10-0.3 Plans.pdf
PDF 7 MB Posted
- Attached to
- Douglass Center Gymnasium Renovations
- Solicitation number
- 2026-01
- Issued by
- Sumter County, Florida
About this file
This document is a comprehensive set of construction documents for the Douglass Gymnasium Renovation project in Live Oak, Florida, involving Suwannee County Commissioners as the owner and multiple engineering and architectural firms including BFB&S Architects, Kever McKee Engineering, Tomahawk Engineering & Consulting, and Dewberry. The project involves a full renovation of the existing gymnasium facility, with work including HVAC system replacements, electrical system upgrades, fire protection improvements, structural modifications, and architectural updates. The project is scheduled for construction in 100% contract documents dated 18 July 2025, with planned renovations to the approximately 15,325 square foot facility that includes gymnasium spaces, classrooms, restrooms, and locker rooms.
The renovation will include installing two packaged air conditioning heat pump units for the gymnasium, two ductless split systems for classroom additions, new electrical and lighting systems, fire alarm and sprinkler system upgrades, and architectural improvements such as new metal roofing, CMU wall modifications, and site improvements including new chain link fencing. The project is designed to meet the Florida Building Code 2023, 8th Edition, and will maintain the existing building's Group A-3 Assembly occupancy classification. The estimated total occupancy load is 1,500 persons, with the renovation maintaining the existing Type V non-sprinklered construction type. Funding and specific budget details are not explicitly stated in the documents, but the comprehensive nature of the drawings suggests a substantial municipal infrastructure investment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 5-1.1 Bid Summary.pdf | ||
| 11-0.1 Instructions.pdf | ||
| 1-1.3. Bid Form Ack.pdf | ||
| 3-0.4. Standard Conditions Construction Contract.pdf | ||
| 2-1.5. Refs form.pdf | ||
| 8-0.0 Advertisement.jpg | JPG image | |
| 9-0.2 Technical Specifications.pdf | ||
| 7-1.6 Time Allocation Ack.pdf | ||
| 12-1.7 Addendum 1.pdf | ||
| 6-1.4 Fillable Forms.pdf | ||
| 4-1.2 Bid Form - Douglass Gymnasium Renovations (BT-13AC).xlsx | XLSX spreadsheet |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT DIRECTORY
OWNER
SUWANNEE COUNTY COMMISSIONERS
13150 VOYLES STREET
LIVE OAK, FL 32060
TEL: 386-364-3450
ARCHITECT
BFB&S ARCHITECTS
2074 CENTRE POINTE BLVD, SUITE 200
TALLAHASSEE, FL 32308
TEL: 850-224-6301
www.bfbsa.com
STRUCTURAL ENGINEER
KEVER MCKEE ENGINEERING
1624 METROPOLITAN BLVD, SUITE A
TALLAHASSEE, FL 32308
TEL: 850-727-5367
www.kevermckee.com
TOMAHAWK ENGINEERING & CONSULTING
1940 BUFORD BLVD.
TALLAHASSEE, FL 32308
TEL: 850-402-1340
CIVIL ENGINEER
DEWBERRY
20684 CENTRAL AVENUE EAST
BLOUNTSTOWN, FL 32424-6209
TEL: 850.354.5204
MEP ENGINEER
969 DOUGLAS ST SW
LIVE OAK, FL 32064
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
CS-1
DOUGLASS
GYMNASIUM -
RENOVATION
COVER SHEET
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
DOUGLASS GYMNASIUM -
RENOVATION
PROJECT LOCATION MAP
969 DOUGLAS ST SW
LIVE OAK, FL 32064
18 JULY 2025
A101
SIM BUILDING SECTION LETTER
SECTION NUMBER
SHEET NUMBER
BUILDING
SECTION
A101
SIM WALL SECTION NUMBERWALL
SECTION
A101
SIM DETAIL NUMBER
SHEET NUMBER
DETAIL
0 COLUMN LETTER OR NUMBER
A - 9
A - 8
A - 7
A
Room name
A
ROOM NAME AND NUMBER
DOOR NUMBER
WINDOW TYPE (INTERIOR)
P-1 WALL PARTITION TYPE
1i WINDOW TYPE (EXTERIOR)A
B
CARD READERC.R.
90 MIN FIRE RATING
FIRE EXTINGUISHER
CABINET
FIRE EXTINGUISHER ON
BRACKET -
DOOR HOLD OPENH.O.
A101
SIM
A - 9
DETAIL NUMBER
BUILDING ELEVATION LETTERBUILDING
ELEVATION
A101
INTERIOR ELEVATION LETTERINTERIOR
ELEVATION
FEC
FEB
SHEET NUMBER
SHEET NUMBER
SHEET NUMBER
SHEET NUMBER
A101
1 Ref
R e f
1 Ref
R e f
1 Ref
R e f
1 Ref
R e f
METAL STUD WALL
STRUCTURAL STEEL FRAMING
REVISION CLOUD
REVISION NUMBER
NORTH ARROW
SPOT ELEVATION
ELEVATION HEIGHT
EL. 0.0
CONCRETE MASONRY
EARTH/COMPACT FILL
PORUS FILL/ GRAVEL
CONCRETE
SAND, MORTAR, GYPSUM BOARD, PLASTER
INFILL CONSTRUCTION
COLUMN LINE / CENTER LINE
PROPERTY LINE
HIDDEN LINE (BEYOND)
BREAK LINE
WOOD- CONTINUOUS/ NON CONTINUOUS
FINISH WOOD
BATT INSULATION
RIGID INSULATION
BLOCK
PLYWOOD
FACE BRICK
GYP. BD.
COND.
DIA., D.
AMP.,A
APPROX.
BLDG.
ARCH.
INCAND.
DWG.(S)
EQUIP.
B.T.U.
COMP.
J.B.
JCT.
JT.
INSUL.
INT.
HDWE
HYD.
H.&V.
I.D.
G.P.M.
H.C.
HT.
H.M.
HTG.
HR.
H.P.
GR.
GWB
H.B.
GALV.
G.F.E.
GAL.
GL.
GND.
FTG.
FP
FT.
GA.
FVC
EXT.
F.D.
FL.
FIN.
F.H.C.
F.E.C.
F.E.
EXIST.
F.C.
F.B.C.
F.A.
EXP.
E.J.
E.W.C.
EXH.
EA.
EQ
ELEV
E.F.
E.C.
BM.
DN.
E
D.S.
DR.
DIFF.
D.J.
DIST.
DIM.
DISC.
CT
DET
CU
C.T.B.
CONN.
CJ
CONT.
CONC.
CL
C.M.U.
CPT
C.O.
CLG.
COL.
C.F.M.
C.I.
CIRC.
CKT.
CER.
CAB.
CAP.
C/B
C.D.
C
LC
BAL.
BRG.
B
BD.
BLK.
AN
ALUM.
ALT.
A.C.
ACP
A.F.F.
A.H.U.
A.C.T.
AJ
JUNCTION BOX
JOINT
JUNCTION
INCANDESCENT
INSULATION
INTERIOR
HARDWARE
HYDRANT
INSIDE DIAMETER
HEATING & VENTILATING
WASTE CLEAN OUT
WIDE FLANGE
WINDOW DIMENSION
WATER CLOSET
WEATHERPROOF
WATER GAGEW.G.
WP.
W.C.O.
WD.
W.D.
WF
W.C.
WOOD
GALLONS PER MINUTE
HANDICAP
HOLLOW METAL
HIGH POINT
HEIGHT
HEATING
HOUR
GYPSUM BOARD
GYPSUM WALLBOARD
HOSE BIBB
GRILLE
GOVERNMENT FURNISHED EQUIPMENT
GALVANIZED
GALLON
GLASS
GROUND
FIRE PROOFING
FOOT-FEET
FIRE VALVE CABINET
FOOTING
GAUGE
VENTILATION
VINYL COMPOSITION TILE
VERTICAL EXPANSION JOINT
VERTICAL
VERIFY IN FIELD
VENT THRU ROOFV.T.R.
VERT.
W.
V.I.F.
W/
WATT
WITH
VENT.
V.E.J.
V.C.
VT
V. VOLT
TELEPHONE
TEMPERATURE
THRESHOLD (THRESH)
TYPICAL
UNLESS NOTED OTHERWISE
TOP OF WALL (BEAM)T.O.W.(B)
TYP.
TOIL.
UNO
UR. URINAL
TOILET
THD.
TEMP.
THK.
T
THICK
EXTERIOR
FIRE EXTINGUISHER & CABINET
FIRE EXTINGUISHER & BRACKET
FIRE HOSE CABINET W/ EXTINGUISHER
FLORIDA BUILDING CODE
FLOOR DRAIN
FLOOR
FINISH
FIRE ALARM
FLEXIBLE CONNECTION
EXISTING
ELECTRIC WATER COOLER
EQUIPMENT
EXPANSION
EXPANSION JOINT (EJ)
EXHAUST
ELEVATION
EXHAUST FAN
EMPTY CONDUIT
FLOOR ELEVATION
EACH
EQUAL
SHEETSHT.
STAND PIPE
SPECIFICATIONS
STORAGE
STAINLESS STEEL
STRAIGHT RESILIENT BASE
SUSPENDED
STRUCTURAL
STOR.
SUSP.
STRUC.
STL
SW.
STEEL
SWITCH
SPEC.
SQ. FT.
SP
SS
SRB
REVOLUTION/MINUTE
ROUGH OPENING
SECTION
SUPPLY AIR
SCHEDULE
RAIN WATER LEADER
SERVICE
SUPPLY GRILLE
SUSPENDED ACOUSTICAL TILE
SECT.
SCH.
S.A.T.
SERV.
S.G.
R.P.M.
R.O.
RM.
S.A.
RWL
ROOM
NOT IN CONTRACTN.I.C.
BEAM
COMPRESSER
DOWN
DRAWING (S)
DOWNSPOUT
EAST
DRAIN
DIFFUSER
DUMMY JOINT
DISTRIBUTION
DISCONNECT
DIMENSION
CERAMIC TILE
DIAMETER
CONDENSING UNIT
CERAMIC TILE BASE
DETAIL
CONNECTION
CONTINUOUS
CONDENSATE
CONTROL JOINT
CONCRETE
RETURN AIR GRILLER.A.G.
ROOF DRAIN
RETURN AIR REGISTER
REGISTER
REINFORCING
RECEPTACLE
RECIRCULATING
RETURN GRILLE
REQUIRED
RECP.
REG.
REINF.
REQ.
R.G.
RET. RETURN
R.A.R.
RDY.
RECIRC.
RD.
R.D.
ROUND
READY
QUARTER
QUANTITY
QUARRY TILE
RETURN AIR
PAINTED
PRESSURE TREATED
QUAN.
RAD.
R
R.A.
RADIUS
RADIUS
QTR.
PTD.
QT
P.T.
PAINT
CONCRETE MASONRY UNIT
CLEAR
CLEAN OUT
CARPET
CEILING
COLUMN
CAST IRON
CIRCULATING
CIRCUIT
CERAMIC
CAPACITY
CENTER LINE
CIRCUIT BREAKER
CEILING DIFFUSER
CABINET
CONDUIT
BALANCE
BRITISH THERMAL UNIT
BEARING
PLUMBING
PLYWOOD
PERIMETER
PRECAST CONCRETE
POUNDS/SQUARE INCH
POUNDS/SQUARE INCH GAGE
PNL.
PSTG.
PSI
PER.
PLBG.
PLYW'D
PL.
PC
PLATE
NUMBER
NOT TO SCALE
ON CENTER
OPENING
OPPOSITE
PLASTIC LAMINATE
OVERHEAD
OUTSIDE DIAMETER
PARTITION
OPP.
P. LAM
OPNG.
PART.
O.H.
NO.
NTS
O.D.
O.C.
ARCHITECTURAL
BOTTOM
BOARD
BLOCK
ANODIZED
ALUMINUM
APPROXIMATELY
AIR CONDITIONED
ACOUSTICAL TILE
ACOUSTICAL PANEL
ABOVE FINISH FLOOR
ACOUSTICAL JOINT
AIR HANDLING UNIT
MODIFIED BITUMEN
MOISTURE RESISTANT
MASONRY OPENING
MISCELLANEOUS
MOUNTING
MOUNTED
METAL THRESHOLD
NOT APPLICABLE
MTD.
MTG.
N
N.A.
NORTH
MISC.
MOD.BIT.
MR
M.T.
MO
MIN. MINIMUM
MAINTENANCE
MAXIMUM
MECHANICAL
MAIN DISTRIBUTION PANEL
MOTORM.
M.D.P.
MECH.
MAX.
MAINT.
MTL. METAL
E.W. EACH WAY
ON CENTER EACH WAYO.C.E.W.
AMP.,A
IN.
EL
INCHES
WELDED WIRE FABRIC
WEATHERPROOF
W.W.F.
WP.
VITROUS CLAY
TEL.
SQUARE FEET
PT
PSF
PANEL
BUILDING
AMPERES
ALTERNATE
CUBIC FEET PER MINUTE
POUNDS/SQUARE FOOT
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
CS-2
DOUGLASS
GYMNASIUM -
RENOVATION
INDEX
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
INDEX OF DRAWINGSABBREVIATIONSGENERAL LEGEND
STRUCTURAL
S0.1 S1.1 S1.2 S2.1 S2.2
CS-1
CS-2
LS1.1
COVER SHEET
INDEX SHEET
LIFE SAFETY PLAN
STRUCTURAL NOTES
FOUNDATION PLAN
ROOF FRAMING PLAN
STRUCTURAL DETAILS
STRUCTURAL DETAILS
ARCHITECTURAL
D1.1
A1.1 A3.1 A3.2 A4.1 A5.1 A7.1 A9.1
DEMOLITION PLAN
FLOOR PLAN
BUILDING ELEVATION
PARTIAL BUILDING ELEVATION
BUILDING SECTIONS
WALL SECTIONS & DETAILS
DOOR SCHEDULE & DOOR DETAILS
ROOF PLAN
ELECTRICAL
E1.0
ED2.1
E1.1 E2.1 E5.1 E6.1 E7.1
SITE PLAN - ELECTRICAL
FLOOR PLAN - DEMOLITION - POWER & SYSTEMS
FLOOR PLAN - RENOVATION - LIGHTING
FLOOR PLAN - RENOVATION - POWER & SYSTEMS
DETAILS - ELECTRICAL
RISER DIAGRAMS - ELECTRICAL
PANEL SCHEDULES - ELECTRICAL
MECHANICAL
M0.1
MD1.1
M1.1 M5.1 M7.1
LEGEND & NOTES - HVAC
FLOOR PLAN - DEMOLITION - HVAC
FLOOR PLAN - RENOVATION - HVAC
DETAILS - HVAC
CONTROLS - HVAC
APPLICABLE CODES
OCCUPANCY GROUP:
GROSS FLOOR AREA:
FLOOR AREA:
TOTAL OCCUPANCY LOAD:
CONSTRUCTION TYPE:
TENENT SEPARATION:
FBC-B: CH. 3, SECTION 302
FBC-B: CH. 10 TABLE 1004.5
FBC SECTION 508
FBC GROUP A-3 ASSEMBLEY
15,325 GSF
3,693 GSF - RESTROOM / LOCKER ROOM
9,061 GSF - GYMNASIUM / LOBBY
2,607 GSF - CLASSROOMS
3,693 GSF @ 50 SF/PERSON = 74 PERSONS
9,061 GSF @ 7 SF/PERSON = 1,295 PERSONS
2,607 GSF @ 20 SF/PERSON = 131 PERSONS
TOTAL ALLOWABLE OCCUPANCY = 1,500 PERSONS
TYPE V NON SPRINKLERED
N/A
OCCUPANCY
THE PLANS ARE FOR INFORMATIONAL PURPOSES ONLY. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ALL CONDITIONS. IF THE CONTRACTOR IS UNABLE TO INTERPRET THE CONSTRUCTION DOCUMENTS, HE/SHE IS RESPONSIBLE FOR REQUESTING CLARIFICATION IN WRITING TO THE ARCHITECT. IF THE CONTRACTOR PROCEEDS WITH ANY WORK BEFORE OBTAINING CLARIFICATION, HE/SHE SHALL BE HELD RESPONSIBLE FOR ALL DEFICIENCIES ASSOCIATED THERE.
DIMENSIONS ARE TAKEN FROM THE FACE OF EXISTING NON AND LOAD BEARING INTERIOR WALLS AND FROM THE FACE OF STUD FOR NEW WALLS.
BEFORE SUBMITTING FOR WORK OR BEGINNING WORK, THE CONTRACTOR WILL BE HELD TO HAVE EXAMINED THE PREMISES AND SATISFIED HIMSELF/HERSELF AS TO THE EXISTING CONDITIONS UNDER WHICH HE/SHE WILL BE OBLIGATED AND COMPLETE THE WORK UNDER THE CONTRACT. NO ALLOWANCE WILL BE MADE SUBSEQUENTLY IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERRORS OR NEGLIGENCE ON HIS/HER PART.
CONTRACTOR SHALL ERECT AND MAINTAIN ALL REASONABLE SAFEGUARDS FOR SAFETY AND HEATH INCLUDING POSTING DANGER SIGNS, AND OTHER WARNING AGAINST HAZARDS, AS WELL AS PROMULGATING SAFETY REGULATIONS. CONTRACTOR SHALL PROVIDE SAFETY PRECAUTIONS AND BARRICADES FOR PEDESTRIANS AT
CONSTRUCTION, VEHICLE ACCESS AND EGRESS LOCATIONS.
THE CONTRACTOR SHALL SUBMIT A COMPLETE DETAILED CONSTRUCTION SCHEDULE AND PLAN PRIOR TO THE PRE-CONSTRUCTION CONFERENCE.
CONTRACTOR SHALL BE RESTRICTED TO AREAS SPECIFIED BY OWNER FOR ON SITE STORAGE OF CONSTRUCTION MATERIALS. COMPARTMENT TRAILERS OR SIMILAR PROTECTIVE STORAGE FACILITIES MAY BE UTILIZED ON SITE TO SECURE ALL EQUIPMENT AND ITEMS REMOVED DURING PROJECT WORK. THE CONTRACTOR IS
RESPONSIBLE FOR THE PROTECTION AND SECURITY OF ALL EQUIPMENT AND ITEMS REMOVED.
CONTRACTOR SHALL COORDINATE WITH LOCAL ELECTRICAL POWER AND WATER UTILITY PROVIDERS TO INSTALL NEW SERVICE TO THE SITE PRIOR TO THE START OF
CONSTRUCTION.
ALL WORK SHALL COMPLY WITH APPLICABLE OSHA AND EPA REGULATIONS AND GUIDELINES.
INSTALL WORK IN ACCORDANCE WITH THE CODES LISTED ON THE INDEX SHEET. IMMEDIATELY NOTIFY THE ARCHITECT WHEN CONFLICTS OCCUR BETWEEN CODES AND
BETWEEN THE CONSTRUCTION DOCUMENTS.
CONTRACTOR SHALL FURNISH AS-BUILT DRAWINGS TO THE ARCHITECT AT COMPLETION OF THE CONSTRUCTION. CHANGES SHALL BE INDICATED CLEARLY BY
MECHANICAL DRAFTING METHODS.
CONTRACTOR SHALL MAINTAIN A CLEAN WORK PREMISES AT ALL TIMES AND SHALL CLEAN CONSTRUCTION SITE OF ALL DEBRIS DAILY.
CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE EXISTING SURFACES OUTSIDE THE SCOPE OF WORK AND SHALL BE RESPONSIBLE FOR RETURNING DAMAGED AREAS (MATERIALS, FINISHES, LANDSCAPE, ETC.) TO THEIR ORIGINAL CONDITION. ALL DISTURBED AREAS OF SOIL TO BE SODDED. ALL PLANTING REPLACEMENT TO BE
GUARANTEED FOR ONE YEAR.
CONTRACTOR SHALL ERECT ALL SAFE GUARDS TO PROTECT ADJACENT AREAS. REMOVE DEBRIS FROM JOB SITE DAILY AND ADHERE TO ENVIRONMENTAL REGULATIONS.
WHERE A NOTE IS SHOWN FOR ONE CONDITION IT SHALL APPLY TO ALL SIMILAR AND LIKE CONDITIONS.
CONTRACTOR SHALL PATCH ALL SPALLED AND ROUGH CONCRETE FLOOR SURFACES TO PROVIDE A CONTINUOUS LEVEL CONCRETE SURFACE.
A DISCOVERY OF ASBESTOS: ALL MATERIAL KNOWN TO CONTAIN ASBESTOS & THAT WILL BE IMPACTED BY DEMOLITION & CONSTRUCTION ACTIVITIES INCLUDED IN THE PROJECT SCOPE OF WORK HAVE BEEN REMOVED. IN THE EVENT CONCEALED CONDITIONS ARE ENCOUNTERED, NOTIFY THE ARCHITECT PRIOR TO PROCEEDING FURTHER
WITH WORK.
A KNOX BOX SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING WITHIN 5’ OF THE MAIN ENTRANCE DOOR. MOUNTING HEIGHT TO BE NOT GREATER THAN 5’ AFF.
KEYS TO BUILDING, PHASE I AND PHASE II ELEVATOR RECALL SHALL BE PROVIDED FOR PLACEMENT IN KNOX BOX. REQUIRED DUE TO SPRINKLER CONTROL VALVES AND/OR FIRE ALARM CONTROL PANEL LOCATED IN THIS SPACE OR THE BUILDING IS PROVIDED WITH ELEVATOR RECALL.
A MINIMUM 6” ADDRESS NUMBERS SHALL BE LOCATED ON THE EXTERIOR OF THE BUILDING. NUMBERS TO BE PLAINLY VISIBLE FROM THE STREET OR OTHER ELEVATIONS AND CONTRAST WITH BACKGROUND. THIS MAY BE WAIVED IF ADDRESS NUMERIC IS ILLUMINATED ON A SIGN SEPARATE FROM THE BUILDING THAT IS VISIBLE FROM THE
STREET.
THE ELEVATION OF THE FLOOR SURFACE ON BOTH SIDES OF ANY DOOR SHALL NOT VARY BY MORE THAN 1/2" INCH FOR A DISTANCE NOT LESS THAN THE WIDTH OF THE
WIDEST LEAF. PLEASE SHOW ON PLANS.
CONTRACTOR SHALL MAKE AVAILABLE TO THE BUILDING INSPECTOR DOCUMENTATION NECESSARY TO VERIFY THAT ALL EXTERIOR ENVELOPE COMPONENTS REQUIRING PRODUCT APPROVAL PER FS 553.842 ARE IN COMPLIANCE WITH PRODUCT APPROVAL INSTALLATION REQUIREMENTS
THE FIRE ALARM CONTRACTOR SHALL SUBMIT PLANS FOR EVALUATION AND APPROVAL PRIOR TO COMMENCEMENT OF NEW WORK. FIRE PROTECTION IS NOT PART OF THE
BUILDING PERMIT EVALUATION.
ALL GUARDRAILS SHALL RESIST A CONCENTRATED LOAD OF 250 POUNDS
GRAB BARS MOUNTED SHALL BE DESIGNED TO RESIST A SINGLE CONCENTRATED LOAD OF 250 POUNDS APPLIED IN ANY DIRECTION AT ANY POINT ON THE GRAB BAR.
GENERAL NOTES
EXISTING BUILDING
BUILDING
ACCESSIBILITY
MECHANICAL
ENERGY CONSERVATION
FUEL GAS
PLUMBING
FIRE PREVENTION
ELECTRICAL
FLORIDA EXISTING BUILDING CODE (FBC-EB) 2023, 8TH EDITION
FLORIDA BUILDING CODE (FBC-B) 2023, 8TH EDITION
FLORIDA BUILDING CODE (FBC-A) 2023, 8TH EDITION
FLORIDA BUILDING CODE (FBC-M) 2023, 8TH EDITION
FLORIDA BUILDING CODE (FBC-EC) 2023, 8TH EDITION
FLORIDA BUILDING CODE (FBC-FG) 2023, 8TH EDITION
FLORIDA BUILDING CODE (FBC-P) 2023, 8TH EDITION
FLORIDA FIRE PREVENTION CODE (FFPC) 2023, 8TH EDITION
NATIONAL ELECTRICAL CODE (NFPA 70) 2020 (per 8th Ed. FBC-B)
GAS
G1.1 LEGEND, NOTES, DETAILS, SPECS & FLOOR PLAN - NATURAL GAS
FIRE PROTECTION
FP0.1
FP1.0
FP1.1
FP5.1
LEGEND, NOTES, SCHEDULES - FIRE PROTECTION
SITE PLANS - FIRE PROTECTION
FLOOR PLAN = RENOVATION - FIRE PROTECTION
DETAILS - FIRE PROTECTION
LIFE SAFETY LEGEND
PATH OF EGRESS
EXIT/AREA OF REFUGE LIGHT
EMERGENCY LIGHT
FIRE EXTINGUISHER BRACKET
FIRE ALARM ANNUNCIATOR, HORN/VISIBLE TYPE
FIRE ALARM MANUAL PULL STATION
FIRE ALARM CONTROL PANEL
FEB
F
H
FACP
EM
FACP
E P
E P
BOILER
FD
FD
DF
D F
D F
31' - 4"
31' - 4"
NEW BLACK VINYL COATED
CHAIN LINK FENCE - 6' HIGH
NEW BLACK VINYL COATED
CHAIN LINK FENCE - 6' HIGH
MECHANICAL YARD
MECHANICAL YARD
SIDEWALK
SIDEWALK
LIFT
STATION
AC-2
AC-1
MEETING ROOM
MEETING ROOM
SIDEWALK
SIDEWALK
RAMP
RAMP
PATH OF EGRESS = 87' - 0"
PATH OF EGRESS = 69' - 0"
PATH OF EGRESS = 56' - 0"
BLEACHERS
BLEACHERS
H
H
H F
H F
H F
F
FEB
H
H
FEB
FEB
FEB
FEB
FEB
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
LS1.1
DOUGLASS
GYMNASIUM -
RENOVATION
LIFE SAFETY PLAN
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/8" = 1'-0"LS1.1
LIFE SAFETY PLAN1
REBAR LAP SPLICE LENGTHS
STD. HOOK DIMENSIONS DEVELOP. LENGTHS
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308 Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
DOUGLAS
GYMNASIUM -
RENOVATION
100% CONTRACT
DOCUMENTS
18 JULY 2025
20030 CJB
PMM
KEVER CKEE
ENGINEERING
1624 Metropolitan Blvd., Ste. A Tallahassee, Florida 32308
Office: 850.727.5367 Authorization No. 31293
M
S0.1
STRUCTURAL
NOTES
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308 Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
DOUGLAS
GYMNASIUM -
RENOVATION
100% CONTRACT
DOCUMENTS
18 JULY 2025
20030 CJB
PMM
KEVER CKEE
ENGINEERING
1624 Metropolitan Blvd., Ste. A Tallahassee, Florida 32308
Office: 850.727.5367 Authorization No. 31293
M
S1.1
FOUNDATION
PLAN
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
DOUGLAS
GYMNASIUM -
RENOVATION
100% CONTRACT
DOCUMENTS
18 JULY 2025
20030 CJB
PMM
KEVER CKEE
ENGINEERING
1624 Metropolitan Blvd., Ste. A Tallahassee, Florida 32308
Office: 850.727.5367 Authorization No. 31293
M
S1.2
ROOF FRAMING
PLAN
XXXXXXXX
X
X
X X X X
X X X X X X
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308 Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
DOUGLAS
GYMNASIUM -
RENOVATION
100% CONTRACT
DOCUMENTS
18 JULY 2025
20030 CJB
PMM
KEVER CKEE
ENGINEERING
1624 Metropolitan Blvd., Ste. A Tallahassee, Florida 32308
Office: 850.727.5367 Authorization No. 31293
M
S2.1
DETAILS
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
DOUGLAS
GYMNASIUM -
RENOVATION
100% CONTRACT
DOCUMENTS
18 JULY 2025
20030 CJB
PMM
KEVER CKEE
ENGINEERING
1624 Metropolitan Blvd., Ste. A Tallahassee, Florida 32308
Office: 850.727.5367 Authorization No. 31293
M
S2.2
DETAILS
DEMOLITION LEGEND
EXISTING WALL TO REMAIN
EXISTING TO BE REMOVED
ELEMENTS THAT ARE DASHED ARE TO BE REMOVED FROM THE PROJECT.
SITE WORK - IF APPLICABLE, PROTECT AS NECESSARY ANY EXISTING VEGETATION, TREES
OR THE LIKE IMMEDIATELY ADJACENT TO THE LIMITS OF THE ALTERATION WORK WHICH
ARE INDICATED ON THE DRAWINGS TO REMAIN, OR IN ANY CASE ARE NOT SPECIFIED OR
DIRECTED TO BE REMOVED.
MASONRY - IN TOOTHING OR CUTTING BACK FOR JOINERY TO OR CONTINUING AN
EXISTING MASONRY SURFACE, EXERCISE CARE SO AS NOT TO WEAKEN STRUCTURALLY
THAT PORTION OF THE STRUCTURE WHICH IS TO REMAIN.
STRUCTURAL STEEL AND CARPENTRY - IN THE COURSE OF ALTERATION WORK SHOULD
THE CONTRACTOR ENCOUNTER, IN EXPOSING FORMERLY COVERED FRAMING, ANY
UNFORESEEN STRUCTURAL DEFECT WHICH MIGHT JEOPARDIZE ANY PART OF THE
EXISTING BUILDING OR THE NEW WORK, THE CONTRACTOR SHALL SHORE UP OR
OTHERWISE SUPPORT THE EXPOSED DEFECT FOR EASE OF INSPECTION BY OWNER'S
REPRESENTATIVE OR ARCHITECT WHO WILL DIRECT FURTHER REPAIR.
TEMPORARY SHORING: IF APPLICABLE, PROVIDE ANY TEMPORARY SHORING, CRIBBING
OR UNDERPINNING AS MAY BE REQUIRED OR DIRECTED BY THE ARCHITECT AT ANY TIME
AND IN ANY PORTION OF THE ALTERATION WORK FOR THE DURATION OF SUCH WORK.
PAINTING - ANY PITTED, CHIPPED, FLAKED, OVERLY THICKENED OR OTHERWISE DAMAGED
EXISTING PAINT SURFACES ENCOUNTERED SHALL BE SANDED, CHIPPED OR OTHERWISE
REMOVED DOWN TO ORIGINAL SURFACE AND REPAIRED. DO NOT SANDBLAST, OR USE
POWER SANDER OR GRINDER.
DEMOLITION WORK - WITH THE EXCEPTION OF ANY SALVABLE ITEMS, AS DIRECTED TO BE
RETAINED BY OWNER, ALL REMOVED STRUCTURES AND MATERIALS SHALL BECOME THE
PROPERTY OF THE CONTRACTOR WHO SHALL PROMPTLY REMOVE THEM FROM THE
PREMISES. NO SUCH ITEMS SHALL BE STORED OR ACCUMULATED ON THE PREMISES.
SALVAGE - ALL ITEMS DEEMED SALVABLE BY OWNER WILL EITHER HAVE BEEN INDICATED
ON THE DRAWINGS, REMOVED PRIOR TO START OF ALTERATION WORK, OR WILL BE
DIRECTED BY OWNER TO BE STORED BY THE CONTRACTOR AND SHALL REMAIN THE
PROPERTY OF THE OWNER. ANY ITEMS TO BE RELOCATED WILL HAVE BEEN INDICATED
ON THE DRAWINGS.
NOTE: THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL VERIFY ALL DIMENSIONS
AND CONDITIONS AT THE SITE BEFORE BID AND PRIOR TO BEGINNING WORK. IF ANY
DISCREPANCIES ARE DISCOVERED NOTIFY THE ARCHITECT.
SEQUENCE OF ALTERATION WORK: IN THE EVENT THAT ANY SPECIAL SEQUENCING OF
THE WORK IS REQUIRED BY OWNER, THE CONTRACTOR SHALL ARRANGE A CONFERENCE
WITH THE OWNER FOR THE PURPOSE OF ESTABLISHING ANY SPECIAL SCHEDULING
BEFORE ANY SUCH WORK IS BEGUN.
PROTECTIONS: PROVIDE ANY SPECIAL BARRICADING AND MAINTAIN ANY REQUIRED
LIGHTS, WARNING AND DIRECTIONAL SIGNS AND OTHER PROTECTIONS NEAR AND ABOUT
THE SITE OF ALTERATION WORK AS MAY BE REQUIRED BY LOCAL AUTHORITIES HAVING
JURISDICTION. BY ANY NECESSARY MEANS PROTECT ANY SURROUNDING ADJACENT
SITES, STRUCTURES, PROPERTIES AND UTILITIES. MAINTAIN ALL SAFETY MEASURES
UNTIL REMOVAL IS DIRECTED BY OWNER'S REPRESENTATIVE OR ARCHITECT. INDEFINITE
UNDERGROUND UTILITIES OR OTHER SERVICES AS MAY BE UNCOVERED SHALL NOT BE
DISTURBED BUT BROUGHT TO THE ARCHITECT'S ATTENTION FOR DIRECTION AS TO HOW
TO PROCEED.
ADDITIONAL TEMPORARY FACILITIES: ANY ADDITIONAL TEMPORARY FACILITIES OR
SERVICES AS MAY BE REQUIRED BY ANY SPECIAL NECESSITIES OF ALTERATION WORK
SHALL BE PROVIDED BY THE CONTRACTOR OUTSIDE OF HOUSE DURING ALL HOURS SUCH
WORK IS IN PROGRESS. PROVIDE PORTABLE TOILET FACILITIES OUTSIDE AS REQUIRED.
SPECIAL PERMITS: SECURE ANY AND ALL PERMITS TO DEMOLISH AND REHABILITATION AS
MAY BE REQUIRED BY LOCAL AUTHORITIES HAVING JURISDICTION OVER SUCH WORK.
DEMOLITION NOTES:
FAP
E P
E P
BOILER
FD
FD
DF
D F
D F
REMOVE EXISTING
LOUVER AND
ENLARGE OPENING
FOR NEW DOOR
REMOVE EXISTING
LOUVER AND
ENLARGE OPENING
FOR NEW DOOR
SIDEWALK
SIDEWALK
LIFT
STATION
CUT CMU PROTRUSIONS TO
BE FLUSH WILL WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
CUT CMU PROTRUSIONS TO
BE FLUSH WILL WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
REMOVE EXISTING
LOUVER AND PREP
FOR NEW HVAC EQUIP.
REMOVE EXISTING
LOUVER AND PREP
FOR NEW HVAC EQUIP.
REMOVE EXISTING
LOUVER AND PREP
FOR CMU INFILL
REMOVE EXISTING
LOUVER AND PREP
FOR CMU INFILL
REMOVE EXISTING
LOUVER AND PREP
FOR NEW HVAC
RETURN DUCT
REMOVE EXISTING
LOUVER AND PREP
FOR NEW HVAC
RETURN DUCT
SAW CUT EXISTING
CMU AS REQ'D FOR
NEW HVAC SUPPLY
DUCT
SAW CUT EXISTING
CMU AS REQ'D FOR
NEW HVAC SUPPLY
DUCT
REMOVE EXISTING
LOUVER AND PREP
FOR CMU INFILL
REMOVE EXISTING
LOUVER AND PREP
FOR CMU INFILL
SIDEWALK
SIDEWALK
RAMP
RAMP
PREP AREA FOR NEW
CONSTRUCTION -
EXCAVATE 4" OF
EXISTING EARTH
PREP AREA FOR NEW
CONSTRUCTION -
EXCAVATE 4" OF
EXISTING EARTH
REMOVE EXISTING
INSULATION FROM
UPPER PORTION
OF WALL (ABOVE
CMU) - PREP FOR
SPRAY FOAM
INSTALLATION -
TYP. THIS WALL
REMOVE EXISTING
INSULATION FROM
UPPER PORTION
OF WALL (ABOVE
CMU) - PREP FOR
SPRAY FOAM
INSTALLATION -
TYP. THIS WALL
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
D1.1
DOUGLASS
GYMNASIUM -
RENOVATION
DEMOLITION PLAN
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/8" = 1'-0"D1.1
DEMOLITION PLAN1
FLOOR PLAN LEGEND
EXISTING TO REMAIN
NEW CMU WALL PARTITION OR CMU INFILL
Name
ROOM NAME AND NUMBER
DOOR NUMBER
INTERIOR WINDOW (LETTER DENOTES TYPE)
P-1 WALL PARTITION TYPE
1iA
90 MIN
FIRE RATING
SPOT ELEVATION
A3.1
A3.1 3
A3.1
FAP
E P
E P
BOILER
FD
FD
DF
D F
D F
31' - 4" 30' - 9" - FENCE
31' - 4" 30' - 9" - FENCE
LOCATE NEW DOOR AT
EXISTING LOUVER
OPENING
PAINT BEIGE TO MATCH EXISTING
LOCATE NEW DOOR AT
EXISTING LOUVER
OPENING
PAINT BEIGE TO MATCH EXISTING
A4.1
A4.1
NEW BLACK VINYL COATED
CHAIN LINK FENCE W/
(2) 48" WIDE GATES - 6' HIGH
NEW BLACK VINYL COATED
CHAIN LINK FENCE W/
(2) 48" WIDE GATES - 6' HIGH
MECHANICAL YARD
MECHANICAL YARD
SIDEWALK
SIDEWALK
SIDEWALK
SIDEWALK
LIFT
STATION
CUT CMU PROTRUSIONS TO
BE FLUSH WILL WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
PROVIDE CONCRETE SLAB
AT SAME ELEVTION AS GYM
A3.21A3.2 2
PROVIDE CONCRETE SLAB
AT SAME ELEVTION AS GYM
CUT CMU PROTRUSIONS TO
BE FLUSH WILL WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
INFILL LOUVER OPENING
W/ CMU (SEE 3/A7.1)
PAINT WHITE TO MATCH
INFILL LOUVER OPENING
W/ CMU (SEE 3/A7.1)
PAINT WHITE TO MATCH
A3.21
O P
P
A3.2 2
O P
P
INFILL LOUVER OPENING
W/ CMU (SEE 3/A7.1)
PAINT WHITE TO MATCH
INFILL LOUVER OPENING
W/ CMU (SEE 3/A7.1)
PAINT WHITE TO MATCH
AC-2
AC-1
MEETING ROOM
MEETING ROOM
A5.1
RAMP
RAMP
FEB
PROVIDE ALUMINUM COLLAR (INTERIOR &
EXTERIOR) AT THE UPPER AND LOWER
HVAC DUCT
PROVIDE ALUMINUM COLLAR (INTERIOR &
EXTERIOR) AT THE UPPER AND LOWER
HVAC DUCT
FEB
FEB
FEB
FEB
FEB
4" NEW #57 GRAVEL GROUND COVER
OVER WEED FABRIC W/ 1/8" x 6" TALL
METAL EDGING AT FENCE LINE
4" NEW #57 GRAVEL GROUND COVER
OVER WEED FABRIC W/ 1/8" x 6" TALL
METAL EDGING AT FENCE LINE
P -1P -1
P -1
P -1P -1
P -1
A A
A A
PAINT WALLS TO MATCH EXISTING
AS NOTED ON A5.1
PAINT WALLS TO MATCH EXISTING
AS NOTED ON A5.1
PROVIDE WOOD FRAMING
W/ CEMENTITIOUS SOFFIT -
PAINT TO MATCH EXTERIOR
AND PROVIDE SEALANT
AT EDGES & JOINTS -
SEE 4/A5.1
GROUT FILL OPENINGS -
PAINT TO MATCH EXTERIOR
SEE 5/A5.1
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A1.1
DOUGLASS
GYMNASIUM -
RENOVATION
FLOOR PLAN
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/8" = 1'-0"A1.1
FLOOR PLAN1
GENERAL NOTE:
ALL PAINT TO MATCH ECISTING
CONDITIONS IN LOCATIONS NOTED
ON FLOOR PLAN
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
A4.1
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
A3.2
AC-1
NEW METAL ROOF: BASIS OF DESIGN - 36" PRO-RIB
CONTRACTOR TO MATCH EXISTING METAL ROOF
COLOR AND PROFILE. PROVIDE NEW 60 MIL. PEEL AND
STICK WATER-PROOFING ON 5/8" DENSGLASS GOLD
EXTERIOR SHEATHING, RIGID INSULATION (R-25 MIN.)
AND METAL ROOF DECK
NEW CMU WALL - PAINTED TO MATCH EXISTING
PROVIDE ALUMINUM COLLAR
(INTERIOR & EXTERIOR) AT THE
UPPER AND LOWER HVAC DUCT
NEW BLACK VINYL COATED
CHAIN LINK FENCE W/
(2) 48" WIDE GATES - 6' HIGH
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
A4.1
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
AC-2
NEW METAL ROOF: BASIS OF DESIGN - 36" PRO-RIB
CONTRACTOR TO MATCH EXISTING METAL ROOF
COLOR AND PROFILE. PROVIDE NEW 60 MIL. PEEL AND
STICK WATER-PROOFING ON 5/8" DENSGLASS GOLD
EXTERIOR SHEATHING, RIGID INSULATION (R-25 MIN.)
AND METAL ROOF DECK
NEW CMU WALL - PAINTED TO MATCH EXISTING
PROVIDE ALUMINUM COLLAR
(INTERIOR & EXTERIOR) AT THE
UPPER AND LOWER HVAC DUCT
NEW BLACK VINYL COATED
CHAIN LINK FENCE W/
(2) 48" WIDE GATES - 6' HIGH
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
A4.1
A5.1
NEW METAL ROOF: BASIS OF DESIGN - 36" PRO-RIB
CONTRACTOR TO MATCH EXISTING METAL ROOF
COLOR AND PROFILE. PROVIDE NEW 60 MIL. PEEL AND
STICK WATER-PROOFING ON 5/8" DENSGLASS GOLD
EXTERIOR SHEATHING, RIGID INSULATION (R-25 MIN.)
AND METAL ROOF DECK
NEW CMU WALL - PAINTED TO MATCH EXISTING
NEW CASEMENT WINDOW
NEW METAL ROOF: BASIS OF DESIGN - 36" PRO-RIB
CONTRACTOR TO MATCH EXISTING METAL ROOF
COLOR AND PROFILE. PROVIDE NEW 60 MIL. PEEL AND
STICK WATER-PROOFING ON 5/8" DENSGLASS GOLD
EXTERIOR SHEATHING, RIGID INSULATION (R-25 MIN.)
AND METAL ROOF DECK
NEW CMU WALL - PAINTED
NEW CASEMENT WINDOW AA
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A3.1
DOUGLASS
GYMNASIUM -
RENOVATION
BUILDING
ELEVATIONS
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/8" = 1'-0"A3.1
North1
1/8" = 1'-0"A3.1
South2
1/8" = 1'-0"A3.1
West3
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
HVAC
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE (TYP.)
NEW METAL ROOF: BASIS OF DESIGN - 36"
PRO-RIB CONTRACTOR TO MATCH EXISTING
METAL ROOF COLOR AND PROFILE. PROVIDE
NEW 60 MIL. PEEL AND STICK
WATERPROOFING ON 5/8" DENSGLASS GOLD
EXTERIOR SHEATHING, RIGID INSULATION
(R-25 MIN.) AND METAL ROOF DECK
MODIFY EXISTING DOWN-
SPOUT SO THAT IT ENDS
LESS THAN 6" ABOVE THE
ROOF OF THE ADDITION
A5.1
A
FENCE
8"
NEW CMU WALL - PAINTED TO MATCH
EXISTING
NEW BLACK VINYL COATED
CHAIN LINK FENCE W/
(2) 48" WIDE GATES - 6' HIGH
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE (TYP.)
NEW METAL ROOF: BASIS OF DESIGN - 36"
PRO-RIB CONTRACTOR TO MATCH
EXISTING METAL ROOF COLOR AND
PROFILE. PROVIDE NEW 60 MIL. PEEL AND
STICK WATERPROOFING ON 5/8"
DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25
MIN.) AND METAL ROOF DECK
MODIFY EXISTING DOWN-
SPOUT SO THAT IT ENDS
LESS THAN 6" ABOVE THE
ROOF OF THE ADDITION
ANEW CMU WALL - PAINTED TO MATCH
EXISTING
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
A4.1
HVAC UNIT
CUT CMU PROTRUSIONS TO
BE FLUSH WITH WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE (TYP.)
NEW METAL ROOF: BASIS OF DESIGN - 36"
PRO-RIB CONTRACTOR TO MATCH EXISTING
METAL ROOF COLOR AND PROFILE. PROVIDE
NEW 60 MIL. PEEL AND STICK
WATERPROOFING ON 5/8" DENSGLASS GOLD
EXTERIOR SHEATHING, RIGID INSULATION (R-25
MIN.) AND METAL ROOF DECK
NEW CMU WALL - PAINTED
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A3.2
DOUGLASS
GYMNASIUM -
RENOVATION
PARTIAL BUILDING
ELEVATIONS
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/4" = 1'-0"A3.2
ELEVATION OF ADDITION1
1/4" = 1'-0"A3.2
ELEVATION OF ADDITION2
1/4" = 1'-0"A3.2
ELEVATION OF ADDITION3
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
2' - 8" 4' - 0"
2' - 8"4' - 0"
NEW METAL ROOF: BASIS OF DESIGN - 36" PRO-RIB
CONTRACTOR TO MATCH EXISTING METAL ROOF COLOR
AND PROFILE. PROVIDE NEW 60 MIL. PEEL AND STICK
WATER-PROOFING ON 5/8" DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25 MIN.) AND METAL
ROOF DECK
EXISTING WOOD
BACKETBALL
COURT -
TO REMAIN
EXISTING CONC.
SLAB - TO REMAIN
NEW CONC. SLAB - SEE STRUCTURAL DWGS
EXISTING BLEACHERS -
TO REMAIN (TYP.)
A4.1
CUT CMU PROTRUSIONS TO BE FLUSH WILL WALL
BETWEEN 9' - 4" AND 11' - 4" TO ELIMINATE NEW ROOF
INTERFERENCE
HVACHVAC
A5.1
A5.1
REINFORCE CELLS PER
STRUCTURAL DWGS.
REINFORCE CELLS PER
STRUCTURAL DWGS.
NEW METAL ROOF: BASIS OF DESIGN - 36" PRO-RIB
CONTRACTOR TO MATCH EXISTING METAL ROOF COLOR
AND PROFILE. PROVIDE NEW 60 MIL. PEEL AND STICK
WATER-PROOFING ON 5/8" DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25 MIN.) AND METAL
ROOF DECK
NEW CONC. SLAB - SEE STRUCTURAL DWGS
CUT CMU PROTRUSIONS TO BE FLUSH WILL WALL
BETWEEN 9' - 4" AND 11' - 4" TO ELIMINATE NEW ROOF
INTERFERENCE
A5.1
PROVIDE CLOSED CELL SPRAY FOAM INSULATION ON
EXISTING EXTERIOR WALL (ABOVE CMU) W/ A SMOOTH
SURFACE (GRID SHADED AREA) - ALL SIDES OF THE
BUILDING ABOVE EXISTING CMU WALL
PAINT TO MATCH EXISTING WALL COLOR
PROVIDE CLOSED CELL SPRAY FOAM INSULATION ON
EXISTING EXTERIOR WALL (ABOVE CMU) W/ A SMOOTH
SURFACE (GRID SHADED AREA) - ALL SIDES OF THE
BUILDING ABOVE EXISTING CMU WALL
PROVIDE CLOSED CELL SPRAY FOAM INSULATION ON
EXISTING EXTERIOR WALL (ABOVE CMU) W/ A SMOOTH
SURFACE (GRID SHADED AREA) - ALL SIDES OF THE
BUILDING ABOVE EXISTING CMU WALL
CMU INFILLCMU INFILL
NEW HVAC DUCTS - PAINTED TO MATCH GREEN FROM
COURT FLOOR (TYP.)
A A
PROVIDE ALUMINUM COLLAR (INTERIOR & EXTERIOR) AT
THE UPPER AND LOWER HVAC DUCT
PROVIDE ALUMINUM COLLAR (INTERIOR & EXTERIOR) AT
THE UPPER AND LOWER HVAC DUCT
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
LEVEL 3
22' - 0"
A4.1
PROVIDE SOFFIT INFILL WHERE
ABANDONED BARN DOOR TRACKS
ARE LOCATED
REMOVE EXISTING HVAC LOUVER &
PROVIDE NEW CMU INFILL
REMOVE EXISTING HVAC LOUVER
FOR NEW HVAC DUCT
PAINTED TO MATCH EXISTING WALL
COLOR
REMOVE EXISTING HVAC LOUVER
FOR NEW HVAC DUCT
PAINTED TO MATCH EXISTING
WALL COLOR
REMOVE EXISTING HVAC LOUVER &
PROVIDE NEW CMU INFILL
SAW CUT OPENING FOR
NEW HVAC DUCT - COORDINATE W/
MEP DWGS. PROVIDE ALUMINUM
COLLAR (INTERIOR & EXTERIOR) AT
THE UPPER AND LOWER HVAC
DUCT
LOCATE NEW DOOR AT EXISTING
LOUVER OPENING
PAINT DOOR AND FRAME TO MATCH
EXISTING
BLEACHERS NOT SHOWN
PROVIDE CLOSED CELL SPRAY FOAM INSULATION ON
EXISTING EXTERIOR WALL (ABOVE CMU) W/ A SMOOTH
SURFACE (GRID SHADED AREA) - ALL SIDES OF THE
BUILDING ABOVE EXISTING CMU WALL
PROVIDE CLOSED CELL SPRAY FOAM INSULATION ON
EXISTING EXTERIOR WALL (ABOVE CMU) W/ A SMOOTH
SURFACE (GRID SHADED AREA) - ALL SIDES OF THE
BUILDING ABOVE EXISTING CMU WALL
PAINTED TO MATCH EXISTING WALL COLOR
PROVIDE CLOSED CELL SPRAY FOAM INSULATION ON
EXISTING EXTERIOR WALL (ABOVE CMU) W/ A SMOOTH
SURFACE (GRID SHADED AREA) - ALL SIDES OF THE
BUILDING ABOVE EXISTING CMU WALL
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A4.1
DOUGLASS
GYMNASIUM -
RENOVATION
BUILDING SECTIONS
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/8" = 1'-0"A4.1
BUILDING SECTION THRU CLASSROOM ADDITIONS - TYP. NORTH & SOUTH1
1/8" = 1'-0"A4.1
LONGITUDINAL BUILDING SECTION - TYP. EAST & WEST2
NEW METAL ROOF: BASIS OF DESIGN -
36" PRO-RIB CONTRACTOR TO MATCH
EXISTING METAL ROOF COLOR AND
PROFILE. PROVIDE NEW 60 MIL. PEEL
AND STICK WATER-PROOFING ON 5/8"
DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25
MIN.) AND METAL ROOF DECK
NEW CONC. SLAB ON 10 MIL.
VAPOR BARRIER - SEE STRUCTURAL
DWGS.
NEW CASEMENT WINDOW
NEW CMU WALL - PAINTED TO MATCH
EXISTING
CMU LINTEL PER STRUCTURAL DWGS.
M A
T C
H E
X
IS
T
P A
IN
T
G R
A Y
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
W H
IT
E
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
B E
IG
E
ROOF BAR JOIST PER STRUCTURAL
DWGS.
NEW CMU WALL - PAINTED
NEW BREAK METAL FASCIA - WRAP
EDGE OF ROOF MATERIAL OVER EDGE
PAINT GREEN TO MATCH
NEW BREAK METAL SOFFIT - WRAP
EDGE OF FASCIA OVER SOFFIT
NEW MARBLE WINDOW SILL
PAINT UNDERSIDE OF METAL DECK &
BAR JOISTS
GRADE
LEVEL 1
0' - 0"
LEVEL 2
10' - 0"
REINFORCE CELLS PER
STRUCTURAL DWGS.
NEW METAL ROOF: BASIS OF DESIGN - 36"
PRO-RIB CONTRACTOR TO MATCH EXISTING
METAL ROOF COLOR AND PROFILE.
PROVIDE NEW 60 MIL. PEEL AND STICK
WATER-PROOFING ON 5/8" DENSGLASS
GOLD EXTERIOR SHEATHING, RIGID
INSULATION (R-25 MIN.) AND METAL ROOF
DECK
CUT CMU PROTRUSIONS TO BE FLUSH WILL
WALL BETWEEN 9' - 4" AND 11' - 4" TO
ELIMINATE NEW ROOF INTERFERENCE
ROOF BAR JOIST PER STRUCTURAL
DWGS.
FLASHING & COUNTER FLASHING - PROVIDE
CLOSURE STRIPS AND SEALANT IN
ACCORDANCE W/ MFG. STANDARD DETAILS
EXISTING CONC. SLAB - FOOTING
AND THICKNESS MAY VARY
NEW CONC. SLAB ON 10 MIL
VAPOR BARRIER - SEE
STRUCTURAL DWGS.
NEW CMU WALL - PAINTED
EXISTING CMU WALL - PAINTED
PAINT UNDERSIDE OF METAL DECK &
BAR JOISTS
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
G R
A Y
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
W H
IT
E
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
B E
IG
E
NEW METAL ROOF: BASIS OF DESIGN -
36" PRO-RIB CONTRACTOR TO MATCH
EXISTING METAL ROOF COLOR AND
PROFILE. PROVIDE NEW 60 MIL. PEEL
AND STICK WATER-PROOFING ON 5/8"
DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25
MIN.) AND METAL ROOF DECK
NEW CONC. SLAB ON 10 MIL.
VAPOR BARRIER - SEE STRUCTURAL
DWGS.
NEW CMU WALL - PAINTED
REINFORCE CMU WALL PER
STRUCTURAL DWGS.
NEW CMU WALL - PAINTED
NEW BREAK METAL FASCIA - WRAP
EDGE OF ROOF MATERIAL OVER EDGE
PAINT GREEN TO MATCH
NEW BREAK METAL SOFFIT - WRAP
EDGE OF FASCIA OVER SOFFIT
PAINT UNDERSIDE OF METAL DECK &
BAR JOISTS
PAINT GRAY TO MATCH EXISTING
CONDITIONS
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
G R
A Y
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
B E
IG
E
M A
T C
H E
X
IS
T
IN
G
P A
IN
T
W H
IT
E
GRADE
PROVIDE NEW P.T. WOOD BLOCKING
ALONG EACH EDGE AND ATTACH
CEMENTITIOUS SOFFIT - PROVIDE
SEALANT & PAINT TO MATCH
EXISTING EXTERIOR
EXISTING OVERHEAD TRACKS -
TO REMAIN, IF POSSIBLE
EXISTING EXTERIOR WALL
EXISTING HEADER
FILL CAVITY W/ CLOSED CELL
SPRAY FOAM INSULATION FIELD VERIFY
1' - 0"
PROVIDE NEW P.T. WOOD BLOCKING
ALONG EACH EDGE AND ATTACH
CEMENTITIOUS SOFFIT - PROVIDE
SEALANT & PAINT TO MATCH
EXISTING EXTERIOR
GROUT FILL OPENINGS -
PAINT TO MATCH EXTERIOR
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A5.1
DOUGLASS
GYMNASIUM -
RENOVATION
WALL SECTIONS &
DETAILS
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1" = 1'-0"A5.1
WALL SECTION THRU CLASSROOM ADDITIONS2
1" = 1'-0"A5.1
WALL SECTION THRU CLASSROOM ADDITIONS3
1" = 1'-0"A5.1
PARTITION - P - 11
1" = 1'-0"A5.1
SOFFIT REPAIR4
1" = 1'-0"A5.1
GROUT INFILL5
EXISTING 8" CMU WALL - SEE
STRUCT. DWGS FOR REQ'D
REINFORCING
CONT. SEALANT
(TYP. BOTH SIDES)
H.M. FRAME - GROUT
FILLED
SAW CUT OPENING - NOTCH
HEAD AS REQ'D FOR NEW DOOR
FRAME & GROUT FILL
5 3/4"
CONT. SEALANT -
(TYP. BOTH SIDES)
H.M. FRAME - GROUT FILLED,
WITH MIN. 3 WALL ANCHORS
PER JAMB
5 3/4"
EXISTING 8" CMU WALL - SEE
STRUCT. DWGS FOR REQ'D
REINFORCING
SAW CUT OPENING - GROUT FILL
CMU CELLS
2"
SCHEDULE
SEE DOOR 2"
4" S
E E
D O
O R
S C
H E
D U
LE
HM1
HOLLOW METAL
DOOR FRAME TYPES
F - HM
FLUSH - HOLLOW METAL
DOOR TYPES
S E
E D
O O
R S
C H
E D
U
LE
SCHEDULE
SEE DOOR
CONT. SEALANT -
(TYP. BOTH SIDES)
EXISTING 8" CMU WALL
GROUT FILL EXISTING CMU CELL &
PROVIDE #5 REBAR @ 16" VERT.
W/ 6" EMBEDMENT
NEW 8" CMU INFILL
GROUT FILL NEW CMU CELL &
PROVIDE #5 REBAR @ 16" VERT.
W/ 6" EMBEDMENT
DOOR SCHEDULE
DOOR
NO. WIDTH HEIGHT THICKNESS
DOOR
TYPE
DOOR
FINISH
FRAME
TYPE
FRAME
FINISH
HDWR
SET
HEAD
DETAIL
JAMB
DETAIL REMARKS
101 3' - 0" 7' - 0" 0' - 1 3/4" F - HM PAINT HM1 PAINT OFFICE 1/A7.1 2/A7.1
102 3' - 0" 7' - 0" 0' - 1 3/4" F - HM PAINT HM1 PAINT OFFICE 1/A7.1 2/A7.1
1 1/2" = 1'-0"A7.1
CMU - HEAD1
1 1/2" = 1'-0"A7.1
CMU - JAMB2
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A7.1
DOUGLASS
GYMNASIUM -
RENOVATION
DOOR SCHEDULE &
DOOR DETAILS
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1 1/2" = 1'-0"A7.1
CMU - INFILL - TYP.3
DOOR 101:
- F-HM: PROVIDE 36" x 80", FLUSH GALVANIZED STEEL, FACTORY APPLIED PRIMER
- HM1 - PROVIDE 2" GALVANIZED STEEL HOLLOW METAL FRAME, FACTORY APPLIED PRIMER
- HINGES: PROVIDE (3) BALL BEARING HINGES - 4.5" x 4.5" STAINLESS STEEL
- LEVER HARDWARE: PROVIDE SCHLAGE ND- SERIES (NE70PD RHO OR SIM.) CLASSROOM FUNCTION
- SILENCERS: PROVIDE SCHLAGE 200 SERIES SILENCER SET (3 PER DOOR)
- DOOR CLOSER: PROVIDE SCHLAGE 700 SERIES (LCN 4040XP AS ALTERNATE) - INTERIOR MOUNTING
- DOOR STOP: PROVIDE SCHLAGE 70 SERIES - WALL MOUNTED
- KICK PLATE: PROVIDE SCHLAGE 95 SERIES (10" HIGH, STAINLESS STEEL)
- THRESHOLD / SWEEP: PROVIDE SCHLAGE - AS NEEDED FOR ACOUSTICS & WEATHER
- DOOR & FRAME PAINT: AS SCHEDULED
DOOR 102:
- F-HM: PROVIDE 36" x 80", FLUSH GALVANIZED STEEL, FACTORY APPLIED PRIMER
- HM1 - PROVIDE 2" GALVANIZED STEEL HOLLOW METAL FRAME, FACTORY APPLIED PRIMER
- HINGES: PROVIDE (3) BALL BEARING HINGES - 4.5" x 4.5" STAINLESS STEEL
- LEVER HARDWARE: PROVIDE SCHLAGE ND- SERIES (NE70PD RHO OR SIM.) CLASSROOM FUNCTION
- SILENCERS: PROVIDE SCHLAGE 200 SERIES SILENCER SET (3 PER DOOR)
- DOOR CLOSER: PROVIDE SCHLAGE 700 SERIES (LCN 4040XP AS ALTERNATE) - INTERIOR MOUNTING
- DOOR STOP: PROVIDE SCHLAGE 70 SERIES - WALL MOUNTED
- KICK PLATE: PROVIDE SCHLAGE 95 SERIES (10" HIGH, STAINLESS STEEL)
- THRESHOLD / SWEEP: PROVIDE SCHLAGE - AS NEEDED FOR ACOUSTICS & WEATHER
- DOOR & FRAME PAINT: AS SCHEDULED
A3.1
A3.1 3
A3.1
A4.1
EXISTING METAL ROOF -
TO REMAIN
EXISTING METAL ROOF -
TO REMAIN
EXISTING METAL ROOF -
TO REMAIN
EXISTING METAL ROOF -
TO REMAIN
EXISTING BARREL ROOF -
TO REMAIN
A4.1
A3.21A3.2 2
CUT CMU PROTRUSIONS TO
BE FLUSH WILL WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
CUT CMU PROTRUSIONS TO
BE FLUSH WILL WALL BETWEEN
9' - 4" AND 11' - 4" TO ELIMINATE
NEW ROOF INTERFERENCE
A5.1
NEW METAL ROOF: BASIS OF DESIGN -
36" PRO-RIB CONTRACTOR TO MATCH
EXISTING METAL ROOF COLOR AND
PROFILE. PROVIDE NEW 60 MIL. PEEL
AND STICK WATER-PROOFING ON 5/8"
DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25
MIN.) AND METAL ROOF DECK -
NEW CLASSROOM ADDITIONS ONLY
NEW METAL ROOF: BASIS OF DESIGN -
36" PRO-RIB CONTRACTOR TO MATCH
EXISTING METAL ROOF COLOR AND
PROFILE. PROVIDE NEW 60 MIL. PEEL
AND STICK WATER-PROOFING ON 5/8"
DENSGLASS GOLD EXTERIOR
SHEATHING, RIGID INSULATION (R-25
MIN.) AND METAL ROOF DECK -
NEW CLASSROOM ADDITIONS ONLY
EXISTING METAL ROOF -
TO REMAIN
EXISTING METAL ROOF -
TO REMAIN
SIDEWALK
SIDEWALK
RAMP
RAMP
Copyright Barnett Fronczak Barlowe & Shuler, Architects. All rights Reserved 2074 Centre Pointe Blvd, Suite #200, Tallahassee, FL 32308
Phone 850 224-6301 Fax 850 561-6978
Tallahassee Florida
Revisions
Date
Project Code
Drawn By:
Checked By:
NOTES
A9.1
DOUGLASS
GYMNASIUM -
RENOVATION
ROOF PLAN
100 % CONTACT
DOCUMENTS
18 JULY 2025
20030 jh2
DS
1/8" = 1'-0"A9.1
ROOF PLAN1
ABBREVIATIONS &
SYMBOLS
AC AIR CONDITIONER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFR ABOVE FINISHED ROOF
AFD ADJUSTABLE FREQ. DRIVE
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
BHP BRAKE HORSE POWER
CD CONDENSATE
CFM CUBIC FEET PER MINUTE
CU CONDENSING UNIT
DDC DIRECT DIGITAL CONTROLS
DN DOWN
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EWT ENTERING WATER TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FPS FEET PER SECOND
GFI GROUND FAULT CIRCUIT
INTERRUPTER
GPM GALLONS PER MINUTE
kW KILLOWATT
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MBH THOUSANDS OF BTU'S PER HOUR
MCA MINIMUM CIRCUIT AMPS
MOCP MAXIMUM OVER CURRENT
PROTECTION
NC NORMALLY CLOSED
NO NORMALLY OPEN
NTS NOT TO SCALE
OA OUTDOOR AIR
PSI POUNDS PER SQUARE INCH
PISG PSI GAUGE
PVC POLYVINYL CHLORIDE
RA RETURN AIR
RG RETURN GRILLE
RTU ROOF TOP UNIT
SA SUPPLY AIR
SG SUPPLY GRILLE
TSP TOTAL STATIC PRESSURE
UNO UNLESS NOTED OTHERWISE
WP WEATHER PROOF
ΔP CHANGE IN PRESSURE
ΔT CHANGE IN TEMPERATURE
SIM SIMILAR
"CONNECT
TO" SYMBOL
"DEMOLISH
TO" SYMBOL
DEMOLISH
EXISTING
EQUIPMENT
DIFFUSER
TAG, NEW
DIFFUSER
TAG,
EXISTING
A-100
TAG
SIZE, IF
SHOWN
12x12
CFM
- 100
TAG CFM
DESIGN CRITERIA
BUILDING TYPE GROUP A4, ASSEMBLY
CLIMATE ZONE 2A, SUWANNEE COUNTY, FLORIDA
OUTDOOR DESIGN
CONDITIONS (SUMMER) 96°F DB, 78°F WB
OUTDOOR DESIGN
CONDITIONS (WINTER) 25°F DB
INTERIOR DESIGN
TEMPERATURES
72°F HEATING, 75°F COOLING
ENERGY COMPLIANCE
METHOD TOTAL BUILDING PERFORMANCE.
COMMISSIONING
COMMISSIONING NOT REQUIRED FOR THIS PROJECT PER EXCEPTION 408 OF
THE FLORIDA BUILDING CODE, ENERGY.
SCOPE OF WORK
THE BASIC HVAC SCOPE OF THIS PROJECT IS TO REMOVE THE EXISTING
PASSIVE EXHAUST SYSTEM AND REPLACE WITH A DUCTED, AIR CONDITIONING
SYSTEM COMPRISED OF (2) PACKAGED AIR CONDITIONING HEAT PUMP UNITS
TO SERVE THE GYMNASIUM AND (2) DUCTLESS SPLIT SYSTEMS TO SERVE THE
PROPOSED CLASSROOM ADDITIONS. REFER TO ARCHITECTURAL DRAWINGS
FOR ENVELOPE UPGRADES.
DUCT SYMBOLS
SUPPLY AIR
DUCTWORK DOWN
SUPPLY AIR
DUCTWORK UP
OUTSIDE AIR
DUCTWORK DOWN
OUTSIDE AIR
DUCTWORK UP
FLEXIBLE CANVAS
CONNECTION
RETURN AIR
DUCTWORK UP
RETURN AIR
DUCTWORK DOWN
EXHAUST AIR
DUCTWORK UP
EXHAUST AIR
DUCTWORK DOWN
FIRE DAMPER
EX. - EXISTING
MECHANICAL
EQUIPMENT WITH
MAINTENANCE
CLEARANCE
MANUAL BALANCE
DAMPER
MOTORIZED DAMPER,
REFER TO
SPECIFICATIONS FOR
VOLTAGE
REQUIREMENTS
FLEXIBLE DUCTWORK
SUPPLY AIR
DIFFUSER
RETURN AIR GRILLE
EXHAUST AIR GRILLE
DEMOLISH EXISTING
DUCTWORK
X"xY"
X"xY"
X"xY"
X"xY"
X"xY"
X"xY"
X"xY"
X"xY"
EX.
MECH. EQUIPMENT
MAINTENANCE
CLEARANCE
M
GENERAL HVAC NOTES
1 TOMAHAWK ENGINEERING AND CONSULTING, INC. SHALL NOT BE HELD RESPONSIBLE FOR
ANY MISUSE AND/OR MISREPRESENTATION OF THIS SET OF DOCUMENTS.
2 THE CONTRACTOR ASSUMES RESPONSIBILITY FOR USE OF THE CONTRACT DOCUMENTS.
THE CONTRACTOR SHALL MAKE HIMSELF AWARE OF PROJECT CONDITIONS AND OWNER
REQUIREMENTS PRIOR TO PROCUREMENT OF EQUIPMENT AND SERVICES. CHANGES IN
PROJECT COST WILL NOT BE GRANTED DUE TO FIELD CONFLICTS AND/OR PROJECT
CONDITIONS.
3 THIS SET OF DRAWINGS AND SPECIFICATIONS SHALL NOT BE CONSIDERED A SET OF
CONSTRUCTION DOCUMENTS UNLESS A SIGNATURE AND DATE ARE AFFIXED TO THE
DRAWINGS AND SPECIFICATIONS BY THE ENGINEER IN RESPONSIBLE CHARGE FOR THE
GIVEN DISCIPLINE.
4 CONFLICTS BETWEEN THIS SET OF DRAWINGS AND THE CONTRACT SPECIFICATIONS SHALL
BE RESOLVED BY THE ENGINEER OF RECORD. THE CONTRACTOR DOES NOT HAVE THE
AUTHORITY TO INTERPRET CONFLICTS AND RESOLVE ISSUES WITHOUT WRITTEN
DIRECTION FROM THE ENGINEER OF RECORD.
5 ANY CONFLICTS IN THE FIELD OR WITHIN THESE DOCUMENTS SHALL BE RECORDED AND
PROVIDED TO THE ENGINEER OF RECORD ON THE CONTRACTOR'S STANDARD
LETTERHEAD. WRITTEN DIRECTION RESOLVING CONFLICT WILL BE ISSUED BY THE
ENGINEER OF RECORD.
6 WHERE THE CONTRACTOR DEVIATES FROM THIS SET OF CONSTRUCTION DOCUMENTS AND
RESUBMISSION OF REVISED DRAWINGS IS REQUIRED BY THE PERMITTING OFFICE/OFFICIAL,
A MINIMUM CHARGE OF $750.00 PER AFFECTED DRAWING SHEET WILL BE BILLED TO THE
CONTRACTOR. THE REVISED DRAWINGS WILL NOT BE PROVIDED AND/OR SUBMITTED TO
THE PERMIT OFFICE UNTIL A PURCHASE ORDER OR SIGNED AGREEMENT IS ISSUED BY THE
CONTRACTOR TO THE DESIGN PROFESSIONAL FOR WORK REQUIRED. THIS SHALL NOT
APPLY TO UNFORESEEN CONDITIONS OR CHANGES REQUIRED FOR THE PROJECT THAT
ARE NOT INITIATED BY THE CONTRACTOR.
7 DRAWINGS ARE SCHEMATIC IN NATURE. THE CONTRACTOR SHALL COORDINATE WITH
OTHER TRADES AND EXISTING EQUIPMENT (WHERE APPLICABLE) TO ENSURE EQUIPMENT
FURNISHED WILL WORK FOR SPACES PROVIDED. FINAL DIMENSIONS OF DUCTWORK AND
PIPING SHALL BE COORDINATED IN FIELD. THE CONTRACTOR ASSUMES ALL
RESPONSIBILITY FOR PROVIDING OFFSETS AND TRANSITIONS IN DUCTWORK AND PIPING
TO FIT IN SPACES PROVIDED AND THESE ADDITIONAL OFFSETS AND TRANSITIONS SHALL BE
PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
8 DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF
SMACNA GUIDELINES AT TIME OF PROJECT PERMIT.
9 THERMOSTATS, HUMIDISTATS, TEMPERATURE SENSORS, HUMIDITY SENSORS, AND/OR
OTHER DEVICES REQUIRING OCCUPANT ADJUSTMENT BUT LOCATED ON WALL SHALL BE
MOUNTED 48" AFF, UNLESS NOTED OTHERWISE.
10 WHERE APPLICABLE AND AVAILABLE, ACTUAL EQUIPMENT DRAWINGS ARE USED FOR
SYMBOLS ON PLAN VIEWS AND IN DETAILS. HOWEVER, SIMPLE BLOCK DIAGRAMS WITH
ESTIMATED DIMENSIONS ARE ALSO USED FOR PLAN VIEWS. WHERE EQUIPMENT OR
DEVICES ARE NOT LABELED, INDUSTRY STANDARD TERMINOLOGY AND SYMBOLOGY SHALL
APPLY.
11 THESE GENERAL NOTES WORK IN CONJUNCTION WITH NOTES SHOWN ON PLAN VIEWS.
THESE NOTES DO NOT SUPERCEDE NOTES SHOWN ON PLAN VIEW DRAWINGS.
CONVERSELY, NOTES SHOWN ON PLAN VIEW DRAWINGS DO NOT SUPERCEDE THESE
GENERAL NOTES.
12 REFER TO EQUIPMENT SCHEDULES FOR AIR AND WATER PRESSURE DROPS ASSOCIATED
WITH COOLING AND HEATING COILS.
13 PROVIDE ACCESS PANELS IN DUCTWORK AND/OR BUILDING CONSTRUCTION WHERE
REQUIRED FOR EQUIPMENT ACCESS AND SERVICE. PANELS SHALL BE SIZED TO SUIT
EQUIPMENT SERVICED. WHERE PANELS WILL BE LOCATED IN FIRE RATED WALLS AND/OR
PARTITIONS, THE ACCESS PANEL SHALL MEET THE RATING OF THE WALL. REFER TO
ARCHITECTURAL DRAWINGS FOR RATINGS OF WALLS AND PARTITIONS.
14 UNLESS NOTED OTHERWISE, DUCTWORK, PIPING, VALVES, DAMPERS, AND ALL ASSOCIATED
ANCILLARY HVAC DEVICES SHALL BE CONSTRUCTED IN ACCORDANCE WITH MECHANICAL
SPECIFICATIONS. ALL EQUIPMENT INSTALLED AS PART OF THIS PROJECT SHALL BE NEW,
UNLESS NOTED OTHERWISE, NO EXCEPTIONS.
15 PAINT DUCTWORK AND DAMPERS VISIBLE THRU REGISTERS FLAT BLACK PRIOR TO OWNER
OCCUPANCY.
16 HVAC EQUIPMENT PROVIDED FROM THIRD PARTY MANUFACTURER SHALL BE INSTALLED IN
ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS.
WHERE CONFLICTS BETWEEN CONTRACT DOCUMENTS AND MANUFACTURER'S
INSTRUCTION ARISE, THE MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL PREVAIL.
17 THE CONTRACTOR SHALL MAKE HIS OR HERSELF AWARE OF THE OWNER'S SCHEDULE AND
BE PREPARED TO WORK AT NIGHT OR ON WEEKENDS TO COMPLETE WORK SHOWN IN
THESE DOCUMENTS. INTERRUPTIONS TO OWNER'S NORMAL WORK SCHEDULE SHALL NOT
BE MADE WITHOUT WRITTEN INSTRUCTION TO DO SO FROM OWNER'S REPRESENTATIVE.
18 FOR EQUIPMENT DEMOLISHED UNDER THIS CONTRACT, THE CONTRACTOR SHALL ALLOW
THE OWNER FIRST REFUSAL OF DEMOLISHED EQUIPMENT. IF EQUIPMENT IS REFUSED, THE
CONTRACTOR SHALL DISPOSE OF DEMOLISHED EQUIPMENT IN ACCORDANCE WITH THE
AUTHORITY HAVING JURISDICTION. IN ADDITION, FOR EQUIPMENT INDICATED TO BE
DEMOLISHED, THE CONTRACTOR SHALL ASSUME THAT THIS ALSO REQUIRES DEMOLITION
OF ALL ASSOCIATED APPURTENANCES INCLUDING ELECTRICAL CONNECTIONS, CONTROLS
CONNECTIONS, ETC.
## THE CONTROLS VENDOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING ALL CONTROL
WIRING AND CONDUIT ASSOCIATED WITH THIS PROJECT, REGARDLESS OF VOLTAGE.
WHERE CONTROL VOLTAGE IS 110V AND ABOVE, THE CONTROLS VENDOR SHALL PROCURE
THE SERVICES OF A FLORIDA LICENSED ELECTRICAL CONTRACTOR TO PROVIDE AND
INSTALL WIRING AND CONDUITS IN ACCORDANCE WITH NEC AND THE LOCAL AUTHORITY
HAVING JURISDICTION.
1 WHERE THERE ARE CONFLICTS BETWEEN LIGHT SWITCHES AND THERMOSTAT/HUMIDISTAT
LOCATIONS, THE LIGHT SWITCHES SHALL PREVAIL. MOUNT THERMOSTAT/HUMIDISTATS
ADJACENT TO LIGHT SWITCHES.
2 AS REQUIRED BY BUILDING CONSTRUCTION, THE CONTRACTOR SHALL PROVIDE
TRANSITIONS AND EQUIVALENT SQUARE DUCT SIZES NEEDED TO FIT THRU JOISTS AND/OR
WALL 2x4 SPACING WHERE ROUND IS SHOWN ON PLANS. THE CONTRACTOR SHALL
PROVIDE THESE TRANSITIONS AND SQUARE DUCTS AT NO ADDITIONAL COST TO THE
OWNER. COORDINATE WITH THE GC IN FIELD FOR JOIST AND WALL 2x4 REQUIREMENTS.
3 WHERE REQUIRED BY BUILDING CONSTRUCTION AND HEIGHT TO EQUIPMENT SERVED, THE
CONTRACTOR SHALL PROVIDE HOISTING MECHANISMS AS WELL AS SCAFFOLDING WHERE
REQUIRED TO INSTALL EQUIPMENT SHOWN WITHIN THESE CONTRACT DOCUMENTS.
EQUIPMENT USED FOR THE INSTALLATION OF EQUIPMENT SHALL MEET ALL OSHA
REQUIREMENTS.
4 PROVIDE MANUAL BALANCE DAMPERS FOR SUPPLY, RETURN, AND EXHAUST TAKE-OFFS
TO REGISTERS WHETHER INDICATED OR NOT. WHERE DAMPERS WILL BE LOCATED ABOVE
INACCESSIBLE CEILINGS, PROVIDE OPPOSED BLADE MANUAL BALANCE DAMPERS FROM
REGISTER MANUFACTURER.
CODE REFERENCES
FBC, BUILDING FLORIDA BUILDING CODE, BUILDING, 2023 EIGHTH EDITION
FBC, EXISTING
BUILDING
FLORIDA BUILDING CODE, EXISTING BUILDING, 2023 EIGHTH EDITION
FBC, MECHANICAL FLORIDA BUILDING CODE, MECHANICAL, 2023 EIGHTH EDITION
FBC, FUEL GAS FLORIDA BUILDING CODE, FUEL GAS, 2023 EIGHTH EDITION
FBC, EXISTING
BUILDING
FLORIDA BUILDING CODE, 2023 EIGHTH EDITION
FBC, ENERGY FLORIDA BUILDING CODE, 2023 EIGHTH EDITION
FFPC FLORIDA FIRE PREVENTION CODE, 2023 EIGHTH EDITION
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019 EDITION
NFPA 51B STANDARD FOR FIRE PREVENTION DURING WELDING, CUTTING, AND OTHER
HOT WORK, 2019 EDITION
NFPA 54 NATIONAL FUEL GAS CODE, 2021 EDITION
NFPA 70 NATIONAL ELECTRIC CODE, 2020 EDITION
NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING
SYSTEMS, 2021 EDITION
NFPA 101 LIFE SAFETY CODE, 2021 EDITION
NFPA 101A GUIDE ON ALTERNATIVE APPROACHES TO LIFE SAFETY, 2019 EDITION
PACKAGED AIR CONDITIONING UNIT SCHEDULE
EQUIPMENT NO. MODEL NO. NOMINAL
TONNAGE
REFRIGERANT
TYPE
HEAT PUMP
(YES/NO)
CFM
(TOTAL
SUPPLY)
CFM
(OUTDOOR
AIR)
TOTAL/SENSIBLE
COOLING (MBH)
ENTERING/LEAVING AIR
TEMPERATURES
(DB°F/WB°F)
HEAT PUMP
HEATING
(MBH)**
GAS HEATING
(INPUT/OUTPUT
MBH)
HOT GAS
REHEAT
(MBH)
EFF. (EER) IPLV (EER)
INDOOR
FAN MOTOR
(HP)
NO. OF
COMPRESSORS
COMP. #1
RLA/LRA
COMP#2
RLA/LRA
NO. OF
CONDENSER
FANS
COND. FAN
HP/FLA MCA MOCP VOLTS/PHASE
AC-1 WHK240 20 R-454B YES 6000 2125 234.9/164.9 80.1°F/66.5°F - 54°F/53°F 140.9 NA 44.0 -- -- 3 2 44.5/270 25.9/178.5 2 1/4.3 108 150 208/230/3Ø
AC-2 DHK240 20 R-454B YES 6000 2125 234.9/164.9 80.1°F/66.5°F - 54°F/53°F 140.9 320.0/259.2 44.0 -- -- 3 2 44.5/270 25.9/178.5 2 1/4.3 118 150 208/230/3Ø
NOTES:
1. BASIS OF DESIGN: EQUIPMENT SHALL BE EQUAL TO TRANE, HIGH EFFICIENCY PACKAGED UNIT.
2. PROVIDE AC-2 WITH DUAL FUEL (HEAT PUMP AND GAS) HEATING. PROVIDE AC-2 WITH MEDIUM GAS HEATING AND STAINLESS STEEL HEAT EXCHANGER.
3. PROVIDE UNITS WITH HAIL GUARDS AND OUTDOOR AIR RAIN HOOD FROM MANUFACTURER.
4. PROVIDE UNITS WITH THE FOLLOWING FACTORY OPTIONS: STAINLESS STEEL CONDENSATE DRAIN PAN, HORIZONTAL DISCHARGE, MOTORIZED OUTDOOR DAMPER, SINGLE ZONE STANDARD SIZE MOTOR, HINGED ACCESS AND FILTER ACCESS, AND HUMIDITY CONTROL.
5. UNITS SHALL BE SINGLE POINT CONNECTION, REFER TO ELECTRICAL DRAWINGS FOR FURTHER INFORMATION.
6. PROVIDE UNITS WITH SUPPLY SIDE SMOKE DETECTORS. SMOKE DETECTOR SHALL SHUT UNIT DOWN UPON DETECTION OF PRODUCTS OF COMBUSTION.
**HEATING RATING INDICATED IS FOR AND OUTDOOR AIR TEMPERATURE OF 22°F AND AN INDOOR AIR TEMPERATURE OF 70°F.
DIFFUSER SCHEDULE
PLAN
MARK CFM NECK
SIZE DESCRIPTION
A
REFER TO PLAN
VIEWS FOR CFM
AND SIZES
ALL ALUMINUM
CONSTRUCTION SUPPLY AIR ,
WITH DIFFUSER WITH DOUBLE
DEFLECTION BLADES, 3/4"
SPACING. PROVIDE WITH
SURFACE MOUNTED BORDER
WHERE LOCATED IN GYPSUM
CEILINGS OR ON WALLS.
GRILLE SHALL BE EQUAL TO
PRICE MODEL 22.
B
REFER TO PLAN
VIEWS FOR CFM
AND SIZES
PRICE…