These documents comprise electrical and fire protection specifications and drawings for a hospital facility renovation project, prepared by TLC Engineering Solutions for Halifax Health in Daytona Beach, Florida. The project includes comprehensive electrical system upgrades involving power distribution, lighting systems, alarm systems, and fire protection infrastructure. Key electrical specifications include installing new electrical systems in compliance with National Electrical Code (NEC), Florida Building Code (8th Edition), and various NFPA standards, with all materials required to be new, U.L. listed, and meeting rigorous testing standards.

The project involves complex electrical infrastructure, including multiple switchgear and distribution panels with varying amperage ratings, automatic transfer switches, and a fire pump system. The electrical system specifications mandate a one-year guarantee, require contractor verification of system operations, and specify detailed requirements for conduit systems, wiring, circuit breakers, and installation practices. The fire protection components include a Patterson fire pump with 125 HP motor and a Grundfos jockey pump, designed to meet stringent healthcare facility fire protection standards. The project appears to be a comprehensive upgrade to the electrical and fire protection systems of a healthcare facility, with precise technical specifications and multiple layers of regulatory compliance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN

WHICH THEY ARE TO BE INSTALLED.

2. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC 110.

A. THE EXCLUSIVELY DEDICATED SPACE EXTENDING FROM FLOOR TO STRUCTURAL

CEILING WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD MUST BE

CLEAR OF ALL PIPING, DUCTS, EQUIPMENT FOREIGN TO THE ELECTRICAL EQUIPMENT

OR ARCHITECTURAL APPURTENANCES IN ACCORDANCE WITH NEC 408.

3. CRITICAL AND LIFE SAFETY LIGHT SWITCHES SHALL BE ROUTED IN CONDUIT AND BOXES

OTHER THAN THAT FOR THE NORMAL BRANCH. ESSENTIAL SYSTEM SWITCHES SHALL BE RED

IN COLOR.

4. PATIENT CARE AREAS SHALL BE PROVIDED WITH GROUNDING IN ACCORDANCE WITH NEC 517.

5. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE RESISTIVE ASSEMBLIES,

(CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT

AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:

A. ALL ELECTRICAL BOXES SHALL BE METALLIC.

B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.

C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.

D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY

FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).

E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY

OF THE WALL RATING SHALL BE MAINTAINED.

F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100

SQUARE INCHES PER 100 SQUARE FEET.

G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL

BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.

H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.

I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH

BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.

6. NON-METALLIC RACEWAYS SHALL NOT BE USED TO SERVE ANY PATIENT CARE SPACE. ALL

WIRING SHALL BE MECHANICALLY PROTECTED BY INSTALLATION IN METALLIC RACEWAYS.

7. ALL DEVICES SHALL BE MOUNTED VERTICAL, UNLESS OTHERWISE NOTED.

8. ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP.

9. THE NUMBER OF ARROWHEADS ON THE HOMERUNS DENOTES THE NUMBER OF CIRCUITS.

10. CONTRACTOR SHALL COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING WORK AND

DURING CONSTRUCTION FOR POWER AND/OR SYSTEM OUTAGES AS WELL AS GENERAL

REQUIREMENTS.

GENERAL NOTES:

CONTRACTOR NOTE:

CONTRACTOR SHALL HAVE A $25,000

FIELD UNFORESEEN CONDITIONS

ALLOWANCE TO BE USED AS

DETERMINED BY THE ENGINEER. NO

ALLOWANCE DOLLARS SHALL BE

SPENT WITHOUT APPROVAL FROM THE

ENGINEER. ANY UNUSED ALLOWANCE

DOLLARS AT THE END OF THE

PROJECT SHALL BE CREDIT BACK TO

THE OWNER.

ALLOWANCE NOTE

ELECTRICAL SPECIFICATIONS

1. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE ALL MATERIALS, LABOR AND AUXILIARIES REQUIRED

TO INSTALL A COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEM. THE ELECTRICAL SYSTEM REQUIRED UNDER THIS DIVISION CONSISTS BASICALLY OF, BUT IS NOT LIMITED TO THE FOLLOWING: LIGHTING SYSTEM, POWER SYSTEM, ALARM SYSTEM, POWER DISTRIBUTION, EQUIPMENT CONNECTIONS, ACCESS PANELS, EMPTY

CONDUIT SYSTEMS AND ALL REQUIRED WIRING.

2. INSTALL IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE AND THE REGULATIONS OF GOVERNING LOCAL, STATE, COUNTY AND OTHER APPLICABLE CODES. PAY FOR ALL REQUIRED LICENSES, FEES AND INSPECTIONS.

3. ALL WORK AND EQUIPMENT UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE WITH THE APPLICABLE

PROVISIONS OF THE FOLLOWING CODES AND STANDARDS:

A. LIFE SAFETY CODE - NFPA 101 (2021 EDITION).

B. FLORIDA BUILDING CODE - 8TH EDITION

C. NATIONAL ELECTRICAL CODE - NFPA 70 (2023 EDITION).

D. STANDARD FOR HEALTH CARE FACILITIES - NFPA 99 (2021 EDITION).

E. NATIONAL FIRE PROTECTION CODE - NFPA 72 (2019 EDITION)

F. FGI - GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTHCARE CARE FACILITIES (2022 EDITION)

4A, ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE U.L. LISTED, BEAR THE U.L. LABEL OR BE LABELED OR LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY. WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE SUBMITTED TO PROVE TO THE ENGINEER THAT EQUIPMENT MEETS OR EXCEEDS AVAILABLE STANDARDS.

4B. PROVIDE SHOP DRAWING SUBMITTALS TO THE ARCHITECT/ENGINEER FOR APPROVAL FOR ALL MATERIAL PROVIDED UNDER THIS DIVISION. EQUIPMENT SHALL NOT BE ORDERED PRIOR TO APPROVAL FROM THE ARCHITECT/ENGINEER.

5. PROVIDE AND INSTALL ALL ELECTRICAL SYSTEMS AND ANY NECESSARY ACCESSORIES AS PER NEC AND LOCAL CODES WHETHER SPECIFIED HEREIN OR SHOWN ON DRAWINGS OR NOT. THE CONTENT OF THESE SPECIFICATIONS (DIVISION 16) AND CONTRACT DOCUMENTS IN GENERAL ONLY REFERS TO WORK REQUIRED ABOVE AND BEYOND

THE REQUIREMENTS OF THE NEC AND LOCAL CODES.

6. DRAWINGS ARE DIAGRAMMATIC. COORDINATE FINAL EQUIPMENT LOCATIONS WITH GOVERNING ARCHITECTURAL AND STRUCTURAL DRAWINGS. LAY OUT BEFORE INSTALLATION SO THAT ALL TRADES MAY INSTALL EQUIPMENT IN SPACES AVAILABLE. PROVIDE COORDINATION AS REQUIRED FOR INSTALLATION IN A NEAT AND WORKMANLIKE

MANNER.

7. CHECK SITE AND EXISTING CONDITIONS THOROUGHLY BEFORE BIDDING. ADVISE ENGINEER OF DISCREPANCIES OR

QUESTIONS NOTED.

8. PROVIDE FIELD SUPERINTENDENT WHO HAS HAD A MINIMUM OF FOUR (4) YEARS PREVIOUS SUCCESSFUL EXPERIENCE ON PROJECTS OF COMPARABLE SIZES AND COMPLEXITY. SUPERINTENDENT SHALL BE PRESENT AT ALL TIMES THAT WORK UNDER THIS DIVISION IS BEING INSTALLED OR AFFECTED. SUPERINTENDENT SHALL HAVE PASSED A PROCTORED H.H. BLOCK JOURNEYMAN EXAM WITH 75% GRADE OR BETTER AND SHALL BE A LICENSED JOURNEYMAN. A RESUME OF THE SUPERINTENDENT'S EXPERIENCE SHALL BE SUBMITTED TO ENGINEER BEFORE STARTING WORK. AT LEAST ONE MEMBER OF THE ELECTRICAL CONTRACTING FIRM SHALL HOLD A STATE MASTER

CERTIFICATE OF COMPETENCY.

9. PROVIDE ALL REQUIRED COORDINATION AND SUPERVISION WHERE WORK CONNECTS TO OR IS AFFECTED BY WORK

OF OTHERS, AND COMPLY WITH ALL REQUIREMENTS AFFECTING THIS DIVISION.

10. SUITABLY PROTECT ALL EQUIPMENT FURNISHED UNDER THIS DIVISION DURING CONSTRUCTION. RESTORE ALL DAMAGED SURFACES AND ITEMS TO "LIKE NEW" CONDITION BEFORE A REQUEST FOR SUBSTANTIAL COMPLETION

INSPECTION.

11. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE A ONE-YEAR GUARANTEE. THIS GUARANTEE SHALL BE BY THE CONTRACTOR TO THE OWNER FOR ANY DEFECTIVE WORKMANSHIP OR MATERIAL WHICH HAS BEEN FURNISHED UNDER THIS CONTRACT AT NO COST TO THE OWNER FOR A PERIOD OF ONE YEAR FROM THE DATE OF

SUBSTANTIAL COMPLETION OF THE WORK.

12A. PERFORM VERIFICATION WORK AS REQUIRED TO SHOW THAT THE SYSTEM IS OPERATING CORRECTLY IN ACCORDANCE WITH CONTRACT DOCUMENTS AND MANUFACTURER'S LITERATURE. ALL VERIFICATION SHALL BE DONE AFTER 3-DAY FULL OPERATIONAL PERIOD. ALL WORK ON THE SYSTEM SHALL BE COMPLETED, AND ALL FORMS AND OTHER INFORMATION SHALL BE SUBMITTED FOR APPROVAL ONE WEEK BEFORE THE REQUEST FOR

FINAL INSPECTION OF THE BUILDING.

12B. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING WORK AND DURING CONSTRUCTION FOR POWER AND/OR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. A SEVEN (7) DAY NOTICE SHALL BE GIVEN FOR ALL POWER OUTAGES. CONTRACTOR SHALL WORK DURING OFF HOURS (EVENINGS &

WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL.

13. WHERE THE REQUIREMENTS OF ANOTHER DIVISION, SECTION, OR PART OF THESE SPECIFICATIONS EXCEED THE

REQUIREMENTS OF THIS DIVISION, THOSE REQUIREMENTS SHALL GOVERN.

14. THE ENTIRE INSTALLATION SHALL BE IN HOT DIPPED RIGID GALVANIZED CONDUIT, OR ELECTRIC METALLIC TUBING, UNLESS SPECIFICALLY NOTED OTHERWISE. RIGID METAL GALVANIZED CONDUIT SHALL BE USED IN ALL DAMP OR WET LOCATIONS OR WHERE SUBJECT TO MECHANICAL DAMAGE. ELECTRIC METALLIC TUBING SHALL HAVE STEEL COMPRESSION TYPE COUPLINGS AND BE USED INSIDE OF BUILDINGS AND ONLY IN DRY AREAS WHERE NOT EXPOSED TO MECHANICAL DAMAGE. MINIMUM CONDUIT SIZE FOR ALL SYSTEMS SHALL BE 3/4". PROVIDE INSULATED BUSHINGS AT ENDS OF ALL CONDUITS. ALL CONDUITS AND BACKBOXES SHALL BE COLOR CODED (FOR FIRE ALARM

- RED, FOR LIFE SAFETY - YELLOW). SUPPORT CONDUIT IN ACCORDANCE WITH THE NEC.

15. BRANCH CIRCUIT AND FEEDER CONDUCTORS FOR ELECTRIC POWER SHALL BE COPPER TYPE THHN/THWN INSULATION FOR BRANCH CIRCUITS AND THWN INSULATION FOR FEEDERS. NO ALUMINUM WIRING SHALL BE PERMITTED. ALL WIRE SHALL BE SIZE SHOWN ON THE DRAWINGS. IF NO SIZE IS SHOWN, WIRE SHALL BE MINIMUM NO. 12, EXCEPT THAT BRANCH "HOMERUNS" OVER 50 FT. IN LENGTH SHALL BE MINIMUM NO. 10. WIRE IN VICINITY OF HEAT-PRODUCING EQUIPMENT SHALL BE TYPE XHHW INSULATION. ALL WIRING SHALL BE MANUFACTURED IN THE

USA. WIRING SHALL BE COLOR CODED ACCORDING TO EXISTING HOSPITAL STANDARDS.

18. MOLDED CASE CIRCUIT BREAKERS: ALL PANELBOARD BRANCH CIRCUIT BREAKERS SHALL BE BOLT-ON THERMAL-MAGNETIC MOLDED CASE TYPE. BREAKERS SHALL BE 1, 2 OR 3 POLE WITH AN INTEGRAL CROSSBAR TO ASSURE SIMULTANEOUS OPENING OF ALL POLES IN MULTI-POLE CIRCUIT BREAKERS. BREAKERS SHALL HAVE AN OVERCENTER,TRIP-FREE,TOGGLE-TYPE OPERATING MECHANISM WITH QUICK- MAKE, QUICK-BREAK ACTION AND ACTIVE HANDLE INDICATION. HANDLES SHALL HAVE "ON", "OFF", AND "TRIPPED" POSITIONS. BOLT-ON CIRCUIT BREAKERS SHALL BE ABLE TO BE INSTALLED IN THE PANELBOARD WITHOUT REQUIRING ADDITIONAL MOUNTING HARDWARE. 120/208 VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 10,000 RMS

SYMMETRICAL AMPERES AT 240VAC.

19. AT THE COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE TWO SETS OF RECORD "AS-BUILT" DRAWINGS IN ACCORDANCE WITH DIVISION 1, SHOWING THE ACTUAL LOCATION OF ALL EQUIPMENT INSTALLED INCLUDING

UNDERGROUND CONDUITS AND JUNCTION BOXES.

20. PROVIDE EXPANSION FITTINGS, WHERE NECESSARY TO COMPENSATE FOR THERMAL EXPANSION AND CONTRACTION, AND FOR CONDUITS RUNNING FROM BUILDING STRUCTURE TO THE OTHER SEPARATE BY

EXPANSION JOINTS. PER NEC 300.7.

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.

ELECTRICAL SYMBOL LEGEND

DN

UP

SYMBOL DESCRIPTION

DDC

VFD

AUTOMATIC TRANSFER SWITCH

DIRECT DIGITAL CONTROL PANEL

VARIABLE FREQUENCY DRIVE

MOTOR CONNECTION

NEW (HEAVY, SOLID LINE)

EXISTING TO REMAIN (LIGHT, SOLID LINE)

EXISTING TO BE REMOVED (HEAVY, DASHED LINE)

FLEXIBLE CONDUIT

CONDUIT CONTINUED

CONDUIT STUBBED OUT OR UP

CONDUIT TURNING DOWN

CONDUIT TURNING UP

GROUND OR GROUND ROD AS NOTED

CONDUIT EXPOSED

CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR

CONDUIT CONCEALED ABOVE CEILING OR IN WAL

BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED

MULTI-SERVICE RACEWAY WITH 5-20R RECEPTACLES, 18" O.C. UNLESS

OTHERWISE NOTED

SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AS NOTED

NOTE: DIAGONAL MARKS INDICATED ON ANY DEVICE REPRESENTS DEVICE

CONNECTED TO EMERGENCY CIRCUIT (RED DEVICE FOR RECEPTACLE);

TYPICAL FOR ANY DEVICE IN LEGEND

TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVER MOUNTED ABOVE COUNTER

TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE

GFCI RECEPTACLE; "WP" INDICATES CAST METAL "IN-USE" WEATHERPROOF COVER,

WEATHER-RESISTANT LISTED

DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER

MULTI-SERVICE FLOOR BOX WITH DUPLEX RECEPTACLE, VOICE/DATA/AV DEVICES

(REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW

VOLTAGE REQUIREMENTS)

FLOOR BOX WITH DUPLEX RECEPTACLE WITH APPROPRIATE FLANGE

30AR

20AF

PEDESTAL MOUNTED DUPLEX RECEPTACLE

DUPLEX RECEPTACLE

NF

30AR NON-FUSED DISCONNECT SWITCH, RATING AS NOTED

NF = NON-FUSED

AR = AMPERE RATING OF SWITCH

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE

NOTED

30/3

3R

MCP

AMPERE

RATING

# OF POLES

NEMA STARTER SIZE

SINGLE RECEPTACLE

FUSED DISCONNECT

BASIC MATERIALS

MOTORIZED DAMPER CONNECTIONMD

FLOOR BOX, TWO DUPLEX RECEPTACLES (QUAD) WITH APPROPRIATE FLANGE

DEVICE ABBREVIATION TAGS:

DUPLEX RECEPTACLE, CEILING MOUNTED

TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE, CEILING MOUNTED

J

MULTI-SERVICE FLOOR BOX WITH TWO DUPLEX RECEPTACLES (QUAD) , VOICE/DATA/AV

DEVICES (REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR

LOW VOLTAGE REQUIREMENTS)

GFCI RECEPTACLE MOUNTED ABOVE COUNTER

DUPLEX RECEPTACLE; EACH RECEPTACLE ON SEPARATE CIRCUIT (PROVIDE

BREAKER WITH 2-POLE COMMON TRIP HANDLE)

SPLIT-WIRED CONTROLLED DUPLEX RECEPTACLE

TWO GFCI DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE

MULTI-SERVICE POWER & DATA FLOOR BOX WITH FURNITURE FEED CONNECTION

(REFER TO TECHNOLOGY DRAWINGS OR OWNER'S VENDOR DRAWINGS FOR LOW

VOLTAGE REQUIREMENTS)

J JUNCTION BOX WALL MOUNTED

J JUNCTION BOX MOUNTED IN OR ABOVE CEILING OR IN STRUCTURE

J WALL MOUNTED FURNITURE FEED POWER CONNECTION

C CLOCK RECEPTACLE, WALL MOUNTED

GROUND BUS BAR, COPPERGND

CONDUIT SEAL-OFF FITTING

SPD SURGE PROTECTIVE DEVICE

ST

SHUNT-TRIP PUSHBUTTON; SEMI-FLUSH WALL MOUNTED UNLESS OTHERWISE NOTED;

NEMA 3R FOR EXTERIOR LOCATIONS

OVERHEAD DOOR PUSHBUTTON CONTROL STATION

PUSHBUTTON STATION

BAS BUILDING AUTOMATION SYSTEM CONTROL PANEL

LCP LIGHTING CONTROL PANEL

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

3R

3R

AF = AMPERE RATING OF FUSE

AR = AMPERE RATING OF SWITCH

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED

BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED

CONDUIT HOMERUN TO ELECTRICAL PANEL

ATS

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED

4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE

SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL

EPO EMERGENCY POWER OFF SHUNT-TRIP PUSHBUTTON, RED MUSHROOM HEAD, CLEAR

LEXAN PROTECTIVE COVER

A

EMERGENCY TWIN-HEAD LIGHT WITH INTEGRAL BATTERY PACK, WALL MOUNTED

TRACK WITH TRACK LIGHT FIXTURE (TRIANGLES INDICATE QUANTITY OF TRACK HEADS)

EXTERIOR POLE-MOUNTED AREA LIGHT FIXTURE, ARMS AS INDICATED ON DRAWINGS

EXIT LIGHT, WALL MOUNTED

EXIT LIGHT, CEILING OR PENDANT MOUNTED; DIRECTIONAL ARROWS AS INDICATED;

SHADED QUADRANT INDICATES FACE(S) OF FIXTURE

CEILING WALLWASHER, ACCENT LIGHT, LANDSCAPING TREE ACCENT LIGHT, FACADE LIGHT

RECESSED, PENDANT OR SURFACE CEILING

FIXTURE RECESSED, PENDANT OR SURFACE CEILING

DIAGONAL HALF SHADING INDICATE FIXTURE CONNECTED TO CRITICAL CIRCUIT OR

PROVIDED WITH INTEGRAL EMERGENCY BATTERY PACK; "E" AFTER FIXTURE TYPE TAG

INDICATES INTEGRAL BATTERY PACK UNLESS OTHERWISE NOTED ON LIGHT FIXTURE

SCHEDULE (TYPICAL FOR ALL LIGHT FIXTURE SYMBOLS)

FULL SHADING INDICATE FIXTURE CONNECTED TO LIFE SAFETY CIRCUIT.

FIXTURE, RECESSED, PENDANT OR SURFACE CEILING

STRIP FIXTURE

FIXTURE, WALL MOUNTED

FIXTURE TYPE

LOWER CASE LETTER INDICATES CONTROLLING SWITCH

a

CIRCUIT NUMBER

LIGHTING

WALL MOUNTED

LINEAR RECESSED, PENDANT OR SURFACE CEILING

ZX-X

LIGHTING CONTROL ZONE NUMBER

EXTERIOR PEDESTRIAN SIDEWALK BOLLARD OR POST-TOP LIGHT FIXTURE

H

H

FS

FS

TS

F

RT

R

F

FIRE ALARM ANNUNCIATOR PANEL - FLUSH MOUNTED

FIRE ALARM TERMINAL CABINET

FIRE ALARM CONTROL PANELFACP

HEAT DETECTOR 135°F FIXED TEMPERATURE, UNLESS OTHERWISE NOTED,

CEILING MOUNTED

ELECTROMAGNETIC DOOR HOLD OPEN DEVICE

SPRINKLER WATERFLOW SWITCH CONNECTION

P

SPRINKLER TAMPER SWITCH CONNECTION

FIREMAN'S PHONE JACK

STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE NOTED

CD = CANDELA RATING

COMBINATION SPEAKER/STROBE, CEILING MOUNTED, 75CD UNLESS OTHERWISE

NOTED

HORN ONLY, WALL MOUNTED

DUCT SMOKE DETECTOR REMOTE TEST SWITCH WITH INDICATING LAMP, WALL

MOUNTED AT 48" AFF, UNLESS OTHERWISE NOTED

SUPERVISED ADDRESSABLE FIRE ALARM CONTROL RELAY

S = SUPPLY

R = RETURN

DUCT SMOKE DETECTOR

E = ELEVATOR WITH RECALL CONTACTS

I = IONIZATION

CEILING SMOKE DETECTOR, PHOTOELECTRIC TYPE UNLESS OTHERWISE

NOTED

MANUAL PULL STATION

FIRE ALARM / DETECTION SYSTEM

F

XXCD CD = CANDELA RATING

COMBINATION SPEAKER/STROBE, WALL MOUNTED, 75CD UNLESS OTHERWISE

NOTED

CD = CANDELA RATING

STROBE, CEILING MOUNTED, 75 CD UNLESS OTHERWISE NOTED

SS SPEAKER ONLY, CEILING MOUNTED

PS PRESSURE SWITCH CONNECTION

XXCD

B R

BEAM SMOKE DETECTOR

BT OR T = BEAM DETECTOR TRANSMITTER

BR OR R = BEAM DETECTOR RECEIVER

F

XXCD

SPEAKER ONLY, WALL MOUNTEDSS

FATC

FAA

VOICE EVACUATION PANELEVAC

MASS NOTIFICATION SYSTEM PANELMNS

SYMBOL DESCRIPTION

NFPA / LEGACY

F

S

S

BR

S

H

DH

XXCD

F H

XXCD

C

S C

S

VS

WS

PS

FACP

FATC

FAA

EVAC

MNS

R

MASS NOTIFICATION SYSTEM PANELDACTDACT

255 S. Orange Avenue Suite 1600

Orlando, FL 32801 P 407.841.9050 www.tlc-engineers.com

© Copyright 2025 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

Emory Neal Boothe, P.E.

Florida License #54603

This item has been electronically signed and sealed Emory Neal Boothe using a Digital Signature and date.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Seal

Drawing No.:

Scale:

Issuance:

Drawing Title:

Approved By:

Project No.:

Drawn By:

Consultants:

925854

12" = 1'-0"

/4 /2

:4

:0

P

M C

R e vi t

L o ca ls \9

-H

H F ir e

P u m p R m E

L E

C -F

IR

E

P R

O T

R

C o d y.

M o rg a n

T

Q C

Y .r vt

H A

L

IF

A X

H E

A L

T H

D A

Y T

O N

A F

IR

E

P U

M P

R O

O M

N

C ly d e

M o rr is

B lv d

D a yt o n a

B e a c h

F

L

925854

CWM

ENB

GENERAL

INFORMATION -

ELECTRICAL

E001

No. Date Description

ELECTRICAL DRAWING INDEX

SHEET DESCRIPTION

E001 GENERAL INFORMATION - ELECTRICAL

E002 ELECTRICAL ONE-LINE DIAGRAM

E111 DEMO & RENO FLOOR PLANS - ELECTRICAL

T-NHA1DPC

BRANCH OF

POWER

N=NORMAL

C=CRITICAL

Q=EQUIPMENT

L=LIFE SAFETY

E=ESSENTIAL

U=UPS

VOLTAGE

H=277/480V

L=120/208V

TRANSFORMER

BLANK =

PANEL AREA SERVED

A=FREESTANDING ED

B=ASC

C=MOB

D=HOSPITAL

FLOOR #

P=PENTHOUSE

G=GROUND

1=FIRST

2=SECOND

PANEL TYPE

DP=DISTRIBUTION

BLANK=BRANCH

PANEL

SG=SWITCHGEAR

SB=SWITCHBOARD

PANEL

DESIGNATION

A,B,C,...

NEW PANEL/TRANSFORMER

DESIGNATIONS

FPL XFMRS VAULT

(2) 1500 KVA

277/480V, 3∅, 4W

1600AF

1600AT

CHILLER #2

(SOUTH CHILLER

BUILDING, 1200 TON)

2500AF

2500AT

200AF

100AT

ATS

1200AF

960AT

PANEL "DPH-1"

(ONCOLOGY)

1200AF

1200AT

800AF

800AT

PANEL "S"

(PHYSICAL FITNESS)

2000AF

1800AT

2500AF

2500AT

MAIN SWITCHGEAR (#1)

(65,000 AIC)

(60,862 SCA)

277/480V, 3∅, 4W

(ONCOLOGY)

5 SETS OF

(3) 750KCMIL,

(1) 500KCMIL

(1) 2/0 GND

4" C.

3 SETS OF

(4) 400KCMIL,

(1)#2/0 GND

4" C.

7 SETS OF

(4) 500KCMIL,

(1) 350KCMIL GND

4" C.

2 SETS OF

(4) 600KCMIL,

(1)#1/0 GND

4" C.

4 SETS OF

(4) 600KCMIL,

(1)#4/0 GND

4" C.

7 SETS OF

(4) 500KCMIL,

(1) 350KCMIL GND

4" C.

MULTI-TAP BOX

2000 AMPS

ESB

277/480V, 3∅, 4W

100 400 600 1200 400 400

SPARE

1250KW @ 0.8 PF

480/277V

60 HZ

2000AF/1800AT

(18,000 AIC)

(10,217 SCA)

5 SETS OF

(3) 750KCMIL,

(1) 500KCMIL

(1) 2/0 GND

4" C.

(18,000 AIC)

(10,185 SCA)

ATS-MCCC-MCC

C-MCC MDP-1

MM

277/480V, 3PH, 4W

2500 AMPS(60,862 SCA)

(65,000 AIC)

NSB

ATS-EQP

600A,4P

(65,000 WSR)

(60,862 SCA)

ATS-LS

400A,4P

(65,000 WSR)

(60,862 SCA)

277/480V, 3PH, 4W

400 AMPS(60,862 SCA)

(65,000 AIC)

LS

T-LLS

9 KVA

480V-

120/208V

SCA = 64,212 AMPS

E-G SET #4 (SOUTH HILL)

FIRE PUMP

277/480V, 3PH, 4W

2500 AMPS(60,862 SCA)

(65,000 AIC)

EQP

TO FP JOCKEY PUMP

LLS

(10,000 AIC)

(100,000 AIC)

(64,000 SCA)

400 600

15 15

ONE-LINE DIAGRAM LEGEND

NEW EQUIPMENT

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT AFFECTED BY PROJECT

EXISTING EQUIPMENT TO BE DEMOLISHED

FUTURE EQUIPMENT

GENERAL ONE-LINE DIAGRAM NOTES

1 REFER TO PANEL SCHEDULES FOR ADDITIONAL LOADS/PANELBOARD REQUIREMENTS NOT

SPECIFICALLY INDICATED ON THIS SHEET.

2 COORDINATE CIRCUIT BREAKER SELECTION AND LUG CAPACITIES WITH SPECIFIED WIRE

SIZES, PROVIDE LUG KITS AS REQUIRED. ALL EQUIPMENT WITH MANUFACTURER'S

RECOMMENDATIONS PRIOR TO INSTALLATION OF EQUIPMENT.

3 CONDUITS SIZED PER EMT, CONTRACTOR TO RESIZE IF USING OTHER TYPES OF CONDUIT.

4 BASIS OF DESIGN: SQUARE 'D'

5 REFER TO SPECIFICATION 260513 2.1 FOR WIRE AND CONDUCTOR TYPE.

ONE-LINE DIAGRAM NOTES:

FIRE PUMP FEEDER TERMINATION ON FP&L BUS INSIDE THE VAULT. COORDINATE

WITH FP&L.

(4) 500 KCMIL - 4" CONDUIT (RGS) ROUTED ON EXTERIOR OF THE SERVICE BUILDING,

TERMINATING AT THE FIRE PUMP CONTROLLERS/ATS AND THE FP&L VAULT.

(3) 500 KCMIL AND (1) 4/0 GROUND - 4" CONDUIT (RGS) ROUTED ON EXTERIOR OF THE

SERVICE BUILDING, TERMINATING AT THE FIRE PUMP CONTROLLERS/ATS AND THE

ESB BOARD.

FIRE PUMP (SERVICE ENTRANCE RATED) CONTROLLER/ATS (REFER TO FP DRAWINGS

FOR SPECS).

4/0 GROUNDING ELECTRODE CONDUCTOR (NEUTRAL/GROUND BOND WITHIN SERVICE

ENTRANCE CONTROLLER).

PROVIDE GROUNDING ELECTRODE (GROUND RODS, BONDING OF STEEL STRUCTURE

AND BONDING OF COLD WATER PIPE).

1" CONDUIT WITH SIGNAL AND ALARM WIRING TO EMERGENCY GENERATOR START

CIRCUIT AND TO FIRE PUMP ANNUNCIATOR (LOCATED IN FOUNTAIN TOWER PBX

LOCATION).

FIRE PUMP EMERGENCY BREAKER SHALL BE ADJUSTABLE TYPE WITH "LSI" SETTINGS.

255 S. Orange Avenue Suite 1600

Orlando, FL 32801 P 407.841.9050 www.tlc-engineers.com

© Copyright 2025 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

Emory Neal Boothe, P.E.

Florida License #54603

This item has been electronically signed and sealed Emory Neal Boothe using a Digital Signature and date.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Seal

Drawing No.:

Scale:

Issuance:

Drawing Title:

Approved By:

Project No.:

Drawn By:

Consultants:

925854

12" = 1'-0"

/4 /2

:4

:0

P

M C

R e v it

L o c a ls

\9

-H

H F ir e

P u m p R m E

L E

C -F

IR

E

P R

O T

R

C o d y .M o rg a n

T

Q C

Y .r v t

H A

L

IF

A X

H E

A L

T H

D A

Y T

O N

A F

IR

E

P U

M P

R O

O M

N

C ly d e

M o rr is

B lv d

D a y to n a

B e a c h

F

L

925854

CWM

ENB

ELECTRICAL

ONE-LINE DIAGRAM

E002

No. Date Description

FIRE PUMP

S

FIRE PUMP

GENERATOR ROOM (GROUND FLOOR)

FP&L VAULT

ELEC RM 02

ELEC RM

DN

C

J

WS VS VS

JOCKEY PUMP

CONTROLLER

VS

VS

FUEL TANK

DIESEL FIRE

PUMP

EXHAUST FAN

FRESH AIR INTAKE

FIRE PUMP

CONTROLLER

EQ

FIRE PUMP CONTROLLER/ATS

SERVICE ENTRANCE

EXISTING "ESB"

EXISTING "EQP" EXISTING "LLS"

DOWN

UP TO ROOF

DOWN TO VAULT

SCOPE OF WORK

255 S. Orange Avenue Suite 1600

Orlando, FL 32801 P 407.841.9050 www.tlc-engineers.com

© Copyright 2025 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

Emory Neal Boothe, P.E.

Florida License #54603

This item has been electronically signed and sealed Emory Neal Boothe using a Digital Signature and date.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Seal

Drawing No.:

Scale:

Issuance:

Drawing Title:

Approved By:

Project No.:

Drawn By:

Consultants:

925854

As indicated

/4 /2

:4

:1

P

M C

R e v it

L o c a ls

\9

-H

H F ir e

P u m p R m E

L E

C -F

IR

E

P R

O T

R

C o d y .M o rg a n

T

Q C

Y .r v t

H A

L

IF

A X

H E

A L

T H

D A

Y T

O N

A F

IR

E

P U

M P

R O

O M

N

C ly d e

M o rr is

B lv d

D a y to n a

B e a c h

F

L

925854

CWM

ENB

DEMO & RENO

FLOOR PLANS -

ELECTRICAL

E111

1/4" = 1'-0"

GROUND FLOOR DEMOLITION PLAN - ELECTRICAL

1/4" = 1'-0"

GROUND FLOOR PLAN - POWER

CODED NOTES

1 NEW FEEDS TO ELECTRIC FIRE PUMP TO BE ROUTED TO ROOF OF SERVICE BUILDING (CONDUIT SHALL BE

RIGID GALVANIZED STEEL.

2 NEW ELECTRIC FIRE PUMP.

3 EXISTING ELECTRICAL WITHIN FIRE PUMP ROOM ASSOCIATED WITH THE EXISTING FIRE PUMP SHALL BE

DEMOLISHED. EXISTING LIGHTING, RECEPTACLES, ETC SHALL REMAIN.

4 NEW FIRE PUMP CONTROLLER/ATS SERVICE ENTRANCE RATED.

5 NEW FIRE PUMP JOCKEY PUMP AND CONTROLLER.

6 CONNECT TO EQUIPMENT BRANCH PANEL "EQP", (1) 3PH - 20A CIRCUIT BREAKER.

7 REMOVE ALL ELECTRICAL ASSOCIATED WITH EXISTING JOCKEY PUMP CONTROLLER.

8 REMOVE ALL ELECTRICAL ASSOCIATED WITH EXISTING FUEL TANK.

9 REMOVE ALL ELECTRICAL ASSOCIATED WITH EXISTING DIESEL FIRE PUMP.

10 EXISTING EXHAUST AND FRESH AIR INTAKE COMPONENTS TO REMAIN.

11 EXISTING FIRE ALARM SYSTEM FLOW AND TAMPER SWITCHES TO BE RELOCATED TO NEW FIRE PUMP PIPING

AND VALVES.

12 EXISTING LIGHT FIXTURES TO REMAIN, RECONNECT TO LIFE SAFETY BRANCH CIRCUITING.

13 EXISTING EMERGENCY BATTERY PACK LIGHTING TO REMAIN.

14 RECONNECT LIGHTING AND RECEPTACLE TO LIFE SAFETY BRANCH "LLS", (1) 1PH - 20A CIRCUIT BREAKER.

15 CHANGE LIGHT SWITCH AND RECEPTACLE TO RED DEVICES AND PROVIDE TAG INDICATING LIFE SAFETY

BRANCH PANEL AND CIRCUIT.

16 EXISTING FIRE ALARM DEVICE TO REMAIN.

17 NEW FEEDS TO ELECTRIC FIRE PUMP TO BE ROUTED ON THE ROOF OF THE SERVICE BUILDING (CONDUIT

SHALL BE RIGID GALVANIZED STEEL).

18 DOWN EXTERIOR WALL WITH CONDUIT FEEDS OVER TO FIRE PUMP ROOM.

19 REMOVE ALL ELECTRICAL ASSOCIATED WITH EXISTING FIRE PUMP CONTROLLER.

GENERAL POWER PLAN NOTES

1 VERIFY AND COORDINATE EXACT ELECTRICAL REQUIREMENTS OF ALL EQUIPMENT WITH MANUFACTURER'S

RECOMMENDATIONS PRIOR TO INSTALLATION OF EQUIPMENT. MODIFY LAYOUT AS REQUIRED PER

MANUFACTURER'S SPACE REQUIREMENTS.

2 COORDINATE FINAL LOCATIONS OF ALL DIVISION 23 EQUIPMENT IN FIELD WITH DIVISION 23. FIELD

LOCATIONS SHALL DICTATE.

3 COORDINATE MOUNTING HEIGHTS AND LOCATIONS OF ALL DEVICES WITH ARCHITECTURAL ELEVATIONS AND

CASEWORK.

1/8" = 1'-0"

FIRST FLOOR - POWER

N N N

N

No. Date Description

1" = 80'-0"

SITE PLAN - ELECTRICAL

2 1/2"

2 1/2"

3-0

FIRE PROTECTION DRAWING INDEX

FIRE PROTECTION LEGEND

FIRE PROTECTION DESIGN CRITERIA

1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13 AND ALL APPLICABLE STATE CODES.

2. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE MARSHAL AND ARCHITECT/ENGINEER.

3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO THE

ARCHITECT/ENGINEER AND STATE FIRE MARSHAL AND SHALL BE APPROVED PRIOR TO ANY

INSTALLATION.

4. PIPE ROUTING SHOWN IS SCHEMATIC ONLY. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO

PROVIDE ANY ADDITIONAL OFFSETS REQUIRED FOR PROPER INSTALLATION AND COORDINATION

WITH OTHER TRADES.

5. PIPING IN AREAS WITH EXPOSED STRUCTURE SHALL BE INSTALLED AS HIGH AS POSSIBLE TO

ALLOW THE OWNER MAXIMUM USE OF THE SPACE.

6. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING DESCRIPTIONS AND HEIGHTS.

7. SPRINKLERS ARE TO BE COORDINATED WITH ALL DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS. SPACING OF SPRINKLERS SHALL BE IN ACCORDANCE WITH NFPA 13 AND THE

LISTING OF THE SPRINKLER.

8. SPRINKLER LOCATIONS SHALL BE CENTERED IN THE TILE. PROVIDE ARMOVER OR SWING JOINT AS

REQUIRED.

9. SPRINKLERS IN AREAS WITH EXPOSED STRUCTURE (OBSTRUCTED CONSTRUCTION) SHALL BE

INSTALLED WITH DEFLECTOR 1" BELOW THE BOTTOM OF THE BEAM (MAXIMUM 22" BELOW ROOF

DECK). EXPOSED BAR JOISTS THAT HAVE SPRAY-ON FIRE PROOFING THAT MAKES THE JOIST SOLID

SHALL BE TREATED LIKE A BEAM WITH THE SPRINKLERS 1" BELOW THE BOTTOM OF THE FIRE

PROOFING.

10. SLEEVE AND/OR FIRESTOP ALL PENETRATIONS THROUGH RATED WALLS, CEILINGS, AND FLOORS WITH U/L LISTED ASSEMBLIES. FIRESTOP ASSEMBLIES SHALL BE EQUAL OR EXCEED THE RATING OF

THE WALL, CEILING OR FLOOR. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES.

11. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND CHASES.

12. PROVIDE A PERMANENTLY ATTACHED NAME TAG TO THE RISER STATING THE REQUIRED DESIGN

CRITERIA FOR EACH HYDRAULICALLY-DESIGNED SYSTEM.

13. PROVIDE SPRINKLERS UNDERNEATH ALL EXPOSED DUCTWORK WHICH IS OVER 48" WIDE AND SPACE HEADS AROUND ALL OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13. HEADS UNDER DUCTS

ARE NOT INDICATED ON THE DRAWINGS BUT ARE REQUIRED AND SHALL BE PROVIDED IN

ACCORDANCE WITH NFPA 13. SPRINKLER LOCATIONS UNDER DUCTWORK AND AROUND

OBSTRUCTIONS SHALL BE GOVERNED BY FINAL INSTALLED LOCATIONS.

14. PROVIDE SPRINKLERS AT THE TOP AND BOTTOM OF ALL STAIRWELLS AND AT THE LANDING OF

EACH FLOOR THAT OPENS INTO MORE THAN ONE FIRE ZONE.

15. PROVIDE SPRINKLER GUARDS ON ALL HEADS IN ELECTRIC ROOMS, TELEPHONE ROOMS, ELEVATOR

ROOMS, ELEVATOR SHAFTS AND ON ANY HEADS LESS THAN 7'-0" ABOVE THE FLOOR.

16. IF SYSTEM PRESSURE EXCEEDS 100 PSI PROVIDE HANGERS PER NFPA 13 17.4.3.4.4 AND 17.4.3.5.2 THAT PREVENTS UPWARD MOVEMENT OF THE PIPE FOR SPRINKLERS IN THE PENDENT POSITION. A MAXIMUM OF 12" FROM THE END SPRINKLER ON A BRANCH LINE AND ALL ARM-OVERS OVER 12".

17. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO

ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY

CIRCUMSTANCES. ANY PIPING RUN OVER ELECTRICAL SHALL BE REROUTED AT NO ADDITIONAL

COST.

18. SPRINKLERS IN EQUIPMENT ROOMS ARE TO BE INTERMEDIATE TEMPERATURE 200°F SPRINKLERS

PER NFPA 13.

19. WET BULK SUPPLY MAINS AND HOSE SUPPLY MAINS EXPOSED TO THE WEATHER SHALL BE

INSULATED AND PROVIDED WITH AN ALUMINUM JACKET.

20. PROVIDE A TEMPORARY STANDPIPE SYSTEM WITH FIRE DEPARTMENT CONNECTIONS DURING

CONSTRUCTION.

GENERAL NOTES

a. THE POINT OF SERVICE AND THE WATER SUPPLY CHARACTERISTIC'S FOR THE FIRE

PROTECTION SYSTEM IS SHOWN ON THE FIRE PROTECTION SITE PLAN.

b. THE FIRE PROTECTION DESIGN, CALCULATIONS, INSTALLATION AND THE ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 13, 2019 EDITION; THE FLORIDA BUILDING CODE AND THE FLORIDA FIRE PREVENTION CODE 8TH EDITION (2023) AND

ALL LOCAL CODES REQUIRED BY THE AUTHORITY HAVING JURISDICTION.

c. AREA OCCUPANCIES AND HAZARD CLASSIFICATIONS ARE LISTED IN THE DESIGN CRITERIA NOTE

LOCATED ON THE CONTRACT DOCUMENTS.

d. THE FIRE PROTECTION CONTRACTOR SHALL PREPARE AND PROVIDE FIRE PROTECTION SYSTEM

LAYOUT DOCUMENTS WITH HYDRAULIC CALCULATIONS. FIRE PROTECTION SYSTEM LAYOUT

DOCUMENTS WITH HYDRAULIC CALCULATIONS SHALL BE SUBMITTED TO THE

ARCHITECT/ENGINEER AND THE LOCAL AHJ FOR ACCEPTANCE PRIOR TO PERMITTING.

e. SEE SITE PLAN FOR THE CHARACTERISTICS WATER SUPPLY PIPING.

f. THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE A HYDRANT FLOW TEST AND PERFORM

HYDRAULIC CALCULATIONS FOR PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT

DOCUMENTS (WORKING PLANS).

g. ALL SYSTEM CONTROL VALVES SHALL BE PROVIDED WITH TAMPER SWITCHES AND INTERFACE

THE ALARM CIRCUIT.

h. THE WATER SUPPLY FOR THE FIRE PROTECTION SYSTEM HAS NOT SHOWN ANY EVIDENCE OF

MICROBIAL INDUCED CORROSION (MIC). THE FIRE PROTECTION CONTRACTOR SHALL NOTIFY

THE ARCHITECT/ENGINEER OF ANY EVIDENCE OF MIC AND PROVIDE NECESSARY WATER

TREATMENT AS NEEDED TO REDUCE OR ELIMINATE MIC.

i. ALL METERING AND BACK FLOW PREVENTION DEVICES SHALL MEET WITH ALL WATER

PURVEYORS REQUIREMENTS.

j. ALL FIRE PROTECTION EQUIPMENT AND COMPONENTS SHALL BE LISTED AND TESTED FOR FIRE

PROTECTION USE. ALL FIRE PROTECTION EQUIPMENT AND COMPONENTS SHALL BE THE U.L.

LISTED AND FM APPROVED.

FLORIDA ADMINISTRATIVE CODE

CHAPTER 61G15-32 NOTES

NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT

SYMBOL DESCRIPTION

- CONTROL VALVE w/TAMPER SWITCH

- HYDRAULIC REFERENCE NODE

- EXISTING SPRINKLER PIPING

- FIRE VALVE CABINET

- REVISION REFERENCE

OR

- CONNECT TO

- DEMO TO

- DEMOLISHED SPRINKLER PIPING

- NEW SPRINKLER PIPING

- U/G GATE VALVE

# - KEYNOTE

- HYDRAULIC REMOTE AREA

- CONTROL VALVE W/ TAMPER SWITCH

- PIPE SIZE

- 2-1/2" FIRE DEPARTMENT VALVE W/ CAP AND CHAIN

- PIPE SIZE AND LENGTH

GENERAL PROVISIONS

PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY

OPERATING FIRE PROTECTION SYSTEM.

CODES AND STANDARDS: THE FIRE SPRINKLER PROTECTION SYSTEMS INSTALLATION,

FLUSHING AND TESTING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 13, AND 24 AND

ALL LOCAL CODES HAVING JURISDICTION.

PIPE THREAD PATTERN: ALL THREADS SHALL BE IN ACCORDANCE WITH LOCAL FIRE

DEPARTMENT SPECIFICATIONS AND NFPA 1963, 2019 REVISION.

UL/FM APPROVAL: ALL EQUIPMENT, VALVES, COUPLINGS, HANGERS AND DEVICES SHALL BE

APPROVED BY UNDERWRITERS' LABORATORY (UL) OR FACTORY MUTUAL (FM) FOR USE IN FIRE

PROTECTION SERVICE.

LICENSURE: THE FIRE PROTECTION SYSTEMS SHALL BE INSTALLED BY A STATE OF FLORIDA

CERTIFIED FIRE PROTECTION CONTRACTOR.

ALL FIRE PROTECTION WORK SHALL BE DONE IN A NEAT AND WORKMAN-LIKE MANNER.

CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED FOR THE

EXECUTION OF THIS WORK.

CONTRACTOR SHALL COORDINATE WORK WITH OTHER TRADES BEFORE FABRICATION OR

INSTALLATION. OFFSETS AND/OR TRANSITIONS REQUIRED SHALL BE PROVIDED WITHOUT

ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL WORK IN A TIMELY

MANNER TO PREVENT DELAYS IN THE CONSTRUCTION.

CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT AND/OR

MATERIAL.

PIPING SHOP DRAWINGS: SUBMIT 1/8" SCALE PIPING SHOP DRAWINGS. SHOP DRAWINGS SHALL

INCLUDE SPRINKLER PIPING CUT LENGTHS, OFFSETS, FITTINGS AND DEVICES, ELEVATIONS,

HANGER LOCATIONS, SPRINKLER HEAD COUNT BY TYPE, ELEVATION SECTIONS AND OTHER

INSTALLATION INFORMATION. SUBMIT HYDRAULIC CALCULATIONS PROVING THE VIABILITY OF

THE MOST HYDRAULICALLY-REMOTE AREAS OF THE PROJECT. INDICATE HYDRAULIC

REFERENCE POINTS AND SUBMIT COMPUTER ANALYZED NODAL CALCULATIONS IN BOTH

TABULAR AND GRAPHICAL FORMATS. HYDRAULIC IMBALANCE SHALL NOT EXCEED 0.01 GPM AT

ANY NODE, AND WATER VELOCITY SHALL NOT EXCEED 20 FEET PER SECOND. DEMONSTRATE

COMPLIANCE WITH THE REQUIREMENTS OF NFPA-13 REGARDING DENSITY, AREA OF

APPLICATION, SELECTION OF HYDRAULICALLY-REMOTE AREAS, AND MAXIMUM COVERAGE PER

SPRINKLER.

COORDINATE ALL PIPE ROUTING WITH ALL OTHER TRADES PRIOR TO INSTALLATION. ROUTE ALL

PIPING TO AVOID DUCTWORK, PIPING, AND BUILDING STRUCTURE.

BASIC MATERIALS AND METHODS

GENERAL: ONLY THE FOLLOWING MATERIALS DESIGNED FOR 175 PSIG CWP SHALL BE USED

FOR FIRE PROTECTION PIPING UNLESS SPECIFICALLY INDICATED OTHERWISE. ALL PIPING

MATERIALS SHALL HAVE A CORROSION RESISTANCE RATING (CCR) OF 1.0 OR GREATER.

PIPE: 2 INCH OR SMALLER PIPE, AND ALL THREADED PIPING SHALL BE BLACK STEEL, SCHEDULE 40, ASTM A-53. 2-1/2 INCH AND LARGER PIPE MAY BE BLACK STEEL, SCHEDULE 10, ASTM A-135.

FITTINGS: SCHEDULE 40 BLACK STEEL PIPE SHALL BE JOINED BY MECHANICAL COUPLINGS,

THREADED OR WELDED FITTINGS; SCHEDULE 10 BLACK STEEL PIPE SHALL BE JOINED BY

ROLLED GROOVE COUPLINGS OR WELDED FITTINGS ONLY. WELDED BRANCH CONNECTIONS

WHICH ARE AT LEAST 2 NOMINAL PIPE SIZES SMALLER THAN THE MAINS ARE PERMITTED.

THREADED FITTINGS ARE ACCEPTABLE ONLY FOR PIPING 2 INCHES AND SMALLER.

HANGERS: ALL HANGER SPACING SHALL COMPLY WITH THE REQUIREMENTS OF NFPA-13.

SPRINKLER HEAD LOCATION: INSTALL SPRINKLER HEADS IN THE CENTER OF THE CEILING TILES

FOR SUSPENDED CEILING APPLICATIONS.

SPRINKLER CAGE GUARD: PROVIDE HEAD GUARDS ON ALL HEADS IN ELECTRICAL ROOMS AND

ON ALL HEADS LESS THAN 7'-0" ABOVE FINISHED FLOOR.

GAUGES: PROVIDE GAUGES AND GAUGE VALVES AS REQUIRED BY NFPA 13. GAUGE

SCALE SHALL BE 0-300 PSI UNLESS OTHERWISE INDICATED.

ACCESS PANELS: PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE NON-

ACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES.

HYDROSTATIC TESTS: ABOVE GROUND AND BELOW GROUND PIPING SYSTEMS SHALL BE

HYDROSTATICALLY TESTED AT NOT LESS THAN 200 PSI PRESSURE, OR AT 50 PSI IN EXCESS OF

THE MAXIMUM PRESSURE, WHICHEVER IS GREATER, FOR A PERIOD OF 2 HOURS. THE TEST

PRESSURE SHALL BE READ FROM A GAUGE LOCATED AT THE LOW ELEVATION POINT OF THE

INDIVIDUAL SYSTEM OR PORTION OF THE SYSTEM BEING TESTED. THE SPRINKLER PIPING

SHALL NOT HAVE LEAKAGE EXCEEDING THE AMOUNTS SPECIFIED IN NFPA 24. LEAKAGE

QUANTITIES SHALL BE DETERMINED BY PUMPING AT THE SPECIFIED TEST PRESSURE FROM A

CALIBRATED CONTAINER. REPAIR LEAKING JOINTS AND RETEST AS NECESSARY UNTIL ALL

SYSTEMS HAVE BEEN TESTED. TEST THE PIPING BETWEEN THE CHECK VALVE IN THE FIRE

DEPARTMENT INLET PIPE AND THE OUTSIDE CONNECTION THE SAME AS THE BALANCE OF THE

SYSTEM.

FIRE PROTECTION VALVES AND ACCESSORIES

QUICK-RESPONSE UPRIGHT SPRINKLERS: SPRINKLER HEADS SHALL BE MANUFACTURED WITH

UPRIGHT DEFLECTORS FOR INSTALLATION ABOVE THE BRANCH LINE WITH BRASS FINISH -

CENTRAL GB-QR OR VIKING MICROFAST MODEL M.

QUICK RESPONSE SEMI-RECESSED SPRINKLERS: SPRINKLER HEADS SHALL BE MANUFACTURED

WITH PENDANT DEFLECTOR FOR INSTALLATION BELOW THE BRANCH LINE WITH CHROME-

PLATED FINISH - RELIABLE G5-56 OR VIKING MICROFAST MODEL M WITH MODEL F-1

ESCUTCHEON.

QUICK-RESPONSE CONCEALED SPRINKLERS: SPRINKLER HEADS SHALL BE MANUFACTURED

WITH PENDANT DEFLECTOR FOR INSTALLATION BELOW THE BRANCH LINE WITH WHITE FINISH -

O:\TLC RELIABLE G5-56 OR VIKING MICROFAST MODEL M.

SPRINKLER CAGE GUARD: PROVIDE SPRINKLER HEAD OPEN-WIRE CAGE GUARD TO PROTECT

HEADS FROM INJURY. CAGE WIRE SHALL BE CADMIUM-PLATED STEEL - TYCO SPRINKLER

GUARD OR VIKING MODEL SPRINKLER GUARD.

BUTTERFLY TYPE ISOLATION, 2-1/2 INCH AND LARGER: ISOLATION VALVES 2-1/2 INCH AND

LARGER SHALL BE CAST IRON BODY BUTTERFLY VALVES WITH THE VALVE SIZE, PRESSURE

RATING, MANUFACTURER AND "UL" AND "FM" CAST INTO THE BODY. VALVE SHALL HAVE

BRONZE OR CAST IRON DISC, NEOPRENE DISC LINER, CAST IRON HANDWHEEL WITH DISC

POSITION INDICATOR, INTEGRAL TAMPER SWITCH, 175 PSIG CWP WORKING PRESSURE, 350

PSIG CWP TEST PRESSURE, AND FLANGED OR GROOVED CONNECTIONS - GRINNELL 8000 FP OR

EQUAL.

ISOLATION VALVE TAMPER SWITCH: PROVIDE AN ELECTRONIC SUPERVISORY OR TAMPER

SWITCH ON EACH ISOLATION VALVE IN THE SPRINKLER SYSTEM. UNIT SHALL HAVE A RED

TAMPER-PROOF COVER WHICH WILL ACTIVATE AN ALARM OR TROUBLE SIGNAL WHEN

ADJUSTED. PROVIDE UNIT WITH SINGLE-POLE, NORMALLY CLOSED MICROSWITCH, MOUNTING

BRACKET, AND NON-RESETTABLE LOCK WITH REMOVABLE RESET KEY - SIMPLEX 2097-9035.

FLOW SWITCH: PROVIDE AN ELECTRIC FLOW SWITCH WHERE INDICATED OR REQUIRED. FLOW

SHALL BE SENSED BY AN IMMERSION PADDLE, WITH AN ADJUSTABLE RETARD SETTING FROM 0

TO 70 SECONDS TO MINIMIZE FALSE ALARMS. FLOW SWITCH SHALL HAVE 2 SEPARATE SINGLE

POLE, DOUBLE THROW MICROSWITCHES TO ACTIVATE A FLOW ALARM, OR TO INDICATE A

TROUBLE SIGNAL IF THE FLOW SWITCH HOUSING IS TAMPERED. FLOW ALARM SHALL BE

AUTOMATICALLY RESETTING. PROVIDE CLAMP-ON HOUSING TO SECURE UNIT TO PIPE, OR

THREADED CONNECTION FOR TEE FITTING - POTTER ELECTRIC SIGNAL CO. VSR-S.

INSPECTOR'S TEST AND DRAIN: TEST AND DRAIN SHALL BE PROVIDED WITH INTEGRAL SIGHT

GLASS, INTEGRAL 1/2 INCH TEST ORIFICE AND POSITIVE POSITIONING OF HANDLE FOR OFF, TEST AND DRAIN OPERATIONS - G/J INNOVATIONS, INC "SURE-TEST" OR AGF MANUFACTURING, INC. "TESTDRAIN".

100 -

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

1.10

1.11

2.00 -

2.1

2.2

2.3

2.4

2.5

2.6

2.7

2.8

2.9

3.00 -

3.1

3.2

3.3

3.4

3.5

3.6

3.7

3.8

SPECIFICATIONS

210100 - AUTOMATIC SPRINKLERS SYSTEMS

FIRE SPRINKLER:

SCOPE OF WORK:

REPLACE EXISTING FIRE PUMP WITH NEW ELECTRIC FIRE PUMP OF EQUAL SIZE AND CAPACITY.

• REMOVE EXISTING FUEL TANKS MUFFLER AND CONTROLLERS.

• REMOVE EXISTING JOCKEY PUMP

• PROVIDE A TEMPORARY FIRE PUMP WHILE THE EXISTING PUMP IS BEING REPLACED

• THE CONTRACTOR TO SECURE, PAY FOR AND OBTAIN A CURRENT FLOW TEST/DATA BEFORE

ORDERING THE NEW FIRE PUMP

PROVIDE NEW:

• NEW 1000 GPM @ 115 PSI ELECTRIC FIRE PUMP.

• VARIABLE SPEED CONTROLLER W/ TRANSFER SWITCH

• NEW JOCKEY PUMP

• NEW JOCKEY PUMP CONTROLLER

• REMOTE FPAP (FIRE PUMP ANNUCIATOR PANEL) TO BE LOCATED AT THE PBX.

THE CONTRACTOR SHALL PREPARE SYSTEM LAYOUT DRAWINGS PER CHAPTER 27, OF NFPA

13 - 2019 EDITION. THE CONTRACTOR SHALL PERFORM HYDRAULIC CALCULATIONS.

CONTRACTOR'S SPRINKLER SYSTEM LAYOUT (SHOP DRAWINGS), HYDRAULIC CALCULATIONS

AND MATERIAL DATA SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER AND AUTHORITY

HAVING JURISDICTION FOR APPROVAL PRIOR TO SYSTEM INSTALLATION.

THE EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE DURING. THE BUILDING SHALL

NOT BE WITH OUT FIRE SPRINKLER PROTECTION AT ANY TIME DURING CONSTRUCTION

EXCEPT FOR THE TIME OF CONNECTING THE NEW FIRE PUMP AND DISCONNECTING THE

EXISTING FIRE PUMP. PROVIDE 72 HOUR NOTICE TO THE OWNER PRIOR TO SYSTEM SHUT

DOWNS. COORDINATION WITH THE OWNER PRIOR TO SHUT DOWN OF THE EXISTING FIRE

SPRINKLER SYSTEM IS REQUIRED TO IMPLEMENT OTHER MEANS OF FIRE SAFETY FOR THE

BUILDING.

TEMPORARY FIRE PROTECTION:

PROVIDE TEMPORARY FIRE PUMP WHILE THE EXISTING FIRE PUMP IS BEING REPLACED.

FIRE SPRINKLER CONSTRUCTION CONSIDERATIONS

ALL WORK CONTAINED WITHIN THESE DOCUMENTS SHALL BE IN FULL COMPLIANCE

WITH ALL FEDERAL, STATE AND LOCAL CODES AND STANDARDS INCLUDING, BUT

NOT LIMITED TO THE FOLLOWING.

APPLICABLE CODES AND STANDARDS

1. FLORIDA ADMINISTRATIVE CODE SECTION 59A-3.080

2. FLORIDA BUILDING CODE: BUILDING, 8TH EDITION (2023)

3. FLORIDA FIRE PREVENTION CODE, 8TH EDITION (2023)

4. NFPA 1, FIRE CODE - 2019 EDITION (FLORIDA SPECIFIC EDITION)

5. NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS - 2019 EDITION

6. NFPA 20, STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION, 2019 EDITION.

7. NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR

APPURTENANCES - 2019 EDITION

8. NFPA 25, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED

FIRE PROTECTION SYSTEMS, 2020 EDITION.

9. NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE - 2019 EDITION

10. NFPA 101, LIFE SAFETY CODE - 2021 EDITION (FLORIDA SPECIFIC EDITION)

11. NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION

OPERATIONS, 2019 EDITION.

12. NFPA 2001, STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEMS - 2018 EDITION.

13. FGI, GUIDELINES FOR THE DESIGN AND CONSTRUCTION OF HOSPITALS - 2022 EDITION

255 S. Orange Avenue Suite 1600

Orlando, FL 32801 P 407.841.9050 www.tlc-engineers.com

© Copyright 2025 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

Aaron Lee Johnson, P.E.

Florida License #71576

This item has been electronically signed and sealed by Aaron Lee Johnson using a Digital Signature and date.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Seal

Drawing No.:

Scale:

Issuance:

Drawing Title:

Approved By:

Project No.:

Drawn By:

Consultants:

925854

12" = 1'-0"

/4 /2

:2

:0

A

M C

R e v it

L o c a ls

\9

-H

H F ir e P u m p R m E

L E

C -F

IR

E

P R

O T

R ja c k ie

.l u k e r.

rv t

H A

L

IF

A X

H E

A L

T H

D A

Y T

O N

A F

IR

E

P U

M P

R O

O M

N

C ly d e

M o rr is

B lv d

D a y to n a

B e a c h

F

L

925854

JLL

ALJ

GENERAL

INFORMATION - FIRE

PROTECTION

FP001

SHEET DESCRIPTION

FP001 GENERAL INFORMATION - FIRE PROTECTION

FP111 DEMO & RENO FLOOR PLANS - FIRE PROTECTION

No. Date Description

11/4/2025 CONSTRUCTION

DOCUMENTS

FIRE PUMPFIRE PUMP

N

255 S. Orange Avenue Suite 1600

Orlando, FL 32801 P 407.841.9050 www.tlc-engineers.com

© Copyright 2025 TLC Engineering Solutions, Inc.

TLC Project No. :

COA 15

Aaron Lee Johnson, P.E.

Florida License #71576

This item has been electronically signed and sealed by Aaron Lee Johnson using a Digital Signature and date.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Seal

Drawing No.:

Scale:

Issuance:

Drawing Title:

Approved By:

Project No.:

Drawn By:

Consultants:

925854

As indicated

/4 /2

:2

:0

A

M C

R e v it

L o c a ls

\9

-H

H F ir e P u m p R m E

L E

C -F

IR

E

P R

O T

R ja c k ie

.l u k e r.

rv t

H A

L

IF

A X

H E

A L

T H

D A

Y T

O N

A F

IR

E

P U

M P

R O

O M

N

C ly d e

M o rr is

B lv d

D a y to n a

B e a c h

F

L

925854

JLL

ALJ

DEMO & RENO

FLOOR PLANS - FIRE

PROTECTION

FP111

1/2" = 1'-0"

LEVEL 1 PLAN - FIRE PROTECTION

1/2" = 1'-0"

LEVEL 1 DEMOLITION PLAN - FIRE PROTECTION

FIRE PROTECTION KEYNOTES

1 EXISTING DIESEL FIRE PUMP TO BE REMOVED.

2 EXISTING FUEL TANK TO BE REOMVED

3 EXISTING FIRE PUMP CONTROLLER TO BE REMOVED

4 EXISTING MUFFLER TO BE REMOVED

5 NEW VARIABLE SPEED FIRE PUMP CONTROLLER W/ TRANSFER SWITCH

6 NEW ELECTRIC FIRE PUMP

7 EXISTING PRESSURE RELIEF VALVE TO REMAIN.

8 DEMO EXISTING JOCKEY PUMP

9 DEMO EXISTING JOCKEY PUMP CONTROLLER

10 NEW JOCKEY PUMP

11 NEW JOCKEY PUMP CONTROLLER

12 8" SUPPLY FROM CITY WATER MAIN

13 EXISTING 8" BACKFLOW PREVENTER WITH TAMPER SWITCHES

14 EXISTING 4-VALVE TEST HEADER

15 EXISTING FIRE DEPARTMENT CONNECTION

PUMP SCHEDULE

DESCRIPTION MANUFACTURER MODEL

INLET

SIZE

OUTLET

SIZE

RATED

PRESSU

RE

RATED

FLOW TYPE

ELECTRICAL

MOTOR HP MOTOR RPM PHASE HERTZ VOLTS

FIRE PUMP PATTERSON 6x5x17SSC 6" 5" 115 1000 HORIZONTAL 125 1775 3 60 480

JOCKEY PUMP GRUNDFOS CR 3-11 1" 1" 131 10 EDIT ME 2 3452 3 60 480

1" = 20'-0"

SITE PLAN - FIRE PROTECTION

No. Date Description

11/4/2025 CONSTRUCTION

DOCUMENTS

E001 - GENERAL INFORMATION - ELECTRICAL
Sheets
E001 - GENERAL INFORMATION - ELECTRICAL
E002 - ELECTRICAL ONE-LINE DIAGRAM
Sheets
E002 - ELECTRICAL ONE-LINE DIAGRAM
E111 - DEMO & RENO FLOOR PLANS - ELECTRICAL
Sheets
E111 - DEMO & RENO FLOOR PLANS - ELECTRICAL
FP001 - GENERAL INFORMATION - FIRE PROTECTION
Sheets
FP001 - GENERAL INFORMATION - FIRE PROTECTION
FP111 - DEMO & RENO FLOOR PLANS - FIRE PROTECTION
Sheets
FP111 - DEMO & RENO FLOOR PLANS - FIRE PROTECTION