1-NS1 and NS4 Switchgear Capacitor Bid Set 2025-09-11.pdf
PDF 2 MB Posted
- Solicitation number
- SLCDA-DCM-542411
- Issued by
- Utah
About this file
These documents are bid set drawings for the Salt Lake City International Airport's NS1 and NS4 Switchgear Capacitor project, prepared by Envision Engineering for the Salt Lake City Department of Airports. The project involves comprehensive electrical system modifications and upgrades across multiple buildings (NS1, NS2, NS3, and NS4), including demolition and replacement of electrical infrastructure such as switchgear, panelboards, fire alarm systems, power distribution equipment, and associated conduits and conductors. The project includes detailed plans for electrical, fire alarm, and power system renovations, with specific focus on buildings NS1 and NS4, located at 1150 N 3850 W in Salt Lake City, Utah.
The bid documents include extensive technical drawings, demolition plans, new installation schematics, one-line diagrams, panelboard schedules, and electrical system details. The project involves complex electrical system upgrades, including replacing existing electrical equipment, reconfiguring power distribution, updating fire alarm systems, and ensuring compliance with current electrical codes and standards. The work encompasses multiple electrical systems, including normal and emergency power systems, fire alarm notification and initiation loops, and various electrical panels and circuits. The project appears to be funded through the airport's capital improvement budget, with precise funding details not explicitly stated in the technical drawings.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 3-Project Manual 2025-09-15.pdf | ||
| 2-ConstructionSafetyManual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 www.envisioneng.com
MANAGEMENT DIVISION
SALT LAKE CITY
SALT LAKE CITY, UT. 84114-5550
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SHEET NO.
PROJECT
OF
NO.
SHEETS
PROJECT NO.
BILL WYATT
MAYOR OF SALT LAKE CITY
EXECUTIVE DIRECTOR OF AIRPORTS
ERIN MENDENHALL
DATE
CIVIL & FACILITIES MANAGER
ROBERT S BAILEY, P.E.
SALT LAKE CITY
INTERNATIONAL AIRPORT
RECORD DRAWING
DESIGN & CONSTRUCTION
PROJECT ADDRESS
TELEPHONE 575-2924
542411
542411
BID DOCUMENTS
ROBERT S. BAILEY, PE
ASSISTANT DIRECTOR,
DESIGN AND PROJECT MGMT
DATE
ENV:2023-215
NS1 AND NS4 SWITCHGEAR CAPACITOR
1150 N 3850 W SALT LAKE CITY, UT 84414
RDPRC CONTACT INFORMATION:
ALEKSANDAR RANKOVIC
PHONE: (801) 990-3566
EMAIL: ARANKOVIC@ENVISIONENG.COM
ABBREVIATION SCHEDULE
NOTE: NOT ALL ABBREVIATIONS MAY BE USED.
C CONDUIT
CLSM CONTROLLED LOW-STRENGTH
MATERIAL
EA EACH
ELEC ELECTRICAL
E, EX EXISTING
GND GROUNDING CONDUCTOR
W/ WITH
QTY QUANTITY
RR REMOVE AND RELOCATED
UG UNDERGROUND
U.N.O. UNLESS NOTED OTHERWISE
RMP ROCKY MOUNTAIN POWER
WP WEATHER PROOF
GENERAL SYMBOLS
DESCRIPTIONSYMBOL REMARKS
XX KEYED NOTE
DETAIL REFERENCE
E-1
TOP NUMBER INDICATES DETAIL NUMBER; BOTTOM
LETTER-NUMBER INDICATES DRAWING SHEET WHERE
DETAIL IS SHOWN; WHERE NOT SPECIFICALLY REFERENCED,
DETAIL IS GENERAL IN NATURE AND SHALL APPLY WHERE
APPLICABLE.
E-2
ELEVATION REFERENCE TOP NUMBER INDICATES ELEVATION NUMBER; BOTTOM
LETTER-NUMBER INDICATES WHERE ELEVATION IS SHOWN.
E-2
SECTION REFERENCE TOP NUMBER INDICATES ELEVATION NUMBER; BOTTOM
LETTER-NUMBER INDICATES WHERE ELEVATION IS SHOWN.
ARCHITECTURAL ROOM NUMBER
REVISION NUMBER USED TO DENOTE CHANGES EITHER ISSUED BY ADDENDUM
OR DURING CONSTRUCTION AND TO DENOTE RECORD
DRAWING CHANGES.
BREAKLINE USED TO BREAK DRAWINGS.
REVISION CLOUD USED TO DENOTE AREAS, DEVICES, EQUIPMENT DETAILS, ETC.
AFFECTED BY THE REVISION.
GENERAL NOTES
1. ALL WORK SHALL BE COORDINATED WITH AIRPORT OPERATIONS THROUGH ENGINEER.
2. ELECTRICAL DRAWINGS ARE BASED ON INFORMATION PROVIDED ON EXISTING AS-BUILT DRAWINGS AND FIELD OBSERVATIONS. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING ANY WORK AND THROUGHOUT DEMOLITION AND CONSTRUCTION.
3. THE CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL SAFETY REGULATIONS.
4. THE CONTRACTOR SHALL CONFINE CONTRACTOR'S EMPLOYEES AND EQUIPMENT TO THE PROJECT WORK AREA.
5. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR'S FIELD OFFICE AND EQUIPMENT PARKING AREA SHALL BE RESTORED TO ITS ORIGINAL CONDITION .
6. THE CONTRACTOR SHALL MEET ALL OPERATING REQUIREMENTS OF THE CONSTRUCTION SAFETY AND SECURITY COMPLIANCE MANUAL FOR THE SLCIA
(LATEST EDITION).
7. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING THE BID, AND SHALL EXAMINE ALL PHYSICAL CONDITIONS WHICH MAY BE MATERIAL TO THE PERFORMANCE OF THEIR WORK. NO ADDITIONAL PAYMENTS WILL BE ALLOWED TO THE CONTRACTOR AS A RESULT OF THE EXTRA WORK MADE NECESSARY BY THE CONTRACTOR'S FAILURE TO DO SO. ANY CASE OF DISCREPANCY OR LACK OF CLARITY SHALL BE PROMPTLY IDENTIFIED TO THE OWNER'S REPRESENTATIVE
AND THE ENGINEER FOR CLARIFICATION.
EQUIPMENT AND CONTROL SYMBOLS
DESCRIPTIONSYMBOL REMARKSMOUNTING
LOAD CENTER (SURFACE-MOUNTED) TOP AT +72" 14"W X 3"D
20"W X 6"DTOP AT +72"LIGHTING AND APPLIANCE PANELBOARD (SURFACE-MOUNTED)
POWER DISTRIBUTION PANELBOARD WALL OR RACK
MOUNTED
THESE SYMBOLS ARE GENERAL IN
NATURE AND MAY VARY IN SIZE AND
SHAPE TO SUIT APPLICATION. CROSS
HATCHING INDICATES "MAIN
PANELBOARD OR SWITCHBOARD" NAME
IS INDICATED IN SEMI-QUOTES (I.E. 'L2A',
'MDP')
SWITCHBOARD PAD MOUNTED
METER BASE TOP AT +72"
PHASING REQUIREMENTS
1. ALL WORK IN SNOWPLOW AND MECHANIC SHOPS SHALL BE ACCOMPLISHED BETWEEN APRIL 15TH AND NOVEMBER
1ST.
2. THE CONTRACTOR SHALL SUBMIT A DETAILED PHASING PLAN TO THE OWNER AND ENGINEER FOR REVIEW AND APPROVAL. THE CONTRACTOR SHALL ALLOW 30 DAYS FOR THE OWNER AND ENGINEER TO REVIEW AND APPROVE
THE PLAN AND NOTIFY EFFECTED PARTIES.
3. THE PHASING PLAN SHALL INCLUDE ALL EQUIPMENT, CONDUIT, CONDUCTORS THAT ARE REQUIRED TO BE MODIFIED IN THIS PROJECT FROM DAY 0 TO COMPLETION. THIS INCLUDES, BUT IS NOT LIMITED TO, ALL PERMANENT AND
TEMPORARY EQUIPMENT, TEMPORARY FEEDERS, TRANSFER SWITCHES, GENERATORS, ETC.
4. OUTAGES SHALL BE LIMITED TO 4 HOURS WHERE POSSBILE AND SHALL TAKE PLACE DURING OFF HOURS. ANY OUTAGE REQUIRING LONGER THAN 4 HOURS SHALL TAKE PLACE DURING THE WEEKEND. THE WEEKEND PERIOD WILL BEGIN AT THE END OF THE DAY ON FRIDAY AND POWER SHALL BE RETURNED BY THE START OF THE STANDARD WORK SHIFT ON MONDAY MORNING. CONTRACTOR SHALL CONFIRM WORK TIMES WITH THE AIRPORT
PRIOR TO DEVELOPING PHASING PLAN.
5. THE PLAN SHALL INCLUDE ANTICIPATED TIME OF COMPLETION AND REQUIRED OUTAGE TIMES TO COMPLETE THE
WORK.
6. THE EXISTING NS4 GENERATOR SHALL BE UTILIZED TO PROVIDE TEMPORARY POWER WHILE THE BUILDING'S ELECTRICAL SERVICE IS NOT IN OPERATION. CONTRACTOR SHALL PROVIDE AND INSTALL TEMPORARY WIRING AS REQUIRED TO REWIRE THE EXISTING GENERATOR AND WILL RETURN THE WIRING BACK TO THE ORGINAL
CONFIGURATION PRIOR TO PROJECT CLOSE OUT.
7. REPLACED ELECTRICAL EQUIPMENT DISTRIBUTED THROUGHOUT NS1 SHALL BE INSTALLED NEXT TO EXISTING EQUIPMENT. BRANCH CIRCUITS AND FEEDERS SHALL BE DEMOLISHED AND REPLACED ON THE NEW PANEL ONE BY
ONE.
BRANCH CIRCUITING SYMBOLS
DESCRIPTIONSYMBOL REMARKS
BRANCH CIRCUIT HOME RUN TO PANEL ARROWS:
NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS
REQUIRED.
2 CIRCUIT, BRANCH CIRCUIT HOME RUN TO PANEL
3 CIRCUIT, 4 WIRE BRANCH CIRCUIT HOME RUN TO PANEL
BRANCH CIRCUITING (U.N.O.) TURNED UP OR TOWARDS
OBSERVER.
BRANCH CIRCUITING (U.N.O.) TURNED DOWN OR AWAY FROM
OBSERVER.
BRANCH CIRCUITING (U.N.O.) CONTINUATION
CONDUIT STUB-IN CAP AND MARK
INCOMING SERVICE
UNDERGROUND FEEDER
J
JUNCTION BOX MOUNT AS NOTED. SUBSCRIPT 'F' INDICATES TO PROVIDE A
FLOOR BOX WITH BLANK COVERPLATE.
ARROWS:
NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS
REQUIRED.
ARROWS:
NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS
REQUIRED.
DESCRIPTIONSYMBOL MOUNTING REMARKS
AS SPECIFIED
OR DETAILED
WALL-MOUNTED FIXTURE REFER TO ARCHITECTURAL EXTERIOR
ELEVATIONS FOR MOUNTING HEIGHT
LIGHT FIXTURES AS SPECIFIED
OR DETAILED
WALL-MOUNTED LINEAR LIGHT FIXTURE AS SPECIFIED
OR DETAILED
EGRESS LIGHT FIXTURE AS SPECIFIED
OR DETAILED
THIS IS AN EXAMPLE OF AN EGRESS
LIGHT FIXTURE. EGRESS LIGHT FIXTURES
ARE HALF-SHADED DIAGONALLY
CEILING MOUNTED EXIT SIGN CEILING
WALL-MOUNTED EXIT SIGN WALL ABOVE
DOOR
DARKENED PORTION OF SIGN
INDICATES
FACE(S); ARROW(S) INDICATE
CHEVRON
DIRECTION(S)
1. LIGHT FIXTURE SYMBOLS ARE GENERAL IN NATURE AND MAY BE SHOWN ON THE DRAWINGS IN VARIOUS SIZES AND SHAPES.
REFER TO THE LIGHT FIXTURE SCHEDULE FOR SPECIFICATION INFORMATION.
2. ARROWS INDICATE AIMING DIRECTION.
LIGHTING SYMBOLS FIRE ALARM SYMBOLS
DESCRIPTIONSYMBOL MOUNTING REMARKS
EOL END OF LINE RESISTOR PER MANUF.
REC.
T TAMPER SWITCH AT VALVE
W WATER FLOW INDICATOR ON FIRE RISER
FSD FIRE/SMOKE DAMPER
HEAT DETECTOR
CARBON MONOXIDE DETECTORCO X
X SMOKE DETECTOR
CEILING
WALL MOUNTED:
MAX 12" FROM
BOTTOM OF CEILINGCARBON MONOXIDE DETECTORCO X
SMOKE DETECTORX
SUBSCRIPT INDICATES SPECIFIC
REQUIREMENTS/OPTIONS:
'SB' DEVICE WITH SOUNDER BASE
'R' DEVICE WITH ADDRESSABLE RELAY
'RES' DEVICE HAS 120V. SMOKE ALARM
W/BATTERY BACKUP
DUCT SMOKE DETECTOR SIDE OF DUCT
F FIRE ALARM MANUAL STATION
Z CONTROL MODULE AT DEVICE(S) TO BE
CONTROLLED
I MONITOR MODULE AT DEVICE(S)
TO MONITOR
R FAN SHUTDOWN RELAY AT CONTROL
PANEL
D
MAGNETIC DOOR HOLDER COORDINATE
WITH DOOR
INSTALLER
COORDINATE WITH DOOR INSTALLER;
SUBSCRIPT 'F' INDICATES TO MOUNT
AT FLOOR LEVEL
WF WATER FLOOD CONTROL FLOOR
FIRE ALARM VISUAL STROBE
FIRE ALARM AUDIO/VISUAL HORN/STROBE
CEILING MOUNTED FIRE ALARM AUDIO/VISUAL HORN/STROBE
FACP FIRE ALARM CONTROL PANEL
INDOOR - REFER TO
TYPICAL ADA AND
EQUIPMENT
MOUNTING HEIGHT
DETAIL.
OUTDOOR - 120"
FROM FINISH
FLOOR TO LENS.
SUBSCRIPT 'WP' INDICATES THAT A
WEATHER PROOF BACK BOX IS REQ.
NUMERIC SUBSCRIPT INDICATES
CANDELA RATING OF STROBE
(I.E. - 15, 75, 110)
X HEAT DETECTOR
X
D
ASD ASD CONTROL PANEL
LIGHTING CONTROLS
DESCRIPTIONSYMBOL MOUNTING REMARKS
SINGLE-POLE TOGGLE SWITCH +48"
THREE-WAY TOGGLE SWITCH +48"3
4 FOUR-WAY TOGGLE SWITCH +48"
WIRING DEVICE SYMBOLS
DESCRIPTIONSYMBOL MOUNTING REMARKS
DUPLEX RECEPTACLE +18"
FOURPLEX RECEPTACLE +18"
GROUND FAULT CIRCUIT INTERRUPTER DUPLEX RECEPTACLE +18"
GROUND FAULT CIRCUIT INTERRUPTER FOURPLEX RECEPTACLE +18"
(5-20R)
SPECIAL PURPOSE OUTLET SUBSCRIPT IN PARENTHESIS INDICATES
NEMA CONFIGURATION IF SHOWN. REFER
TO DRAWINGS AND/OR EQUIPMENT
SCHEDULES. CONFIRM EXACT
CONFIGURATION WITH OWNER PRIOR TO
INSTALLATION.
+18"
NON-FUSED DISCONNECT SWITCH +60"
F FUSED DISCONNECT SWITCH +60"
PB PULL BOX
ELECTRONIC SYSTEM GENERAL SYMBOLS
DESCRIPTIONSYMBOL REMARKSMOUNTING
PANEL
NAME
ELECTRONIC SYSTEM PANELBOARD (SURFACE MOUNT) TOP AT 72" ELECTRONIC SYSTEMS MAY INCLUDE
BUT ARE NOT SPECIFICALLY LIMITED
TO, TELEPHONE, DATA, TELEVISION,
LIGHTING CONTROL, CLOCKS, FIRE
ALARM, ACCESS CONTROL, SECURITY,
CCTV, SOUND SYSTEM, NURSE CALL,
OR INTERCOM.
ELECTRONIC SYSTEM PANELBOARD (FLUSH MOUNT) TOP AT 72"PANEL
NAME
ELECTRONIC SYSTEM TERMINAL BOARD TOP AT 72"
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EG002
09/11/2025
09/11/2025
09/11/2025
09/11/2025
DRAWING INDEX, GENERAL NOTES
AND SYMBOLS
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
SHEET INDEX
EG001 COVER SHEET
EG002 DRAWING INDEX, GENERAL NOTES AND SYMBOLS
EG003 AIRPORT MAP
EG004 VICINITY MAP
EG500 DETAILS
EG501 DETAILS
ED100 DEMOLITION PLAN - NS1 SOUTH - POWER
ED101 DEMOLITION PLAN - NS1 NORTH - POWER
ED401 DEMOLITION PLAN - NS4 AND ENLARGED NS1
EP100 NEW PLAN - NS1 SOUTH
EP101 NEW PLAN - NS1 NORTH
EP401 NEW PLAN - NS4 AND ENLARGED NS1
EP700 ONE-LINE DIAGRAMS NOTES AND SYMBOLS
EP701 ONE-LINE DIAGRAMS - DEMO - SERVICE AND NS4
EP702 ONE-LINE DIAGRAMS SERVICE - NS1 - DEMOLITION
EP703 ONE-LINE DIAGRAMS - SERVICE AND NS4
EP704 ONE-LINE DIAGRAMS - NS1
EP801 PANELBOARD SCHEDULES
EP802 PANELBOARD SCHEDULES
EP803 PANELBOARD SCHEDULES
FD100 DEMOLITION PLAN - NS1 SOUTH - FIRE ALARM
FD101 DEMOLITION PLAN - NS1 NORTH - FIRE ALARM
FD200 DEMOLITION PLAN - NS2 - FIRE ALARM
FD300 DEMOLITION PLAN - NS3 - FIRE ALARM
FD500 DEMOLITION PLAN - FIRE ALARM RISER DIAGRAM
FA100 NS1 SOUTH - FIRE ALARM
FA101 NS1 NORTH - FIRE ALARM
FA200 NS2 - FIRE ALARM
FA300 NS3 - FIRE ALARM
FA500 NEW PLAN - FIRE ALARM RISER DIAGRAM
A LEGIBLE FULL SET OF APPROVED PLANS AND DOCUMENTS SHALL BE
REQUIRED TO BE ON-SITE FOR INSPECTION AT ALL TIMES.
PROJECT SCOPE:
BUILDING NS1:
BUILDING NS2:
BUILDING NS3:
BUILDING NS4:
THE RMP SERVICE TRANSFORMER THAT RMP IS REPLACING SITS OUTSIDE BUILDING NS4, AND SERVES BOTH NS1 AND NS4 BUILDINGS WITH A SINGLE POWER METER AND TWO (2) SERVICE DISCONNECTS INSIDE THE RESPECTIVE BUILDINGS. THIS PROJECT WILL REMOVE BOTH TAPS FROM THE TRANSFORMER TO PROVIDE A
SINGLE SERVICE DISCONNECT.
REMOVE AND REPLACE ALL ELECTRICAL DISTRIBUTION PANELBOARDS, SWITCHBOARDS, AND TRANSFORMERS WITHIN THE BUILDING. ALL FEEDER AND BRANCH CIRCUIT CONDUIT AND CONDUCTORS SHALL BE DEMOLISHED AND REPLACED. THE EXISTING BUILDING FEEDERS FROM THE EXISTING UTILITY TRANSFORMER TO THE EXISTING MAIN PANEL SHALL REMAIN IN PLACE AND BE PROTECTED. IT WILL BE EXTENDED TO NEW ELECTRICAL EQUIPMENT ON BOTH ENDS. ALL ACCESSIBLE CONDUIT SHALL BE REMOVED. THE ONLY ABOVE GRADE CONDUIT ALLOWED TO REMAIN AND BE REUSED IS CONDUIT INSIDE WALLS AND PORTIONS OF CONDUIT THAT PENETRATE THE BUILDING SUCH AS OUTER WALLS AND ROOF DECK. IN-WALL CONDUIT AND BACKBOXES SHALL REMAIN AND BE REUSED. ALL OUTLETS AND OUTLET COVER PLATES ARE TO BE DEMOLISHED AND REPLACED. SWITCHES, DISCONNECTS, STARTERS, ETC. SHALL REMAIN IN PLACE AND BE REUSED. LIGHTING IS STAYING. ALL OTHER DEVICES AND EQUIPMENT NOT SPECIFICALLY MENTIONED SHALL REMAIN IN PLACE AND BE REUSED.
THE FIRE ALARM SYSTEM SHALL BE UPGRADED IN THIS BUILDING. THE EXISTING MAIN CONTROL UNIT IS A SIMPLEX 4100U AND SHALL REMAIN. ALL INITIATION DEVICES SHALL BE REPLACED AT A 1:1 RATIO. NOTIFICATION APPLIANCES SHALL BE REPLACED AT A 1:1 RATIO, WITH ADDITIONAL DEVICES INSTALLED AS REQUIRED FOR FULL NOTIFICATION COVERAGE. NAC/TAC PANELS SHALL BE REMOVED AND NEW NAC PANELS SHALL BE PROVIDED. ALL CONDUIT AND WIRING SHALL REMAIN IN PLACE AND BE REUSED WHERE POSSIBLE. NEW
CONDUIT AND WIRING SHALL BE REQUIRED WHERE NEW DEVICES HAVE BEEN ADDED.
THE FIRE ALARM SYSTEM SHALL BE UPGRADED IN THIS BUILDING. THE EXISTING MAIN CONTROL UNIT IS A SIMPLEX 4100U AND SHALL REMAIN. ALL INITIATION DEVICES WILL BE REPLACED AT A 1:1 RATIO. NOTIFICATION APPLIANCES SHALL BE REPLACED AT A 1:1 RATIO, WITH ADDITIONAL DEVICES INSTALLED AS REQUIRED FOR FULL NOTIFICATION COVERAGE. NAC/TAC PANELS SHALL BE REMOVED AND NEW NAC PANELS SHALL BE PROVIDED. THE NEW NAC PANEL IN THIS BUILDING SHALL BE MOVED TO THE OPPOSITE SIDE OF THE WALL IT IS CURRENTLY ON. ALL CONDUIT AND WIRING SHALL REMAIN IN PLACE AND BE REUSED WHERE POSSIBLE. NEW CONDUIT AND WIRING SHALL BE REQUIRED WHERE NEW DEVICES HAVE BEEN ADDED AND FOR RELOCATION OF
NAC PANEL.
THE FIRE ALARM SYSTEM SHALL BE UPGRADED IN THIS BUILDING. THE EXISTING MAIN CONTROL UNIT IS A SIMPLEX 4100U AND SHALL REMAIN. ALL INITIATION DEVICES WILL BE REPLACED AT A 1:1 RATIO. NOTIFICATION APPLIANCES SHALL BE REPLACED AT A 1:1 RATIO, WITH ADDITIONAL DEVICES INSTALLED AS REQUIRED FOR FULL NOTIFICATION COVERAGE. NAC/TAC PANELS SHALL BE REMOVED AND NEW NAC PANELS SHALL BE PROVIDED. ALL CONDUIT AND WIRING SHALL REMAIN IN PLACE AND BE REUSED WHERE POSSIBLE. NEW
CONDUIT AND WIRING SHALL BE REQUIRED WHERE NEW DEVICES HAVE BEEN ADDED.
THE RMP SERVICE TRANSFORMER THAT SITS OUTSIDE THIS BUILDING SERVES BOTH NS1 AND NS4 WITH A SINGLE POWER METER AND TWO (2) SERVICE DISCONNECTS INSIDE THE RESPECTIVE BUILDINGS. THIS PROJECT INVOLVES REMOVING BOTH TAPS FROM THE TRANSFORMER TO PROVIDE A SINGLE SERVICE DISCONNECT.
THE MAIN DISTRIBUTION SWITCHBOARD, MAIN EMERGENCY SWITCHBOARD, AND MCC-B LOCATED INSIDE THE MAIN ELECTRICAL ROOM SHALL BE DEMOLISHED. OUTSIDE THE BUILDING, THE RMP METER BASE AND EXISTING TRANSFORMER PAD SHALL BE REMOVED. THE RMP SERVICE TRANSFORMER SHALL BE RELOCATED BY RMP TO A PADVAULT PROVIDED BY DIV 26. A NEW MAIN SERVICE DISCONNECT AND DISTRIBUTION SWITCHBOARD SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING TO FEED BUILDINGS NS1 AND NS4. A POWER FACTOR CORRECTION CABINET AND CAPACITORS SHALL ALSO BE INSTALLED. UNDERGROUND CONDUIT WORK SHALL BE
REQUIRED TO REFEED EQUIPMENT.
INSIDE THE BUILDING, THE REMOVED MCC AND SWITCHBOARDS SHALL BE REPLACED. EXISTING CONDUIT STUBS SHALL BE REUSED AND EXISTING FEEDERS SHALL BE EXTENDED TO NEW EQUIPMENT AS NEEDED.
THE EXISTING GENERATOR SHALL BE REWIRED AS TEMPORARY POWER WHILE THE ELECTRICAL SERVICE IS DOWN. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY CONNECTIONS AND RETURNING THE
SYSTEM TO ITS ORGINAL CONFIGURATION.
GENERAL PROJECT NOTES
1. THE KNOWN UNDERGROUND UTILITIES ARE SHOWN ON THE PLANS IN THEIR APPROXIMATE LOCATIONS. THE CONTRACTOR SHALL LOCATE ALL UNDERGROUND UTILITIES BY USING NON-DESTRUCTIVE METHODS SUCH AS GROUND PENETRATING RADAR, POT HOLING, OR OTHER APPROVED MEANS.
2. THE CONTRACTOR SHALL FOLLOW THE PANELBOARD SCHEDULES AS INDICATED IN THE DRAWINGS. NO DEVIATION WILL BE
ALLOWED WITHOUT WRITTEN APPROVAL FROM THE ELECTRICAL ENGINEER.
3. AT A MINIMUM, THE CONTRACTOR SHALL INSTALL THE WIRE SIZE AS CALLED OUT ON THE DRAWINGS. HOWEVER, THE CONTRACTOR IS RESPONSIBLE TO ENSURE THE WIRE IS SIZED LARGE ENOUGH TO ALLOW FOR VOLTAGE DROP.
4. ELECTRICAL DRAWINGS ARE BASED ON INFORMATION PROVIDED ON EXISTING AS-BUILT DRAWINGS AND FIELD SURVEY. THE CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND AFTER DEMOLITION/CONSTRUCTION. THE CONTRACTOR SHALL VERIFY ALL EXISTING ELECTRICAL UTILITIES PRIOR TO DEMOLITION OR
EXCAVATION.
5. THE CONTRACTOR SHALL ENSURE THAT ALL AREAS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS
AND OBSTRUCTIONS AT ALL TIMES.
6. EXAMINE STRUCTURAL ELEMENTS PRIOR TO CUTTING AND CORE DRILLING. STRUCTURAL STEEL SHALL BE LOCATED BY USING NON-DESTRUCTIVE TESTING PROCEDURES SUCH AS GROUND PENETRATING RADAR (RADIO FREQUENCY) OR OTHER APPROVED
MEANS.
7. MATERIALS AND DEVICES ASSUMED TO CONTAIN HAZARDOUS MATERIALS ARE TO BE DISPOSED OF AT A FACILITY THAT IS CERTIFIED BY STATE AND FEDERAL ENVIRONMENTAL AGENCIES TO ACCEPT THESE ITEMS FOR DISPOSAL. MATERIALS TO BE REMOVED FROM THE PROJECT SITE FOR DISPOSAL ARE TO BE REPACKAGED IN THE CONTAINERS OF THE REPLACEMENT
LIGHTING TUBE BOXES TO HELP ENSURE AGAINST DAMAGE AND BREAKAGE.
8. UTILIZE GALVANIZED RIGID STEEL CONDUIT WHERE CONDUIT IS SUBJECT TO VEHICULAR DAMAGE (0-10' AFF) AND ELSEWHERE
THAT IS EXPOSED TO POTENTIAL DAMAGE OR WEATHER.
9. PROVIDE INTERMEDIATE JUNCTION / PULLBOXES AS REQUIRED BY NEC CODE.
10. PROVIDE TRU TAPE FOR ALL RACEWAY EXCEEDING 100' PRIOR TO WIRE PULLS. MARK AS-BUILT DRAWINGS WITH RACEWAY
FOOTAGES.
11. PROVIDE A MINIMUM OF 7 DAY NOTICE FOR ALL UTILITY AND DISTRIBUTION BOARD SHUTDOWNS. COORDINATE WITH THE
AIRPORT.
12. CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE, AND LOCAL SAFETY AND ENVIRONMENTAL REGULATIONS.
13. THE CONTRACTOR SHALL CONFINE CONTRACTOR'S EMPLOYEES AND EQUIPMENT TO THE PROJECT WORK AREA.
14. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR'S FIELD OFFICE AND EQUIPMENT PARKING AREA SHALL BE RESTORED
TO ITS ORIGINAL CONDITION BY THE CONTRACTOR.
15. CONTRACTORS REQUIRING DIMENSIONS NOT NOTED, SHALL CONTACT THE ENGINEER FOR SUCH INFORMATION PRIOR TO PROCEEDING WITH THE WORK IN QUESTION. MOST, BUT NOT ALL UNDERGROUND, UTILITIES ARE SHOWN IN THEIR APPROXIMATE
LOCATION ON THE DRAWINGS.
16. THE CONTRACTOR SHALL INFORM ALL UTILITY OWNERS 48 HOURS PRIOR TO ANY EXCAVATION THAT MIGHT AFFECT THESE UTILITIES. IF DAMAGE TO EXISTING UTILITIES IS CAUSED AS A RESULT OF THE CONTRACTOR'S OPERATIONS, THE UTILITIES SHALL BE IMMEDIATELY REPAIRED TO THE SATISFACTION OF THE OWNER AT THE EXPENSE OF THE CONTRACTOR.
17. ALL EXCAVATED MATERIAL, REGARDLESS OF CLASSIFICATION, SHALL BE REMOVED FROM AIRPORT PROPERTY AND PROPERLY DISPOSED OF BY THE CONTRACTOR. THE COSTS FOR EXCAVATING, HAULING, AND DISPOSING OF THE EXCAVATED MATERIAL SHALL BE INCLUDED IN THE CONTRACT UNIT PRICE FOR EACH TYPE OF EXCAVATION IDENTIFIED AS AN ITEM OF WORK IN THE
CONTRACT BID SCHEDULE.
18. THE CONTRACTOR SHALL MAINTAIN A BROOM CLEAN CONDITION ON ALL PUBLIC AND AIRPORT ROADS USED FOR THE CONTRACTOR'S HAULING OPERATION. THE CONTRACTOR SHALL REPAIR AND RESTORE THE ROAD SURFACE, IF DAMAGED AS A RESULT OF CONTRACTOR'S OPERATIONS, TO THE SAME CONDITION AS EXISTED PRIOR TO THE START OF CONSTRUCTION AT THE CONTRACTOR'S OWN EXPENSE. ANY DAMAGE TO AIRPORT APRONS, RUNWAYS, OR TAXIWAYS AS A RESULT OF
CONTRACTOR'S OPERATIONS, SHALL ALSO BE REPAIRED IN A LIKE MANNER.
19. THE CONTRACTOR SHALL MEET ALL OPERATING REQUIREMENTS OF THE CONSTRUCTION SAFETY AND SECURITY COMPLIANCE MANUAL FOR THE SLCIA (LATEST EDITION). CONTRACTOR SHALL SUBMIT A FOD (FOREIGN OBJECT DEBRIS) PLAN A MINIMUM OF
72 HOURS PRIOR TO CONSTRUCTION.
20. THE CONTRACTOR SHALL ADHERE TO ALL COUNTY, CITY, STATE, AND AIRPORT TRAFFIC REGULATIONS CONCERNING THE USE
OF STREETS OR ROADS FOR HAULING.
21. ALL UNDERGROUND CONDUITS ENTERING EQUIPMENT, JUNCTION BOXES, AND LIKE SYSTEMS INSIDE OR OUTSIDE SHALL BE SEALED WITH AN APPROVED MATERIAL OR FITTING IN COMPLIANCE WITH NEC ARTICLE 300.5(G) AND CONTRACT DOCUMENTS.
22. INSULATED THROAT CONNECTORS OR PLASTIC BUSHINGS SHALL BE UTILIZED FOR ALL CONDUIT SIZES USED ON THIS PROJECT.
23. A DEDICATED NEUTRAL CONDUCTOR SHALL BE PROVIDED FOR ALL LIGHTING AND POWER CIRCUITS.
24. THE CONTRACTOR SHALL LABEL ALL ELECTRICAL EQUIPMENT AS IT IS CALLED OUT IN THE SPECIFICATIONS.
25. THE CONTRACTOR SHALL PROVIDE A DETAILED PHASING PLAN PRIOR TO THE START OF CONSTRUCTION. MAXIMUM OUTAGE TIME OF ANY PIECE OF EQUIPMENT SHALL BE LIMITED TO 4 HOURS UNLESS COORDINATED OTHERWISE WITH THE AIRPORT IN ADVANCE. THE CONTRACTOR SHALL BE REQUIRED TO PROVIDE ALL TEMPORARY EQUIPMENT, CONDUCTORS, RACEWAYS, PANELBOARDS, ETC AS REQUIRED TO MAINTAIN TEMPORARY POWER THROUGHOUT THE DURATION OF THE PROJECT. THE EXISTING 300kVA GENERATOR LOCATED INSIDE THE NS4 MAIN ELECTRICAL ROOM SHALL BE UTILIZED FOR TEMPORARY POWER FOR BUILDING NS4 WHILE THE EXTERIOR WORK IS BEING COMPLETED. THE AIRPORT SHALL PROVIDE FUEL AND ALL REQUIRED OPERATIONAL MAINTENANCE WHILE THE GENERATOR IS IN OPERATION. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED
TEMPORARY CONNECTIONS.
26. ALL CONDUCTORS ROUTED UNDERGROUND SHALL BE TYPE XHHW-2.
27. ALL NEW UNDERGROUND ELECTRICAL SPLICES SHALL UTILIZE THE 3M 90 SERIES RESIN KIT.
28. ALL WORK SHALL BE COORDINATED WITH THE AIRPORT THROUGH THE ENGINEER.
29. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING THE BID, AND SHALL EXAMINE ALL PHYSICAL CONDITIONS WHICH MAY BE MATERIAL TO THE PERFORMANCE OF THEIR WORK. NO ADDITIONAL PAYMENTS WILL BE ALLOWED TO THE CONTRACTOR AS A RESULT OF THE EXTRA WORK MADE NECESSARY BY THE CONTRACTOR'S FAILURE TO DO SO. ANY CASE OF DISCREPANCY OR LACK OF CLARITY SHALL BE PROMPTLY IDENTIFIED TO THE OWNER'S REPRESENTATIVE AND THE ENGINEER FOR
CLARIFICATION.
2100 NORTH
DELIVERY AND ACCESS ROUTE
W E
S T
FAA TOWER
GATE 16
CONCOURSE B
CONCOURSE A
EG004
ROCKY MOUNTAIN POWER
REPRESENTATIVE
JUSTIN BEALES
PHONE: 801-419-6861
EMAIL: justin.beales@pacificorp.com
WORK ORDER: 7448485
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EG003
09/11/2025
09/11/2025
09/11/2025
09/11/2025
AIRPORT MAP
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
SCALE: NTS
CAMPUS MAP
TO I-215
BUILDING NS1
ADDRESS: 3850 W 1150 N
BUILDING NS4
ADDRESS: 3851 W 1200 N
ED100
EP100
ED101
EP101
BUILDING NS2
ADDRESS: 3849 W 1200 N
BUILDING NS3:
ADDRESS: 3848 W 1200 N
ED401
EP401
ED401
EP401
ED100
EP100
FD200
FD300
FD300
FA200
FA300
FA300
FD100
FA100
FD101
FA101
FD100
FA100
APPROXIMATE LOCATION
OF EXISTING PANEL 'AL'
APPROXIMATE ROUTING
OF NEW BUILDING NS1 FEEDERS.
PROVIDE BARRICADES AS REQUIRED PER DETAIL 3/EG500
AND STEEL PLATES AS REQUIRED TO COVER OPEN TRENCHES
WHEN WORK IN THE AREA IS NOT ACTIVE.
COORDINATE WITH THE AIRPORT.
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EG004
09/11/2025
09/11/2025
09/11/2025
09/11/2025
VICINITY MAP
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
SCALE: NTS
VICINITY MAP
PROVIDE YELLOW CAUTION TAPE
STRUNG BETWEEN BARRICADES
RUBBER BASE (43 LBS MIN.)
NOTES:
1. 10' MAXIMUM SPACING BETWEEN BARRICADES.
2. USE ROADTECH 33000 SERIES BARRICADE OR APPROVED EQUAL.
3. PROVIDE BARRICADE AROUND ALL WORK AREAS WHERE VEHICLE TRAFFIC
IS EXPECTED.
12" X 24" VERTICAL PANEL ON
BOTH SIDES
WITH ORANGE AND WHITE
REFLECTIVE
HIGH INTENSITY SHEETING
TRENCHING GENERAL NOTES:
TRENCHING KEYED NOTES:
1. PROVIDE PULL 1/4" NYLON ROPES IN ALL CONDUITS.
2. HORIZONTAL AND VERTICAL SEPARATION BETWEEN
CONDUIT SHALL BE MAINTAINED BY INSTALLING HIGH
IMPACT SPACERS WITH HORIZONTAL INTERVALS OF (8)
EIGHT FEET.
3. ALL MARKER TAPE SHALL CONTAIN #10 TRACER WIRE.
4. REFER TO THE ROCKY MOUNTAIN POWER SIX STATE
ESR FOR ADDITIONAL INFORMATION.
5. VERIFY ALL REQUIREMENTS WITH UTILITIES PRIOR TO
TRENCHING.
MARKER TAPE WITH TRACER WIRE LABELED, "CAUTION
BURIED ELECTRIC CONDUITS BELOW" DIRECTLY OVER
POWER CONDUITS 12" MINIMUM BELOW GRADE.
P-153 CLSM (500 PSI) UP TO 5" BELOW EXISTING
ASPHALT LEVEL
NEW ASPHALT DEPTH TO MATCH EXISTING 5" THICK
ASPHALT. ASPHALT EDGE SHALL BE SAWCUT CLEAN
PRIOR TO REPLACEMENT.
ALL CONDUITS SHOWN SHALL BE SCHEDULE 40 PVC;
SEE PLANS AND ONE-LINE DIAGRAMS FOR SIZES.
UNDISTURBED EARTH.
TRENCHES SHALL BE A UNIFORM DEPTH FOR ENTIRE
LENGTH OF TRENCH SO CONDUITS CAN SIT FLAT
(HORIZONTAL) WITH THE GROUND.
T1
T2
T3
T4
T5
T6
T5
T2
T6
T4
12" MIN.
M
IN
M
A X
T5
T2
T6
T4
12" MIN.
M
IN
M
A X
T5
T2
T6
T4
12" MIN.
M
IN
T3
T1 T1
SITE POWER/BRANCH
CIRCUITS
RMP POWER
(SECONDARY POWER)
RMP POWER
(PRIMARY POWER)
6" MIN
T3
6" MIN
T3
6" MIN
TRANSFORMER PADVAULT DIMENSION CHART (2.4-25 KV)
TRANSFORMER
RATING
75-750 KVA
1000-2500 KVA
DIMENSIONS
B SI #C D EA
56" 48" 44" 42" 56" 7992600
84" 54" 72" 48" 62" 7992958
COORDINATE ALL REQUIREMENTS WITH
RMP. REFER TO RMP PUBLICATION ZG-521
FOR ADDITIONAL INFORMATION.
3'-0"
3'-0" 3'-0"
3'-0"
PAD
BLOCKOUT
KEEP THIS AREA CLEARKEEP THIS AREA CLEAR
10'-0"
10'-0" 10'-0"
10'-0" RADIUS
NOTE: TRANSFORMER PAD CLEARANCES
• TRANSFORMERS IN EQUIPMENT YARDS MUST MEET ADDITIONAL REQUIREMENTS.
• SEE RMP ESR WHITEPAPER FOR ADDITIONAL INFORMATION.
12" DIA. HDPE SUMP
A
84"
1/2" DIA. GROUNDING INSERTS
4 EA. REQ'D.
(2 EA. OUTSIDE WALLS
2 EA. INSIDE WALLS)
2.38" DIA. TERM-A-DUCTS
2 EA. REQ'D.
(1 EA. NEAR WALL
1 EA. FAR WALL)
6.63" DIA. TERM-A-DUCTS
24 EA. REQ'D.
(12 EA. NEAR WALL
12 EA. FAR WALL)
D
B
C
5'-8" LONG GALV. "C" CHANNEL
2 EA. REQ'D.
(1 EA. NEAR & FAR WALLS)
72"
BASE
8,081 LBS.
6.33" DIA. TERM-A-DUCTS
12 EA. REQ'D.
(6 EA. NEAR WALL
6 EA. FAR WALL)
GALV. PULL IRON
4 EA. REQ'D.
(1 EA. CORNER)
2'-0" LONG GALV. "C" CHANNEL
4 EA. REQ'D.
(1 EA. WALL)
3.51" DIA. TERM-A-DUCT
1 EA. REQ'D.
FULL 180° OPEN
(TYPICAL)
TOP
PCORP #7992600 - SI #1790023
3,650 LBS.
112"
3/8" DIA. INSERTS W/
HOLD DOWN CLEATS
2 EA. REQ'D.
(SEE DETAIL 1)
16" X 60" BLOCKOUT
NO. 25P GALV. DIAMOND PLATE
DOORS W/ LOCKING BOLTS
84"
8"
E
NOTES:
1. COORDINATE ALL REQUIREMENTS WITH ROCKY MOUNTAIN POWER PRIOR
TO INSTALLATION. REFER TO ROCKY MOUNTAIN POWER DOCUMENTS GV
001 AND ZG 301 FOR GENERAL INFORMATION REGARDING EQUIPMENT
BASES AND INSTALLATION REQUIREMENTS.
2. REBAR REFER TO ROCKY MOUNTAIN POWER MATERIAL SPECIFICATION
ZG 531 FOR ADDITIONAL INFORMATION ON PRE-CAST PAD VAULTS.
3'-0"3'-0"
WINDOW
10'-0"
KEEP THIS
AREA
CLEAR
NO PAD IN
THIS AREA
10'-0" 10'-0"
DOOR
20'-0"
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EG500
09/11/2025
09/11/2025
09/11/2025
09/11/2025
DETAILS
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
SCALE: NTS
TRENCHING DETAIL
SCALE: NTS
ROCKY MOUNTAIN POWER TRANSFORMER PAD VAULT
SCALE: NTS
BARRICADE DETAIL
NOTES:
WHEN INSTALLED ON PAD, SWITCHBOARDS AND DISTRIBUTION BOARDS SWITCH HANDLES SHALL NOT EXCEED 6'-7" FROM GRADE LEVEL
TO CENTER OF SWITCH HANDLE. PROVIDE A PAD THICKNESS OF MIN 4" OR 6" ABOVE GRADE.
EQUIPMENT DEPTH +10" MIN
6" MIN
E Q
U
IP
M E
N T
W
ID
T H
M
IN
PLAN VIEW
4" MIN
M
IN
M
IN
COORDINATE DIMENSIONS WITH SHOP
DRAWINGS, PAD TO BE 4" GREATER ON
EACH SIDE THAN DIMENSION OF
TRANSFORMER
CONCRETE PAD
SECTION VIEW
ELECTRICAL EQUIPMENT
BUILDING
WIRE TIE EACH REBAR
CROSSING (TYP)
6" MIN
1/4" 12"
3" ABOVE GRADE
3/4" BULLNOSE FINISHED
EDGES (TYP)
SURFACE
ELECTRICAL EQUIPMENT
M
IN
4" MIN
#4 REBAR AT 12" OC EACH WAY
TOP AND BOTTOM
REBAR 3" FROM EDGE
OF PAD (TYP)
EQUIPMENT FOOTPRINT
CP 25WB CAULK ON
BOTH SIDES OF
WALL
DAMMING MATERIAL
(BACKER ROD, FIBER-GLASS OR
MINERAL WOOL).
METAL PIPE
OR
CONDUIT
FIRE RATED CONCRETE
WALL (SOLID OR
BLOCK)
METALLIC CONDUIT
1/4" MINIMUM
DIAMETER
BEAD OF 3M FIRE
BARRIER CP 25 CAULK
OR MP MOLDABLE
PUTTY
1/4" MINIMUM
DIAMETER BEAD OF
3M FIRE BARRIER CP
25 CAULK OR MP
MOLDABLE PUTTY
STEEL STUD
GYPSUM BOARD
SOUND ATTENUATION
INSULATION (STC WALLS)
NOTE:
1. TYPICAL DETAILS SHOWING
GENERAL FIRE STOPPING
PROCEDURE. ACTUAL PROCEDURE
DEPENDS UPON ANNULAR SPACE
BETWEEN PIPE AND/OR INSULATION
AND OPENING. FOLLOW
MANUFACTURER'S INSTRUCTIONS.
2. FIRESTOP TESTED UP TO 4 HOURS IN
ACCORDANCE WITH ASTM E 814 (UL
1479) & CAN/ULC S115.
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EG501
09/11/2025
09/11/2025
09/11/2025
09/11/2025
DETAILS
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
SCALE: NTS
EXTERIOR EQUIPMENT CONCRETE PAD
DETAIL
SCALE: NTS
TYPICAL CONCRETE WALL PENETRATION
DETAIL
SCALE: NTS
TYPICAL GYPBOARD WALL PENETRATION
DETAIL
J
J
J J
J J
J
J J
J
JJ
J
J
J
J
J
J J J
J
J
J
J
J
J
JJ
'CW'
'RGLT'
'RGHT'
ED100
ED100
BAY 6BAY 7BAY 8BAY 9BAY 10BAY 11BAY 12BAY 13BAY 14
ED100
WP (ROOF) WP (ROOF)
POWER DEMO COLOR DESIGNATION:
COLOR ACTION
REWIRE: DISCONNECT BRANCH CIRCUIT OR FEEDER FROM DEVICE OR EQUIPMENT
AND PROTECT FOR REWIRING. COMPLETELY REMOVE ALL BRANCH CIRCUIT
CONDUCTORS. DEMOLISH ALL ACCESSIBLE CONDUIT. THE ONLY CONDUIT THAT IS
ALLOWED TO REMAIN IS BELOW GRADE, IN WALLS, AND PENETRATING THE ROOF
DECK. ALL EXISTING BRANCH CIRCUITS AND FEEDERS TO FEED FROM NEW
EQUIPMENT.
DEMOLISH AND REPLACE: DEMOLISH DEVICE OR EQUIPMENT AND DISCONNECT
BRANCH CIRCUIT OR FEEDER. COMPLETELY REMOVE ALL BRANCH CIRCUIT OR
FEEDER CONDUCTORS. DEMOLISH ALL ACCESSIBLE CONDUIT. THE ONLY CONDUIT
THAT IS ALLOWED TO REMAIN IS BELOW GRADE, IN WALLS, AND PENETRATING THE
ROOF DECK. ALL EXISTING BRANCH CIRCUITS AND FEEDERS TO FEED FROM NEW
EQUIPMENT.
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
ED100
09/11/2025
09/11/2025
09/11/2025
09/11/2025
DEMOLITION PLAN - NS1 SOUTH -
POWER
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
KEYED NOTES #
SCALE: 1/8" = 1'-0"
ENLARGED NS1 SOUTH - DEMOLITION -
POWER
SCALE: 1/8" = 1'-0"
ENLARGED NS1 SOUTH WASHBAY -
DEMOLITION
DEMOLITION NOTES:
1. ALL OUTLETS AND OUTLET COVER PLATES ARE TO BE DEMOLISHED
AND REPLACED.
2. SWITCHES, DISCONNECTS, STARTERS, ETC. SHALL REMAIN IN PLACE
AND BE REUSED.
3. LOCATIONS OF ALL EXISTING EQUIPMENT, BOXES, MANHOLES,
UNDERGROUND LINES, ETC. ARE APPROXIMATE AND SHALL BE FIELD
VERIFIED PRIOR TO ANY WORK.
4. ALL ACCESSIBLE CONDUIT AND BRANCH CIRCUIT AND FEEDER WIRING
SHALL BE REMOVED. ALL IN-WALL CONDUIT AND BACKBOXES SHALL
REMAIN AND BE PROTECTED FOR REUSE.
5. SEE POWER DEMOLITION DESIGNATION FOR EXPLAINATION OF COLOR
CODING.
6. THE EXISTING CONDUIT STUBS THROUGH THE EXISTING SLAB ARE
SHOWN IN THEIR APPROXIMATE SIZE AND LOCATIONS.
7. THE DEMOLITION AND INSTALLATION OF NEW ELECTRICAL EQUIPMENT
SHALL BE COMPLETED IN PHASES TO MINIMIZE THE OUTAGE TIMES. THE
CONTRACTOR SHALL PROVIDE A DETAILED PHASING PLAN TO THE
AIRPORT AND ENGINEER FOR REVIEW PRIOR TO STARTING ANY WORK.
22"x34" SHEET SCALE: 1/8" = 2'-0" 11"X17" SHEET
22"x34" SHEET SCALE: 1/8" = 2'-0" 11"X17" SHEET
BREAK RM.KITCHENGYM
O F F
IC
E
A R E A
O F F
IC
E
A R E
AM
E N 'S
WMN'S
STOR.
MECH.
STOR.
4 4
J
J
J
J
J
J
J
J
J
J
ED401
'RGLS'
'T-RGLS'
'W'
'RGHS'
ED100
BAY 1BAY 2BAY 3BAY 4BAY 5
'FACP'
(ON ROOF)
(ON ROOF)
(ON ROOF)
(ON ROOF)
(ON ROOF)
WP
WP
WP
WP
WP
(ON ROOF) WP
POWER DEMO COLOR DESIGNATION:
COLOR ACTION
REWIRE: DISCONNECT BRANCH CIRCUIT OR FEEDER FROM DEVICE OR EQUIPMENT
AND PROTECT FOR REWIRING. COMPLETELY REMOVE ALL BRANCH CIRCUIT
CONDUCTORS. DEMOLISH ALL ACCESSIBLE CONDUIT. THE ONLY CONDUIT THAT IS
ALLOWED TO REMAIN IS BELOW GRADE, IN WALLS, AND PENETRATING THE ROOF
DECK. ALL EXISTING BRANCH CIRCUITS AND FEEDERS TO FEED FROM NEW
EQUIPMENT.
DEMOLISH AND REPLACE: DEMOLISH DEVICE OR EQUIPMENT AND DISCONNECT
BRANCH CIRCUIT OR FEEDER. COMPLETELY REMOVE ALL BRANCH CIRCUIT OR
FEEDER CONDUCTORS. DEMOLISH ALL ACCESSIBLE CONDUIT. THE ONLY CONDUIT
THAT IS ALLOWED TO REMAIN IS BELOW GRADE, IN WALLS, AND PENETRATING THE
ROOF DECK. ALL EXISTING BRANCH CIRCUITS AND FEEDERS TO FEED FROM NEW
EQUIPMENT.
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
ED101
09/11/2025
09/11/2025
09/11/2025
09/11/2025
DEMOLITION PLAN - NS1 NORTH -
POWER
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
KEYED NOTES #
SCALE: 1/8" = 1'-0"
ENLARGED NS1 NORTH - DEMOLITION -
POWER
DEMOLITION NOTES:
1. ALL OUTLETS AND OUTLET COVER PLATES ARE TO BE DEMOLISHED
AND REPLACED.
2. SWITCHES, DISCONNECTS, STARTERS, ETC. SHALL REMAIN IN PLACE
AND BE REUSED.
3. LOCATIONS OF ALL EXISTING EQUIPMENT, BOXES, MANHOLES,
UNDERGROUND LINES, ETC. ARE APPROXIMATE AND SHALL BE FIELD
VERIFIED PRIOR TO ANY WORK.
4. ALL ACCESSIBLE CONDUIT AND BRANCH CIRCUIT AND FEEDER WIRING
SHALL BE REMOVED. ALL IN-WALL CONDUIT AND BACKBOXES SHALL
REMAIN AND BE PROTECTED FOR REUSE.
5. SEE POWER DEMOLITION DESIGNATION FOR EXPLAINATION OF COLOR
CODING.
6. THE EXISTING CONDUIT STUBS THROUGH THE EXISTING SLAB ARE
SHOWN IN THEIR APPROXIMATE SIZE AND LOCATIONS.
7. THE DEMOLITION AND INSTALLATION OF NEW ELECTRICAL EQUIPMENT
SHALL BE COMPLETED IN PHASES TO MINIMIZE THE OUTAGE TIMES. THE
CONTRACTOR SHALL PROVIDE A DETAILED PHASING PLAN TO THE
AIRPORT AND ENGINEER FOR REVIEW PRIOR TO STARTING ANY WORK.
MEN'S
S
TO
R
M E C H
S
TO
R
TELECOM
EQUIPMENT (E)
LIGHTING
CONTACTOR (E)
D1 SEWER MANHOLE (E)
D8 COMM DB (E)
D21 NS1 SECONDARY (E)
NS4 SECONDARY (D)
NS1 FEEDER
STUBS (E)
RMP
PRIMARY (D)
RMP
PRIMARY (E)
RMP PRIMARY DEMOLITION
POINT
SERVICE TRANSFORMER PAD (D)
D3
APPROXIMATE AREA OF ASPHALT
REMOVAL. COORDINATE EXACT
AREA WITH NEW EQUIPMENT
'MCC-A (D)'
'MDP- (D)'
'EMDP (D)'D6
'MDP- (D)'
D6
D6
'MDS (D)D6
D6
'ATS (E)'
D1D1 D1
D2
GENERATOR (E)
CONCRETE EQUIPMENT PAD (E)D9
'METER (D)' D7
D5
D11
D4
D15
D20
'RGLO (D)'
'EGP (D)''RGLN (D)'
'RGHN (D)'
ED401
'EGP' FEEDER
PULLBOX (D)
LIGHTING CONTACTOR (RR)
STACKED TRANSFORMERS
'T-RGLN' (D) AND 'T-RGLO' (D)
FIBER OPTIC PULL BOX (E)
'M1'
'T-M1'
'T-RGLN (D)'
'T-RGLO (D)'
FIBER OPTIC PULLBOX (E)
D17 D17 D17 D17
D17
D17
'EGP' FEEDER PULLBOX (D)
LIGHTING CONTACTOR
PULL BOX (RR)
D12
D13
D14D14D14D14
D22D22
D22D22
RMP PRIMARY (E) D16 RMP VAULT (E)D1
E D
4/
NS1 SECONDARY D23
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
ED401
09/11/2025
09/11/2025
09/11/2025
09/11/2025
DEMOLITION PLAN - NS4 AND
ENLARGED NS1
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
KEYED NOTES
D1 PROTECT AND MAINTAIN.
D2 PROTECT AND MAINTAIN DURING CONSTRUCTION. DISCONNECT AND
REFEED EQUIPMENT AS REQUIRED FOR DEMOLITION OF THE OTHER
EQUIPMENT AND REQUIRED FOR PHASING.
D3 RMP TO REMOVE EXISTING TRANSFORMER. DEMOLISH EXISTING PAD.
D4 RMP TO REMOVE CONDUCTORS. CONTRACTOR TO DEMOLISH CONDUIT
BETWEEN DEMOLITION POINT AND EXISTING TRANSFORMER LOCATION
FOR REMOVAL OF TRANSFORMER AND PAD.
D5 RMP TO REMOVE CONDUCTORS. DEMOLISH SECONDARY CONDUITS
AFTER TEMPORARY POWER HAS BEEN ESTABLISHED AND RMP HAS
REMOVED CONDUCTORS.
D6 DEMOLISH EXISTING ELECTRICAL EQUIPMENT. EQUIPMENT TO BE
DEMOLISHED IN PHASES.
D7 RMP TO REMOVE METER AND METERING CONDUCTORS. CONTRACTOR TO
DEMOLISH ALL REMAINING METERING EQUIPMENT.
D8 APPROXIMATE LOCATION OF EXISTING COMMUNICATIONS DUCT BANK.
CONTRACTOR SHALL FIELD VERIFY THE EXACT LOCATION, WIDTH, AND
DEPTH OF THIS DUCT BANK PRIOR TO ANY EXCAVATION.
SCALE: 1/16" = 1'-0"
RMP PRIMARY - DEMO
SCALE: 1/4" = 1'-0"
DEMOLITION PLAN - NS4
SCALE: 1/4" = 1'-0"
ENLARGED NS1 CORRIDOR - DEMOLITION
PLAN
SCALE: 1/2" = 1'-0"
NS1 CORRIDOR ELEVATION - DEMOLITION
KEYED NOTES
D9 EXISTING CONCRETE PAD TO REMAIN.
D11 PROTECT EXISTING CONDUIT STUBS FOR BUILDING NS1.
D12 DEMOLISH EXISTING PULL BOX FOR INSTALLATION OF NEW DISCONNECT.
D13 DISCONNECT AND REMOVE EXISTING LIGHTING CONTACTOR AND
JUNCTION BOX FOR RELOCATION. SEE EP102 FOR NEW LOCATION.
D14 CAP CONDUIT 3" ABOVE FLOOR.
D15 ABANDON THE REMAINING CONDUIT IN PLACE.
D16 EXSISTING RMP PRIMARY TO BE ABANDONED IN PLACE AFTER
INSTALLATION OF NEW PRIMARY.
D17 DEMOLISH EQUIPMENT AND CONDUIT AS REQUIRED FOR REMOVAL OF
EQUIPMENT. DEMOLISH ALL EXISTING BRANCH CONDUIT.
D20 CONTRACTOR TO LOCATE SEWER LINES PRIOR TO ANY EXCAVATION.
D21 RMP TO REMOVE CONDUCTORS. CONTRACTOR SHALL DEMOLISH
CONDUIT ENCOUNTERED DURING EXCAVATION. ABANDON REMAINING
PORTIONS.
D22 DEMOLISH ALL CONDUIT ABOVE 3".
D23 RMP TO REMOVE CONDUCTORS. CONTRACTOR SHALL ABANDON THIS
PORTION OF CONDUIT.
DEMOLITION NOTES:
1. ALL OUTLETS AND OUTLET COVER PLATES ARE TO BE DEMOLISHED
AND REPLACED.
2. SWITCHES, DISCONNECTS, STARTERS, ETC. SHALL REMAIN IN PLACE
AND BE REUSED.
3. LOCATIONS OF ALL EXISTING EQUIPMENT, BOXES, MANHOLES,
UNDERGROUND LINES, ETC. ARE APPROXIMATE AND SHALL BE FIELD
VERIFIED PRIOR TO ANY WORK.
4. ALL ACCESSIBLE CONDUIT AND BRANCH CIRCUIT AND FEEDER WIRING
SHALL BE REMOVED. ALL IN-WALL CONDUIT AND BACKBOXES SHALL
REMAIN AND BE PROTECTED FOR REUSE.
5. SEE POWER DEMOLITION DESIGNATION FOR EXPLAINATION OF COLOR
CODING.
6. THE EXISTING CONDUIT STUBS THROUGH THE EXISTING SLAB ARE
SHOWN IN THEIR APPROXIMATE SIZE AND LOCATIONS.
7. THE DEMOLITION AND INSTALLATION OF NEW ELECTRICAL EQUIPMENT
SHALL BE COMPLETED IN PHASES TO MINIMIZE THE OUTAGE TIMES. THE
CONTRACTOR SHALL PROVIDE A DETAILED PHASING PLAN TO THE
AIRPORT AND ENGINEER FOR REVIEW PRIOR TO STARTING ANY WORK.
22"x34" SHEET SCALE: 1/4" = 2'-0" 11"X17" SHEET
22"x34" SHEET SCALE: 1/4" = 2'-0" 11"X17" SHEET 22"x34" SHEET SCALE: 1/2" = 2'-0" 11"X17" SHEET
22"x34" SHEET SCALE: 1/16" = 2'-0" 11"X17" SHEET
J
J J
J J
J
J J
J
JJ
J
J
J
J
J
J J J
J
J
J
J
J
J
JJ
'RGLT'
'CW'
'RGHT'
BAY 14 BAY 13 BAY 12 BAY 11 BAY 10 BAY 9 BAY 8 BAY 7 BAY 6
EGP- 14EGP- 14
EGP- 14EGP- 14
W-1,3,5 W-13,15,17 W-13,15,17W-2,4,6 W-2,4,6W-8,10,12W-8,10,12
CW-1,3,5
CW-37,39,41
RGLS-1RGLS-1RGLS-3RGLS-3RGLS-3RGLS-3RGLS-5RGLS-5RGLS-5
RGLS-5
RGLS-11 RGLS-11 RGLS-11 RGLS-11 RGLS-9 RGLS-9 RGLS-9 RGLS-9 RGLS-7 RGLS-7
RGLS-19
RGLS-17
RGLS-17
RGLS-17 RGLS-17
RGLS-17
RGLS-15 RGLS-15
RGLS-15
RGLS-15RGLS-15
RGLS-15
RGLS-15
RGLS-5
RGLS-13
RGLS-13
RGLS-13
RGLS-13 RGLS-13 RGLS-13
RGLS-13
RGLT-1
RGLT-7
RGLT-1
RGLT-3
RGLT-3
RGLT-5
RGLT-5
RGLT-16
RGLT-18,20
RGLT-14
RGLT-15RGLT-15
RGLT-9
RGHS- 1
RGHS- 1
RGHS- 1
RGHS- 1
RGHS- 1
RGHS- 1
EGP- 10
RGHS- 1
RGHS- 1
RGHS- 1
EGP- 10
RGHS- 1
RGHS- 1
RGHS- 1
RGHS- 1
RGHS- 1
RGHS- 5
RGHS- 5
RGHS- 5
RGHS- 5
RGHS- 5
RGHS- 5
EGP- 10
RGHS- 5
RGHS- 5
RGHS- 5
RGHS- 5
RGHS- 5
RGHS- 3
RGHS- 3
RGHS- 3
RGHS- 3
RGHS- 3
RGHS- 3
EGP- 10
RGHS- 3
RGHS- 3
RGHS- 3
RGHS- 3
RGHS- 3
RGHT- 3
RGHT- 3
EGP- 10
RGHT- 3
RGHT- 3
RGHT- 3
EGP- 10
RGHT- 3
RGHT- 3
RGHT- 3
EGP- 10
RGHT- 3
RGHT-38,40,42
RGHT-2,4,6
RGLS-32,34,36RGLS-32,34,36 RGLS-32,34,36
RGLS-37,39,41 RGLS-37,39,41RGLS-37,39,41RGLS-38,40,42RGLS-38,40,42RGLS-38,40,42
RGLS-26,28,30RGLS-26,28,30RGLS-26,28,30 RGLS-14,16,18
RGLS-8,10,12
RGLT-8,10,12 RGLT-8,10,12
RGLT-2,4,6RGLT-2,4,6
+30' AFF+30' AFF+30' AFF+30' AFF+30' AFF+30' AFF
+30' AFF +30' AFF +30' AFF +30' AFF +30' AFF +30' AFF +30' AFF +30' AFF +30' AFF
+30' AFF+30' AFF+30' AFF
+30' AFF
+30' AFF
+30' AFF
+30' AFF
+30' AFF +30' AFF
+30' AFF
+30' AFF
+30' AFF+30' AFF
+30' AFF
+30' AFF
+30' AFF
+30' AFF
+30' AFF+30' AFF
+30' AFF
+30' AFF
+30' AFF
EGP- 14EGP- 14
EGP- 14 EGP- 14
RGHT-20,22,24
RGHT-14,16,18
WP (ROOF)
RGLT-23 RGLT-21
WP (ROOF)
RGLT-8,10,12
RGLT-19
RGLT-19
RGLT-2,4,6
RGLT-13RGLT-11
RGLT-17
RGHT- 1 RGHT- 1 RGHT- 1 EGP- 10 RGHT- 1 RGHT- 1
RGHT- 5 RGHT- 5 RGHT- 5
POWER COLOR DESIGNATION:
COLOR ACTION
REWIRE: PROVIDE NEW BRANCH CIRCUIT OR FEEDER CONDUITS AND
CONDUCTORS. RECONNECT AND INSTALL DEVICE OR EQUIPMENT.
PROVIDE NEW DEVICES OR EQUIPMENT, INCLUDING ALL REQUIRED BRANCH
CIRCUITS, FEEDER CONDUITS, AND CONDUCTORS, AS NECESSARY.
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EP100
09/11/2025
09/11/2025
09/11/2025
09/11/2025
NEW PLAN - NS1 SOUTH
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
SCALE: 1/8" = 1'-0"
ENLARGED NS1 SOUTH - ELECTRICAL
SCALE: 1/8" = 1'-0"
ENLARGED NS1 SOUTH WASHBAY -
ELECTRICAL
GENERAL POWER NOTES:
1. DIV 26 CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF ALL
EXISTING CONDUIT AND EQUIPMENT. THE DIVISION 26 CONTRACTOR
SHALL PROVIDE ALL LABOR AND SUPPLIES AS REQUIRED TO
COMPLETELY REPLACE AND RELOCATE THE INDICATED EQUIPMENT
REGARDLESS IF IT IS SHOWN ON THE PLANS OR NOT. THIS INCLUDES
BUT IS NOT LIMITED TO ALL EXISTING CONDUIT AND CONDUCTORS.
2. THE FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES.
3. COORDINATE ALL OUTAGES WITH THE AIRPORT PRIOR TO ANY WORK.
THE AIRPORT MUST BE PROVIDED A MINIMUM OF 14 DAYS NOTICE.
4. THE EXISTING CONDUIT STUBS THROUGH THE EXISTING SLAB ARE
SHOWN IN THEIR APPROXIMATE SIZE AND LOCATIONS. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO CONFIRM THE SIZE AND
LOCATIONS AND ENSURE NEW EQUIPMENT IS PLACED DIRECTLY ON
TOP OF THE EXISTING STUBS OR EXTENDED FROM THE STUBS TO THE
NEW EQUIPMENT.
5. ALL CONDUIT ROUTING SHOWN ON THIS SHEET IS SCHEMATIC IN
NATURE. DIV 26 CONTRACTOR SHALL DETERMINE THE EXACT ROUTING
OF ALL CONDUIT IN THE FIELD AND WILL COORDINATE WORK WITH ALL
EXISTING EQUIPMENT.
6 THE ANTICPATED LARGEST DIMENSIONS OF EQUIPMENT HAVE BEEN
SHOWN ON THIS PLAN. CONTRACTOR TO CONFIRM AND COORDINATE
THE EXACT LOCATION, DIMENSIONS, AND PAD REQUIREMENTS WITH
THE ACTUAL EQUIPMENT PROVIDED.
7. LOCATIONS OF ALL EXISTING EQUIPMENT, BOXES, MANHOLES,
UNDERGROUND LINES, ETC. ARE APPROXIMATE AND SHALL BE FIELD
VERIFIED PRIOR TO ANY WORK.
8. PROVIDE NEW OUTLETS AND COVER PLATES.
9. CONNECT NEW BRANCH CIRCUIT WIRING TO EXISTING DISCONNECTS.
22"x34" SHEET SCALE: 1/8" = 2'-0" 11"X17" SHEET
BREAK RM.KITCHENGYM
O F F
IC
E
A R E A
O F F
IC
E
A R E
AM
E N 'S
WMN'S
STOR.
MECH.
STOR.
4 4
J
J
J
J
J
J
J
J
J
F F
J
'RGLN'
'RGLO'
'T-RGLN'
'T-RGLO'
'EGP'
'T-RGLS'
'RGLS'
'M1'
'T-M1'
'W'
'RGHN'
'RGHS'
EP401
M1-1
M1-1
M1-1
M1-9
M1-17
M1-15
M1-15M1-19
M1-21
M1-25
M1-23
M1-11
M1-5
RGLO-11
RGLO-16
RGLO-15
RGLO-15
RGLO-13
RGLO-13RGLO-13
RGLO-15
RGLO-19
RGLO-17
RGLO-19
RGLO-27
RGLO-27
RGLO-27
RGLO-39
M1-17
RGLO-39
RGLO-37
RGLO-37
RGLO-33
RGLO-33
RGLO-35
RGLO-35
RGLO-35
RGLO-29
RGLO-38
RGLO-40RGLO-42
RGLN-7
RGLO-38
RGLO-40
RGLO-42
RGLO-38
RGLO-40
RGLO-42 RGLO-38 RGLO-40
RGLO-38RGLO-36
RGLO-28 RGLO-14
RGLO-12
RGLO-9
RGLO-24
RGLO-8
RGLO-5
RGLO-22
RGLO-6 RGLO-31
RGLO-23
RGLO-29
M1-3
M1-7
M1-27
RGLO-2 RGLO-4
RGLO-20
RGLO-26
RGLO-21
RGLO-30
RGLO-10
RGLO-18
RGLO-7
RGLO-18
RGLN-32,34
RGLN-5
RGLN-37
RGLN-37 RGLN-37
RGLN-37
RGLN-37
RGLN-25
RGLN-27
RGLN-21RGLN-19RGLN-17RGLN-15 RGLN-13
RGLN-37
RGLN-39
RGLN-39
RGLN-28
RGLN-39
RGLN-14
RGLN-23
RGLN-30
RGLN-8
RGLN-1RGLN-1
RGLN-8
RGLN-1
RGLN-22
RGLN-4
RGLN-4 RGLN-4
RGLN-2
RGLN-2
RGLN-2
RGLN-2
RGLN-16
RGLN-29 RGLN-29
RGLN-31
RGLN-33
RGLN-33
RGLN-33
RGLN-33
RGLN-41
RGLN-16
RGLN-35
RGLS-1
RGLS-7
EGP- 10
EGP- 12
EGP- 12EGP- 10EGP- 12
EGP- 12
EGP- 12
EGP- 12
EGP- 12
EGP- 12
EGP- 10
EGP- 12
EGP- 12
EGP- 10
EGP- 10
EGP- 10
EGP- 10
EGP- 10
EGP- 10
EGP- 10
EGP- 10
EGP- 10
EGP- 8
EGP- 8
EGP- 8
EGP- 10
EGP- 8
EGP- 14
EGP- 14
EGP- 14
EGP- 14
EGP- 14
EGP- 14EGP- 14
EGP- 14EGP- 14
EGP- 10 RGHN- 7 RGHN- 7 EGP- 10 RGHN- 7 RGHN- 7
RGHN- 7 RGHN- 7 RGHN- 7 RGHN- 7 RGHN- 7 RGHN- 7
EGP- 10 RGHN- 7 RGHN- 7 RGHN- 7 EGP- 10 RGHN- 7
RGHN- 5
RGHN- 5
RGHN- 5
RGHN- 9
RGHN- 9
RGHN- 9
RGHN- 9
EGP- 10
RGHN- 9
RGHN- 9
EGP- 10
RGHN- 11
RGHN- 11
RGHN- 11
RGHN- 11RGHN- 11
RGHN- 11 RGHN- 11
RGHN- 8RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 8
RGHN- 12RGHN- 12
RGHN- 12
RGHN- 12 RGHN- 12
RGHN- 12
RGHN- 12
RGHN- 12
EGP- 10
RGHN- 12
EGP- 10
RGHN- 12
RGHN- 12
RGHN- 12
RGHN- 12
RGHN- 10 RGHN- 10
RGHN- 10RGHN- 10
RGHN- 10
RGHN- 10
RGHN- 10
RGHN- 10
RGHN- 10
RGHN- 10
RGHN- 10
RGHN- 10
BAY 1BAY 2BAY 3BAY 4BAY 5
M1-8,10,12
'FACP (E)'
RGHN- 17RGHN- 17 RGHN- 1RGHN- 17
RGHN- 17 RGHN- 17 RGHN- 17 RGHN- 1
EGP- 10EGP- 10
RGHN-20,22,24 RGHN-19,21,23
RGHN- 17
RGHN- 1RGHN- 17RGHN- 17
W-7,9,11
RGHN- 17RGHS- 1
EGP- 10 RGHN- 17
RGHS- 1
RGHS- 1
EGP- 10
RGHS-7,9,11
RGHS- 1
RGHS- 1
RGHS- 1 RGHS- 1
RGHS- 1
W-7,9,11
RGHS- 1 RGHS- 1
M1-2,4,6
RGLN-27 RGLN-25
RGHN-25,27,29
RGHN-26,28,30
M1-14,16
M1-24,26,28
RGLO-15
M1-21
RGLN-1RGLN-3
RGLN-3
RGLN-9
RGLN-3
RGLN-9
RGLN-9
RGLN-3RGLN-3
RGLN-3 RGLN-3
RGLO-23
RGLO-28
RGLO-28
(ON ROOF)
WP
(ON ROOF)WP
(ON ROOF)
WP
RGLO-11
RGLO-39 RGLO-39
(ON ROOF)WP
(ON ROOF)
WP
RGLN-36,38
RGLS-14,16,18 RGLS-14,16,18 RGLS-14,16,18
RGLS-8,10,12 RGLS-8,10,12
RGLS-8,10,12
RGLS-20,22,24 RGLS-20,22,24
RGLS-2,4,6RGLS-2,4,6
RGHN- 11
+30' AFF+30' AFF+30' AFF+30' AFF+30' AFF
+30' AFF +30' AFF
+30' AFF +30' AFF +30' AFF
EGP- 10
EGP-5,7
RGHN- 15
MOUNT OUTLET TO CEILING
NS1 EM
BUILDING
DISCONNECT
NS1
NORMAL
POWER
DISCONNECT
P8
P8
RGHN- 11
RGHN- 11
RGHN- 11 RGHN- 11
RGHN- 11
EGP- 10
EGP- 12
RGLO-34
RGLO-32
RGLN-11
RGLN-10
WP RGLO-1,3
(ON ROOF)
POWER COLOR DESIGNATION:
COLOR ACTION
REWIRE: PROVIDE NEW BRANCH CIRCUIT OR FEEDER CONDUITS AND
CONDUCTORS. RECONNECT AND INSTALL DEVICE OR EQUIPMENT.
PROVIDE NEW DEVICES OR EQUIPMENT, INCLUDING ALL REQUIRED BRANCH
CIRCUITS, FEEDER CONDUITS, AND CONDUCTORS, AS NECESSARY.
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY INTERNATIONAL AIRPORT
SHEET: OF 30
DESIGNED
DRAWN
CHECKED
APPROVED
DATE
DATE
DATE
DATE
REVISIONS
DATENO. REMARKS BY APV BB
BB
AR
AR
ENV:2023-215
THIS SHEET IS INTENDED TO BE PRINTED IN COLOR.
PROJECT 54 2411
EP101
09/11/2025
09/11/2025
09/11/2025
09/11/2025
NEW PLAN - NS1 NORTH
NS1 AND NS4 SWITCHGEAR
CAPACITOR
NS1 AND NS4 SWITCHGEAR CAPACITOR
BID SET
KEYED NOTES
P8 CONTRACTOR SHALL INSTALL DISCONNECT ON EXTERIOR WALL.
COORDINATE EXACT LOCATION IN THE FIELD. ROUTE FEEDER OUT THE
TOP OF THE DISCONNECT AND PENETRATE INTO THE BUILDING ABOVE
THE EXISTING CEILING LEVEL (APPROXIMATELY 10' AFF). ROUTE FEEDER
ABOVE CEILING AND THROUGH THE BUILDING TO THE NEW PANELBOARD
LOCATION. SEAL ALL PENETRATIONS AS REQUIRED.
SCALE: 1/8" = 1'-0"
ENLARGED NS1 NORTH - ELECTRICAL
GENERAL POWER NOTES:
1. DIV 26 CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF ALL
EXISTING CONDUIT AND EQUIPMENT. THE DIVISION 26 CONTRACTOR
SHALL PROVIDE ALL LABOR AND SUPPLIES AS REQUIRED TO
COMPLETELY REPLACE AND RELOCATE THE INDICATED EQUIPMENT
REGARDLESS IF IT IS SHOWN ON THE PLANS OR NOT. THIS INCLUDES
BUT IS NOT LIMITED TO ALL EXISTING CONDUIT AND CONDUCTORS.
2. THE FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES.
3. COORDINATE ALL OUTAGES WITH THE AIRPORT PRIOR TO ANY WORK.
THE AIRPORT MUST BE PROVIDED A MINIMUM OF 14 DAYS NOTICE.
4. THE EXISTING CONDUIT STUBS THROUGH THE EXISTING SLAB ARE
SHOWN IN THEIR APPROXIMATE SIZE AND LOCATIONS. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO CONFIRM THE SIZE AND
LOCATIONS AND ENSURE NEW EQUIPMENT IS PLACED DIRECTLY ON
TOP OF THE EXISTING STUBS OR EXTENDED FROM THE STUBS TO THE
NEW EQUIPMENT.
5. ALL CONDUIT ROUTING SHOWN ON THIS SHEET IS SCHEMATIC IN
NATURE. DIV 26 CONTRACTOR SHALL DETERMINE THE EXACT ROUTING
OF ALL CONDUIT IN THE FIELD AND WILL COORDINATE WORK WITH ALL
EXISTING EQUIPMENT.
6 THE ANTICPATED LARGEST DIMENSIONS OF EQUIPMENT HAVE BEEN
SHOWN ON THIS PLAN. CONTRACTOR TO CONFIRM AND COORDINATE
THE EXACT LOCATION, DIMENSIONS, AND PAD REQUIREMENTS WITH
THE ACTUAL EQUIPMENT PROVIDED.
7. LOCATIONS OF ALL EXISTING EQUIPMENT, BOXES, MANHOLES,
UNDERGROUND LINES, ETC. ARE APPROXIMATE AND SHALL BE FIELD
VERIFIED PRIOR TO ANY WORK.
8. PROVIDE NEW OUTLETS AND COVER PLATES.
9. CONNECT NEW BRANCH CIRCUIT WIRING TO EXISTING DISCONNECTS.
FF
'RGLO''RGLN'
'T-RGLO''T-RGLN'
LIGHTING CONTACTOR (RR)
'M1'
'EGP'
'RGHN'
'T-M1'
FIBER OPTIC PULL BOX (E)
GENERAL POWER NOTES:
1. DIV 26 CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF ALL EXISTING CONDUIT AND
EQUIPMENT. THE DIVISION 26 CONTRACTOR SHALL PROVIDE ALL LABOR AND SUPPLIES AS
REQUIRED TO COMPLETELY REPLACE AND RELOCATE THE INDICATED EQUIPMENT
REGARDLESS IF IT IS SHOWN ON THE PLANS OR NOT. THIS INCLUDES BUT IS NOT LIMITED TO
ALL EXISTING CONDUIT AND CONDUCTORS.
2. THE FIRE ALARM SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES.
3. COORDINATE ALL OUTAGES WITH THE AIRPORT PRIOR TO ANY WORK. THE AIRPORT MUST
BE PROVIDED A MINIMUM OF 14 DAYS NOTICE.
4. THE EXISTING CONDUIT STUBS THROUGH THE EXISTING SLAB ARE SHOWN IN THEIR
APPROXIMATE SIZE AND LOCATIONS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONFIRM
THE SIZE AND LOCATIONS AND ENSURE NEW EQUIPMENT IS PLACED DIRECTLY ON TOP OF
THE EXISTING STUBS OR EXTENDED FROM THE STUBS TO THE NEW EQUIPMENT.
5. ALL CONDUIT ROUTING SHOWN ON THIS SHEET IS SCHEMATIC IN NATURE. DIV 26
CONTRACTOR SHALL DETERMINE THE EXACT ROUTING OF ALL CONDUIT IN THE FIELD AND
WILL COORDINATE WORK WITH ALL EXISTING EQUIPMENT.
NEW RMP PRIMARYP1
GENERATOR (E)
P4
TELECOM
EQUIPMENT (E)
TELECOM
EQUIPMENT (E)
'ATS (E)'
P4
'EMDP'P3
'MDP'
P3
'MCC-A'
P3
'PFC'
MAIN
DISTRIBUTION
SWITCHBOARD
'MSB'
MAIN SERVICE
DISCONNECT
'MSD'
RMP METER,
CT, PULL
SECTION
EQUIPMENT PAD
NS1 FEEDERP1
FIBERGLASS ELBOW
NEW RMP TRANSFORMER LOCATION
TRANSFORMER BY RMP
NEW PAD-VAULT BY DIV 26
EG500
NEW RMP SECONDARYP1
APPROXIMATE AREA OF NEW
ASPHALT. SURFACE EDGE OF
NEW ASPHALT SHALL EXTEND
24" BEYOND ALL NEW
EQUIPMENT PADS
COMM DB (E)
FIBERGLASS ELBOW
FIBERGLASS ELBOW
NS1 EM FEEDER P1
NS1 EM FEEDERP1
SEWER MANHOLE (E)
P11
P12
P13P13P13
BUILDING NS1
RMP PRIMARY (N) RMP VAULT (E)
E P
EG500
3/
BUILDING FEEDER
NS1 EM BUILDING DISCONNECT
'NS1-EM-DSC'
P1 NS1 NORMAL POWER DISCONNECT
'NS1-DSC'
P1
P9
ALL ASPHALT IN THIS VIEW IS A HEAVY DUTY PAVEMENT SECTION.
ALL EXCAVATION AND REPAIR SHALL BE IN ACCORDANCE WITH DETAIL 1 ON
SHEET EG501.
P10P10
240 E. MORRIS AVE. SUITE 200
SALT LAKE CITY, UT 84115
P (801) 534-1130 F (801) 534-1080 www.envisioneng.com
SALT LAKE CITY
DEPARTMENT OF AIRPORTS
P.O. BOX 145550
SALT LAKE CITY, UT 84114-5550
PROJECT ADDRESS:
ENGINEERING DIVISION
SALT LAKE CITY…