINLESS STEEL FILLER BEHIND ANY MIRRORS AND OTHER
WALL MOUNTED ACCESSORIES WHEN ITEM IS INSTALLED PARTIALLY OVER CERAMIC TILE.
ARCHITECTURAL NOTES
AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITIONS OF CODE ENFORCEMENT PROCEDURES ( DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC). THE VA
SHALL FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ).
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION
GUIDE AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL). SEE ABOVE.
INTERNATIONAL BUILDING CODE (IBC) 2021.
NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE, 2024 ED. NFPA 101 TAKES
PRECEDENCE OVER IBC.
NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8.
NATIONAL ELECTRICAL CODE (NEC) NFPA 70, 2023.
NFPA 13, 2022 ED., STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEM.
INTERNATIONAL PLUMBING CODE (IPC), 2022.
NFPA 72, 2022 ED., NATIONAL FIRE ALARM AND SIGNALING CODE.
Revisions: Date: 3 OF 45
L
L
L
L
L
L
L
L
L
OVERHEAD
LIFT
SPRINKER
RISER
D.F. D.F.
D F
SOLID
DISP
FD
FD
RAMP
DN.
DN DN
DN
DN
SHOWN AREA
PROJECT
NORTH
CONSTRUCTION ZONE
TEMPORARY ICRA BARRIER
TEMPORARY ICRA DOOR
OUT OF SCOPE
TEMPORARY ICRA AIR PRESSURE+ ---
TEMPORARILY SEAL EXISTING DOOR FOR DURATION OF
CONSTRUCTION.
TEMPORARY ICRA BARRIER FRAMED TO THE CEILING
ABOVE. CONSTRUCT WITH MTL STUDS AND 5/8" TYPE X
GYP EACH SIDE.
TEMPORARY ICRA DOOR AND FRAME.
1. COMPLY WITH ALL REQS LISTED IN THE INFECTION
CONTROL SECTION OF SPECIFICATION 01 35 26 - SAFETY
REQUIREMENTS.
2. CONSTRUCTION ZONE ENTRANCES AND EXITS SHALL BE
LOCKED AT ALL TIMES UNLESS IN USE BY THE
CONTRACTOR. WHEN IN USE, ACCESS WILL BE
CONTROLLED AND MONITORED BY THE CONTRACTOR.
3. ADHESIVE WALK OFF CONSTRUCTION MATS TO BE USED
AT ALL CONSTRUCTION ZONE AND ANTE ROOM
ENTRANCES AND EXITS.
4. TEMP BARRIERS AND DOORS MAY ONLY BE DEMOLISHED
ONCE GIVEN FINAL APPROVAL BY THE VA COR.
5. ICRA PLAN IS ONLY GIVEN AS A SUGGESTED METHOD,
COORDINATE WITH VA FOR FINAL LAYOUT.
A B C F
ED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AS101
ICRA PLAN
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
LEGEND
GENERAL NOTES
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
PROJECT
NORTH
1/8" = 1'-0"
ICRA PLAN
ICRA NOTES:
CLASS IV
1. BARRIERS MUST BE HARD BARRIERS UNLESS TEMPORARY TO
INSTALL FINAL BARRIER.
2. CONTAINMENT MUST INCLUDE AN ANTEROOM TO ENSURE
PRESSURE CONTROL. ANTEROOM MUST BE LARGE ENOUGH FOR
EQUIPMENT STAGING, CART CLEANING, WORKERS' PPE AND
CLEANING.
3. WORKER CLOTHING AND/OR PPE MUST BE REMOVED OR CLEAN
AND FREE OF VISIBLE DUST BEFORE LEAVING THE WORK AREA
ANTEROOM. HEPA VACUUMING OF CLOTHING OR USE OF COVER
SUITS IS ACCEPTABLE.
4. WORKERS MUST WEAR SHOE COVERS OR HAVE A METHOD TO
CLEAN SHOES IN ANTEROOM. SHOE COVERS MUST BE REMOVED
PRIOR TO EXITING THE ANTEROOM TO THE OCCUPIED SPACE (NON-
WORK AREA.) DAMAGED SHOE COVERS MUST BE CHANGED
IMMEDIATELY.
WORK AREA CLEANING:
1. CLEAN WORK AREAS INCLUDING ALL ENVIRONMENTAL SURFACES,
HIGH HORIZONTAL SURFACES AND FLOORING MATERIALS.
2. CHECK ALL SUPPLY AND RETURN AIR REGISTERS FOR DUST
ACCUMULATION ON UPPER SURFACES AS WELL AS AIR DIFFUSER
SURFACES.
REMOVAL OF CRITICAL BARRIERS:
1. CRITICAL BARRIERS MUST REMAIN IN PLACE DURING ALL WORK
INVOLVING DRYWALL REMOVAL, CREATION OF DUST AND ACTIVITES
BEYOND SIMPLE TOUCH-UP WORK. THE BARRIER MAY NOT BE
REMOVED UNTIL A WORK AREA CLEANING HAS BEEN PERFORMED.
ADDITIONAL CLEANING MAY BE NEEDED AFTER REMOVAL OF
BARRIER.
2. ALL (PLASTIC OR HARD) BARRIER REMOVAL ACTIVITIES MUST BE
COMPLETED IN A MANNER THAT PREVENTS DUST RELEASE. USE THE
FOLLOWING PRECAUTIONS WHEN REMOVING HARD BARRIERS:
i. CAREFULLY REMOVE SCREWS AND PAINTER TAPE.
ii. IF DUST WILL BE GENERATED DURING SCREW REMOVAL, USE
HAND-HELD HEPA VACUUM.
iii. DRYWALL CUTTING IS PROHIBITED DURING REMOVAL
PROCESS.
iv. CLEAN ALL STUD TRACKS WITH HEPA VACCUM BEFORE
REMOVING OUTER HARD BARRIER.
v. USE A PLASTIC BARRIER TO ENCLOSE AREA IF DUST COULD
BE GENERATED.
NEGATIVE AIR REQUIREMENTS:
1. THE USE OF NEGATIVE AIR MUST BE DESIGNED TO REMOVE
CONTAMINANTS FROM WORK AREA.
2. NEGATIVE AIR DEVICES (FANS, FILTERS, MONITORING AND
DOCUMENTATION EQUIPMENT) MUST REMAIN OPERATIONAL AT ALL
TIMES AND IN PLACE FOR A PERIOD AFTER COMPLETION OF DUST
CREATING ACTIVITIES TO REMOVE CONTAMINANTS FROM THE WORK
AREA AND BEFORE REMOVAL OF CRITICAL BARRIERS.
HVAC SYSTEMS:
1. UPON REMOVAL OF CRITICAL BARRIERS, REMOVE ISOLATION OF
HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.
2. VERIFY THAT HVAC SYSTEMS ARE CLEAN AND OPERATIONAL.
3. VERIFY AND DOCUMENT THROUGH A TAB THE HVAC SYSTEMS
MEETS ORIGINAL AIRFLOW AND AIR EXCHANGE DESIGN
SPECIFICATIONS.
WATER SYSTEMS:
1. UNTIL THE POTABLE WATER SYSTEM IS ACTIVATED AND IN USE,
FLUSHING SHALL CONTINUE ATLEAST TWICE PER WEEK IN
ACCORDANCE WITH THE VHA DIRECTIVE 1061.
Revisions: Date: 4 OF 45
L
L
L
L
L
L
L
L
OVERHEAD
LIFT
SPRINKER
RISER
D.F. D.F.
D F
SOLID
DISP
FD
FD
RAMP
DN.
DN DN
DN
DN
SHOWN AREA
PROJECT
NORTH
EMERGENCY EGRESS ROUTE
1 HR FIRE RATED WALL
SMOKE & 2 HR FIRE RATED WALL
FIRE EXTINGUISHER CABINET
PROJECT AREA
FEC
A B C F
ED
FEC
FEC
FEC
FEC
MEDICAL SVC
BATH/SHOWER
144A
CLINICAL SUP
GENERAL
CLINICAL SUP 2
BED
CLINICAL SUP
EKG
CLINICAL SUP
2BED
CLINICAL SUP 2
BED
CLINICAL SUP
LOUNGE
CLINICAL SUP 2
BED
CLINICAL SUP 2
BED
CLINICAL SUP 2
BED
CLINICAL SUP 2
BED
CLINICAL SUP 1
BED
117A
CLINICAL SUP
HALLWAY
CLINICAL SUP
BATH/SHOWER
117B
STAIRWELL
ST1
CLINICAL SUP
HALLWAY
121A
CLINICAL SUP
STORAGE
IT CLOSET
CLINICAL SUP
WORKROOM
CLINICAL SUP
BATH/SHOWER
116B
CLINCIAL SUP
BATH/SHOWER
115A
CLINICAL SUP
BATH/SHOWER
114A
CLINICAL SUP
BATH/SHOWER
113A
CLIICAL SUP
BATH/SHOWER
112A
CLINICAL SUP
BATH/SHOWER
111A
CLINICAL SUP
BATH/SHOWER
110A
CLINICAL SUP
BATH/SHOWER
109A
CLINICAL SUP
BATH/SHOWER
108A
CLINICAL SUP
LOUNGE
CLINICAL SUP
OFFICE/EXA
CLINICAL SUP
BATH/SHOWER
106A
CLINICAL SUP
HAC
CLINICAL SUP
BATH/SHOWER
CLINICAL SUP 2
BED
CLINICAL SUP
BATH/SHOWER
104A
CLINICAL SUP
S/RESTROOM
CLINICAL SUP
1BED
CLINICAL SUP
OFFICE
CLINICAL SUP
BATH/SHOWER
136A
CLINICAL
SUP/BATHROOM
102A
CLINICAL SUP 2
BED
CLINICAL SUP
BATH/SHOWER
138A
CLINICAL SUP 1
BED
CLINICAL SUP 1
BED
139 CLINICAL SUP
BATH/SHOWER
139A
CLINICAL SUP
STORAGE
CLINICAL SUP
S/RESTROOM
CLINICAL SUPP
BATH/SHOWER
142A
CLINICAL SUP
EXAM NURSE
CLINICAL EXAM
NURSE
CLINICAL SUP
BATH/SHOWER
143A
MEDICAL SVC
EXAM_PHYSI
MEDICAL SVC
EXAM_PHYSI
MEDICAL SVC
BATH/SHOWER
145A
FMS MER
146 CLINICAL SUP
BATH/SHOWER
CLINICAL SUP
CORRIDOR
C1
CLINICAL SUP
CORRIDOR
C1W
CLINICAL SUP
SOILED
141 SF
EXAM
146 SF
EXAM
231 SF
CLINICAL SUP
NURSING
STATION
100 SF
OFFICE
92 SF
OFFICE
99 SF
OFFICE
60 SF
PATIENT AREA
133 SF
EXAM
131 SF
EXAM
130 SF
EXAM
46 SF
RESTROOM
105 SF
OFFICE
76 SF
ELECTRICAL
164 SF
EXAM
NO WORK OUTSIDE OF PROJECT AREA, TYP
1. NFPA BUILDING CONSTRUCTION: TYPE II.
2. NFPA OCCUPANCY CLASSIFICATION: BUSINESS.
3. # OF REQ'D EGRESS OPENINGS: 2.
4. 2,225 SF BUSINESS AT 150 SF / OCCUPANT = 15
OCCUPANTS
5. MAX TRAVEL DISTANCE: 300' - 0" (BUSINESS OCCUPANCY)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AS201
FIRE AND LIFE SAFETY
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
LEGEND
GENERAL NOTES
FIRE AND LIFE SAFETY DETAILS
KEY PLAN
PROJECT
NORTH
1/8" = 1'-0"
FIRE & LIFE SAFETY PLAN
1. CORRIDORS AND EGRESS PASSAGEWAYS TO REMAIN
CLEAR AND FREE OF DEBRIS.
2. PROVIDE ANY SIGNAGE FOR ROUTES OF EGRESS
AFFECTED BY CONSTRUCTION ZONES.
3. REPLACEMENT OF CEILING TILES AT THE END OF EACH
SHIFT IS REQIURED FOR WORK AREAS OUTSIDE OF A
RATED CONSTRUCTION BARRIER (IF PROVIDED). IF THE
TILES CANNOT BE REPLACED, THE SPRINKLER SYSTEM
MAY BE CONSIDERED OUT OF SERVICE IN THESE AREAS
AND 1-HOUR FIRE RATED SEPARATION WILL BE
REQUIRED BETWEEN THE CONSTRUCTION AREA AND THE
OCCUPIED PORTIONS OF THE BUILDING.
Revisions: Date: 5 OF 45
L
L
L
L
L
L
L
L
OVERHEAD
LIFT
SPRINKER
RISER
D.F. D.F.
D F
SOLID
DISP
FD
FD
RAMP
DN.
DN DN
DN
DN
SHOWN AREA
PROJECT
NORTH
DEMOLISH ACT CEILING GRID AND TILES
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
OUT OF SCOPE
F
E
EXISTING SINK AND
CABINETRY TO REMAIN.
2 3
6 6
EXISTING COLUMNS TO
REMAIN, TYPICAL.
(NO WORK)
DEMOLISH EXISTING RELITE.
SAWCUT AND DEMOLISH CONCRETE SLAB AS REQUIRED
FOR NEW PLUMBING WORK.
DEMOLISH EXISTING CABINETRY AND CASEWORK,
TYPICAL.
DEMOLISH EXISTING PARTITION.
DEMOLISH RAILING, TYPICAL.
DEMOLISH PLUMBING FIXTURES AND ACCESSORIES. SEE
PLUMBING PLANS.
231 SF
CLINICAL SUP
NURSING
STATION
141 SF
CLINICAL SUPPLY
WAITING ROOM
146 SF
CLINICAL SUP
TREATMENT
76 SF
ELECTRICAL
105 SF
CLINICAL SUP
CLEAN
46 SF
RESTROOOM
88 SF
CLINICAL SUP
SOILED
1307 SF
CLINICAL SUP
CORRIDOR
C1W
99 SF
CLINICAL SUP
STORAGE
99 SF
CLINICAL SUP
KITCHEN
100 SF
CLINICAL SUP
COMPUTER
177 SF
CLINICAL SUP
EXAM/TREATMENT
192 SF
CLINICAL SUP
EXAM/TREATMENT
241 SF
CLINICAP SUP
EXAM/TREAT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AD101
OVERALL DEMO FLOOR PLAN
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
LEGEND
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
PROJECT
NORTH
1/4" = 1'-0"
OVERALL DEMO FLOOR PLAN
GENERAL NOTES
1. DEMOLISH EXISTING ACT. PREPARE ROOM FOR NEW ACT
CEILING.
2. DEMOLISH EXISTING WALLS AS REQUIRED FOR
INSTALLATION OF NEW WORK AND ELECTRICALCONDUITS.
3. DEMOLISH FLOORING IN WORK AREA.
4. THE CONTRACTOR SHALL VERIFY ALL EXISTING
CONDITIONS BEFORE BEGINNING OF WORK, ANY
CONFLICTS BETWEEN EXISTING CONDITIONS AND THE
CONTRACT DOCUMENTS SHALL BE BROUGHT IMMEDIATELY
TO THE ATTENTION OF THE COR.
Revisions: Date: 6 OF 45
L
L
L
L
L
L
L
L
OVERHEAD
LIFT
SPRINKER
RISER
D.F. D.F.
D F
SOLID
DISP
FD
FD
RAMP
DN.
DN DN
DN
DN
SHOWN AREA
PROJECT
NORTH
DEMOLISH ACT CEILING GRID AND TILES
EXISTING DOOR TO REMAIN
EXISTING DOOR TO DEMOLISH
OUT OF SCOPE
F
E
4 4
231 SF
CLINICAL SUP
NURSING
STATION
141 SF
CLINICAL SUPPLY
WAITING ROOM
146 SF
CLINICAL SUP
TREATMENT
76 SF
ELECTRICAL
105 SF
CLINICAL SUP
CLEAN
46 SF
RESTROOOM
88 SF
CLINICAL SUP
SOILED
1307 SF
CLINICAL SUP
CORRIDOR
C1W
99 SF
CLINICAL SUP
STORAGE
99 SF
CLINICAL SUP
KITCHEN
100 SF
CLINICAL SUP
COMPUTER
DEMO EXISTING LIGHT.
DEMO EXISTING CURTAIN TRACK.
DEMO EXISTING PATIENT LIFT/
EXISTING CEILING TO REMAIN AT ROOM.
EXISTING CEILING TO REMAIN AT ROOM, REPLACE TILES
AT ALL NEW AND EXISTING ACT CEILINGS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AD102
OVERALL DEMO REFLECTED CEILING PLAN
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
PROJECT
NORTH
1/4" = 1'-0"
OVERALL DEMO REFLECTED CEILING PLAN
LEGEND
KEY NOTES (THIS SHEET ONLY)
KEY PLAN
GENERAL NOTES
1. REPLACEMENT OF CEILING TILES AT THE END OF EACH
SHIFT IS REQIURED FOR WORK AREAS OUTSIDE OF A RATED
CONSTRUCTION BARRIER (IF PROVIDED). IF THE TILES
CANNOT BE REPLACED, THE SPRINKLER SYSTEM MAY BE
CONSIDERED OUT OF SERVICE IN THESE AREAS AND 1-HOUR
FIRE RATED SEPARATION WILL BE REQUIRED BETWEEN THE
CONSTRUCTION AREA AND THE OCCUPIED PORTIONS OF
THE BUILDING.
Revisions: Date: 7 OF 45
L
L
L
L
L
L
L
L
OVERHEAD
LIFT
SPRINKER
RISER
D.F. D.F.
D F
SOLID
DISP
FD
FD
RAMP
DN.
DN DN
DN
DN
SHOWN AREA
PROJECT
NORTH
1. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS
BETWEEN EXISTING CONDITIONS AND THE CONTRACT
DOCUMENTS SHALL BE BROUGHT IMMEDIATELY TO THE
ATTENTION OF THE COR.
2. DIMENSIONS SHOWN ARE FROM GRID LINES TO FACE OF
STUD, CENTERLINE OF STRUCTURAL COLUMNS,
CENTERLINE OF OPENINGS, UON
3. ANY DOORS NOT DIMENSIONED SHALL BE INSTALLED 6"
FROM THE INTERSECTING WALL OR CENTERED ON THE
WALL, UON.
4. ENSURE THAT ALL REQUIRED BACKING IS INSTALLED IN
WALLS PRIOR TO INTALLING DRYWALL.
5. PATCH WALLS WHERE DEMOLISHED FOR INSTALLATION
OF NEW WORK.
6. PROVIDE BACKING AND BLOCKING FOR ALL VV AND CC
PROVIDED ITEMS.
F
E
NO WORK
NO WORK
6' - 6"
/4
100 SF
OFFICE
92 SF
OFFICE
131 SF
EXAM
133 SF
EXAM
130 SF
EXAM
164 SF
EXAM
99 SF
OFFICE
146 SF
EXAM
141 SF
EXAM
60 SF
PATIENT AREA
105 SF
OFFICE
ELECTRICAL
RESTROOM
CLINICAL SUP
SOILED
CLINICAL SUP
CORRIDOR
C1W
CLINICAL SUP
NURSING
STATION
CLINICAL SUP
CORRIDOR
C1W
3" 3"
13' - 3 3/8"
19' - 1 1/8"
7' - 1 1/8"
/8
/8
6"
/8
380 SF
CORRIDOR
C-151
AE421a
AE421a
5 2
100 123
ALIGN
ALIGN
ALIGN
ALIGN
AE421b
AE421b
AE421b
AE421b 7
INFILL RELITE LOCATIONS TO MATCH EXISTING WALLS
AND FINISHES. PAINT ENTIRE EAST WALL WHERE RELITE
INFILLED.
PATCH DOOR LOCATION TO MATCH EXISTING WALL AND
FINISHES. PATCH FLOORING/ COVE AT INFILL, MATCH
EXISTING FLOORING AND PATTERN.
NEW CONCRETE SLAB PATCHING WHERE EXISTING SLAB
DEMOLISHED FOR NEW WORK. PATCH EXISTING VAPOR
BARRIER AND PROVIDE #4 REBAR AT 16 O.C. EACH WAY.
DOWEL INTO EXISTING SLAB 4 INSHES EACH SIDE TO
PREVENT SETTLEMENT. SEE PLUMBING SHEETS FOR
COORDINATION.
INSTALL NEW FLOOR/FINISH.
PAINT ALL WALLS AND CEILING.
INSTALL NEW PLUMBING FIXTURES AND ACCESSORIES.
EXISTING COLUMN TO REMAIN.
EXISTING HANDRAILS TO REMAIN, NO WORK, TYP.
CAP FLOOR DRAIN AND PATCH CONCRETE FLOOR.
OUT OF SCOPE
EXISTING DOOR TO REMAIN
NEW DOOR
WALL TAG (SEE WALL SCHEDULE ON
SCHEDULES SHEET)
DOOR TAG (SEE DOOR SCHEDULE ON
SCHEDULES SHEET)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AE101
OVERALL FLOOR PLAN
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
PROJECT
NORTH
LEGEND
GENERAL NOTES
KEY PLAN
1/4" = 1'-0"
OVERALL FLOOR PLAN
KEY NOTES (THIS SHEET ONLY)
NEW ROOM SCHEDULE
ROOM # NAME
PROGRAM
NET
DESIGNED
NET
100 EXAM 125 NSF 141 SF
123 EXAM 125 NSF 146 SF
124 EXAM 125 NSF 131 SF
125 EXAM 125 NSF 133 SF
126 EXAM 125 NSF 130 SF
129 OFFICE 100 NSF 105 SF
133 EXAM 125 NSF 164 SF
134 OFFICE 100 NSF 99 SF
135 OFFICE 100 NSF 100 SF
149 PATIENT
AREA
- 60 SF
150 OFFICE 100 NSF 92 SF
Revisions: Date: 8 OF 45
L
L
L
L
L
L
L
L
OVERHEAD
LIFT
SPRINKER
RISER
D.F. D.F.
D F
SOLID
DISP
FD
FD
RAMP
DN.
DN DN
DN
DN
WAP
WAP
PP
WAP
WAP
PP
SHOWN AREA
PROJECT
NORTH
2x4 ACOUSTICAL CEILING TILE
GYPSUM BOARD ON METAL STUDS
SUPPLY GRILLE PER MECHANICAL
(SIZE & PROPORTION MAY VARY)
LIGHT FIXTURE PER ELECTRICAL
RETURN GRILLE PER MECHANICAL
(SIZE & PROPORTION MAY VARY)
EXHAUST GRILLE PER MECHANICAL
(SIZE & PROPORTION MAY VARY)
F
E
CLINICAL SUP
NURSING
STATION
CLINICAL SUP
CORRIDOR
C1W
CLINICAL SUP
CORRIDOR
C1W
CLINICAL SUP
SOILED
RESTROOM
ELECTRICAL
EXAM
EXAM
EXAM
OFFICE
OFFICE
OFFICE
EXAM
CORRIDOR
C-151
EXAM
EXAM
PATIENT AREA
F
E
2 24
AFF
ACT 2x4
8' - 6"
AFF
ACT 2x4
8' - 6"
AFF
ACT 2x4
8' - 6"
AFF
ACT 2x4
8' - 6"
AFF
ACT 2x4
8' - 6"
AFF
ACT 2x4
8' - 6"
AFF
ACT 2x4
8' - 6"
F
E F
E
NEW ACT CEILINGS AT 8'-6", TYPICAL IN PROJECT AREA,
ALL ROOMS WHERE EXISTING ACT DEMOLISHED, EXCEPT
WHERE NOTED.
REPLACE ACT CEILING TILES AT EXISTING CEILING GRIDS
NOTED TO REMAIN.
EXISTING CEILINGS OUTSIDE OF WORK AREA, NO WORK.
EXISTING GWB CEILING, PAINT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AC101
OVERALL REFLECTED CEILING PLAN
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
PROJECT
NORTH
1/4" = 1'-0"
OVERALL REFLECTED CEILING PLAN
KEY NOTES (THIS SHEET ONLY)
LEGEND
GENERAL NOTES
KEY PLAN
1. THE CONTRACTOR SHALL VERIFY ALL EXISTING
CONDITIONS BEFORE BEGINNING OF WORK, ANY
CONFLICTS BETWEEN EXISTING CONDITIONS AND THE
CONTRACT DOCUMENTS SHALL BE BROUGHT IMMEDIATELY
TO THE ATTENTION OF THE COR.
Revisions: Date: 9 OF 45
J
D Mo
J
D Mo
F
A5107
GLOVE
DISPENSER
A5080
PAPER TOWEL
DISPENSER
A5108
SHARPS
DISPOSAL
M1803 WORKSTATIONM1804
DUAL MONITOR
MOUNT
F2010 WASTE BASKET
M0506 TV
M9025 EXAM BED
A1066 MIRROR
F0206 BARIATRIC CHAIRA5145
GARMENT
HOOK
F2310
MAGAZINE
RACK
A5075
SOAP
DISPENSER
A5180
PRIVACY
CURTAIN
TRACK
F0340 STOOL
131 SF
EXAM
AE421a
5 2
F
F
F
LEVEL 1
0' - 0"
M0506TV A1066 MIRROR
F2010 WASTE BASKET
M1804
DUAL MONITOR
MOUNT
M1803 WORKSTATION
F0206 BARIATRIC CHAIR
M9025 EXAM BED
F0340 STOOL INTEGRAL COVE BASE, TYP
F3200 CLOCK
LEVEL 1
0' - 0"
A1066 MIRROR F2310 MAGAZINE RACK
A5180
PRIVACY CURTAIN
TRACK
F0206 BARIATRIC CHAIRM9025 EXAM BED
A5145 GARMENT HOOK
INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
A5075
SOAP
DISPENSER
A5108
SHARPS
DISPOSAL
M1803WORKSTATION
M0506 TV
M9025 EXAM BED
F2010 WASTE BASKET
F3200 CLOCK
F0340STOOL
M1804
DUAL MONITOR
MOUNT
INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
A5108
SHARPS
DISPOSAL
A5107
GLOVE
DISPENSER
A5080
PAPER TOWEL
DISPENSER
A5075
SOAP
DISPENSER
F2310
MAGAZINE
RACK
A5180
PRIVACY
CURTAIN
TRACK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AE421a
EXAM ROOM 124 - ENLARGED FLOOR PLAN
AND INTERIOR ELEVATIONS
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
GENERAL NOTES
1. ALL WALL MOUNTED EQUIPMENT SHALL HAVE METQAL
BLOCKING IN WALL BEHIND. THIS INCLUDES BACKING FOR
WALL MOUNTED DOOR STOPS, DISPENSES, PHONES,
GARMENT HOOKS, ETC. ENSURE THAT ALL REQUIRED
BACKING IS INSTALLED PRIOR TO INSTALLING DRYWALL.
SEE TYPICAL BLOCKING DETAIL.
2. SEE SIGNAGE SHEET FOR SIGNAGE LOCATION PLAN,
MESSAGE SCHEDULE, AND SIGN TYPES.
1/2" = 1'-0"
EXAM ROOM 124 - ENLARGED FLOOR PLAN
1/2" = 1'-0"
EXAM ROOM 124 - INTERIOR EAST ELEV
1/2" = 1'-0"
EXAM ROOM 124 - INTERIOR SOUTH ELEV
1/2" = 1'-0"
EXAM ROOM 124 - INTERIOR NORTH ELEV
1/2" = 1'-0"
EXAM ROOM 124 - INTERIOR WEST ELEV
PROJECT
NORTH
EQUIPMENT SCHEDULE
MARK
FURN /
INST
BY DESCRIPTION COMMENTS
A1066 CC MIRROR A HIGH QUALITY 1/4" POLISHED FLOAT GLASS MIRROR 36X18, FRAMED IN A ONE-PIECE, BRIGHT POLISHED, STAINLESS STEEL CHANNEL FRAME WITH 90° MITERED CORNERS. ALL EDGES OF THE MIRROR ARE PROTECTED BY ABSORBING FILLER STRIPS.
MIRROR HAS A GALVANIZED STEEL BACK WITH INTEGRAL HORIZONTAL HANGING BRACKETS AND WALL HANGER FOR CONCEALED MOUNTING. FOR MOUNTING ABOVE SINGLE WALL MOUNTED LAVATORIES LOCATED IN TOILET AREAS, DOCTORS EXAMINATION OFFICES, ETC. MAY ALSO BE USED ABOVE DOUBLE LAVATORIES, EITHER WALL OR COUNTERTOP MOUNTED, FOUND IN RESTROOM
AREAS.
A5075 VV SOAP DISPENSER DISPOSABLE SOAP DISPENSER. ONE-HANDED DISPENSING OPERATION. DESIGNED TO ACCOMMODATE DISPOSABLE SOAP
CARTRIDGE AND VALVE.
A5080 VV PAPER TOWEL
DISPENSER
A SURFACE MOUNTED, SATIN FINISH STAINLESS STEEL, SINGLE-FOLD, PAPER TOWEL DISPENSER. DISPENSER FEATURES: TUMBLER LOCK; FRONT HINGED AT BOTTOM; AND REFILL INDICATOR SLOT. MINIMUM CAPACITY 400 SINGLE-FOLD PAPER TOWELS. FOR
GENERAL PURPOSE USE THROUGHOUT THE FACILITY.
A5082 VV PAPER TOWEL
DISPENSER
PAPER TOWEL DISPENSER
A5107 VV GLOVE DISPENSER EXAMINATION GLOVE DISPENSER BOX FOR WALL MOUNTING. FABRICATED OF EITHER COLD ROLLED STEEL WITH A WHITE BAKED ENAMEL FINISH, PLASTIC OR ACRYLIC. PROVIDED WITH WALL BRACKET TO FACILITATE MOUNTING AND DEMOUNTING.
A5108 VV SHARPS DISPOSAL A CONTAINER FOR COLLECTING AND TRANSPORTING SYRINGES AND OTHER SHARPS FOR DECONTAMINATION AND DISPOSAL.
AVAILABLE IN 2 GALLON AND 8 GALLON WITH LOCKING ROTOR. COMPLIES WITH OSHA REGULATIONS FOR HANDLING SHARPS.
A5145 CC GARMENT HOOK A SURFACE MOUNTED, SATIN FINISH STAINLESS STEEL, DOUBLE GARMENT HOOK. EQUIPPED WITH A CONCEALED MOUNTING BRACKET THAT IS SECURED TO A CONCEALED WALL PLATE. FOR GENERAL PURPOSE USE THROUGHOUT THE FACILITY TO HANG
VARIOUS ITEMS OF APPAREL.
A5180 CC PRIVACY CURTAIN
TRACK
SURFACE MOUNTED CUBICLE TRACK, WITH CURTAIN. TRACK CONSTRUCTED OF THICK EXTRUDED ALUMINUM. EQUIPPED WITH SELF LUBRICATING CARRIERS, BEADED DROP CHAIN HOOKS, AND FLAME RESISTANT CURTAIN. TO INCLUDE REMOVABLE END CAPS.
DESIGNED TO BE SUSPENDED AROUND PATIENT AREAS WHERE PRIVACY IS NEEDED. PRICE LISTED IS PER FOOT OF THE TRACK, CURTAINS TO BE PRICED PER QUOTE.
F0206 VV BARIATRIC CHAIR A BARIATRIC SIDE CHAIR WITH ARMS FOR USE IN A WAITING ROOM, LOBBY OR OTHER PATIENT AREA. CHAIR WILL HAVE A PADDED
SEAT AND BACK AND HAVE A CAPACITY OF 800 POUNDS.
F0340 VV STAFF STOOL SELF ADJUSTING STOOL. CONSISTS OF A FOAM PADDED UPHOLSTERED SEAT WITH ATTACHED FOOT REST FOR ADDED COMFORT.
MOUNTED ON SWIVEL CASTERS. DESIGNED FOR DOCTOR'S USE DURING EXAMINATIONS.
F2010 VV WASTE BASKET "STEP-ON" WASTEPAPER BASKET WITH INNER LINER AND FOOR PEDAL ACTIVATED FLIP TOP.
F2310 VV MAGAZINE RACK WALL MOUNTED PAMPHLET RACK UP TO 12 (TWELVE) PAMPHLET HOLDING POCKETS. UNIT IS USED TO STORE AND DISPLAY
EDUCATIONAL PAMPHLETS.
F3200 VV CLOCK CLOCK, 12" DIAMETER. ROUND SURFACE, EASY TO READ NUMBERS WITH SWEEP SECOND HAND. WALL MOUNTED UNIT FOR USE WHEN IMPRACTICAL TO INSTALL A FULLY SYNCHRONIZED CLOCK SYSTEM. BATTERY OPERATED, (BATTERIES NOT INCLUDED).
M0506 VV FLAT SCREEN TV. FLAT SCREEN TELEVISION WITH APPROXIMATELY 32'" TO 40' DIAGONAL SCREEN SIZE. THE TV WILL HAVE BUILT-IN SPEAKERS, NTSC TUNER, A 16:9 WIDE SCREEN ASPECT RATIO, A MINIMUM OF 1280 X 768 RESOLUTION AND A REMOTE CONTROL.
M1803 VV WORKSTATION A WALL MOUNTED RETRACTABLE WORK STATION. WORK STATION IS USED AS A COMPUTER STATION IN TREATMENT ROOMS, EXAM
ROOMS AND AREAS WHERE PHYSICAL SPACE IS LIMITED.
M1804 VV DUAL MONITOR
MOUNT
WALL MOUNTED DUAL MONITOR MOUNT.
M9025 VV EXAM BED TABLE, EXAMINATION/TREATMENT WITH CABINET. CABINET TYPE EXAM TABLE WITH THREE SECTION UPHOLSTERED TOP ADJUSTABLE TO A FULL CHAIR POSITION. CONCEALED HEEL STIRRUPS, DUAL OUTLETS, DRAWERS, AND STORAGE SPACE WITH OPTIONAL ARMBOARD. UNIT IS DESIGNED FOR GENERAL USE IN EXAMINATION/TREATMENT ROOMS.
Revisions: Date: 10 OF 45
J
D Mo
J
D Mo
J
FS
D Mo a
J
FS
D Mo a
F
AE421b
F0340 STOOL
M9025 EXAM BED
M0506 TV
F2010 WASTE BASKET
M1803 WORKSTATIONM1804
DUAL MONITOR
MOUNT
A5108
SHARPS
DISPOSAL
A5080
PAPER TOWEL
DISPENSER
A5075
SOAP
DISPENSER
A5107
GLOVE
DISPENSER
A5180
PRIVACY
CURTAIN
TRACK
F2310
MAGAZINE
RACK
A5145
GARMENT
HOOK
F0206 BARIATRIC CHAIR
A1066 MIRROR
133 SF
EXAM
FFF
LEVEL 1
0' - 0"
F2010
WASTE
BASKET
M0506TV
F3200 CLOCK
M9025 EXAM BED
A1066 MIRROR
M1803WORKSTATION
M1804
DUAL MONITOR
MOUNT
F0340 STOOL
F0206 BARIATRIC CHAIR
INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
A1066MIRROR
M9025EXAM BED
F0206 BARIATRIC CHAIR
A5145
GARMENT
HOOK F2310 MAGAZINE RACK
A5180
PRIVACY CURTAIN
TRACK
INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
F3200 CLOCK
M0506 TV
M1803WORKSTATION
M1804
DUAL MONITOR
MOUNT
F2010 WASTE BASKET
M9025 EXAM BED
F0340STOOL
A5108
SHARPS
DISPOSAL
A5075
SOAP
DISPENSER
INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
A5107 GLOVE DISPENSER
A5080
PAPER TOWEL
DISPENSER
A5108 SHARPS DISPOSAL
A5075
SOAP
DISPENSER
F2310
MAGAZINE
RACK
A5180
PRIVACY
CURTAIN
TRACK
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
F
AE421b
130 SF
EXAM
126 AE421b 7
A5108
SHARPS
DISPOSAL
M1804
DUAL MONITOR
MOUNT
A5080
PAPER TOWEL
DISPENSER
A5107
GLOVE
DISPENSER
A5075
SOAP
DISPENSER
A5180
PRIVACY
CURTAIN
TRACK
F2310
MAGAZINE
RACK
A5145
GARMENT
HOOK
F0206 BARIATRIC CHAIR
A1066 MIRROR
F0340 STOOL
M9025 EXAM BED
M0506 TV
F2010 WASTE BASKET
M1803 WORKSTATION FFF
LEVEL 1
0' - 0"
F3200 CLOCK
M0506TV
M1804
DUAL MONITOR
MOUNT
F2010
WASTE
BASKET
F0340 STOOL
M9025 EXAM BED
F0206 BARIATRIC CHAIR
A1066 MIRROR
INTEGRAL COVE BASE, TYP
M1803WORKSTATION
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
A1066MIRROR
M9025EXAM BED
A5145
GARMENT
HOOK F2310 MAGAZINE RACK
A5180
PRIVACY CURTAIN
TRACK
F0206 BARIATRIC CHAIR INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
F3200 CLOCK
M0506 TV
M9025 EXAM BED
M1804
DUAL MONITOR
MOUNT
M1803WORKSTATION
A5108
SHARPS
DISPOSAL
A5075
SOAP
DISPENSER
F0340STOOL
F2010 WASTE BASKET
INTEGRAL COVE BASE, TYP
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
A5180
PRIVACY
CURTAIN
TRACK
F2310
MAGAZINE
RACK
A5075
SOAP
DISPENSER
A5108 SHARPS DISPOSAL
A5080
PAPER TOWEL
DISPENSER
A5107 GLOVE DISPENSER
LEVEL 1
0' - 0"
LEVEL 1
0' - 0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AE421b
EXAM ROOM 125 & 126 - ENLARGED FLOOR
PLAN AND INTERIOR ELEVATIONS
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
1/2" = 1'-0"
EXAM ROOM 125 - ENLARGED FLOOR PLAN
PROJECT
NORTH
1/2" = 1'-0"
EXAM ROOM 125 - INTERIOR EAST ELEV
1/2" = 1'-0"
EXAM ROOM 125 - INTERIOR SOUTH ELEV
1/2" = 1'-0"
EXAM ROOM 125 - INTERIOR NORTH ELEV
1/2" = 1'-0"
EXAM ROOM 125 - INTERIOR WEST ELEV
1/2" = 1'-0"
EXAM ROOM 126 - ENLARGED FLOOR PLAN
1/2" = 1'-0"
EXAM ROOM 126 - INTERIOR EAST ELEV
1/2" = 1'-0"
EXAM ROOM 126 - INTERIOR SOUTH ELEV
1/2" = 1'-0"
EXAM ROOM 126 - INTERIOR NORTH ELEV
1/2" = 1'-0"
EXAM ROOM 126 - INTERIOR WEST ELEV
PROJECT
NORTH
Revisions: Date: 11 OF 45
VERTICAL WALL STUDS
@ 16" OR 24" OC
CUT HORIZONTAL
FASTENER FROM STUD
FASTEN AT BOTH ENDS
WITH MIN 4 TAPPING
SCREWS
WALL FINISH
ISOMETRIC VIEW
PLAN VIEW
GENERAL NOTES:
1. CONTRACTOR SHALL COORDINATE LOCATIONS OF
HORIZONTAL FASTENERS.
2. ALL WALL MOUNTED EQUIPMENT SHALL HAVE METAL
BLOCKING IN WALL BEHIND. ENSURE ALL REQUIRED
BACKING IS INSTALLED PRIOR TO INSTALLING GYP.
BLOCKING AT
TOP & BOTTOM
1/4" PLY BACK WITH
PLAM FINISH
RECESSED ADJUSTABLE
SHELF STANDARDS, TYP
3/4" PLY ADJUSTABLE SHELF
WITH PLAM FINISH
3/4" PLY END OR DIVIDER
PANEL WITH PLAM FINISH
FACE OF WALL
3/4" PLY BOTTOM WITH
PLAM FINISH
3/4" PLY DOOR WITH
PLAM EA SIDE
4" x 3/8" DIA
WIRE PULL
1' - 3"
3/4" x 2-1/2" BLOCKING
ANCHORED TO IN-WALL
BLOCKING, TYP
SDSF COUNTERTOP & BACKSPLASH
4" x 3/8" DIA WIRE PULL
3/4" PLY DOOR WITH
PLAM FINISH EA SIDE
3/4" PLY TOE KICK WITH
PLAM FINISH & BASE
3/4" x 2-1/2"
BLOCKING, TYP
3/4" PLY BOTTOM WITH
PLAM FINISH
2x4 PRESSURE
TREATED FRAME
BLOCKING AT TOP &
BOTTOM OF CABINET
1/4" PLY BACK WITH
PLAM FINISH
3/4" PLY END OR DIVIDER
PANEL WITH PLAM FINISH
FACE OF WALL
3/4" PLY FAUX
DRAWER FRONT
WITH PLAM FINISH
PIPING PER PLUMBING
3"
3/4" x 1-1/2" PLY FRAME
WITH PLAM FINISH, TYP
DROP-IN SINK & FACUET
PER PLUMBING
2' - 0"
SDSF COUNTERTOP & BACKSPLASH
4" x 3/8" DIA
WIRE PULL, TYP
3/4" PLY TOE KICK
WITH PLAM FINISH
& BASE
3/4" PLY BOTTOM WITH
PLAM FINISH
2x4 PRESSURE
TREATED FRAME
BLOCKING AT TOP &
BOTTOM OF CABINET
1/4" PLY BACK WITH
PLAM FINISH
3/4" PLY END OR DIVIDER
PANEL WITH PLAM FINISH
FACE OF WALL
1/2" PLY DRAWER
FRONT WITH PLAM
FINISH, TYP
1/2" PLY DRAWER BACK,
SIDES & BOTTOM WITH
PLAM FINISH, TYP
2' - 0"
E Q
E Q
E Q
E Q
3"
DRAWER SLIDE, TYP
3/4" x 2-1/2"
BLOCKING, TYP
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-501
DETAILS
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
GENERAL NOTES
1. ALL WALL MOUNTED EQUIPMENT SHALL HAVE BLOCKING IN
WALL BEHIND. THIS INCLUDES BACKING FOR WALL
MOUNTED DOOR STOPS, DISPENSERS, PHONES, ETC.
ENSURE THAT ALL REQUIRED BACKING IS INSTALLED
PRIOR TO INSTALLING DRYWALL. SEE TYPICAL BLOCKING
DETAIL.
TYPICAL BLOCKING DETAIL
1 1/2" = 1'-0"
PLAM WALL CABINET DETAIL
1 1/2" = 1'-0"
PLAM BASE CABINET DETAIL - SINK & DOOR
1 1/2" = 1'-0"
PLAM BASE CABINET DETAIL - 4 EQ DRAWERS
Revisions: Date: 12 OF 45
PERSPECTIVE 1 -FRONT PERSPECTIVE 2 -BACK
FRAME OPTIONAL KEY CYLINDER
12" BACK TO BACK LADDER
PULL
OPTIONAL THUMB TURN
12" BACK TO BACK LADDER
PULL
FRAME
2" CLEAR OPENING 5" DOOR OVERHANG
SLAB
1 1/2" MINIMUM CLEARANCE
TRACK
FINISHED FRAME
/4
C L E
A R
O P
E N
H E
IG
H
T
2"
1/2" 2 1/2"
1 1/2" MINIMUM CLEARANCE
/4
TRACK
DOOR
1 3/4"
/4
2 1/2"
WALL WALL
3' - 4"
DOOR
1 3/4" METAL STUD
WALL
WOOD BLOCKING
BY OTHERS
/4
2 3/4"
1/4"
5/8" 3 5/8" 5/8"
4 7/8"
SERENITY DOUBLE
SOUND SEAL SYSTEM 2
/4
2"
/4
2"
METAL STUD
WALL
SERENITY DOUBLE
SOUND SEAL SYSTEM
DOOR
2"
/4
/2
METAL STUD
WALL
SERENITY
SOUND SEAL
DOOR
1"
A-510
Sim
A-510
Sim
OPEN DOOR VIEW CLOSED DOOR VIEW
A-510
5 Sim
A-510
8 Sim
A-510
6 Sim
A-510
7 Sim
DOOR
CONCEALED FLOOR GUIDE
OPTIONAL KEY CYLINDER OPTIONAL PRIVAVY
INDICATOR
OPTIONAL THUMB TURN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-510
INTERIOR SLIDING DOOR DETAILS
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
6" = 1'-0"
PERSPECTIVE VIEWS
1" = 1'-0"
FRONT VIEWS
1" = 1'-0"
VIEW A-A
1" = 1'-0"
VIEW B-B
6" = 1'-0"
DETAIL 01
6" = 1'-0"
DETAIL 02
6" = 1'-0"
DETAIL 04
6" = 1'-0"
DETAIL 03
1 1/2" = 1'-0"
DOOR HANDLES
3" = 1'-0"
12" BACK TO BACK LADDER PULL
3" = 1'-0"
SMALL MORTISE LOCK
Revisions: Date: 13 OF 45
A(C)T ACOUSTICAL CEILING TILE
GWB GYPSUM WALLBOARD
P PAINT
SV SHEET VINYL
LVT LUXURY VINYL TILE
RB RESILIENT BASE
FINISH ABBREVIATIONS
9" 4"
DOOR HEIGHTS AND WIDTHS PER SCHEDULE
GLAZING
SURFACE SLIDING
DOOR HEIGHTS AND WIDTHS PER SCHEDULE
MTL DOOR
FRAME
SHIM AS
REQ'D
RUNNER
BETWEEN
STUDS
1/2"
CONST
JOINT
SEE NOTE 1
VERTICAL STUDS @ 2'-0" MAX. W/
GYPSUM WALL BOARD. 1'-4" W/ GYPSUM
LATH & PLASTER DOUBLE STUDS FOR
SUPPORTING CONC. BACKER BOARD
PROVIDE CONTINUOUS BRACING
WHEN STUDS EXCEED 10'-0" AND
ARE FINISHED BOTH SIDES
JAMB ANCHOR CLIPS 3 PER
SIDE - COORDINATE W/
HINGE REINFORCEMENT
NOTE 1: OMIT BRACE WHEN 'D' DIMENSION
IS LESS THAN 2'-0" FOR GYP. WALL BOARD
OR 16" FOR PLASTER PARTITION
ELEVATION AT DOOR FRAME
DETAIL D
JAMB ANCHORS
(FURNISHED W/ FRAME)
DETAIL C
FRAME FACE
MIN
US 3/16"
E Q
E Q
D
E Q
E Q
V A
R
IE
S S
E E
D O
O R
S C
H E
D
VARIES SEE DOOR SCHED
DETAIL B
A A
1/2" M
IN
5/8" M
AX
FRAME FACE
MIN
US 3/16"
/4
M
IN
STUD
W
IDTH
/4
M
IN
JAMB DEPTH
MINUS 3/16"
STUD
W
IDTH
1/2"
DETAIL D, TYP
M A
X
DETAIL B
PROVIDE SOUND
DEADENING WHERE
REQUIRED
/8
SECTION A
DOUBLE STUDS JAMB ANCHOR
GYPSUM WALL
BOARD PANELS
CONTROL JOINT
ISOMETRIC OF CONSTRUCT JOINT
/4
M
IN
DETAIL C
SANITARY
STOP
MTL DOOR FRAME
MTL ANCHOR CLIP
SHIM AS
REQ'D
CRIPPLE STUD, DO NOT
ANCHOR TO BEARING STUD
1/2" M
IN
CAULK ALL
AROUND
ADJUSTABLE
ANCHOR
STANDARD FRAME
EXPOSED MASONRY OR BRICK
1/2"
S.F.T.U.
NOMINAL
CMU OR 1/2"
FRAMES IN MASONRY PARTITION
CASING BEAD
ADJUSTABLE
ANCHOR
STANDARD FRAME
MASONRY BLOCK PLASTERED
GROUT
5/8"
S.F.T.U.
NOMINAL
CMU OR 7/8"
PLASTER ON
METAL LATH
CAULK ALL
AROUND
GROUT
CERAMIC TILE
ADJUSTABLE
ANCHOR
STANDARD FRAME
MASONRY BLOCK WITH CERAMIC TILE FINISH
GROUT
SETTING BED
CAULK ALL
AROUND
1/2"
S.F.T.U.
NOMINAL
CMU OR 3/4"
*** FRAME WIDTH FOR NOMINAL MASONRY
4 3/4" W/ 4" CMU
6 3/4" W/ 6" CMU
8 3/4" W/ 8" CMU
METAL STUD AND PLASTER FINISH
FRAMES WITH METAL STUD
AND PLASTER PARTITIONS
GAUGE AS
SPECIFIED
ADD RETURN ON
FRAME WHERE
DRYWALL FINISH
IS REQUIRED
STANDARD DOOR FRAME
FRAMES IN METAL STUD PARTITIONS
CERAMIC TILE
FINISH WHERE
REQUIRED
CAULK ALL
AROUND BOTH
SIDES
STANDARD FRAME
FOR DRYWALL
JAMB ANCHORS
DOUBLE STUDS
BACK TO BACK
DRYWALL, THICKNESS
SINGLE OR DOUBLE AS
REQUIRED
FRAMES IN MASONRY PARTITION
FACED WITH GWB
STANDARD FRAME
ADJUSTABLE
ANCHORS
GROUT
CAULK ALL
AROUND
CERAMIC TILE
FINISH WHERE
REQUIRED
TILE FINISH
FRAME AT CONCRETE WALLS
DOUBLE EGRESS DOOR FRAME
PLAN
JAMB 'B'
HEAD 'A'
NOTE: SHOWING SWING OF
DOUBLE EGRESS DOORS
A B
C
A C
B
NOTE: SHOWING SWING OF
DOUBLE EGRESS DOORS
DOOR
DOOR
DOOR STOP (BEYOND)
PLATE WELDED
TO FRAME
/2
"2 1/2" MIN
+/- 1/4"
/4
7/8"
08 11 13-01
METAL STUDS
PER STD DTL 3/4"
1/4"
7/8"
08 11 13-01
MTL STUDS
PER STD DTL 11/16"
1/4"
1/4"
1/4"
CAULK ALL
AROUND
CASING BEAD
WHERE PLASTER
IS REQUIRED
CONCRETE
GROUT
VENEER
PLASTER ON
PLASTER BASE
TROWEL CUT
AT FRAME
EDGES
ANCHOR
STANDARD
FRAME
CONVENTIONAL
PLASTER
GYP LATH
CERAMIC TILE
CAULK BOTH
SIDES
ANCHOR
STANDARD
FRAME
CERAMIC TILE
GWB
CEMENT
BACKER BOARD
PIPE SEPARATORS
WELDED TO PLATE
F.H. CSK.
EXP. BOLT
THROAT OPENING = PARTITION
WIDTH + 1/8" MIN
1/2" 1/2"
/8
1 15/16"VARIESVARIES
TYPE 'X' GYP
STEEL STUD FRAMING WITH FIBER GLASS
SOUND BATT INSULATION
TYPE 'X' GYP
5/8"
5/8" 3 5/8"
5/8"
STRUCTURE ABV
"FINISH CLG
GA FILE NO.
WP 1052
50-54 STC
(2 LAYERS)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-601
SCHEDULES, DETAILS, DOOR TYPES &
DETAILS
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 EM AJ
CONSTRUCTION
DOCUMENTS
ROOM FINISH SCHEDULE
ROOM
ROOM
NAME
CEILING FLOOR
MAT
BASE WAINSCOT WALL
COMMENTSMAT FIN MAT HT MAT HT MAT FIN
100 EXAM AT SV SV 4" - - GWB P
123 EXAM AT P SV SV 4" - - GWB P
124 EXAM AT SV SV 4" - - GWB P
125 EXAM AT SV SV 4" - - GWB P
126 EXAM AT SV SV 4" - - GWB P
129 OFFICE AT LVT PLANK RB 4'
4"
- - GWB P
130 RESTROOM EX P SV SV 4" - - GWB P
133 EXAM AT SV SV 4" - - GWB P
134 OFFICE AT LVT PLANK RB 4" - - GWB P
135 OFFICE AT LVT PLANK RB 4" - - GWB P
149 PATIENT AREA AT LVT PLANK RB GWB P
150 OFFICE AT LVT PLANK RB 4" - - GWB P
C-151 CORRIDOR AT LVT PLANK RB 4" - - GWB P MATCH EXISTING CONDITIONS AT CORRIDOR
DOOR SCHEDULE
MARK ROOM #
ROOM
NAME
DOOR SIZE DOOR
TYPE
GLAZING
TYPE
HW
SET
MATERIAL FIRE
RATING COMMENTSWIDTH HT THK DOOR FRAME
100 100 EXAM 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
123 123 EXAM 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
124 124 EXAM 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
125 125 EXAM 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
126 126 EXAM 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
133 133 EXAM 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
135 135 OFFICE 3' - 0" 6' - 8" 0' - 1 3/4" 1 TEMPERED 3E WOOD METAL --
149 149 PATIENT AREA 4' - 0" 7' - 0" 0' - 1 3/4" 6 - SDH1 WOOD METAL -- SLIDING DOOR 42" NET CLEAR OPENING
150 150 OFFICE 3' - 0" 6' - 8" 0' - 1 3/4" 1 TEMPERED 3E WOOD METAL --
1/4" = 1'-0"
DOOR TYPES
3/4" = 1'-0"
PARTITION FRAMING AT DOORS
3" = 1'-0"
INTERIOR DOOR FRAMES
1" = 1'-0"
WALL TYPES
Revisions: Date: 14 OF 45
F
E
AE421a
5 2
AE421b
AE421b 7
IN-04.02-04
IN-04.02-05
IN-04.02-02
IN-04.02-03
IN-04.02-09
IN-04.02-06
IN-04.02-08
IN-04.02-07
EXAM
EXAM
EXAM
EXAM
EXAM
EXAM
PATIENT AREA
OFFICE
OFFICE
OFFICE
CLINICAL SUP
NURSING
STATION
IN-04.02-01
OFFICE
ELECTRICAL
RESTROOM
CLINICAL SUP
SOILED
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AW001
SIGNAGE MESSAGE SCHEDULE, IN-04.02,
IN-07.02
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RENOVATE B211A SPECIALTY
CARE
WHITE CITY VA MEDICAL CENTER - WHITE CITY, OR
692-22-102
211A
08/15/2025 MK AJ
CONSTRUCTION
DOCUMENTS
1/4" = 1'-0"
LEVEL 1 - SIGNAGE LOCATION PLAN
PROJECT
NORTH
6" = 1'-0"
IN-04.02 - ROOM IDENTIFICATION
GENERAL NOTES
1. CONTRACTOR TO MATCH EXISTING SIGNAGE AT THE VA
MEDICAL CENTER.
SIGNAGE MESSAGE SCHEDULE
MARK ROOM # ROOM NAME MESSAGE NOTES
IN-04.02-01 135 OFFICE Office
IN-04.02-02 150 OFFICE Office
IN-04.02-03 124 EXAM Exam
IN-04.02-04 100 EXAM Exam
IN-04.02-05 123 EXAM Exam
IN-04.02-06 125 EXAM Exam
IN-04.02-07 126 EXAM Exam
IN-04.02-08 133 EXAM Exam
IN-04.02-09 149 PATIENT AREA Patient Area
Revisions: Date: 15 OF 45
FIRE PROTECTION WET
FIRE PROTECTION PRE-ACTION
PIPING SYSTEMS
FPW
FPPA
PIPING SYMBOLS
PL4
PL7
A
26-P 3
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
PUMP NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (PUMP)
DRAWING NUMBER WHERE DRAWN
FIRE PROTECTION DRYFPD
FIRE PROTECTION OTHERFPO
ABBREVIATIONS
CONTINUATION
DROP IN PIPE
ELBOW
TEE
UNION
TOP CONNECTION
BOTTOM CONNECTION
TOP…
This is the start of the file's text. The full file is on GovTribe.