1-PUMP STATION NO. 4 MODIFICATIONS PLANS.pdf
PDF 3 MB Posted
- Attached to
- Montour Township Board of Supervisors - Pump Station No. 4 Modifications (General & Electrical)
- Solicitation number
- Not on record
- Issued by
- Pennsylvania
About this file
This document is a comprehensive set of construction plans and electrical specifications for Pump Station No. 4 Modifications prepared for the Montour Township Board of Supervisors in Columbia County, Pennsylvania. The project involves the replacement and modification of components of the existing submersible pumping station and is divided into two separate contracts: General Construction (including general, mechanical, and site work) and Electrical Construction. The electrical scope of work includes the installation of new submersible pumps, a 40 kilowatt diesel-fired emergency generator with sub-base fuel tank, automatic transfer switch, distribution panel, pump control panel, disconnect switches, lighting fixtures, conduit systems, and associated wiring and grounding infrastructure. The plans are dated October 2026 and were prepared by JHA Companies located in Camp Hill, Pennsylvania. All work must comply with the National Electrical Code (NEC 2017), National Electrical Safety Code (NESC), National Fire Protection Association (NFPA) standards, International Building Code (IBC 2015), OSHA regulations, and all applicable state and local codes.
The electrical specifications establish detailed requirements for all materials, installation methods, and testing procedures. Conduit shall be Schedule 40 PVC underground with rigid galvanized steel for exposed applications, with minimum 3/4-inch sizing. All wiring must be copper THWN building wire installed in raceway, with separate green insulated equipment grounding conductors for all feeder and branch circuits. The 40 kilowatt generator must be a packaged diesel system from manufacturers such as MTU (Rolls Royce), Cummins, or Kohler, complete with cooling system, fuel system rated for 24-hour runtime at full load, battery charger, engine block heater, and weatherproof enclosure. The automatic transfer switch shall be ASCO Series 300 or equivalent with solid-state controls, adjustable voltage sensing (factory-set at 90% pickup and 85% dropout), and in-phase controls for motor loads. The panelboard basis of design is Eaton with acceptable alternates from Schneider or engineer-approved equals, featuring bolt-on circuit breakers with minimum 10,000 RMS symmetrical amperes short circuit rating at 120/240 volts. All electrical work requires insulation resistance testing, conductor continuity testing, and torque testing of terminations prior to energization, with all test results submitted to the owner in three copies. The contractor must provide a one-year warranty on all work and materials and shall obtain all necessary permits, licenses, and approvals from local authorities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 3-Contract 1-Bidding Documents.pdf | ||
| 4-Contract 2-Bidding Documents.pdf | ||
| 2-Contract Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PUMP STATION NO. 4 MODIFICATIONS
OCTOBER, 2026
MONTOUR TOWNSHIP
BOARD OF SUPERVISORS
COLUMBIA COUNTY, PENNSYLVANIA
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID C-1.00
COVER SHEET
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
OU
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
O U
OU OU OU
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID C-1.01
SITE PLAN
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID C-9.10
DETAILS
IN
D
IAN
H
EAD
C
AM
PG
R O
U N
D
S AC
C
ESS R
O
AD
READING STREET
VALVE
VAULT
WET
WELL
LADDER
METER ASSEMBLY
MAIN DISCONNECT
AUTOMATIC
TRANSFER SWITCH
PANEL MDP
PUMP
CONTROL
PANEL
P
1A 10
P
1D10
1M10
LS
1J10
LS
1L 10
LS
1H 10
LS
1G10
LS
P-01
DISC
1B6
P-02
DISC
1E 6
JUNCTION
BOX 'JB-1'1P
EMERGENCY
GENERATOR
IN
D
IAN
H
EAD
C
AM
PG
R O
U N
D
S AC
C
ESS R
O
AD
READING STREET
VALVE
VAULT
WET
WELL
DEMOLITION KEYNOTES-
EXISTING SERVICE ENTRANCE EQUIPMENT, PUMP CONTROL PANEL, FLOATS
AND PUMPS SHALL REMAIN IN SERVICE DURING CONSTRUCTION. LID
PENETRATIONS SHALL BE ABANDONED, AND EXISTING WETWELL SIDE
PENETRATIONS EXCAVATED, CLEANED, AND PUT BACK IN SERVICE FOR
CONSTRUCTION PERIOD. BACKBOARD AND CONTROL PANEL SHALL BE
TEMPORARILY RELOCATED AND SUPPORTED AS REQUIRED.
A. FOLLOWING COMMISSIONING OF NEW PUMPING EQUIPMENT, AND
DISCONNECTION OF EXISTING PPL SECONDARY SERVICE - EXISTING
EQUIPMENT RACK, AND ALL EQUIPMENT, CONDUCTORS, AND RACEWAYS
SHALL BE DISCONNECTED AND REMOVED. RESTORE ABANDONED
SURFACES TO MATCH ADJACENT.
B. COORDINATE WITH INSTALLATION AND COMMISSIONING OF NEW
PUMPING EQUIPMENT, AND DISCONNECT AND REMOVE ABANDONED
RISER AND CONDUCTORS FROM EXISTING PPL RISER POLE.
C. SUITABLY CLOSE ABANDONED UNDERGROUND RACEWAYS, AND
ABANDON IN PLACE.
SHEET KEYNOTES-
1. REFER TO TECHNICAL SPECIFICATIONS FOR ADDITIONAL ELECTRICAL
PROJECT REQUIREMENTS
2. REFER TO SHEET 1 FOR MASTER DRAWING INDEX AND FACILITY ID
LEGEND
3. REFER TO SHEET 2 FOR ELECTRICAL SYMBOLS & ABBREVIATIONS.
GENERAL SHEET NOTES
NOTES:
1. COORDINATE W/APPROPRIATE EQUIPMENT MANUFACTURER BEFORE
CONNECTING COMPONENT
2. S.T.P = SHIELDED TWISTED PAIR
3. V.S.C. = VENDOR PROVIDED CABLE
4. #14AWG = #14 AWG, THHN INSULATED COPPER CONDUCTORS
5. ALL ANALOG WIRING SHALL BE INSTALLED IN RGS CONDUIT
1A P-01 P-01 DISC. V.S.C. 1 N/A
1B P-01 DISC. JB-1 14AWG 3 3/4"
1D P-02 P-02 DISC. V.S.C. 1 N/A
1E P-02 DISC. JB-1 14AWG 3 3/4"
1G LS-1 JB-1 V.S.C. 1 N/A
1H LS-2 JB-1 V.S.C. 1 N/A
1J LS-3 JB-1 V.S.C. 1 N/A
1L LS-4 JB-1 V.S.C. 1 N/A
1M LS-5 JB-1 V.S.C. 1 N/A
1P JB-1 PCP 14AWG 20 1"
* = EXPOSED RACEWAY ONLY, 1 INCH MINIMUM EMBEDDED SIZE. SIZE
SHOWN IS MINIMUM FOR SINGLE CIRCUIT. CIRCUITS OF LIKE NOISE
LEVEL MAY BE COMBINED.
** = INTRINSICALLY SAFE WIRING MUST BE HOUSED IN SEPARATE RACEWAY
PER NEC.
DATA/CONTROL SCHEDULE
KEYNOTE FROM TO CABLE No. OF RACEWAY
TYPE CABLES SIZE *
1. & 2. = SEE TEMPLATES
3. SERVICE ENTRANCE, POWER, AND INTERCONNECTING WIRING FOR THIS
EQUIPMENT NOT SHOWN FOR DRAWING CLARITY. REFER TO SHEET
E-601 FOR WIRING TO DISTRIBUTION AND CONTROL EQUIPMENT. REFER
TO DETAILS #3 & #4, SHEET E-501 FOR RACK CONSTRUCTION AND
MOUNTING SPECIFICS.
4. INSTALL FREE-STANDING, VENDOR-FURNISHED CONTROL PANEL 'PCP' IN
APPROXIMATE LOCATION SHOWN. TERMINATE POWER AND CONTROL
CIRCUITRY SHOWN IN PUMP CONTROL PANEL 'PCP' CONTROL PANEL
PER EQUIPMENT MANUFACTURER'S INSTRUCTIONS.
5. PROVIDE APPROPRIATELY-SIZED, NEMA 4X STAINLESS JUNCTION BOX
FOR TRANSITION OF VENDOR-FURNISHED FLOAT SWITCH CABLE AND
PUMP PROTECTION CONDUCTORS FROM PUMP CABLES, TO BUILDING
WIRE FOR RUN BACK TO CONTROL PANEL 'PCP'. PROVIDE
APPROPRIATELY-RATED CGB FITTINGS FOR VENDOR-FURNISHED
CABLES, AND SEAL BUILDING WIRE AT JUNCTION BOX. REFER TO SHEET
KEYNOTE #8.
6. PROVIDE 3P/60A, NON-FUSIBLE DISCONNECT SWITCHES FOR LOCAL
LOCK-OUT OF SUBMERSIBLE PUMPS, PER SHEET E-601.
VENDOR-PROVIDED SUBMERSIBLE CABLE SHALL TRANSITION TO
BUILDING WIRE WITHIN SWITCH FOR RUN BACK TO CONTROL PANEL
'PCP'. PROVIDE APPROPRIATELY-RATED CGB FITTING FOR
VENDOR-FURNISHED CABLE. REFER TO SHEET KEYNOTE #8.
7. PROVIDE AIR-GAP RACK BOX ASSEMBLY TO SUIT DISCONNECT
SWITCHES AND TERMINAL BOX, IN APPROXIMATE LOCATION SHOWN.
REFER TO SHEET E-501, DETAIL #1 FOR SUGGESTED ARRANGEMENT.
8. SUGGESTED ROUTING OF UNDERGROUND CONDUIT. FIELD
CONDITIONS, AND UNDERGROUND FACILITIES SHALL GOVERN FINAL
LOCATIONS. PROVIDE EMBEDDED RACEWAY PER DETAIL #2, ON SHEET
E-501. REFER TO TEMPLATES THIS SHEET FOR SUGGESTED DUCTBANK
ARRANGEMENTS.
9. PROVIDE 40 KW DIESEL FIRED, EMERGENCY GENERATOR, WITH
SUB-BASE FUEL TANK PER SHEET E-601, IN APPROXIMATE LOCATION
SHOWN. REFER TO FOUNDATION DETAIL ON DRAWING E-501.
10. ROUTE VENDOR-PROVIDED CABLE FROM SUBMERSIBLE EQUIPMENT TO
WETWELL LID PENETRATION, AND AIR-GAP ASSEMBLY. PROVIDE
APPROPRIATE STRAIN-RELIEFS, AND ANTI-CHAFE BUSHINGS AT
SLEEVES.
11. POLE MOUNTED FLOOD LIGHTING FIXTURE, TYPE AS SPECIFIED ON
LIGHTING SCHEDULE, SHEET E-501. CONNECT TO CIRCUIT SHOWN ON
SHEET E-601.
SCALE:2 1/4" = 1'-0"
PUMP STATION PLAN
4' 8'2'0
SCALE:1 1/8" = 1'-0"
PUMP STATION DEMO PLAN
8' 16'4'0
C
B
A
C = UNDERGROUND SCHEDULE 40 PVC RACEWAY CONTAINING
STATUS/CONTROL WIRING, MINIMUM DEPTH - 24"
P3 = UNDERGROUND SCHEDULE 40 PVC RACEWAY CONTAINING
3-PHASE POWER WIRING. REFER TO DRAWING E-601 FOR
SIZES AND QUANTITIES, MINIMUM DEPTH - 24"
P1 = UNDERGROUND SCHEDULE 40 PVC RACEWAY CONTAINING
SINGLE-PHASE POWER WIRING. REFER TO DRAWING
E-602 FOR SIZES AND QUANTITIES, MINIMUM DEPTH - 24"
SP = SPARE SCHEDULE 40 PVC CONDUIT - MINIMUM DEPTH - 24"
BOTTOM NUMBER DENOTES RACEWAY SIZE IN INCHES.
CONDUIT TEMPLATES ARE SHOWN TO SUGGEST DUCTBANK
ARRANGEMENTS ONLY. FIELD CONDITIONS SHALL GOVERN ACTUAL
ARRANGEMENT OF UNDERGROUND CONDUIT RUNS.
CENTERLINE-TO-CENTERLINE, AND CENTERLINE-TO-EDGE DIMENSIONS ARE
MINIMUMS, AND ARE TYPICAL WHERE SHOWN.
REFER TO TRENCH AND DUCTBANK DETAILS ON SHEET E-501.
CONDUIT BUBBLE
NOMENCLATURE:
TEMPLATE NOTE
SCALE: none
TEMPLATE 2
SCALE: none
TEMPLATE 1
6" 7 1/2"
P3
SP
19 1/2"
6"
12"
6" 7 1/2"
P3
C
19 1/2"
6"
19 1/2"
SP
7 1/2"
C
A
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID E-101
ELECTRICAL - EXISTING (DEMO) &
PROPOSED PLANS
UTILITY
METER
BASE
200A
FUSED
DISC
AUTO.
XFER
SWITCH
-DIST-
PANEL
HOT-DIP GALV. UNISTRUT
(TYP)
HSS 3 x 3 x 1/4
(TYP.)
-GENERATOR STRUCTURE TOP OF CONCRETE-
1/ 4"
C
AP
P L.
(T
YP
8'-10" CENTER/CENTER POSTS
NOTE: FULLY WELD ENTIRE ELECTRICAL RACK ASSEMBLY.
3/ 4"
BA
SE
P L.
(T
YP
8" (T
YP
-P O
ST
H
SS
x x
/4 W
/ 1 /4
" C
AP
P L.
-P O
ST
H
SS
x x
/4 W
/ 1 /4
" C
AP
P L.
1' -0
(R
EF
3' -3
1'
-6
1' -6
3/ 4"
6' -5
/4
BASE PLATE BP-1.
FOR DETAIL,
REFER TO
(TYP.)
1/4" GUSSET
PL's. (TYP.)
E-501
BASE PL. 3/4" x 10" x 0'-10" W/
(4) 13/16"Ø HOLES FOR
3/4"Ø HILTI HVU STAINLESS
STEEL ADHESIVE ANCHORS.
(6 5/8" MIN. EMBEDMENT).
POST HSS 4 x 4 x 1/4.
TYP.
1/4
5"
3 1/2" 3 1/2"
5"
10"
BASE PL.
CL BASE PL. & POST.
1/
2"
BA
SE
P L.
P
O
ST
5"
BA
SE
P L.
5"
1/
2"
C L
NOTES: 1.) PROVIDE (4) 1/4" x 3" x 0'-8" GUSSET PLATES TO BOTTOM
OF POST. FULLY WELD TO BASE PLATE AND POST.
2.) PROVIDE (1/4") CAP PLATE TO TOP OF POST.
1. REFER TO TECHNICAL SPECIFICATIONS FOR ADDITIONAL ELECTRICAL
PROJECT REQUIREMENTS
2. REFER TO SHEET 1 FOR MASTER DRAWING INDEX AND FACILITY ID LEGEND
3. REFER TO SHEET 2 FOR ELECTRICAL SYMBOLS & ABBREVIATIONS.
GENERAL NOTES
GENERAL ELECTRICAL NOTES
1. ALL BRANCH CIRCUIT WIRING SHALL BE 2#12 & 1#12 GRD., 3/4" CONDUIT,
UNLESS NOTED OTHERWISE (PROVIDED SEPARATE NEUTRALS AND
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR FOR
ALL FEEDER AND BRANCH CIRCUITS). TERMINATE EACH GROUNDING
CONDUCTOR ON A GROUNDING LUG, BUS, OR BUSHING. ALL BRANCH
CIRCUIT WIRING IS SHOWN DIAGRAMMATIC. CONTRACTOR SHALL
COORDINATE ACTUAL CIRCUIT ROUTING WITH OTHER TRADES AND
BUILDING CONSTRUCTION.
2. ALL NEW WIRING SHALL BE ROUTED IN RACEWAY. PROVIDE PULL BOXES
AT LOCATIONS NEEDED, AND ADEQUATELY SIZED AS REQUIRED FOR THE
EQUIPMENT SERVED.
3. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL EQUIPMENT/DEVICE
REQUIREMENTS FOR EQUIPMENT PROVIDED. CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL ASSOCIATED EQUIPMENT & TERMINATIONS TO
EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS.
4. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED, AND
SHALL MEET THE REQUIREMENTS OF BOTH THE NATIONAL ELECTRICAL
CODE (NEC 2017, ARTICLE 250), AND THE EQUIPMENT/SYSTEM
MANUFACTURER'S REQUIREMENTS FOR TYPES, SIZES, AND QUANTITIES OF
EQUIPMENT GROUNDING CONDUCTORS, EXCEPT WHERE SPECIFIC TYPES,
LARGER SIZES, OR MORE CONDUCTORS THAN REQUIRED BY NEC ARE
INDICATED.
5. THE CONTRACTOR SHALL VERIFY DIMENSIONS AND EXISTING CONDITIONS
PRIOR TO THE START OF THE WORK, NOTIFY THE ENGINEER OF ANY
SIGNIFICANT CHANGES IN DIMENSIONS AND CONDITIONS.
6. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, TOOLS, EQUIPMENT,
AND NECESSARY FACILITIES, AND PERFORM ALL LABOR AND SERVICES OF
EVERY DESCRIPTION AS MAY BE NECESSARY TO COMPLETE THE SCOPE
OF THE WORK DEFINED IN THE CONTRACT DOCUMENTS.
7. FABRICATE AND INSTALL ALL WORK IN STRICT ACCORDANCE WITH THE
NATIONAL ELECTRICAL CODE (NEC 2017), THE NATIONAL ELECTRICAL
SAFETY CODE (NESC), NATIONAL FIRE PROTECTION ASSOCIATION (NFPA),
INTERNATIONAL BUILDING CODE (IBC2015), AMERICANS WITH DISABILITIES
ACT (ADA), NECA STANDARD OF INSTALLATION, OSHA, ALL APPLICABLE
STATE AND LOCAL CODES, GENERAL CONDITIONS AND SUPPLEMENTAL
TERMS OF THE CONTRACT. ALL EQUIPMENT SHALL BE UNDERWRITERS
LABORATORIES (U.L.) LISTED FOR ITS APPLICATION WHERE SUCH ITEMS
ARE REQUIRED.
8. ALL CONTRACTORS AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR
THE PROPER PERFORMANCE OF THEIR WORK, COORDINATION WITH
OTHER TRADES, MEANS AND METHODS OF CONSTRUCTION, AND SAFETY
AND SECURITY WHILE ON SITE.
9. PROTECT EXISTING PROPERTY DURING CONSTRUCTION. REPAIR OR
REPLACE, WITHOUT ADDITIONAL CHARGE TO THE OWNER, ANY EXISTING
WORK DAMAGED DURING THE COURSE OF CONSTRUCTION.
10. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO
CONVEY, IN A GENERAL WAY, THE SCOPE OF THE WORK. THEY ARE NOT
INTENDED TO ILLUSTRATE ALL CONDITIONS WHICH MAY BE ENCOUNTERED
AT THE SITE.
11. UNDERGROUND RACEWAYS SHALL BE SCHEDULE 40 PVC, UNLESS
OTHERWISE NOTED. UNDERGROUND RACEWAYS SHALL TRANSITION TO
RIGID GALVANIZED STEEL PRIOR TO EMERGING FROM THE GROUND. ALL
EXPOSED RACEWAYS SHALL BE RIGID GALVANIZED STEEL.
12. EQUIPMENT LOCATIONS AS DESIGNATED ON THE ELECTRICAL PLANS ARE
DIAGRAMMATIC. FINAL LOCATIONS SHALL BE DETERMINED BY FIELD
CONDITIONS.
SCALE:1 1/2" = 1'-0"
JUNCTION BOX ASSEMBLY
TYPICAL AIR GAP
12"
PIPING SHOWN FOR
REFERENCE ONLY
EXIST. SOIL
4" - COMPACTED 2A
AGGREGATE
OR 6" - TOPSOIL & SEED
6"
4'-0" MIN.
3'-0"
3" WARNING
METAL TAPE (TYP.)
EDGE OF
EXISTING GRADE
SELECT
BACKFILL
SAND,
LIMESTONE
DUST OR
CONCRETE
CONDUIT, QUANTITY,
AND SIZES AS REQUIRED
FINISH SURFACE TO MATCH
EXISTING CONDITIONS.
NOTE: TYPICAL TRENCH FOR
CONDUITS FOR POWER,
CONTROL AND SIGNAL WIRING.
CLEAN COMPACTED
EARTH FILL
6"
6"
6"
7 1/2"
7 1/2" 12"
18" 12" 12"
SCALE:2 NONE
TRENCH DETAIL
TYPICAL
LB FITTING (TYP.)
NEW NEMA 4X
TERMINAL BOX
CABLE SEAL (TYP.)
CROUSE-HINDS #CGB, OR
APPROVED EQUIVALENT
BOLT UNISTRUT
TO CONCRETE BUSHED SLEEVE. (TYP)
WET WELL COVER
INSTALL CABLES ACCESSIBLE FROM HATCH
WITHOUT ENTERING WET WELL
SIDE SECTION
1. CONTRACTOR TO SMOOTH AND DEBURR ALL
ROUGH METAL EDGES.
NOTE`:
FRONT VIEW
CONDUIT FROM GENERATOR
FOUNDATION AREA
3/8" S.S. OPEN EYE BOLT
S.S. KELLEMS TYPE CABLE GRIP
PUMP POWER CORD
FLOAT SWITCH CORDS
ROUND HOLE STOCK (ALUMINUM
3003H14)-.125" THICK 1/4" DIAMETER,
40% OPEN AREA WITH MARGIN (TYP.)
PUMP DISCONNECT
SWITCH (TYP.)
SCALE:3 1/2" = 1'-0".
EQUIPMENT RACK ELEVATION
0 2' 4'1'
SCALE:4 1" = 1'-0".
BASE PLATE BP-1 DETAIL
0 1' 2'6"
NOTE
NOTES
MOUNTING LEGEND
NOTESCATALOG NUMBERTYPE MANUFACTURER LAMPS MTG. VOLT GENERAL DESCRIPTION
C = CEILING
CA = CABLE
P = POLE
PE = PENDANT
S = SURFACE
W = WALL
ALL FIXTURE AND MATERIAL SUBSTITUTIONS REQUIRE SUBMISSION AND REVIEW BY ENGINEER.
1. MOUNT (2) FIXTURES, 180° APART, ON 2" RGS CONDUIT POLE, SUCH THAT BOTTOM/FIXTURE IS 8'-0" ABOVE FINISHED SURFACE.
A
SCALE:5 NONE
LUMINAIRE SCHEDULE
WALKWAY FLOOD120P 5INCLUDEDRFL3-40-4K-W-UNV-K-DBSHUBBELL
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID E-501
ELECTRICAL - CONST DETAILS,
GENERAL NOTES, & SCHEDULE
SHEET KEYNOTES-
c
SCALE:2 NONE
PUMP STATION PROPOSED ONE LINE DIAGRAM
1. COORDINATE WITH PPL TO SWITCH EXISTING AERIAL
SERVICE OVER TO NEW RISER, AT SUCH TIME AS NEW
SYSTEM IS READY FOR COMMISSIONING. PROVIDE
GROUNDING, AND EQUIPMENT PER PPL SPECIFICATIONS
AND SKETCHES. CONTACT PPL TO SCHEDULE
SWITCHOVER @ 1.800.342.5775. REFER TO SHEET E-701
FOR PHYSICAL SERVICE LOCATION, AND E-101 FOR PLAN
INFORMATION.
2. PROVIDE SURGE PROTECTION DEVICE, CONNECTED TO
MDP AS SHOWN. EQUIPMENT SHALL BE AS
MANUFACTURED BY EATON, MODEL #SPD 250 240H 2 P,
OR APPROVED EQUIVALENT.
3. UTILITY'S RISER POLE, WITH UTILITY-OWNED PRIMARY
CONDUCTORS INSTALLED, TERMINATED, AND ENERGIZED
BY UTILITY. PROVIDE UTILITY-APPROVED RISER, AND
SUNLIGHT-RESISTANT CABLES w/ 3-FEET OF COILED
SPOIL FOR UTILITY'S TERMINATION TO AERIAL
SECONDARY.
4. PROVIDE 40kW, 120/240V, THREE-PHASE, DIESEL-FIRED
STANDBY GENERATOR, LOCATED IN THE APPROXIMATE
AREA SHOWN ON SHEET E-101. ACCEPTABLE EQUIPMENT
SHALL BE COMPLIANT WITH APPLICABLE SPEC SECTION,
AND INCLUDE AN INTEGRAL SUB-BASE FUEL TANK,
CAPABLE OF SUPPORTING THE MACHINE FOR 24-HOURS,
AT 100% RATED LOAD.
5. SPARE RACEWAYS SHALL BE EQUIPPED WITH
PULLSTRINGS, AND APPROPRIATELY CAPPED 6 INCHES
ABOVE GRADE OR SLAB.
6. PROVIDE NEMA 3R, 3P/200A, FUSIBLE,
SERVICE-ENTRANCE RATED DISCONNECT SWITCH,
MOUNTED ON EQUIPMENT RACK AS SHOWN ON SHEET
E-101, AND CONNECTED PER THIS SHEET. PROVIDE (3)
200A FUSES INSTALLED, AND REMIT (3) 200A FUSES
(LOOSE, PACKAGED) TO OWNER, FOR HIS USE AS
SPARES.
7. PROVIDE UTILITY APPROVED, SELF-CONTAINED METER
BASE. METER SHALL BE PROVIDED BY UTILITY.
8. CONNECT SERVICE ENTRANCE EQUIPMENT TO GROUND
PER UTILITY, AND NEC ARTICLE 250 REQUIREMENTS.
9. PROVIDE NEMA 3R, 3P/200A, AUTOMATIC TRANSFER
SWITCH, MOUNTED ON EQUIPMENT RACK SHOWN ON
SHEET E-101, AND CONNECTED PER THIS SHEET. REFER
TO APPROPRIATE SPECIFICATION SECTION FOR MORE
DETAIL.
10. PROVIDE 200A, COPPER-BUSSED, NEMA 3R, 240/120V,
THREE-PHASE, CIRCUIT BREAKER DISTRIBUTION PANEL
PER APPROPRIATE SPECIFICATION SECTION,
CONFIGURED AS SHOWN. APPROXIMATE LOCATION OF
EQUIPMENT SHOWN ON SHEET E-101.
12. INSTALL PUMP CONTROL PANEL FURNISHED BY PUMP
VENDOR. CONNECT LINE AND LOAD SIDE POWER WIRING
PER MANUFACTURERS REQUIREMNTS. REFER TO SHEET
E-101 FOR CONTROL WIRING DATA.
13. INSTALL VENDOR-PROVIDED SUBMERSIBLE PUMP CABLE,
FROM PUMP TO TOPSIDE SWITCH, ON AIR-GAP TERMINAL
BOX RACK. REFER TO SHEET E-101 FOR EQUIPMENT
LOCATION, AND DETAIL #1 ON SHEET E-501 FOR
ASSEMBLY SPECIFICS.
14. PROVIDE (3) NEW, NEMA 4X STAINLESS, 3P/30A
NON-FUSIBLE DISCONNECT SWITCHES FOR LOCAL
LOCK-OUT OF PUMP MOTORS.
MAIN
DISCONNECT
SWITCH
AUTO.
TRANSFER
SWITCH
8a b b
1. REFER TO TECHNICAL SPECIFICATIONS FOR ADDITIONAL
ELECTRICAL PROJECT REQUIREMENTS
2. REFER TO SHEET 1 FOR MASTER DRAWING INDEX AND
FACILITY ID LEGEND
3. REFER TO SHEET 2 FOR ELECTRICAL SYMBOLS &
ABBREVIATIONS.
GENERAL NOTES
PANEL SCHEDULE "P1"
CKT # LOAD DESCRIPTION
FEEDER
GRD COND. AMPS POLE
WATTS PER PHASE
POLE AMPS COND. GRD
FEEDER
LOAD DESCRIPTION CKT #
QTY SIZE A B C A B C SIZE QTY
1 PUMP CONTROL PANEL 3 2 8 1 1/4" 100 3 6100 0 3 30 3/4" 10 10 3 SURGE SUPRESSOR 2
3 - - - - - - 6100 0 - - - - - - 4
5 - - - - - - 6100 0 - - - - - - 6
7 PLATFORM RECEPTACLE 2 12 12 3/4" 20 1 180 100 1 20 3/4" 12 12 2 GENERATOR BATTERY CHARGER 8
9 ///////////////////////////////////////// - - - - - - - - - - - - - - ///////////////////////////////////////// 10
11 SPARE - - - - 20 1 0 2000 1 25 3/4" 10 10 2 GENERATOR BLOCK HEATER 12
13 SPARE - - - - 20 1 0 0 1 20 - - - - SPARE 14
15 ///////////////////////////////////////// - - - - - - - - - - - - - - ///////////////////////////////////////// 16
17 0 100 1 20 3/4" 12 12 2 PLATFORM LIGHTING 18
19 0 0 1 20 - - - - SPARE 20
21 ///////////////////////////////////////// - - - - - - - - - - - - - - ///////////////////////////////////////// 22
23 0 0 24
25 0 0 26
27 ///////////////////////////////////////// - - - - - - - - - - - - - - ///////////////////////////////////////// 28
29 0 0 30
TOTAL KILOWATTS PER PHASE 6280 6100 6100 100 0 2100
TOTAL A Ø WATTS 6380 TOTAL A Ø AMPS 53 VOLTAGE: 120/ 240V 3Ø, 4W LOCATION: PUMP STATION
INTERIOR
NOTES: COPPER BUS, BOLT ON BREAKERS
TOTAL B Ø WATTS 6100 TOTAL B Ø AMPS 51 AMPACITY: 100A MAIN BREAKER: 200A
TOTAL C Ø WATTS 8200 TOTAL C Ø AMPS 68 AIC RATING: T.B.D. MOUNTING: SURFACE
TOTAL 3 Ø WATTS 20680 TOTAL 3 Ø AMPS 57
REMARKS: ** USE 90°C WIRE ONLY, *** USE 'D' RATED BREAKER
PROVIDE WARNING LABEL "WARNING POTENTIAL ARC-FLASH HAZARDS EXIST WHILE WORKING ON THIS ENERGIZED EQUIPMENT. 240 VOLT, OPEN DELTA SERVICE. NO SINGLE-POLE
BREAKER SHALL BE CONNECTED TO 'B' PHASE.
CONDUCTOR SIZE KEY
a. PROVIDE (4) #3/0 & (1) #4 GRD, 4"C.
b. PROVIDE (4) #3/0 & (1) #4 GRD, 2"C.
c. PROVIDE (3) #10 & (1) #10 GRD, 3/4" C.
d. VENDOR PROVIDED CABLE ASSEMBLY
A kWH kWH
METER
BASE BY
CONTRACTOR,
METER BY
UTILITY
7.5
PUMP
P1 c
PUMP
P2
13 d 13 d
7.5
PUMP
CONTROL
PANEL
PANEL
'P1'
G
40kW DIESEL GENSET
W/SUB-BASE FUEL TANK
3P/150A c c
SCALE:1 NONE
PUMP STATION DEMOLITION ONE LINE DIAGRAM
b b
DEMOLITION KEYNOTES-
A. COORDINATE WITH INSTALLATION AND COMMISSIONING
OF NEW PUMPING EQUIPMENT, AND DISCONNECT AND
REMOVE ABANDONED RISER FROM EXISTING PPL RISER
POLE.
B. FOLLOWING COMMISSIONING OF NEW PUMPING
EQUIPMENT, AND REMOVAL OF EXISTING PPL
SECONDARY SERVICE (REFER TO KEYNOTE 'A', ABOVE),
EXISTING EQUIPMENT RACK, AND ALL EQUIPMENT,
CONDUCTORS, AND RACEWAYS SHALL BE
DISCONNECTED AND REMOVED. RESTORE ABANDONED
SURFACES TO MATCH ADJACENT.
10 12
4-FOOT
RISER
ASSEMBLY
4-FOOT
RISER
ASSEMBLY
B
B
B
B
B
B B
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID E-601
ELECTRICAL - EXISTING (DEMO),
P&ID, & PANEL SCHEDULE
ELECTRICAL LEGENDELECTRICAL SPECIFICATIONS
CONDENSED ELECTRICAL TECHNICAL SPECIFICATIONS:
16.1 GENERAL DESCRIPTION
1. PLANS AND SPECIFICATIONS
A. THE PLANS AND SPECIFICATIONS ARE CONTRACT BID
DOCUMENTS, AND ARE FOR THE PURPOSE OF ILLUSTRATING THE
GENERAL CHARACTER AND SCOPE OF WORK FOR CONTRACTORS
TO PREPARE A BID PROPOSAL. THE PLANS ARE NOT SHOP
DRAWINGS AND DO NOT DISMISS THE CONTRACTOR FROM THE
RESPONSIBILITY OF PREPARING FABRICATION AND INSTALLATION
SHOP DRAWINGS, NOR DO THEY RELIEVE THE CONTRACTOR
FROM THE RESPONSIBILITY OF COORDINATING WITH THE WORK
OF OTHER TRADES AND THE BUILDING STRUCTURE.
2. SUBMITTALS
A. COORDINATION: COORDINATE PREPARATION AND PROCESSING
OF SUBMITTALS WITH PERFORMANCE OF CONSTRUCTION
ACTIVITIES. TRANSMIT EACH SUBMITTAL SUFFICIENTLY IN
ADVANCE OF PERFORMANCE OF RELATED CONSTRUCTION
ACTIVITIES TO AVOID DELAY.
B. SUBMITTAL PREPARATION: PLACE A PERMANENT LABEL OR TITLE
BLOCK ON EACH SUBMITTAL FOR IDENTIFICATION. INDICATE THE
NAME OF THE ENTITY THAT PREPARED EACH SUBMITTAL ON THE
LABEL OR TITLE BLOCK.
C. COLLECT PRODUCT DATA INTO A SINGLE SUBMITTAL FOR EACH
ELEMENT OF CONSTRUCTION OR SYSTEM. PRODUCT DATA
INCLUDES PRINTED INFORMATION, SUCH AS MANUFACTURER'S
INSTALLATION INSTRUCTIONS, CATALOG CUTS, STANDARD
COLOR CHARTS, ROUGHING-IN DIAGRAMS AND TEMPLATES,
STANDARD WIRING DIAGRAMS, AND PERFORMANCE CURVES.
WHERE PRODUCT DATA MUST BE SPECIALLY PREPARED
BECAUSE STANDARD PRINTED DATA IS NOT SUITABLE FOR USE,
SUBMIT AS "SHOP DRAWINGS." SUBMIT PRODUCT DATA FOR THE
FOLLOWING:
1) LUMINAIRES
2) PANELBOARDS
3) WIRE AND CABLE
4) CONDUIT/RACEWAYS
5) TRANSFORMER
6) GENERATOR
7) TRANSFER SWITCH
D. SUBMIT OPERATION AND MAINTENANCE DATA FOR EACH TYPE OF
PRODUCT SPECIFIED IN 1) TO 7) ABOVE FOR INCLUSION IN AN
OPERATION AND MAINTENANCE MANUAL.
E. RECORD DRAWINGS: SUBMIT TWO COPIES OF AS-BUILT
DRAWINGS.
3. WARRANTY
A. THE CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE, IN
WRITING, ALL WORK, ARTICLES, APPLIANCES, MATERIALS,
EQUIPMENT, AND WORKMANSHIP FURNISHED, INSTALLED, OR
SUPPLIED UNDER THIS CONTRACT FOR A PERIOD OF ONE YEAR
FROM THE DATE OF ACCEPTANCE BY THE OWNER.
B. THE CONTRACTOR SHALL ADJUST, REPAIR, OR REPLACE ANY
DEFECTIVE PART OF THE SYSTEM WITHOUT COST TO THE
OWNER.
4. CODES AND STANDARDS
A. PROVIDE EQUIPMENT AND INSTALLATION IN ACCORDANCE WITH
THIS SPECIFICATION AND APPLICABLE REQUIREMENTS OF THE
FOLLOWING:
a. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
b. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
c. AMERICANS WITH DISABILITIES ACT (PUBLIC LAW 101-336)
d. AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
e. NATIONAL ELECTRICAL CODE (NEC)
f. OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA)
g. UNDERWRITERS LABORATORIES INC. (UL)
h. NATIONAL FIRE PROTECTION ASSOCIATION: NATIONAL FIRE
CODES (NFPA)
i. BUILDING OFFICIALS' AND CODE ADMINISTRATORS
INTERNATIONAL, INC. (BOCA), 1996 EDITION
j. PENNSYLVANIA DEPARTMENT OF LABOR AND INDUSTRY FIRE
AND PANIC REGULATIONS
k. ALL LOCAL CODES AND ORDINANCES
B. THE CONTRACTOR SHALL OBTAIN ALL PERMITS, LICENSES, AND
APPROVALS WITH THE DEPARTMENTS HAVING JURISDICTION, PAY
ALL CHARGES AND FEES, FILE ALL NECESSARY PLANS, AND GIVE
ALL NOTICES NECESSARY AND INCIDENT TO DO THE LAWFUL
PROSECUTION OF THE WORK. CONTRACTOR SHALL OBTAIN AND
FURNISH TO THE OWNER ALL CERTIFICATES FOR WORK FOR
WHICH CERTIFICATES ARE REQUIRED. THE CONTRACTOR SHALL
PAY FOR ALL STATE, COUNTY, BOROUGH, AND TOWNSHIP FEES,
PERMITS, LICENSES, LAWS, AND/OR OTHER FEES WHICH MAY BE
REQUIRED IN THE PERFORMANCE OF HIS CONTRACT AND NOT
OTHERWISE PROVIDED FOR.
16.2 CONDUIT
1. SHEET METAL BOXES SHALL BE NEMA TYPE 1 GALVANIZED STEEL
ENCLOSURE WITH SCREW COVER.
2. CONDUIT SIZE SHALL BE 3/4", MINIMUM. WHERE SIZE IS NOT SHOWN
ON THE DRAWING, INSTALL 3/4" CONDUIT UNLESS RECOMMENDED
OTHERWISE BY THE EQUIPMENT MANUFACTURER.
3. LISTING AND LABELING: METAL CONDUITS, TUBING, AND FITTINGS
SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, BY A
QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION
AND APPLICATION.
4. GALVANIZED STEEL RIGID CONDUIT SHALL COMPLY WITH ANSI C80.1
AND UL 6, AND SHALL BE USED FOR ALL AREAS.
5. LIQUID-TIGHT FLEXIBLE METAL CONDUIT SHALL EMPLOY PVC JACKET,
COMPLY WITH UL 360, AND SHALL BE INSTALLED FOR FINAL
CONNECTION TO EQUIPMENT AND INSTRUMENTATION.
6. SUPPORT CONDUIT AT DISTANCES NOT EXCEEDING NEC
RECOMMENDATIONS FOR SPECIFIC CONDUIT TYPES INSTALLED.
7. CONDUIT ENTRY TO ENCLOSURES, PULL BOXES, OR EQUIPMENT
SHALL BE VIA CONDUIT HUB - LISTED FOR INSTALLATION WITH
RACEWAY SYSTEM. DOUBLE LOCKNUTS ARE NOT SUITABLE FOR
RACEWAY ENTRANCES.
16.3 WIRE AND CABLE
BUILDING WIRE
A. FEEDERS AND BRANCH CIRCUITS: COPPER, STRANDED
CONDUCTOR, 600 VOLT INSULATION, TYPE THWN, COMPLYING
WITH UL 83.
B. INSTRUMENTATION WIRING SHALL BE SHIELDED/STRANDED
COPPER PAIRS TWISTED TOGETHER HAVING A TINNED COPPER
DRAIN WIRE AND OVERALL PVC THE CABLES SHALL BE RATED
FOR 600 VOLTS AND 90 DEGREES C.
C. ALL WIRING SHALL BE INSTALLED IN RACEWAY.
2. WIRING CONNECTIONS AND TERMINATIONS
A. SPLICE ONLY IN ACCESSIBLE JUNCTION BOXES.
B. USE SOLDERLESS PRESSURE CONNECTORS WITH INSULATING
COVERS FOR STRANDED TO STRANDED WIRE AND INSULATED
SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR SOLID TO
STRANDED AND SOLID TO SOLID COPPER WIRE SPLICES AND
TAPS, NO. 8 AWG AND SMALLER.
C. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH
ELECTRICAL TAPE TO 150 PERCENT OF THE INSULATION VALUE
OF THE CONDUCTOR.
3. WIRE/CABLE IDENTIFICATION
A. LABEL EACH WIRE AT ALL TERMINATION POINTS.
B. THE FOLLOWING COLOR CODING SHALL BE USED THROUGHOUT:
120/240V - 3 PHASE:
PHASE A - BLACK
PHASE B - RED
PHASE C - BLUE
NEUTRAL - WHITE
GROUND - GREEN
4. CABLE TESTING
A. ALL NEW CABLES, INCLUDING ALL TERMINATIONS SHALL BE
TESTED AFTER INSTALLATION, AND PRIOR TO BEING ENERGIZED.
B. CABLE TEST SHALL CONSIST OF A CONDUCTOR CONTINUITY TEST
FOR ALL CABLES 600 VOLTS AND BELOW.
C. TORQUE TEST ALL CONDUCTOR TERMINATIONS AND
CONNECTIONS TO CABLE AND EQUIPMENT PER
MANUFACTURER'S SPECIFICATIONS.
D. CORRECT MALFUNCTIONING PRODUCTS AT SITE, WHERE
POSSIBLE, AND RETEST TO DEMONSTRATE COMPLIANCE;
OTHERWISE, REMOVE AND REPLACE WITH NEW AND RETEST.
6. APPLICATIONS
A. CONCEALED INTERIOR LOCATIONS: BUILDING WIRE IN RACEWAYS,
OR MC CABLE IN ACCORDANCE WITH NEC REQUIREMENTS.
B. EXPOSED INTERIOR LOCATIONS: BUILDING WIRE IN RACEWAYS.
C. EXTERIOR LOCATIONS: BUILDING WIRE IN RACEWAYS (RIGID
GALVANIZED STEEL CONDUIT).
16.4 PANELBOARDS
1. BASIS OF DESIGN: EATON. ACCEPTABLE ALTERNATES: SCHNEIDER
(SQUARE-D), OR ENGINEER APPROVED EQUAL.
2. BUS STRUCTURE AND MAIN LUGS AS SHOWN ON ONE-LINE DIAGRAM
AND PANEL SCHEDULE.
3. CIRCUIT BREAKERS SHALL BE BOLT-ON, THERMAL-MAGNETIC,
MOLDED CASE CIRCUIT BREAKERS. BREAKERS SHALL BE 1, 2, OR 3
POLES WITH AN INTEGRAL CROSSBAR TO ASSUME SIMULTANEOUS
OPENING OF ALL POLES IN MULTIPLE POLE CIRCUIT BREAKERS.
CIRCUIT BREAKERS SERVING MECHANICAL LOADS SHALL BE UL
LISTED TYPE HACR.
4. SHORT CIRCUIT RATING SHALL BE MINIMUM 10,000 RMS SYMMETRICAL
AMPERES @ 120/240V.
5. BRANCH CIRCUIT PANELBOARDS SHALL BE LISTED BY
UNDERWRITER'S LABORATORIES AND SHALL BEAR THE UL LABEL.
6. CIRCUIT BREAKERS PROVIDED FOR EXISTING PANELBOARDS SHALL
BE COMPATIBLE WITH EXISTING PANELBOARD AND SHALL MEET THE
SHORT CIRCUIT RATING OF THE EXISTING PANELBOARD.
16.5 BOXES
1. PROVIDE ELECTRICAL BOXES AS REQUIRED FOR SPLICES, TAPS, EASE
OF WIRE PULLING, EQUIPMENT CONNECTIONS, AND CODE
COMPLIANCE, WHETHER OR NOT SPECIFICALLY SHOWN ON THE
DRAWINGS. VERIFY AND COORDINATE THE LOCATION OF ALL BOXES
AND OUTLETS WITH OTHER TRADES.
2. POLYMER CONCRETE SECTIONAL, OPEN BOTTOM BOX FOR
EMBEDMENT, LISTED FOR USE AS A SPLICE BOX, PULL BOX,
EQUIPMENT ENCLOSURE. STACKABLE FOR INCREASED DEPTH.
STRAIGHT SIDES FOR EASY ADJUSTMENT OF BOX TO GRADE.
3. EMBEDDED BOXES SHALL BE PROVIDED WITH A MINIMUM ANSI TIER 5,
BOLT-DOWN LID.
16.6 LIGHTING
1. PROVIDE LIGHTING LUMINAIRES AND ASSOCIATED CONTROLS AS
INDICATED ON THE CONTRACT DRAWINGS.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR TRAINING OWNER'S
PERSONNEL FOR OPERATION AND MAINTENANCE OF ALL LUMINAIRES
AND ASSOCIATED CONTROLS PROVIDED AS PART OF THIS PROJECT.
3. AFTER INSTALLING LUMINAIRES, SWITCHES, AND ACCESSORIES, AND
AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED, TEST UNITS TO
CONFIRM PROPER OPERATION.
16.7 SECONDARY GROUNDING
1. ELECTRICAL GROUNDING SYSTEM SHALL FULLY COMPLY WITH THE
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE - ARTICLE 250.
2. CONNECT ALL NONCURRENT CARRYING METAL PARTS SUCH AS
METAL CONDUITS, RACEWAYS, OUTLET BOXES, CABINETS,
SUPPORTS, AND SIMILAR PARTS OF ALL ELECTRICAL EQUIPMENT AND
APPARATUS TO THE GROUNDING SYSTEM.
3. EQUIPMENT GROUNDING CONDUCTORS: COMPLY WITH NEC ARTICLE
250 FOR TYPES, SIZES, AND QUANTITIES OF EQUIPMENT GROUNDING
CONDUCTORS, EXCEPT WHERE SPECIFIC TYPES, LARGER SIZES, OR
MORE CONDUCTORS THAN REQUIRED BY NEC ARE INDICATED.
4. PROVIDE A SEPARATE, GREEN INSULATED EQUIPMENT GROUNDING
CONDUCTOR FOR ALL FEEDER AND BRANCH CIRCUITS. TERMINATE
EACH ON A GROUNDING LUG, BUS, OR BUSHING.
16.8 ELECTRICAL IDENTIFICATION
1. ALL WIRE AND CABLE SHALL BE MARKED. POWER CABLES SHALL BE
COLOR CODED AS NOTED IN PARAGRAPH 16.3.3.B. CONTROL AND
INSTRUMENTATION WIRE SHALL BE NUMBERED AT BOTH ENDS.
2. ENGRAVED THREE-LAYER LAMINATED PLASTIC, BLACK LETTERS ON A
WHITE BACKGROUND.
3. PROVIDE NAMEPLATES TO IDENTIFY ALL ELECTRICAL DISTRIBUTION
AND CONTROL EQUIPMENT, AND LOADS SERVED. PANELBOARDS
SHALL HAVE PANEL NAME, AMPERAGE, AND VOLTAGE PROVIDED ON
FRONT COVER OF PANEL. PANELS SHALL BE PROVIDED WITH TYPED
CIRCUIT DIRECTORIES IDENTIFYING ALL LOADS SERVED.
4. PROVIDE SELF-ADHESIVE WARNING LABELS, FACTORY PRINTED,
MULTICOLOR, CONFIGURED FOR DISPLAY ON FRONT COVER, DOOR
OR OTHER ACCESS TO EQUIPMENT. WARNING LABELS AND SIGNS
SHALL INCLUDE THE FOLLOWING LEGENDS:
A. EACH NEW PANELBOARD: "WARNING: POTENTIAL ARC-FLASH
HAZARDS EXIST WHILE WORKING ON THIS ENERGIZED
EQUIPMENT".
B. WORKSPACE CLEARANCE: "WARNING: OSHA REGULATION - AREA
IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR
42 INCHES".
16.9 GENERATOR
1. BASIS OF DESIGN: MTU, A ROLLS ROYCE COMPANY. ACCEPTABLE
ALTERNATES: CUMMINS, KOHLER, OR ENGINEER APPROVED EQUAL.
2. PACKAGED DIESEL ENGINE GENERATOR SYSTEM SHALL INCLUDE
ENGINE GENERATOR, COOLING SYSTEM, FUEL SYSTEM, COMBUSTION
AIR INTAKE AND ENGINE EXHAUST SYSTEMS, STARTING SYSTEM,
WEATHERPROOF, CORROSION-RESISTANT ENCLOSURE, AND THE
FOLLOWING ADDITIONAL FEATURES:
3. BATTERY CHARGER
4. GENERATOR SET MAIN CIRCUIT BREAKER
5. ENGINE BLOCK HEATER
6. ENGINE EXHAUST PIPING.
7. SOUND LIMITING, WEATHERTIGHT ENCLOSURE.
8. RATINGS: 40 KW, 120/240 VAC, 3 PHASE, 60 Hz.
9. SERVICE CONDITIONS:
10. AMBIENT TEMPERATURE: 0°C TO PLUS 40°C.
11. RELATIVE HUMIDITY: 0 - 95%; ALTITUDE: SEA LEVEL TO 1450 FEET.
12. ENGINE: THE ENGINE SHALL BE 4 CYCLE, RADIATOR AND FAN
COOLED. THE HORSEPOWER RATING AT ITS MINIMUM TOLERANCE
LEVEL SHALL BE SUFFICIENT TO DRIVE THE ALTERNATOR AND ALL
CONNECTED ACCESSORIES.
13. SPEED GOVERNOR: MECHANICAL TYPE.
14. AC GENERATOR: SYNCHRONOUS, FOUR POLE, 2/3 PITCH, REVOLVING
FIELD, DRIP-PROOF CONSTRUCTION, SINGLE PRELUBRICATED
BEARING, AIR COOLED BY A DIRECT DRIVE CENTRIFUGAL BLOWER
FAN, AND DIRECTLY CONNECTED TO THE ENGINE WITH A SINGLE
FLEXIBLE DRIVE DISC.
15. THE GENERATOR SHALL BE CAPABLE OF DELIVERING RATED kW
OUTPUT AT RATED FREQUENCY AND POWER FACTOR, AT VOLTAGE
NOT MORE THAN 5% ABOVE OR BELOW RATED VOLTAGE.
16. COOLING SYSTEM: SKID MOUNTED RADIATORS RATED FOR FULL LOAD
OPERATION IN 104°F AMBIENT AS MEASURED AT THE GENERATOR AIR
INLET. RADIATOR SHALL BE BY 50/50 ETHYLENE GLYCOL/WATER
MIXTURE BY THE EQUIPMENT SUPPLIER.
17. ENGINE EXHAUST SYSTEM: MUFFLER: INDUSTRIAL TYPE, SIZED AS
RECOMMENDED BY THE ENGINE MANUFACTURER. CONNECTIONS
FROM ENGINE TO EXHAUST SYSTEM:
18. FLEXIBLE CONNECTIONS OF CORRUGATED STAINLESS STEEL PIPE.
CONNECTION FROM EXHAUST PIPE TO MUFFLER: STAINLESS STEEL
JOINTS WITH LINERS.
19. LUBRICATION SYSTEM: POSITIVE DISPLACEMENT, MECHANICAL, FULL
PRESSURE, LUBRICATION OIL PUMP. FULL FLOW LUBRICATION OIL
FILTERS WITH REPLACEABLE SPIN-ON CANISTER ELEMENTS AND
DIPSTICK OIL LEVEL INDICATORS.
20. STARTING AND CONTROL BATTERIES: STARTING BATTERY BANK
CALCIUM/LEAD ANTIMONY TYPE, 12 VDC, SIZED AS RECOMMENDED BY
THE GENERATOR MANUFACTURER.
21. BATTERY CABLES: SIZED AS RECOMMENDED BY THE GENERATOR
MANUFACTURER.
22. DOUBLE-WALL SUB-BASE FUEL TANK, OF SUFFICIENT CAPACITY TO
SUPPORT 24-HOURS RUN TIME AT 100% LOAD..
23. BATTERY CHARGER: UL LISTED 10 AMP VOLTAGE REGULATED
BATTERY CHARGER EQUIPPED WITH FLOAT, TAPER, AND EQUALIZE
CHARGE SETTINGS. THE CHARGER SHALL BE PROVIDED WITH
OPERATIONAL MONITOR INDICATING: LOSS OF POWER, LOW BATTERY
VOLTAGE, HIGH BATTERY VOLTAGE, AND WITH ANALOG DC
VOLTMETER, AMMETER, 12 HOUR EQUALIZE CHARGE TIMER AND
AC/DC FUSES.
24. CONTROL AND MONITORING: CONTROL PANEL MOUNTED ON THE
GENERATOR SET (WITHIN GENERATOR ENCLOSURE) WITH WITH
STANDARD FEATURES AND METERING.
25. IN ADDITION, PROVISION SHALL BE MADE FOR A COMMON ALARM
CONTACT "GENERATOR TROUBLE".
26. GENERATOR MAIN CIRCUIT BREAKER: SET MOUNTED & WIRED; UL
LISTED, MOLDED CASE.
27. WATER JACKET HEATER: ENGINE MOUNTED, THERMOSTATICALLY
CONTROLLED, SIZED AS RECOMMENDED BY GENERATOR
MANUFACTURER.
16.10 AUTOMATIC TRANSFER SWITCH
1. BASIS OF DESIGN: ASCO, SERIES 300. ACCEPTABLE ALTERNATES:
EATON, OR ENGINEER APPROVED EQUAL
2. TRANSFER SWITCH COMPLETE WITH ACCESSORIES SHALL BE UL
LISTED.
3. ENCLOSURE NEMA RATING AS SHOWN ON DRAWINGS.
4. SOLID STATE CONTROLS: REPETATIVE ACCURACY OF ALL SETTINGS
PLUS OR BETTER OVER AN OPERATING TEMPERATURE RANGE OF
MINUS 20°C TO 70°C.
5. TRANSFER SWITCH FEATURES:
6. ADJUSTABLE VOLTAGE SENSING FOR EACH PHASE; (PICK-UP
85%-100%;
7. DROP-OUT 75%-88%). FACTORY SET FOR PICK-UP AT 90% AND
DROP-OUT AT 85%.
8. ADJUSTABLE TIME DELAY OVERRIDE OF NORMAL SOURCE (0-3
SECONDS), FACTORY SET AT 1 SECOND.
9. VOLTAGE/FREQUENCY LOCKOUT RELAY (PICK-UP 85%-100%):
FACTORY SET AT 95%.
10. ADJUSTABLE RETRANSFER TIME DELAY (0-30 MINUTES); FACTORY SET
AT 10 MINUTES WITH AUTOMATIC DEFEAT OF THE DELAY UPON LOSS
OF VOLTAGE OR SUSTAINED UNDERVOLTAGE OF THE EMERGENCY
SOURCE, PROVIDED THE NORMAL SUPPLY HAS BEEN RESTORED.
11. IN-PHASE CONTROLS: FOR TRANSFER AND RETRANSFER OF MOTOR
LOADS.
12. TEST SWITCH AND SWITCH POSITION PILOT LIGHTS.
13. SOURCE AVAILABLE INDICATING LIGHTS.
14. ONE NORMALLY OPEN SPDT CONTACT FOR EACH OF ATS SWITCH
POSITIONS.
15. ENGINE STARTING AND SHUT-DOWN CONTACTS.
16. ENGINE-GENERATOR EXERCISER: SOLID STATE PROGRAMMABLE TIME
SWITCH WITH EXERCISE TRANSFER SELECTOR SWITCH, PUSH
BOTTON PROGRAMMING CONTROLS, AND INTEGRAL BATTERY
16.11 TESTING
1. AFTER ELECTRICAL INSTALLATION IS COMPLETE, MAKE TESTS TO
DEMONSTRATE THAT ENTIRE SYSTEM IS IN PROPER WORKING ORDER
AND IN ACCORDANCE WITH DRAWINGS AND SPECIFICATIONS. MAKE
NO TESTS LESS THAN OUTLINED HEREAFTER, UNLESS REQUESTED IN
WRITING AND APPROVED BY THE OWNER. TESTS ARE IN ADDITION TO
AND NOR A SUBSTITUTION FOR TESTS OF INDIVIDUAL ITEMS.
2. TESTING SHALL BE PER NETA ATS.
3. PAY ALL COSTS FOR TESTS, INCLUDING COSTS TO RETEST
OCCASIONED BY DEFECTS AND FAILURES OF EQUIPMENT TO MEET
SPECIFICATIONS.
A. REPLACE WIRING AND EQUIPMENT FOUND DEFECTIVE, OR
FAILING TO MEET SPECIFIED REQUIREMENTS, WITHOUT CHARGE,
UNLESS WRITTEN ACCEPTANCE FOR REPAIR IS GIVEN BY OWNER.
B. FURNISH THREE COPIES OF ALL TEST RESULTS TO OWNER.
4. CALIBRATION: FURNISH SUITABLE ELECTRICAL INSTRUMENTS,
INCLUDING VOLTMETERS, AMMETERS, WATTMETERS, AND ALL OTHER
EQUIPMENT NECESSARY TO PERFORM TESTS SPECIFIED. MAKE
NECESSARY OPENINGS IN CIRCUITS FOR TESTING INSTRUMENTS AND
PLACE AND CONNECT ALL INSTRUMENTS, EQUIPMENT, AND DEVICES,
NECESSARY FOR THE TESTS. UPON COMPLETION OF TESTS, REMOVE
INSTRUCTIONS AND INSTRUMENT CONNECTIONS AND RESTORE ALL
CIRCUITS TO PERMANENT CONDITION. CONDUCT TESTS IN PRESENCE
OF OWNER.
5. TESTS:
A. INSULATION RESISTANCE TESTS OF CIRCUITS, 600 VOLTS AND
BELOW:
B. DO NOT SUBJECT CONDUCTORS RATED 600 VOLTS AND BELOW
TO HIGH POTENTIAL DIELECTRIC TESTS. TEST COMPLETE
FEEDER AND BRANCH CIRCUIT OF 600 VOLTS OR BELOW WITH
EVERYTHING BUT POWER SUPPLY AND POWER-CONSUMING
EQUIPMENT, CONNECTED THERETO.
C. DETERMINE INSULATION RESISTANCE VALUES WITH ALL
SWITCHES AND OVERCURRENT DEVICES IN PLACE.
D. USE MEGOHMETER HAVING OUTPUT OF AT LEAST 500 VOLTS TO
DETERMINED INSULATION RESISTANCE VALUE FOR 600 VOLT
RATED CONDUCTORS.
E. ALL CABLES FAILING INSULATION TEST SHALL BE REMOVED,
REPLACED, AND RE-TESTED.
F. WHERE TESTS OF ANY OF THE ABOVE-REFERENCED EQUIPMENT
ARE INCLUDED IN OTHER SECTIONS OF SPECIFICATIONS,
COORDINATE TESTING, AS DIRECTED BY OWNER, TO AVOID
DUPLICATION AND CONFLICT BETWEEN TESTS.
G. PERFORM ABOVE TESTS IN ADDITION TO, AND NOT IN
SUBSTITUTION FOR REQUIRED MANUFACTURER'S FACTORY
TESTS.
5. OPERATING TESTS:
A. OPERATE CIRCUIT BREAKERS AND CONTROL DEVICES TO SHOW
CORRECT AND SATISFACTORY OPERATIONS.
B. WHERE TESTS OF ANY OF THE ABOVE-REFERENCED EQUIPMENT
ARE INCLUDED IN OTHER SECTIONS OF SPECIFICATIONS,
COORDINATE TESTING, AS DIRECTED BY OWNER, TO AVOID
DUPLICATION AND CONFLICT BETWEEN TESTS.
OL
G
MOTOR, HORSEPOWER AS INDICATED ON PLANS
EQUIPMENT DESIGNATION REFER TO GENERAL,
MECHANICAL & PLUMBING DRAWINGS FOR
SCHEDULES
FUSE
CIRCUIT BREAKER
FUSED DISCONNECT SWITCH
NON-FUSED DISCONNECT SWITCH
PULL OUT DISCONNECT
TRANSFORMER
GENERATOR
GROUND
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
OVERLOAD RELAY
CONDUCTORS NOT CONNECTED
CONDUCTORS CONNECTED
DISTRIBUTION PANELBOARD, SWITCHBOARD OR
MOTOR CONTROL CENTER, SHOWN TO SCALE ON
PLANS
DISCONNECT SWITCH, TYPE AND SIZE AS INDICATED
ON DRAWINGS
LP1-14
NEW EXPOSED WIRING IN RACEWAY
NEW WIRING CONCEALED IN CEILING, WALL OR
UNDERGROUND
BRANCH CIRCUIT HOMERUN TO PANEL , NUMBER OF
ARROWS = NUMBER OF RACEWAYS. ALPHA-NUMERIC
DESIGNATION = PANEL - CIRCUIT #
CONDUIT TURNING DOWN
CONDUIT TURNING UP
JUNCTION BOX
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID E-701
ELECTRICAL - CONDENSED
ELECTRICAL SPECIFICATIONS,
LEGEND & NOTES
18'-0" EMERGENCY GENERATOR PAD
16'-0" 1'-0"
WALL
1'-0"
WALL
-EMERGENCY GENERATOR-
'-0
" E M
ER
G
EN
C
Y G
EN
ER
AT
O
R P
AD
9' -0
1'
-0
W
AL
L
-ANCHOR EMERGENCY GENERATOR PER MANUFACTURERS RECOMMENDATIONS-
NOTES: 1.) REFER TO THE DRAWINGS FOR THE EMERGENCY GENERATOR ORIENTATION.
2.) CONTRACTOR SHALL VERIFY CONDUIT ENTRANCE LOCATION.
3.) REFER TO ELECTRICAL DRAWINGS FOR FINAL CONDUIT ARRANGEMENT.
4.) CONCRETE ENCASE CONDUITS UNDER GENERATOR FOUNDATION.
5.) CONTRACTOR SHALL VERIFY FINAL FOUNDATION SIZE WITH MANUFACTURER.
-HANDRAIL AND TOE PLATE (ALUMINUM) TYP. ALL AROUND PERIMETER (OUTBOARD)-
9" 9"
2'-6"
FOUNDATION
2'-6"
FOUNDATION
9"
9" 9"
2' -6
FO
U N
D
AT
IO
N
9" 9"
2' -6
FO
U N
D
AT
IO
N
A S-101
A S-101
OSHA COMPLIANT
-LADDER (ALUM.)-
7"
4'-3"
1' -0
W
AL
L
3/ 4"
C H
AM
FE
R
TY
P.
A
LL
E
XP
O
SE
D
-E D
G
ES
9"
ELECTRICAL EQUIPMENT RACK.
REFER TO DRAWING E501 FOR
CONTRUCTION DETAILS.
EXISTING
APPROX.
GRADE.
-FOUNDATION LINE(BEYOND)-
-EMERGENCY GENERATOR-
11'-0" EMERGENCY GENERATOR FOUNDATION
9'-0" 1'-0"
WALL
1'-0"
WALL
9" 9"
2'-6"
FOUNDATION
(CONT.) TYP.
(3) #5's EQ. SPA. (BOT.)
(TYP. ALL AROUND)
#6's @ 10 O.C. EACH WAY
(TYP. TOP & BOTTOM)
-BACKFILL-
COMPACTED PENNDOT 2A
COARSE AGGREGATE
(TYP.)
-COMPACTED SUBGRADE-
(TYP.)
TOP OF CONCRETE.
3/4" CHAMFER
(TYP.)
-COMPACTED SUBGRADE-
(TYP.)
5' -8
C
O N
C R
ET
E
W
AL
L 1'
-4
SL
AB
8' -0
" E M
ER
G
EN
C
Y G
EN
ER
AT
O
R F
O U
N D
AT
IO
N
#5 's
O
.C
(T
YP
. E
AC
H F
AC
E)
1' -0
FT
G
3" C
L.
(T
YP
3" C
L.
(T
YP
2" C L.
1 1/2" CL.
(TYP. EACH FACE)
#5's @ 10 O.C. (O.F.) BENT.
#5's @ 10 O.C. (I.F.)
(TYP. ALL AROUND). VERT.
#5 DOWELS @ 10 O.C. (BENT)
(TYP. EACH FACE).
TYP. ALL AROUND. (VERT).
2" x 4" KEYWAY.
(TYP. ALL AROUND).
2" x 4" KEYWAY.
(TYP. ALL AROUND).
NOTES:
1.) CONCRETE FOR FOUNDATION SHALL BE 4000 PSI.
2.) ALL REINFORCEMENT BARS SHALL CONFORM TO ASTM A615, GRADE 60.
3.) ANCHOR GENERATOR TO FOUNDATION PER MANUFACTURERS RECOMMENDATIONS.
EXISTING
GRADE
EL. 479.00
1' -9
(T
YP
1' -9
(T
YP
3' -6
(T
YP
HANDRAIL &
TOE PLATE.
(ALUMINUM)
(TYP. ALL
AROUND).
(3) #5's EQ. SPA. (BOT.)
(TYP. ALL AROUND)
2'-6"
FOUNDATION
(CONT.) TYP.
#5's @ 10 O.C.
(TYP. ALL AROUND).
(6") COMPACTED
PENNDOT 2A
COARSE AGGR.
ON WEED BARRIER
FABRIC OVER
COMP. SUBGRADE.
TYP. ALL AROUND,
ALL 4 SIDES.
4' -0
4'
-0
EL. 483.00
Scale:A 1/2" = 1'-0".
SECTION - EMERGENCY GENERATOR FOUNDATION
0 2' 4'1'
SCALE:1 3/8" = 1'-0"
PLAN - EMERGENCY GENERATOR FOUNDATION
4'2'1'0
FULL TENSION
DEVELOPMENT
LAP SPLICES.
CORNER REBAR SIZE &
SPACING TO MATCH
WALL REINFORCING.
(TYP.)
90° HOOKS.
(INSIDE BARS).
Scale:2 NONE
DETAIL - TYP. CORNER BARS
1. IT IS REQUIRED THAT THE CONTRACTOR VISIT THE PROJECT SITE
PRIOR TO BIDDING TO BECOME FAMILIAR WITH THE BUILDING
STRUCTURE AND EXISTING CONDITIONS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING
CONDITIONS PRIOR TO THE START OF WORK. NOTIFY ENGINEER OF
ANY SIGNIFICANT CHANGES IN DIMENSIONS OR CONDITIONS.
3. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, TOOLS,
EQUIPMENT AND NECESSARY FACILITIES, AND PERFORM ALL LABOR
AND SERVICES OF EVERY DESCRIPTION AS MAY BE NECESSARY TO
COMPLETE THE SCOPE OF WORK DEFINED ON THE DRAWINGS.
4. CONTRACTOR SHALL ARRANGE FOR ALL INSPECTIONS REQUIRED BY
LOCAL MUNICIPALITY.
5. FABRICATE AND INSTALL ALL WORK IN STRICT ACCORDANCE WITH
THE IBC, ALL APPLICABLE STATE AND LOCAL CODES, AND THE
REQUIREMENTS OF THE OWNER.
6. ALL CONTRACTORS AND SUBCONTRACTORS SHALL BE RESPONSIBLE
FOR THE PROPER PERFORMANCE OF THEIR WORK, COORDINATING
WITH OTHER TRADES, MEANS AND METHODS OF CONSTRUCTION,
SAFETY AND SECURITY ON SITE.
7. PROTECT EXISTING PROPERTY DURING CONSTRUCTION. REPAIR OR
REPLACE, WITHOUT ADDITIONAL CHARGE TO THE OWNER, ANY
EXISTING WORK DAMAGED DURING THE COURSE OF CONSTRUCTION.
8. UNLESS ITEMS OF MATERIAL, EQUIPMENT OR WORK ARE
SPECIFICALLY NOTED TO BE PROVIDED OR FURNISHED BY OTHERS,
THEY SHALL BE PROVIDED UNDER THIS CONTRACT.
9. ALL WORK SHALL BE PERFORMED BY SKILLED WORKERS IN A
WORKMANLIKE AND PROFESSIONAL MANNER CONSISTENT WITH
INDUSTRY STANDARDS.
10. DURING THE CONSTRUCTION, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE REMOVAL OF ALL TRASH AND SOLID WASTE.
11. RELOCATE UTILITIES IN THE WORK AREA AS REQUIRED.
12. CONTRACTOR SHALL TEMPORARILY SUPPORT/SHORE EXISTING
CONSTRUCTION AS NEEDED.
13. CONTRACTOR SHALL DEWATER ALL EXCAVATIONS. MAINTAIN WATER
LEVEL TWO (2') FEET BELOW PROPOSED SUBGRADE ELEVATION.
PUMPS SHALL BE RUNNING (24) HOURS A DAY, (7) DAYS A WEEK.
14. CONTRACTOR TO PERFORM A PA ONE CALL.
15. CONTRACTOR RETAIN A PENNSYLVANIA LICENSED SURVEYOR TO
ENSURE THE FOUNDATION IS PLACED INSIDE OF ALL PROPERTY
BOUNDARIES, EASEMENTS, AND SETBACKS. CONTRACTOR'S
SURVEYOR SHALL PERFORM A BOUNDARY SURVEY.
GENERAL NOTES
5. BAR CHAIRS, HIGH CHAIRS, SUPPORT BARS AND ALL OTHER
ACCESSORIES SHALL BE PROVIDED IN ACCORDANCE WITH ACI AND
CRSI STANDARDS.
6. BACKFILL AGAINST WALLS SHALL BE DEPOSITED EVENLY ON EACH
SIDE UNTIL THE LOWER FINAL GRADE IS REACHED. CONTRACTOR
SHALL BRACE THE EXTERIOR PERIMETER WALLS UNTIL SUCH TIME
THE TOP SLAB HAS BEEN PLACED AND FULLY CURED FOR THE 28 DAY
STRENGTH OF 4000 PSI.
7. SIZE AND LOCATION OF ALL WALL AND FLOOR PENETRATIONS SHALL
BE VERIFIED BY THE CONTRACTOR REQUIRING THE OPENING PRIOR
TO PLACING OF CONCRETE.
8. CONTRACTOR SHALL PROVIDE LATERAL SUPPORT OF ALL CONCRETE
WALLS UNTIL SUPPORTING ELEMENTS HAVE BEEN INSTALLED.
9. ANCHOR BOLTS SHALL BE STAINLESS STEEL.
10. NON-SHRINK, NON-METALLIC GROUT TO HAVE A MINIMUM
COMPRESSIVE STRENGTH OF 5000 PSI.
11. ALL REINFORCING SPLICES SHALL BE IN ACCORDANCE WITH ACI 318.
12. CONTRACTOR TO TAKE 4 COMPRESSION TEST CYLINDERS FOR EACH
POUR. EACH SET OF CYLINDERS SHALL BE BROKEN AT 7 AND 28 DAYS
WITH ONE HELD IN RESERVE..
GENERAL STRUCTURAL NOTES
GENERAL STRUCTURAL NOTES
WELDING
1. ALL WELDING SHALL BE IN ACCORDANCE WITH THE "STRUCTURAL
WELDING CODE" AWS D1.1, LATEST EDITION USING E70XX
ELECTRODES UNLESS SPECIFIC WELDING PROCEDURE REQUIRES
OTHERWISE.
2. PROPERLY PREPARE STEEL BEFORE WELDING NEW STEEL TO
EXISTING.
3. ALL WELDERS USED ON THIS PROJECT SHALL BE AWS CERTIFIED
WELDERS FOR THE TYPE OF WELDING BEING DONE.
STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL WORK SHALL CONFORM WITH THE AISC
SPECIFICATION FOR STRUCTURAL STEEL FOR BUILDINGS ADOPTED
JULY 07, 2016.
2. ALL PLATE STRUCTURAL STEEL SHALL CONFORM TO ASTM A36. ALL
CUT AND EXPOSED EDGES SHALL BE GROUND SMOOTH.
3. TUBULAR STEEL SHALL CONFORM TO ASTM A500, GRADE B. ALL WELD
SEAMS MUST BE GROUND SMOOTH.
4. ALL CONNECTIONS SHALL BE WELDED.
5. ALL BASE PLATES & CAP PLATES SHALL BE WELDED TO THE COLUMNS.
6. CONTRACTOR SHALL PROVIDE LATERAL SUPPORT OF ALL STEEL
MEMBERS UNTIL SUPPORTING ELEMENTS HAVE BEEN INSTALLED.
7. ALL HIGH STRENGTH BOLTS TO BE IN ACCORDANCE WITH ASTM
A325N.
8. ALL STRUCTURAL STEEL SHALL BE CLEANED AND GALVANIZED.
AFTER INSTALLATION IS COMPLETE, GALVANIZE WITH REPAIR PAINT
THOSE AREAS WHICH NEED TO BE TOUCHED-UP. REMOVE LOOSE
MILL SCALE, LOOSE RUST OR OTHER FOREIGN MATTER PRIOR TO
GALVANIZING.
9. ALL EXTERIOR EQUIPMENT SUPPORTS SHALL BE HOT-DIPPED
GALVANIZED.
RAILING (HANDRAIL, MID-RAIL/GRAB BAR, AND TOE PLATE)
1. ALL HANDRAILS SHALL BE CONSTRUCTED PER THE 2018 IBC AND OSHA
STANDARDS. CONTRACTOR SHALL SUBMIT COMPLETE SHOP
DRAWINGS AND STRUCTURAL CALCULATIONS SEALED AND SIGNED BY
A REGISTERED PENNSYLVANIA PROFESSIONAL ENGINEER, DESIGNED
USING THE MOST STRINGENT LOADING REQUIREMENTS OF THE
CODES AND STANDARDS LISTED ABOVE.
2. HANDRAIL SHALL BE ALUMINUM, ROUND STRUCTURAL TUBING OR PIPE
CONFORMING TO ASTM B429 ALLOY 6063-T6 OR ASTM B221 ALLOY
6063-T5/T52 OR DRAWN TUBE CONFORMING TO ASTM B210 ALLOY
6063-T832, (1.9") INCHES O.D.
4. ALL TOE PLATES SHALL BE ALUMINUM CONFORMING TO ASTM B209
ALLOY 6061-T6.
5. ALL RAILINGS SHALL BE EITHER WELDED CONSTRUCTION (SMOOTH
ALL WELDS) OR CONCEALED MECHANICAL FASTENERS.
6. ANCHOR HANDRAIL ASSEMBLIES PER DETAILS USING S.S. BOLTS.
LADDER
1. PROVIDE ALUMINUM LADDER MANUFACTURED BY HALLIDAY TYPE LIB
ANCHORED WITH STAINLESS STEEL RODS AND EPOXY ADHESIVE. SIDE
RAILS SHALL EXTEND TO TOP OF RAILING.
FOUNDATION
1. CONTRACTOR TO RETAIN A PENNSYLVANIA LICENSED GEOTECHNICAL
ENGINEER, WHO SHALL VERIFY THAT THE SUBGRADE CAN SUPPORT
2000 PSF.
2. BACKFILL MATERIAL SHALL BE COMPACTED TO (100%) PERCENT OF
THE STANDARD PROCTOR MAXIMUM DRY DENSITY PER ASTM 0698.
CONCRETE
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH ACI 301-10 AND
318-14.
2. ALL CAST-IN-PLACE CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE
STRENGTH OF 4000 PSI AT (28) DAYS, UNLESS NOTED OTHERWISE.
3. ALL REINFORCING BARS SHALL MEET THE REQUIREMENTS OF ASTM
A615, GRADE 60. DETAILING SHALL CONFORM TO ACI 315, LATEST
EDITION.
4. PROVIDE CORNER BARS AT ALL CORNERS AND INTERSECTIONS PER
ACI MANUAL OF STANDARD PRACTICE.
(CONT.)
NOTES:
1.) LAP LENGTHS PER ACI 318, GRADE "B".
2.) DECREASE SPLICE LENGTHS BY 30%
TO DETERMINE DEVELOPMENT LENGTHS.
FOR ALL NON-PRESTRESSED CONCRETE
REINFORCEMENT ON THE PROJECT
OTHER THAN THE VAULTS.
TOP BARS ARE DEFINED AS REINFORCEMENT
WITH MORE THAN (12") OF FRESH CONCRETE
PLACED BELOW HORIZONTAL REINFORCEMENT
(WALLS, SLABS, BEAMS, ETC.)
#4 2'-1" #5 2'-7" #6 3'-1"
#8 5'-2" #7 4'-6"
LAP SPLICE
-LENGTH-
#9 5'-10"
OTHER BARS
LAP LENGTH
-LAP SPLICE SCHEDULE-
#10 6'-5"
TOP BARS
LAP LENGTH ***
2'-8" 3'-4" 4'-0"
6'-8" 5'-10"
7'-6" 8'-4"
BAR SIZE:
PUMP STATION NO. 4
MODIFICATIONS
FOR
MONTOUR TWP BOARD
OF SUPERVISORS
LOCATED IN
COLUMBIA COUNTY, PENNSYLVANIA
AS NOTED MES
MES
CJG
2026-10-21
2024-0786
CALL BEFORE YOU DIG!
LOCATION MAP
MD NY OH PA VA WV
www.jhacompanies.com
3705 E TRINDLE RD # 100
CAMP HILL, PA 17001
FOR BID S-101
EMERGENCY GENERATOR
FOUNDATION PLAN, SECTION,
DETAILS & NOTES
File details come from the government source that posted it. Updated .