1-Scaleybark Plans.pdf
PDF 3 MB Posted
- Attached to
- Scaleybark Station Drainage Repairs
- Solicitation number
- 269- 2026-1942
- Issued by
- Mecklenburg County, Charlotte City, North Carolina
About this file
This document is a comprehensive set of engineering and construction plans for the Scaleybark Station Drainage Repair Project, part of the LYNX Blue Line light rail system for the Charlotte Area Transit System (CATS). The project, identified with CATS No. 13-0021, is scheduled for completion by August 22, 2025, and involves drainage repair work at the Scaleybark Station. The plans include detailed design specifications for drainage structures, trench drain installations, pavement repairs, and traffic control measures across multiple project segments (Scaleybark L1, L2, and L3). The project involves installing polymer concrete drainage channels, repairing pavement, adjusting utility infrastructure, and implementing comprehensive traffic management strategies during construction.
The project will require extensive traffic control and coordination, with specific provisions for maintaining two-way traffic, protecting property access, and minimizing disruption to the surrounding area. The construction will involve precise drainage infrastructure improvements, including 12-inch and 4-inch trench drain systems with specific load-bearing specifications, pavement milling and repair, and utility adjustments. The project documents indicate that the work will be performed in phases, with careful attention to traffic management, signage, and safety protocols. The plans are prepared by LaBella Associates and include detailed technical specifications, profile views, traffic control details, and a detour route map for South Boulevard during construction activities.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Freeland Ln So ut h
Bv
Whitton St
Sou th
Bv
Clanton Rd
Pe lto n St
W es ton StHartford AvDe wi tt L n
So ut h Bv
Hollis Rd
S Tryon
St
Gle as on W y
Dex te r S t
Blairhill Rd
Yorkshire Dr
Sara h Dr
El le nw oo d Pl
W eo na Av
Whitton St
D ew itt Ln
Sl oa n St
An so n St
C ra ft St
Script Ln
Gra nd
Unio n W y Sk y Ha ve n
Dr
Cr au gh we ll D r
Greystone Rd
New Bern Station Ct
Conway Av
Scaleybark Rd
South Bv
O ld
Pi ne vil le
Rd
Yancey Rd
E Peterson Dr
S Tryon
St
W ebster Pl
Tyson St
Southside Dr
13-0021
08/22/2025
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
SCALEYBARK STATION
DRAINAGE REPAIR PROJECT
SCALEYBARK STATION DRAINAGE REPAIR PROJECT
LYNX BLUE LINE
CATS NO.: 13-0021
AUGUST 22, 2025
Cover Sheet
General Notes Plan & Profile .................................................................................................... 3-4
Traffic Control Plans .........................................................................................7-9
TOTAL SHEETS 09
Details ..................................................................................................................5-6
INDEX OF SHEETS
VICINITY MAP
SCALE: NTS
PROJECT
AREA
8/22/2025
13-0021
08/22/2025
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
ABBREVIATIONSGENERAL NOTES GENERAL NOTES
ABAND...........................ABANDONED
A.D................................. ALGEBRAIC DIFFERENCE
ASPH............................. ASPHALT
APPROX........................ APPROXIMATELY
B/C................................. BACK OF CURB
BIT..................................BITUMINOUS
BM..................................BENCH MARK
BRG.............................. .BEARING
CB...................................CATCH BASIN
C&G................................CURB AND GUTTER
CL...................................CLEARANCE
C/L FENCE.....................CHAIN LINK FENCE
CMP................................CORRUGATED MTL PIPE
CONC.............................CONCRETE
CONST...........................CONSTRUCTION
DB...................................DEED BOOK
DCB................................DOUBLE CB
DI....................................DROP INLET
DIA..................................DIAMETER
DW..................................DRIVEWAY
DIM.................................DIMENSION
E.....................................EAST/EASTING
EA...................................EACH
ELEV...............................ELEVATION
EOP................................EDGE OF PAVEMENT
ESMT..............................EASEMENT
EXIST.............................EXISTING
F/C..................................FACE OF CURB
FES.................................FLARED END SECTION
FH...................................FIRE HYDRANT
FOC................................FIBER OPTIC CABLE
GV.................................. GAS VALVE
HORIZ............................ HORIZONTAL
INT..................................INTERSECTION
INV..................................INVERT
IP.................................... IRON PIN SET
L......................................LENGTH
LF................................... LINEAR FOOTAGE
LT....................................LEFT
lb.....................................POUND
LP................................... LIGHT POLE
MAX................................MAXIMUM
MIN.................................MINIMUM
MONO............................ MONOLITHIC
mph.................................MILES PER HOUR
MTL.................................METAL
N.....................................NORTH/NORTHING
NTS..........................NOT TO SCALE
O/H...........................OVER HEAD
OC............................ON CENTER
PAVT........................PAVEMENT
PC............................POINT OF CURVATURE
PERM.......................PERMANENT
PG............................PAGE PI.............................POINT
OF INT PK............................PK NAIL SET
PP............................POWER POLE
PROP.......................PROPOSED
PSE..........................PERM SW ESMT
PT.............................POINT OF TANGENCY
PVI...........................POINT OF VERT INT
PUE..........................PERM UTILITY ESMT
r................................RADIUS
RT............................RIGHT
RCP......................... REINFORCED CONC PIPE
RELOC.....................RELOCATE
R/W..........................RIGHT OF WAY
S...............................SOUTH
SD............................STORM DRAIN
SF............................ SQUARE FOOT
S/R FENCE..............SPLIT RAIL FENCE
SS............................SANITARY SEWER
STA..........................STATION
STD..........................STANDARD
SW...........................SIDEWALK
TAN..........................TANGENT
TCE..........................TEMP CONST ESMT
TEMP.......................TEMPORARY
TP............................ TRAVERSE POINT
T/W..........................TEST WIRE
TYP..........................TYPICAL
U/G...........................UNDER GROUND
VC............................VERTICAL CURVE
VERT........................VERTICAL
W..............................WEST W/............................WITH
WM...........................WATER METER
W VAULT.................WATER VAULT
WV...........................WATER VALVE
60p...........................SIXTY PENNY NAIL SET
'................................FOOT ''..............................INCH
THE CONTRACTOR SHALL SET AND ADJUST PROPOSED CURB ELEVATIONS AS NECESSARY TO ENSURE
PROPER LONGITUDINAL GRADE FOR DRAINAGE. THE CONTRACTOR SHALL RETAIN EXISTING
PAVEMENT, UNLESS OTHERWISE NOTED.
PROPOSED DRIVEWAY ENTRANCE DIMENSIONS ARE FROM EXPANSION JOINT TO EXPANSION JOINT. MATCH
REPLACEMENT MATERIALS TO THE EXISTING SURFACE ACCORDINGLY:
GRADES, ELEVATIONS AND LOCATIONS SHOWN ARE APPROXIMATE. AS DIRECTED BY THE ENGINEER, THEY MAY BE ADJUSTED TO ACCOMMODATE UNFORESEEN CONDITIONS. STATIONS, OFFSETS AND ELEVATIONS REFER TO THE CENTER OF DROP INLETS, MANHOLES AND JUNCTION BOXES, AND THE MIDPOINT OF THE LIP
FOR CATCH BASINS. ALL PIPES SHALL BE RCP CLASS III, UNLESS OTHERWISE NOTED.
WEEPHOLES ARE TO BE CONSTRUCTED IN ALL DRAINAGE STRUCTURES, A MINIMUM OF 1 WEEPHOLE PER STRUCTURE. WEEPHOLES ARE TO BE CONSTRUCTED IN THE BOTTOM 1/3 OF STRUCTURE AND COVERED ON THE OUTSIDE OF THE STRUCTURE BY A BAG MADE OF FILTER FABRIC AND FILLED W/#78 STONE. THERE
WILL BE NO SEPARATE PAYMENT FOR THIS WORK.
THE CONTRACTOR SHALL ADJUST ALL WATER VALVES, WATER METER BOXES AND WATER VAULTS TO
FINISHED GRADE. WATER METERS LOCATED IN SIDEWALKS OR CONCRETE DRIVEWAYS SHALL BE
INSTALLED WITHIN CONCRETE BOXES.
GAS LINES WILL BE ADJUSTED/RELOCATED AS NEEDED BY PIEDMONT NATURAL GAS. THE CONTRACTOR
SHALL CONTACT PIEDMONT NATURAL GAS AT LEAST TWO WEEKS PRIOR TO CONSTRUCTION.
THE CONTRACTOR SHALL USE CARE WHEN WORKING AROUND SANITARY SEWERS AND WATER LINES.
SHOULD THE CONTRACTOR DAMAGE EXISTING SEWER OR WATER LINES, HE SHALL IMMEDIATELY
REPLACE THE LINE AT HIS EXPENSE WITH DUCTILE IRON PIPE. THE CONTRACTOR SHALL REPLACE SANITARY SEWER AND/OR WATER LINE, WITH A MINIMUM TEN FOOT SECTION OF DUCTILE IRON PIPE WHEN DRAINAGE PIPE COMES WITHIN TWO FEET OF SAID LINES, VERTICALLY OR HORIZONTALLY.
NO SUBSURFACE PLANS ARE AVAILABLE ON THIS PROJECT. THE CONTRACTOR MAY MAKE HIS OWN
INVESTIGATION TO DETERMINE SUBSURFACE CONDITIONS.
THE CONTRACTOR SHALL RELOCATE ALL MAIL BOXES AS REQUIRED BY SECTION 107-12 OF THE NCDOT STANDARD SPECIFICATIONS FOR ROADS AND STRUCTURES. COORDINATE THIS WORK WITH THE U.S.
POSTAL SERVICE.
THE CONTRACTOR SHALL REMOVE AND RESET FENCES AS NOTED ON THE PLANS AND/OR AS DIRECTED
BY THE ENGINEER.
CONCRETE - SIX INCH PORTLAND CEMENT CONCRETE (3600 PSI).
ASPHALT - (COMMERCIAL) TWO INCH SF9.5B COURSE AND FOUR INCH I19.OB
INTERMEDIATE COURSE.
RESIDENTAL TWO INCH SF9.5B COURSE AND FOUR INCH AGGREGATE
BASE (ABC) COURSE.
GRAVEL - SIX INCH INCIDENTAL STONE
SIDEWALK SHALL BE FOUR INCHES THICK, AND SIX INCHES THICK AT DRIVEWAY CROSSINGS, PER CITY
STD. NO. 10.22.
FOR LOCATES OF UTILITIES NOT MEMBERS OF NORTH CAROLINA ONE-CALL CONTACT
FOR UTILITY LOCATES CALL NORTH CAROLINA ONE-CALL @ 1-800-632-4949.
PROJECT MANAGER & UTILITY COORDINATOR.
UTILITIES ARE ILLUSTRATED FOR INFORMATION PURPOSES ONLY. THE CITY WILL NOT BE HELD RESPONSIBLE FOR THE ACCURACY OF UTILITY LOCATIONS, SIZES, DEPTHS, OR FOR COMPLETENESS OF
UTILITY INFORMATION.
PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL NOTIFY AND MEET WITH ALL UTILITY OWNERS, THE CITY UTILITY COORDINATOR AND CITY INSPECTOR WHOSE FACILITIES WILL BE AFFECTED TO DETERMINE UTILITY LOCATIONS. THE CONTRACTOR SHALL PROTECT ALL UTILITIES FROM DAMAGE CAUSED BY HIS OPERATIONS OR THOSE OF HIS AGENTS. THE CONTRACTOR SHALL HOLD THE CITY HARMLESS FOR ANY THIRD-PARTY INCONVENIENCE CREATED BY WORK OF HIS OWN FORCES OR THAT OF HIS AGENTS. ANY
DAMAGES INCURRED SHALL BE THE CONTRACTORS FINANCIAL RESPONSIBILITY.
AS NEEDED, THE CONTRACTOR SHALL ADJUST/RELOCATE THE SANITARY SEWER AND WATER LINES ONLY.
ALL OTHER ADJUSTMENTS/RELOCATIONS WILL BE PERFORMED BY THE VARIOUS UTILITY OWNERS. THE CONTRACTOR SHALL COORDINATE WORK WITH UTILITY OWNERS SO AS NOT TO ADVERSELY AFFECT THE PROJECT SCHEDULE. THE CITY WILL NOT BE HELD RESPONSIBLE FOR ANY DELAYS OR DISRUPTIONS TO
THE WORK SCHEDULE OF OTHER UTILITY OWNERS.
THE CONTRACTOR SHALL REMOVE TREES, SHRUBS, AND HEDGES WITHIN THE LIMITS OF DISTURBANCE UNLESS SHOWN ON THE PLANS TO BE PROTECTED AND THOSE THAT FALL WITHIN THE TREE PROTECTION BARRIERS. WHEN ROOT PRUNING IS NECESSARY, CUT ROOTS CLEANLY USING A DISC TRENCHER OR OTHER APPROVED METHOD IN ACCORDANCE WITH SECTION 01000 OF THE CITY OF CHARLOTTE LANDSCAPE CONSTRUCTION STANDARDS. PRUNING SHALL BE PER THE LATEST STANDARD OF THE LANDSCAPE CONSTRUCTION STANDARDS MANUAL (TYP.) USE PLYWOOD FORMS WHEN TREE ROOTS ARE ADJACENT TO PROPOSED CURB & GUTTER OR SIDEWALK. USE CLD STD. 40.11 FOR BRIDGING TREE ROOTS. TREES SPECIFIED BY THE PLANS TO HAVE ASPHALT CURBING MUST USE CLD STD. 40.13. TREE PROTECTION SHALL BE IN ACCORDANCE WITH CLD STD. 40.02 AND WITH SECTION 1000 OF THE CITY OF CHARLOTTE LANDSCAPE CONSTRUCTION STANDARDS. WHEN THE TREE IS CLOSE TO THE WORK AREA TREE PROTECTION CLD STD.
40.12 SHALL BE USED.
CONTRACTOR SHALL OBTAIN APPROVAL FROM THE CITY PRIOR TO REMOVING ANY TREES. IN ADDITION, ALL TREES LOCATED WITHIN THE LOD THAT ARE TO REMAIN AFTER CONSTRUCTION SHALL BE INSPECTED BE THE CITY TO VERIFY
THEY ARE SUITABLE TO REMAIN.
FOLLOWING CONSTRUCTION STAKING THE PROJECT TEAM (CONTRACTOR, CITY INSPECTOR, CITY ARBORIST AND CONSULTANT, IF APPLICABLE) WILL HOLD AN ON-SITE MEETING TO ENSURE THE LIMITS OF DISTURBANCE AND THAT TREES PROPOSED FOR PROTECTION ARE CLEARLY IDENTIFIED. THE TEAM WILL WALK THE PROJECT AREA AND AGREE ON THE TREES TO BE PROTECTED AND THOSE TO REMOVE, DISCUSS PROPOSED CONSTRUCTION ACTIVITIES, AND IDENTIFY ANY ADDITIONAL TREES TO PROTECT THAT WERE NOT ORIGINALLY MARKED AS SUCH. THE CONTRACTOR WILL BE GIVEN APPROVAL FOR TREE REMOVAL, IN WRITING, AFTER APPROPRIATE TREE PROTECTION HAS BEEN
INSTALLED AND BEFORE ANY CLEARING OR REMOVAL CAN BEGIN.
THE CONTRACTOR ASSUMES RESPONSIBILITY FOR "IN-KIND" REPLACEMENT OF TREES DAMAGED THAT HAVE BEEN
MARKED FOR PROTECTION OR NOT MARKED FOR REMOVAL.
STD. NO.: TITLE:
STANDARDS
STD. NO.: TITLE:
LIMITS OF PROPOSED SLOPES ARE INDICATED IN THE PLANS, DETAILS AND STANDARD DRAWINGS. THE MAXIMUM SLOPE SHALL NOT EXCEED A 3:1 (HORIZONTAL TO VERTICAL) UNLESS DESIGNATED BY THE ENGINEER. A CUT SLOPE OF 2:1 MAXIMUM WILL BE USED ONLY AS DIRECTED BY THE ENGINEER.
THE CONTRACTOR SHALL MAINTAIN EROSION CONTROL DEVICES IN ACCORDANCE WITH THE
APPROPRIATE CITY AND STATE EROSION AND SEDIMENT CONTROL ORDINANCES. THE CONTRACTOR SHALL PREVENT STANDING WATER DUE TO CONSTRUCTION. DISTURBED AREAS SHALL BE SEEDED
AND MULCHED AT THE DIRECTION OF THE ENGINEER.
THE CONTRACTOR SHALL CONSTRUCT 6-INCH THICK CONCRETE ACCESSIBLE RAMPS AT
INTERSECTIONS IN ACCORDANCE WITH THE LATEST REVISIONS FOR ACCESSIBLE RAMP DETAILS, CONSTRUCTION PLANS & NCDOT STANDARD DRAWINGS.
THE CONTRACTOR SHALL SAWCUT EXISTING ASPHALT AND/OR CONCRETE SURFACES PRIOR TO
REMOVAL UNLESS OTHERWISE DIRECTED BY THE ENGINEER. SAW CUT WIDTH SHALL BE 1 FOOT
MINIMUM FROM THE EXISTING EDGE OF PAVEMENT. SAW CUT PAVEMENT SHALL BE REPLACED AS WELL AS ADDITIONAL PAVEMENT REQUIRED TO TIE-IN TO FACE OF PROPOSED CURB AND GUTTER.
TRAFFIC CONTROL SHALL BE IN ACCORDANCE WITH THE 2006 EDITION OF THE "WORK AREA TRAFFIC
CONTROL HANDBOOK" (WATCH) AND THE TRAFFIC CONTROL PLANS ON SHEETS 6-8.
THE FOLLOWING STANDARDS AND THE LATEST REVISION THERETO ARE APPLICABLE TO THIS
PROJECT AND BY REFERENCE ARE CONSIDERED A PART OF THESE PLANS. NCDOT STANDARDS
SHALL BE USED. CHARLOTTE LAND DEVELOPMENT STANDARDS MAY BE USED IF THERE IS NOT
AN APPLICABLE NCDOT STANDARD.CDOT HAS DETERMINED THAT NO PAVEMENT DEGRADATION FEE IS TO BE ASSESSED.
CDOT AND E&PM HAVE AGREED ON THE STREET CUTS FOR WHICH A PAVEMENT DEGRADATION FEE IS REQUIRED. THE DEGRADATION FEE ASSESSMENT SHALL BE PAID VIA INTERNAL CITY MECHANISMS (DTI)
PRIOR TO CONSTRUCTION.
BASE DATA
EXISTING CONDITIONS TAKEN FROM A COMPILATION OF GROUND SURVEYS BY NV5 DATED
OCTOBER 16, 2024, FEBRUARY 4, 2025, AND FEBRUARY 25, 2025. ALL COORDINATES BASED ON
NAD 83 AND NAVD 88.
STRUCTURES INCLUDING STORM DRAIN PIPE, STORM STRUCTURES, SEWER PIPE, AND RETAINING WALLS SHALL HAVE A TOLERANCE OF ±0.10 FEET. STRUCTURES INCLUDING RISERS, WEIRS, AND ORIFICES, SHALL HAVE A TOLERANCE OF ±0.05 FEET.
STREAM IMPROVEMENT STRUCTURES SHALL HAVE A VERTICAL TOLERANCE OF ±0.10 FEET, AND A
PLANIMETRIC TOLERANCE OF ±0.50 FEET,
300.01........................................................................................METHOD OF PIPE INSTALLATION 840.01........................................................................................BRICK CATCH BASIN 840.03........................................................................................FRAME, GATES, AND HOOD 840.15........................................................................................BRICK DROP INLET 840.16........................................................................................DROP INLET FRAME AND GRATES 840.29........................................................................................FRAME AND NARROW SLOT FLAT GRATES 840.32........................................................................................BRICK JUNCTION BOX 840.34........................................................................................TRAFFIC BEARING JUNCTION BOX 840.35........................................................................................TRAFFIC BEARING GRATED DROP INLET
10.17..........................................................................................CURB AND GUTTER 10.18..........................................................................................VERTICAL CURB 10.20..........................................................................................CURB TRANSITION 2'-6" TO 1'-6" STANDARD 10.22..........................................................................................CONCRETE SIDEWALKS 10.23..........................................................................................SIDEWALK TRANSITION
CONVENTIONAL SIGNS
Proposed Guardrail
Proposed Rip Rap Ditch
Proposed Asphalt Pavement
Proposed Pavement Removal
Proposed Gravel
Tree Protection
Guy Wire
Accessible Ramp
Existing Water Meter
Fence
Proposed Edge of Pavement
Existing Drop Inlet
Existing Utility Pole
Existing Storm Drainage
Railroad Tracks
New Property Line
Slope Stake Line
Existing Property Line
Existing Gas Line
Existing Underground Telecommunications
Existing Sanitary Sewer
Proposed Storm Drainage
Existing Water Line
Existing Gas Valve
Existing Sanitary Sewer Manhole
Existing Water Valve
Existing Storm Drain Manhole
Proposed Storm Drain Manhole
Existing Telephone Manhole
Existing Catch Basin
Proposed Catch Basin
Existing Light Pole
Temporary Construction Easement
Proposed Drop Inlet
Existing Fire Hydrant
Iron Pin
Existing Structures
Proposed Light Pole
Proposed Utility Pole
Existing Underground Electric
Proposed Telephone Manhole
Existing Electric Manhole
Proposed Electric Manhole
Proposed Fire Hydrant
Existing Tree
Proposed Sanitary Sewer Manhole
Sidewalk/Utility Easement
Storm Drainage Easement
Maintained as R/W Line
D
T
WM
S
GV
WV
T
E
E
S
Proposed Curb & Gutter, Conc. Drive, Sidewalk
Proposed Sidewalk Bridging Tree Roots
Silt Fence
Scaleybark L2
Scaleybark L1
Scaleybark L3
SOUTH BLVD 28' BST
FR
EELAN
D
LN
36' BST
SOUTH BLVD 42' BST
Freeland Ln
So ut h Bv
Whitton St
So ut h Bv
Hollis Rd
Dex te r S t
Yorkshire Dr
Sara h Dr
El le nw oo dP l
W eo na Av
Whitton St
D ew itt Ln
Sl oa n St
An so n St
C ra f t St
Script Ln
Gra nd
Unio n W y Sk y H av en
Dr
C ra ug hw ell Dr
Conway Av
Scaleybark Rd
S outh
Bv
O ld
Pi ne vi lle
Rd
Yancey Rd
E Peterson Dr
S TryonSt
W ebster Pl
Tyson St
SouthsideDr
13-0021
08/22/2025
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
PROJECT
AREA
SCALEYBARK L1 - PROFILE VIEW
STA. 10+00 - 15+71
SEE SHEET 04 FOR
VERTICAL LOCATE TABLE
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
SCALEYBARK L2 - PROFILE VIEW
STA. 20+00 - 21+40
SCALEYBARK L3 - PROFILE VIEW
STA. 30+00 - 31+67
VERTICAL LOCATE TABLE
NOTE:
THE TRENCH DRAINS ARE INTENDED
TO FOLLOW THE SLOPE OF THE TRACK.
MINOR ADJUSTMENTS MAY BE NEEDED
TO MATCH THE TRACK SLOPE.
NOTES:
1. IT IS NECESSARY TO ENSURE MINIMUM DIMENSIONS SHOWN ARE SUITABLE FOR EXISTING GROUND CONDITIONS.
2. MINIMUM CONCRETE STRENGTH OF 4,000 PSI IS REQUIRED. CONCRETE SHOULD BE VIBRATED TO ELIMINATE
AIR POCKETS.
3. EXPANSION AND CONTRACTION CONTROL JOINTS AND REINFORCEMENT ARE REQUIRED TO PROTECT CHANNEL AND
CONCRETE SURROUND.
4. THE FINISHED LEVEL OF THE CONCRETE SURROUND MUST BE APPROX. 1/8" ABOVE THE TOP OF THE CHANNEL EDGE.
5. CONCRETE BASE THICKNESS SHOULD MATCH SLAB THICKNESS.
6. REFER TO ACO'S LATEST INSTALLATION INSTRUCTIONS FOR FURTHER DETAILS.
7. USE THE POWERDRAIN CONCRETE ANCHORS (PART #97496) FOR LOAD CLASS F APPLICATIONS. TWO ANCHORS REQUIRED
PER HALF METER LENGTH.
8. GRATES SHALL BE SECURED USING THE 4 BOLT LOCKING OPTION.
9. PROVIDE 1/2" EXPANSION JOINT WITH JOINT FILLER AND SEALER BETWEEN TRAVEL LANES ON SOUTH BLVD.
10. PLACE CONTRACTION JOINTS AT 10' INTERVALS.
11. CENTER U BARS WITHIN CONCRETE SURROUNDING TRENCH DRAIN. PROVIDE 3" MINIMUM CLEARANCE FROM TOP EDGE
OF CONCRETE.
SPECIFICATION CLAUSE
S300K POWERDRAIN - LOAD CLASS F
GENERAL
THE SURFACE DRAINAGE SYSTEM SHALL BE POLYMER
CONCRETE S300K CHANNEL SYSTEM WITH DUCTILE
IRON EDGE RAILS AS MANUFACTURED BY ACO
POLYMER PRODUCTS, INC OR APPROVED EQUAL
MATERIALS
CHANNELS SHALL BE MANUFACTURED FROM
POLYESTER RESIN POLYMER CONCRETE WITH AN
INTEGRALLY CAST-IN DUCTILE IRON EDGE RAIL.
MINIMUM PROPERTIES OF POLYMER CONCRETE WILL
BE AS FOLLOWS:
COMPRESSIVE STRENGTH: 14,000 P SI
FLEXURAL STRENGTH: 4,000 PSI
TENSILE STRENGTH: 1 , 5 0 0 P S I
WATER ABSORPTION: 0 .07 %
FROST PROOF Y E S
DILUTE ACID AND ALKALI RESISTANT YES
B117 SALT SPRAY TEST COMPLIANT Y ES
THE SYSTEM SHALL BE 12" NOMINAL INTERNAL WIDTH
WITH A 14.2" OVERALL WIDTH AND A BUILT-IN SLOPE
OF 0.50%. CHANNEL INVERT SHALL HAVE DEVELOPED
"V" SHAPE. ALL CHANNELS SHALL BE INTERLOCKING
WITH A MALE/FEMALE JOINT.
CHANNEL SHALL WITHSTAND LOADING TO PROPER
LOAD CLASS AS OUTLINED BY EN 1433. GRATE TYPE
SHALL BE APPROPRIATE TO MEET THE SYSTEM LOAD
CLASS SPECIFIED AND INTENDED APPLICATION.
GRATES SHALL BE SECURED USIN THE 'POWERLOK'
BOLTLESS LOCKING SYSTEM OR THE 4 BOLT LOCKING
OPTION. CHANNEL AND GRATE SHALL BE CERTIFIED
TO MEET THE SPECIFIED EN 1433 LOAD CLASS. THE
SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS.TRENCH DRAIN NOTES:
1. MINIMUM CONCRETE STRENGTH OF 4,000 PSI IS REQUIRED. CONCRETE SHOULD BE VIBRATED TO ELIMINATE AIR
POCKETS.
2. THE FINISHED LEVEL OF THE CONCRETE SURROUND MUST BE APPROX. 1/8" [3mm] ABOVE THE TOP OF THE CHANNEL
EDGE.
3. THE SURFACE DRAINAGE SYSTEM SHALL BE POLYMER CONCRETE S100K CHANNEL SYSTEM WITH DUCTILE IRON EDGE
RAILS AS MANUFACTURED BY ACO POLYMER PRODUCTS, INC.OR APPROVED EQUAL.
4. CHANNELS SHALL BE MANUFACTURED FROM POLYESTER RESIN POLYMER CONCRETE WITH AN INTEGRALLY CAST-IN DUCTILE IRON EDGE RAIL. MINIMUM PROPERTIES OF POLYMER CONCRETE WILL BE AS FOLLOWS:
COMPRESSIVE STRENGTH: 14,000 PSI
FLEXURAL STRENGTH: 4,000 PSI
TENSILE STRENGTH: 1,500 PSI
WATER ABSORPTION: 0.07%
FROST PROOF YES
DILUTE ACID AND ALKALI RESISTANT YES
B117 SALT SPRAY TEST COMPLIANT YES
5. THE SYSTEM SHALL BE 4" NOMINAL INTERNAL WIDTH WITH A 6" OVERALL WIDTH AND A BUILT-IN SLOPE OF 0.5%.
CHANNEL INVERT SHALL HAVE DEVELOPED "V" SHAPE. ALL CHANNELS SHALL BE INTERLOCKING WITH A MALE/FEMALE
JOINT.
6. CHANNEL SHALL WITHSTAND LOADING TO PROPER LOAD CLASS AS OUTLINED BY EN 1433. GRATE TYPE SHALL BE APPROPRIATE TO MEET THE SYSTEM LOAD CLASS SPECIFIED AND INTENDED APPLICATION. GRATES SHALL BE SECURED USING THE 4 BOLT LOCKING OPTION. CHANNEL AND GRATE SHALL BE CERTIFIED TO MEET THE SPECIFIED EN 1433 LOAD CLASS. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIO
TRENCH DRAIN NOTES:
13-0021
08/22/2025
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
12" TRENCH DETAIL - EN 1433 LOAD CLASS F
NOT TO SCALE
4" TRENCH DETAIL - EN 1433 LOAD CLASS C
NOT TO SCALE
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
DETAIL 2A
Not to scale
PAVEMENT REPAIR WITH MILLING
Not to scale
DETAIL 3A
PAVEMENT REPAIR WITH MILLING ADJACENT TO CURB
AND GUTTER WITH STORM DRAINAGE
*NOTES:
*NOTES:
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
PROJECT NOTESGENERAL NOTES
A) ALL TRAFFIC CONTROL DEVICES AND PROCEDURES SHALL CONFORM TO THE REQUIREMENTS OF THE MOST CURRENT EDITIONS OF THE CHARLOTTE DEPT. OF TRANSPORTATION(CDOT) WORK AREA TRAFFIC CONTROL HANDBOOK(W.A.T.C.H.), THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES(M.U.T.C.D.), THE NORTH CAROLINA DEPARTMENT OF TRANSPORTATION(NCDOT) SUPPLEMENT TO THE M.U.T.C.D., THE NCDOT ROADWAY STANDARD DRAWINGS AND THE
CURRENT EDITION OF THE NCDOT STANDARD SPECIFICATIONS FOR ROADS AND STRUCTURES.
B) CONSTRUCTION PHASING MAY DICTATE THAT TWO OR MORE TYPICAL DRAWINGS OR STANDARDS BE USED IN ONE AREA OF CONSTRUCTION. CHANNELIZING DEVICES ASSOCIATED WITH THESE TYPICALS SHALL BE MOVED, SUPPLEMENTED, CHANGED, OR REMOVED AS REQUIRED BY THE CONSTRUCTION PHASING OF THE PLANS. THE LOCATION AND POSITIONING OF THESE DEVICES SHALL BE APPROVED BY THE ENGINEER TO ENSURE THAT THE MOTORIST DOES NOT RECEIVE FALSE
INFORMATION WHEN TWO OR MORE TYPICALS AND/OR ROADWAY STANDARD DRAWINGS OVERLAP.
C) OPERATIONAL SIGNS ARE GENERALLY MOUNTED ON PORTABLE SUPPORTS. THESE ARE NORMALLY USED FOR SHORT-TERM OPERATIONS TO WARN AND GUIDE TRAFFIC THROUGH OR AROUND CONSTRUCTION AREAS WITHIN A CONSTRUCTION ZONE. OPERATIONAL SIGNS SHALL BE INSTALLED PRIOR TO THE START OF OPERATIONS AS SHOWN ON THE PLANS OR AS DIRECTED BY THE ENGINEER. SIGNS SHALL BE MAINTAINED IN PROPER POSITION AND KEPT CLEAN AND LEGIBLE AT ALL TIMES. IF NEED BE, THEY SHALL BE BALLASTED OR WEIGHTED IN SUCH A MANNER THAT THEY WILL BE STABLE UNDER WIND AND VEHICLE ACTIONS.* THEY SHALL BE REMOVED WHEN NOT APPLICABLE. THE BOTTOM OF THE
SIGN SHALL BE A MINIMUM OF 1 FOOT ABOVE THE PAVEMENT SURFACE.
D) THE CONTRACTOR SHALL MARK ALL HAZARDS WITHIN THE LIMITS OF THE PROJECT WITH WELL-MAINTAINED SIGNS, BARRICADES, WARNING AND/OR CHANNELIZING DEVICES. ON CONNECTING ROADS, ALL BARRICADES, SIGNS, WARNING, AND/OR CHANNELIZING DEVICES SHALL BE MOVED, SUPPLEMENTED, CHANGED, OR REMOVED AS REQUIRED DURING THE
PROGRESS OF CONSTRUCTION AS APPROVED BY THE ENGINEER.
E) FLAGGERS' ATTIRE SHALL INCLUDE A FLUORESCENT ORANGE VEST, SHIRT, OR JACKET WORN AS THE OUTER LAYER OF CLOTHING. THE FLAGGER SHALL BE EQUIPPED WITH A STOP/SLOW PADDLE (SEE MUTCD, PART IV, SECTION 6F-2, PAGE 6F-1). RED FLAGS WILL BE ACCEPTABLE IN LIEU OF THE PADDLE IN EMERGENCY SITUATIONS ONLY. FLAGGERS, PROPERLY EQUIPPED AND INSTRUCTED, WILL BE PROVIDED BY THE CONTRACTORS AND STATIONED AT THE LOCATIONS SPECIFIED
OR AS DIRECTED BY THE ENGINEER. A FLUORESCENT ORANGE CAP MAY BE REQUIRED.
F) THE CONTRACTOR SHALL BE REQUIRED TO FURNISH, INSTALL, RELOCATE, AND MAINTAIN ALL TRAFFIC CONTROL DEVICES, SIGNS, BARRICADES, WARNING AND/OR CHANNELIZING DEVICES FOR WORK SITES AND DETOUR ROUTES AS SHOWN IN TRAFFIC CONTROL PLANS UNLESS OTHERWISE SPECIFIED WITHIN THE TRAFFIC CONTROL PLANS. THE LOCATION AND POSITIONING OF THESE BARRICADES, SIGNS, ETC. SHALL BE APPROVED BY THE ENGINEER.
G) WORK ON THE PROJECT OR ANY SEPARATE ACTIVITY THEREIN SHALL NOT START UNTIL ALL OF THE REQUIRED SIGNS, BARRICADES, WARNING, AND/OR CHANNELIZING DEVICES ARE INSTALLED AND APPROVED BY THE ENGINEER.
H) THE PROJECT NOTES ARE NOT INTENDED TO BE USED AS GENERAL NOTES FOR THE PROJECT. THEY ARE TO BE USED AT
SPECIFIC LOCATIONS AS REQUIRED BY THE DETAILS OF THE TRAFFIC CONTROL PLANS.
I) THE CONTRACTOR SHALL CONTACT IMPLEMENTATION MANAGER WITH THE CITY OF CHARLOTTE DEPARTMENT OF TRANSPORTATION (CDOT) TWO WEEKS PRIOR TO BEGINNING ANY WORK THAT WILL REQUIRE THE PLACEMENT OF SIGNS OR OTHER TRAFFIC CONTROL DEVICES BY THE CITY. CONTACT MUST BE IN WRITING TO THE MANAGER, TRANSPORTATION
ENGINEERING DIVISION, WITH CURRENT TELEPHONE CONTACT.
J) THE CONTRACTOR IS TO NOTIFY CDOT 10 WORKING DAYS IN ADVANCE OF ANY ROAD CLOSURE OR 5 WORKING DAYS PRIOR TO CLOSING ONE OR MORE TRAVEL LANES. ALL SIGNAL REVISIONS OR SHIFTS OF SIGNAL HEADS WILL BE THE RESPONSIBILITY OF CDOT FORCES; HOWEVER, PRIOR TO REVISING TRAFFIC LANES WHICH REQUIRE SIGNAL REVISIONS, THE CONTRACTOR SHALL NOTIFY THE CDOT IMPLEMENTATION SECTION MANAGER A MINIMUM OF 30 CALENDAR DAYS IN ADVANCE. THE TRAFFIC LANES SHALL NOT BE SHIFTED UNTIL THE REQUIRED SIGNAL REVISION / SHIFT IS COMPLETE AND
READY FOR ACTIVATION.
K. THE CONTRACTOR MUST HAVE A MINIMUM OF TWO FLAGMEN PRESENT DURING ALL PERIODS OF CONSTRUCTION ACTIVITY TO ASSIST IN THE MOVEMENT OF TRAFFIC THROUGH THE WORK AREA. ADDITIONAL FLAGMEN MAY BE REQUIRED
AS DIRECTED BY THE ENGINEER OR CDOT.
L. ANY EXISTING PAVEMENT MARKINGS DETERMINED BY THE ENGINEER TO BE MISLEADING OR IN CONFLICT WITH THE TRAFFIC CONTROL PLAN SHALL BE REMOVED IMMEDIATELY BY THE CONTRACTOR PRIOR TO PROCEEDING WITH ANY
CONSTRUCTION ACTIVITY.
M. ALL TEMPORARY PAVEMENT MARKINGS APPLIED BY THE CONTRACTOR SHALL BE IN PAINT UNLESS OTHERWISE
SPECIFIED ON THE PLANS OR IN THE SPECIAL PROVISIONS.
N) THE CONTRACTOR SHALL MAINTAIN TWO WAY TRAFFIC ON ALL PORTIONS OF THIS PROJECT UNLESS OTHERWISE SPECIFIED HEREIN, AND WILL BE REQUIRED TO PROVIDE PROPERTY OWNERS AND TENANTS ACCESS TO THEIR PROPERTY
THROUGHOUT THE PROJECT, INCLUDING INGRESS AND EGRESS FOR BUSINESSES.
O) TRAFFIC CONTROL PLANS (TCP) FOR THIS PROJECT CONSIST OF SEVERAL TYPICAL DRAWINGS AND STANDARDS SHOWING TRAFFIC CONTROL DEVICES TO BE USED WHERE VARIOUS TYPES OF CONSTRUCTION ACTIVITIES ARE OCCURRING ON THE PROJECT. THESE DRAWINGS ARE FOR TYPICAL SITUATIONS AND SHOULD BE ADAPTED TO THE ACTUAL FIELD CONDITIONS WHICH EXIST. DUE TO THE UNFORESEEN FIELD SITUATIONS, IT MAY BE IMPOSSIBLE TO ADAPT THE PRESCRIBED TYPICAL DRAWING OR STANDARD EXACTLY AS SHOWN TO THE ACTUAL FIELD SITUATIONS. THE CONTRACTOR, AT THE DIRECTION OF THE ENGINEER, SHALL MOVE, SUPPLEMENT, CHANGE, AND/OR REMOVE THE TRAFFIC CONTROL DEVICES ASSOCIATED WITH THESE TYPICAL DRAWINGS AND/OR STANDARD DRAWINGS TO ENSURE THAT THE
MOTORIST CAN PASS THROUGH THE CONSTRUCTION AREA IN A SAFE AND EFFICIENT MANNER.
* BALLASTING SHALL BE DONE WITH SANDBAGS OR OTHER YIELDING MATERIALS PLACED IN SUCH A POSITION THAT THEY
DO NOT BECOME MISSILES OR CAUSE UNREASONABLE DAMAGE IF HIT.
P. THE CONTRACTOR IS TO NOTIFY (BY MAIL) ALL PROPERTY OWNERS AND OCCUPANTS WHO HAVE DIRECT ACCESS TO THE ROADWAY CONTAINING THE PROJECT SITE A MINIMUM OF 5 AND A MAXIMUM OF 10 WORKING DAYS PRIOR TO INSTALLING TRAFFIC CONTROL DEVICES IN FRONT OF THOSE PROPERTIES. NOTIFICATIONS SHOULD INCLUDE CONTACT PERSONS
NAME, TELEPHONE NUMBER, EMAIL ADDRESS, AND MAILING ADDRESS.
Q. THE CONTRACTOR SHALL PATROL THE WORK SITE AS NEEDED TO ENSURE THAT ALL TRAFFIC CONTROL DEVICES ARE IN
PLACE AND FUNCTIONING PROPERLY AT ALL TIMES.
R. DURING PERIODS OF INACTIVITY OR AT NIGHT, EQUIPMENT SHALL NOT BE PARKED IN SUCH A MANNER AS TO BLOCK THE MOTORISTS' VIEW OF TRAFFIC OR TRAFFIC CONTROL DEVICES AND SHALL BE AT LEAST 10 FEET AWAY FROM THE TRAVEL
LANE.
S. WHENEVER TRAFFIC MUST BE ROUTED ACROSS THE CENTERLINE, THE TWO OPPOSING DIRECTIONS MUST BE PHYSICALLY SEPARATED. TRAFFIC CONES CAN BE USED FOR THIS PURPOSE DURING DAYLIGHT HOURS; REFLECTORIZED DRUMS MUST BE USED AT NIGHT. TRANSPORTATION OR THEIR APPOINTED REPRESENTATIVES ARE AUTHORIZED TO STOP
T. TRAFFIC SHALL NOT BE ROUTED ACROSS THE CENTERLINE WITH CONES OR DRUMS DURING NON-WORKING HOURS UNLESS THE PAVEMENT MARKINGS ARE APPROPRIATELY MODIFIED AND APPROVED BY THE ENGINEER.
U. THE CITY ENGINEER OR DIRECTOR OF THE CHARLOTTE DEPARTMENT OF TRANSPORTATION OR THEIR APPOINTED REPRESENTATIVES ARE AUTHORIZED TO STOP ANY WORK WITHIN CDOT RIGHT OF WAY THAT DOES NOT FOLLOW THIS TRAFFIC CONTROL PLAN OR AS REQUIRED BY THE W.A.T.C.H. AND THE M.U.T.C.D. UNTIL SUCH REQUIREMENTS ARE MET.
CONSTRUCTION PHASING
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
S Tr yo n
St
Hartford Av
So ut h Bv
Freeland Ln De wi tt Ln
Clanton Rd
Yancey Rd
E Peterson Dr
O ld
Pi ne vil le
Rd
S I-7
Hy
E Woodlawn Rd
S Tr yo n St
So ut h B v
Scaleybark Rd
WORK AREA
C
K
E
L B
D
F
Bowman Rd
F
L I
I
I
B D
F
A
Briabend Dr
J
ROAD
CLOSED
SOUTH BLVD
SIGN LEGEND
13-0021
08/22/2025
REW
REW
JAB
JAB
400 S . T r yon S t reet, Suite 1300 Char lot te, NC 28285
(704) 376-6423 N.C. L icense # C-0430 label lapc.com
DIAGRAM A - SOUTH BLVD DETOUR ROUTE
| 2025-08-22T14:27:18-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |