This is an Asset Detail Report from VFA for a Wooden Storage Building (Chicken Coop) located at Trimborn Farm, owned by MILW County and managed by the Museum & Art Center in Greendale, Wisconsin. The asset, numbered 3156, is a 288 square foot, one-story wooden structure built in the 1850s, with a total area of 5,727 square feet including basement and attic. The building currently has a "Poor" condition rating and is used for guided educational tours and storing landscaping implements. The asset is classified as an Assembly Occupancy with an Unprotected Wood Frame construction type, and its current replacement value is $61,417.

The report outlines several renewal requirements with estimated costs totaling $27,313, including branch wiring, building structure repair, exterior door replacement, fire extinguisher renewal, interior lighting updates, electrical panel updates, and various maintenance tasks. Most renewal actions are categorized as "Beyond Useful Life" with priorities ranging from "Currently Critical" to "Future Planning", with action dates spanning from June 2021 to June 2035. The report also notes potential hazardous materials like asbestos and lead, given the building's 1850s construction date, and highlights that the structure lacks HVAC, plumbing, and has limited accessibility features.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Asset Detail Report By Asset Name

Department/Division: Museum & Art CentersAsset: Wooden Storage Building (Chicken Coop) Site: Trimborn Farm Asset Number: 3156

Assets are ordered by Asset Name Currency: USD

Statistics

FCI Cost: 24,224 FCI: 0.39 RI Cost: 27,313 RI: 0.44 Total Requirements Cost: 27,313 Asset Condition Rating: Poor

Current Replacement Value: 61,417 Date of most Recent Assessment:

Jun 9, 2020

Type Building Area 288 SF Use Museum / Art Center Construction Type IBC - Type V B Floors 1 Historical Category On Register

Address 1 8801 W Grange Ave City Greendale Address 2 - State/Province/Region UNITED STATES OF AMERICA Year Constructed 1850 Zip/Postal Code 53129 Year Renovated - Architect - Ownership MILW County - Owned Commission Date -

Decommission Date -

Inventory: No Occupancy Classification: A-3 Assembly

Insurable Value of Building: 0 Insurable Value of Contents: 0

Mission Category: Category 3

Photo

Wooden Storage Building (Chicken Coop)

Asset Description

Copyright 2025 VFA, Inc. All rights reserved. Jul 22, 2025 12:34:18 PM Page 1 of 4

Building General Description:

The Wooden Storage Bldg.

(Chicken Coop), Asset #3157, is located at W Grange Ave.

Greendale, WI

53129

The building is a one (1) story, 288 square foot structure built in the 1850’s. two (2) story, including a basement and attic for the total area of 5,727 square foot structure, built in and renovated in 2006.

Building interior is used to provide guided educational tours and houses landscaping implements.

Per the IBC Chapter 3 and the Wisconsin Administrative Code, SPS 354, the building is classified primarily as Assembly Occupancy. According to the IBC Chapter 6 and the Wisconsin Administrative Code, SPS 351.02, the facility is primarily construction

TYPE

V-B, Unprotected Wood Frame, as determined from field observations and as-built drawings.

The building has the following general systems:

ARCHITECTURAL/STRUCTURAL

SYSTEMS

Foundation Walls and Footings Concrete Ft

Building Structure Wood Framed

Veneered Walls

Siding

Windows Wood Single Gazing

Exterior Door x

Roofing

Shingles

Slab on Grade Concrete

5"

HANDICAPPED

ACCESSIBILITY

Building 3157's compliance with handicapped accessibility was evaluated utilizing International Building Code - ICC/ANSI A117.1, and

ADAAG.

This building is not exempt per the Codes.

The building does not have an accessible entry threshold.

HAZARDOUS

MATERIALS

An asbestos report was not provided for this building, however, based on the 1850’s date of construction asbestos and lead containing materials are presumed to be present in the building.

MECHANICAL

HVAC:

[none]

PLUMBING:

[none]

FIRE

PROTECTION:

Fire Extinguisher Dry Chem

ELECTRICAL

Copyright 2025 VFA, Inc. All rights reserved. Jul 22, 2025 12:34:18 PM Page 2 of 4

Distribution Panel

Branch Wiring, Equipment and Devices

Lighting Interior Fixtures

DISCLAIMER

This report reflects equipment or system deficiencies, and construction cost estimates to correct those deficiencies. The construction cost estimates may not reflect the actual total project costs. The construction cost estimates do not include costs for project management, owner services, planning and design, plan review fees, construction management, construction general conditions, overhead and profit, testing services and design and construction contingencies. All projects need to be submitted to the AE & ES section of DAS-FM to verify actual cost estimates for any Capital Improvement Project (CIP) budget requests.

Requirements

Requirement Name Renewal Prime System Category Priority Action Date Estimated

Cost

Branch Wiring, Equipment & Devices Renewal

Yes D5021 - Branch Wiring Devices

Beyond Useful Life

3 - Necessary Not Yet Critical

Jun 9, 2025 1,925

Building Structure - Wood Framed Renewal

Yes B1020 - Roof Construction

Beyond Useful Life

4 - Future Planning

Jun 9, 2030 1,259

Exterior Door - 3 x 7 Wood Renewal

Yes B2030 - Exterior Doors

Beyond Useful Life

3 - Necessary Not Yet Critical

Jun 9, 2025 2,336

Fire Extinguisher - Dry Chem Renewal

Yes D4031 - Fire Extinguishers

Beyond Useful Life

4 - Future Planning

Jun 9, 2030 113

Lighting - Interior Fixtures Renewal

Yes D5022 - Lighting Equipment

Beyond Useful Life

4 - Future Planning

Jun 9, 2030 407

Panel PB-007 - 30A 120/240V 1PH 2C MLO Renewal

Yes D5012 - Low Tension Service and Dist.

Beyond Useful Life

3 - Necessary Not Yet Critical

Jun 9, 2025 3,781

Repair & Refinish Exterior Wood Siding

No B2010 - Exterior Walls

Maintenance 1 - Currently Critical

Jun 9, 2021 4,006

Repair Concrete Slab Crack No A1030 - Slab on Grade

Maintenance 2 - Potentially Critical

Jun 9, 2023 876

Copyright 2025 VFA, Inc. All rights reserved. Jul 22, 2025 12:34:18 PM Page 3 of 4

Requirement Name Renewal Prime System Category Priority Action Date Estimated

Cost

Replace Duplex Receptacles with GFCI Devices

No D5021 - Branch Wiring Devices

Code Compliance

5 - Does Not Meet Current Codes or Standards

Roofing - Wood Shingles Renewal Yes B3010 - Roof Coverings

Beyond Useful Life

1 - Currently Critical

Jun 9, 2021 6,063

Slab on Grade - Concrete 5" Renewal

Yes A1030 - Slab on Grade

Beyond Useful Life

4 - Future Planning

Jun 9, 2030 148

Veneered Walls - Wood Siding Renewal

Yes B2010 - Exterior Walls

Beyond Useful Life

4 - Future Planning

Jun 9, 2035 873

Windows - Wood - Single Glazing Renewal

Yes B2020 - Exterior Windows

Beyond Useful Life

1 - Currently Critical

Jun 9, 2020 5,237

Total 27,313

Copyright 2025 VFA, Inc. All rights reserved. Jul 22, 2025 12:34:18 PM Page 4 of 4