1-EQ TANK SLIDE GATE REPLACEMENT DRAWINGS.pdf
PDF 3 MB Posted
- Attached to
- Equalization Basin Gates Upgrade
- Solicitation number
- US.255820
- Issued by
- Northampton County, Pennsylvania
About this file
This document is a set of bid plans and drawings for the Equalization Basin Gates Upgrade project prepared by CP Engineers, LLC for the Sunbury Municipal Authority (SMA) in Sunbury, Northumberland County, Pennsylvania. The project, identified as Contract No. CP-410, involves the removal and replacement of slide gates at the Sunbury Wastewater Treatment Plant (WWTP). The base bid work includes replacement of five existing aluminum slide gates at Aeration Tank T-14, consisting of two 30" x 30" upward-opening gates and three 72" x 36" downward-opening weir gates. Additionally, unit price work is available for the optional removal and replacement of up to seven additional slide gates of the same types at Aeration Tanks T-11, T-12, and T-13, along with minor concrete and metal fabrication work as necessary. The work must be substantially complete by April 30, 2027. A non-mandatory pre-bid meeting is scheduled for 11:00 a.m. on Thursday, October 15, 2026, at the Sunbury WWTP, with attendance strongly encouraged. Contractors are responsible for field verification of existing conditions, including gate dimensions, opening sizes, anchor stud locations, stem centerlines, operator locations, and mounting conditions prior to fabrication.
The replacement slide gate assemblies must include frames, slides, stems, operators, anchors, hardware, seals, and all accessories required for complete operating installations. Gates shall be manufactured to fit existing bolt patterns and mounting conditions without modification to existing concrete structures unless approved by the Engineer. All installation work must comply with manufacturer specifications and contract specifications, including field adjustments to ensure smooth operation and specified leakage performance, as well as field testing in accordance with contract requirements. The project is funded by the SMA's existing cash reserves and is subject to Pennsylvania public bidding and prevailing wage requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 4-Addendum No. 1.pdf | ||
| 2-EQ TANK SLIDE GATE REPLACEMENT SPECIFICATIONS.pdf | ||
| 5-BidTab Gate Replacement.pdf | ||
| 3-Addendum No. 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
FOR
PROFESSIONAL ENGINEER
COMMONWEALTH OF PENNSYLVANIA
FOR
C P
E ng in ee rs
M ic ha el
.S ha m al la
C lie nt s\
Su nb ur y
M un ic ip al A ut ho ri ty
\C P
-4
E
Q T an k
Sl id e G at e
R ep l\D R
A W
IN
G
S\ C
U R
R E
N T
\G E
N E
R A
L \G
-0
_C O
V E
R S
H E
E T
.d w g
T hu
Se p
:1
9p m
G-001 COVER SHEET
SUNBURY MUNICIPAL AUTHORITY
BID PLANS
WWTP EQ TANK SLIDE GATE REPLACEMENT
SUNBURY
NORTHUMBERLAND COUNTY, PENNSYLVANIA
CONTRACT NO. CP-410
SEPTEMBER 2026
BID PLANS
WWTP EQ TANK SLIDE GATE REPLACEMENT
SUNBURY
NORTHUMBERLAND CO, PENNSYLVANIA
BRIAN L BOOK
LIC. NO. PA043016
CP-410
KEY MAP
SCALE 1:12,000
1" = 100'
CP ENGINEERS
2013 SANDY DRIVE
SUITE 101
STATE COLLEGE, PA 16803
(814) 753-4249
CPENGINEERS.COM
PROJECT LOCATION
SMA BOARD MEMBERS & MANAGEMENT
NORMAN KOCH, CHAIRMAN
THOMAS McBRYAN, VICE CHAIRMAN
CORY FASOLD, SECRETARY/TREASURER
DAVID PERSING, ASST. SECRETARY/TREASURER
THOMAS KRIEGER, BOARD MEMBER
MICHAEL THOMAS, BOARD MEMBER
JEROME ALEX, BOARD MEMBER
DERRICK BACKER, SMA GENERAL MANAGER
MATT BILLMAN, SMA WWTP MANAGER
30"X30" SLIDE GATE
GATE No. G-1.6
30"X30" SLIDE GATE
GATE No. G-1.5
30"X30" SLIDE GATE
GATE No. G-1.4
30"X30" SLIDE GATE
GATE No. G-1.3
30"X30" SLIDE GATE
GATE No. G-1.1
30"X30" SLIDE GATE
GATE No. G-1.2
72"X36" SLIDE GATE
GATE No. G-2.3
BAFFLE
BAFFLE
BAFFLEBAFFLEBAFFLE
BAFFLE
72"X36" SLIDE GATE
GATE No. G-2.2
72"X36" SLIDE GATE
GATE No. G-2.1
72"X36" SLIDE GATE
GATE No. G-2.4
72"X36" SLIDE GATE
GATE No. G-2.5
72"X36" SLIDE GATE
GATE No. G-2.6N
LETTER REVISIONS ARE NOT TO BE USED FOR CONSTRUCTIONC
P
E ng in ha el
.S ha m
C lie nt s\
Su nb ur y
M un ic ip al A ut ho ri ty
\C P
-4
E
Q T an k
Sl id e G at e
R ep l\D R
A W
IN
G
S\ C
U R
R E
N T
\C
IV
IL
\C
-1
_S
IT
E P
L A
N .d w
Se p
:1 9p m
PROFESSIONAL ENGINEER
C.W.O. PENNSYLVANIA
BRIAN L. BOOK
LIC. NO. PE043016 C-101
WWTP EQ TANK SLIDE
GATE REPLACEMENT
SUNBURY MUNICIPAL AUTHORITY
462 S. 4TH STREET, SUNBURY
NORTHUMBERLAND CO, PENNSYLVANIA
SITE PLAN
CP ENGINEERS
2013 SANDY DRIVE
SUITE 101
STATE COLLEGE, PA 16803
(814) 753-4249
CPENGINEERS.COM
0 1010 20 30
SCALE: 1" = 10' - 0"
1"=10' (1:10)
PLANT SCHEMATIC VIEW1
NTS
EXISTING WALKWAY TYP.A
PLAN NOTES:
1. BASE BID WORK SHALL INCLUDE REMOVAL AND REPLACEMENT OF THE EXISTING TYPE G-1 AND
TYPE G-2 SLIDE GATES LOCATED AT AERATION TANK T-14.
2. SLIDE GATES LOCATED AT AERATION TANKS T-11, T-12, AND T-13 ARE SHOWN FOR REFERENCE
AND UNIT PRICE WORK.
3. UNIT PRICE WORK SHALL BE PERFORMED ONLY AS AUTHORIZED BY THE OWNER.
4. EXISTING FEATURES AND EQUIPMENT SHOWN ARE APPROXIMATE AND ARE BASED ON AVAILABLE
RECORD INFORMATION AND LIMITED FIELD OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY
EXISTING CONDITIONS AFFECTING THE WORK.
5. COORDINATE SLIDE GATE REMOVAL AND REPLACEMENT WITH EXISTING TANK COMPONENTS,
PIPING, BAFFLES, WALKWAYS, AND OTHER FACILITIES TO REMAIN.
6. PROTECT EXISTING FACILITIES FROM DAMAGE DURING THE WORK.
7. REFER TO DRAWING C-501 AND SECTION 40 05 59 FOR SLIDE GATE REQUIREMENTS.
NTS
PLANT SCHEMATIC VIEW2
PLANT ENTRANCE
PROPOSED LAYDOWN AREA
AERATION BASINS
WHERE WORK IS TO
BE PERFORMED
A C-101
N
TYP1
TYP
PROPOSED LAYDOWN AREA
CONCRETE
SLIDE GATE
HAND WHEEL OPERATOR
ANCHOR TYP.
BAFFLE
SLIDE GATE
CONCRETE
HAND WHEEL OPERATOR
ANCHOR TYP.
6"
PLAN
ELEVATION
SIDE ELEVATION
BAFFLE GUSSET
BAFFLE GUSSET
3'
2'
2' -6
8'
2"
LETTER REVISIONS ARE NOT TO BE USED FOR CONSTRUCTIONC
P
E ng in ha el
.S ha m
C lie nt s\
Su nb ur y
M un ic ip al A ut ho ri ty
\C P
-4
E
Q T an k
Sl id e G at e
R ep l\D R
A W
IN
G
S\ C
U R
R E
N T
\C
IV
IL
\C
-5
D E
T A
IL
S.
dw
Se p
:1 9p m
PROFESSIONAL ENGINEER
C.W.O. PENNSYLVANIA
BRIAN L. BOOK
LIC. NO. PE043016 C-501
WWTP EQ TANK SLIDE
GATE REPLACEMENT
SUNBURY MUNICIPAL AUTHORITY
462 S. 4TH STREET, SUNBURY
NORTHUMBERLAND CO, PENNSYLVANIA
DETAILS
CP ENGINEERS
2013 SANDY DRIVE
SUITE 101
STATE COLLEGE, PA 16803
(814) 753-4249
CPENGINEERS.COM
NTS2 TYPE G-2 SLIDE GATES1 TYPE G-1 SLIDE GATES
NTS
NTS3 SLIDE GATE SCHEDULE
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING GATE DIMENSIONS, OPENING SIZE, ANCHOR STUD LOCATIONS, STEM CENTERLINE, OPERATOR LOCATION, AND MOUNTING CONDITIONS PRIOR TO FABRICATION
OF REPLACEMENT GATES.
2. NOTIFY THE ENGINEER OF ANY DISCREPANCIES BETWEEN FIELD CONDITIONS AND THE CONTRACT
DOCUMENTS PRIOR TO FABRICATION.
3. REMOVE EXISTING SLIDE GATES, OPERATORS, AND ACCESSORIES INDICATED FOR REPLACEMENT. PROTECT
ADJACENT CONCRETE SURFACES AND EXISTING FACILITIES DURING DEMOLITION.
4. REPAIR DAMAGED CONCRETE AND GROUT RESULTING FROM GATE REMOVAL AS DIRECTED BY THE
ENGINEER.
5. FURNISH AND INSTALL COMPLETE REPLACEMENT SLIDE GATE ASSEMBLIES, INCLUDING FRAME, SLIDE, STEM, OPERATOR, ANCHORS (IF REQUIRED), HARDWARE, SEALS, AND ACCESSORIES REQUIRED FOR A COMPLETE
OPERATING INSTALLATION.
6. REPLACEMENT GATES SHALL BE MANUFACTURED TO FIT THE EXISTING BOLT PATTERN, OPENINGS AND MOUNTING CONDITIONS WITHOUT MODIFICATION OF THE EXISTING CONCRETE STRUCTURE UNLESS
APPROVED BY THE ENGINEER.
7. INSTALL GATES PLUMB, LEVEL, AND SQUARE IN ACCORDANCE WITH THE MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS.
8. FIELD ADJUST GATES AFTER INSTALLATION TO PROVIDE SMOOTH OPERATION AND SPECIFIED LEAKAGE
PERFORMANCE.
9. PERFORM FIELD TESTING IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS.
1. BAFFLE TO BE REPLACED IN-KIND, IN CONJUNCTION WITH REPLACEMENT OF GATE G-2.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING GATE DIMENSIONS, OPENING SIZE, ANCHOR
STUD LOCATIONS, STEM CENTERLINE, OPERATOR LOCATION, AND MOUNTING CONDITIONS
PRIOR TO FABRICATION OF REPLACEMENT GATES.
3. NOTIFY THE ENGINEER OF ANY DISCREPANCIES BETWEEN FIELD CONDITIONS AND THE
CONTRACT DOCUMENTS PRIOR TO FABRICATION.
4. REMOVE EXISTING SLIDE GATES, OPERATORS, AND ACCESSORIES INDICATED FOR
REPLACEMENT. PROTECT ADJACENT CONCRETE SURFACES AND EXISTING FACILITIES DURING
DEMOLITION.
5. REPAIR DAMAGED CONCRETE AND GROUT RESULTING FROM GATE REMOVAL AS DIRECTED BY
THE ENGINEER.
6. FURNISH AND INSTALL COMPLETE REPLACEMENT SLIDE GATE ASSEMBLIES, INCLUDING
FRAME, SLIDE, STEM, OPERATOR, ANCHORS (IF REQUIRED), HARDWARE, SEALS, AND
ACCESSORIES REQUIRED FOR A COMPLETE OPERATING INSTALLATION.
7. REPLACEMENT GATES SHALL BE MANUFACTURED TO FIT THE EXISTING BOLT PATTERN,
OPENINGS, AND MOUNTING CONDITIONS WITHOUT MODIFICATION OF THE EXISTING
CONCRETE STRUCTURE UNLESS APPROVED BY THE ENGINEER.
8. INSTALL GATES PLUMB, LEVEL, AND SQUARE IN ACCORDANCE WITH THE MANUFACTURER'S
WRITTEN INSTALLATION INSTRUCTIONS.
9. FIELD ADJUST GATES AFTER INSTALLATION TO PROVIDE SMOOTH OPERATION AND SPECIFIED
LEAKAGE PERFORMANCE.
10. PERFORM FIELD TESTING IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS.
GENERAL NOTES
NTS4 BAFFLE DETAIL
NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING BAFFLE DIMENSIONS, OPENING SIZE,
ANCHOR STUD LOCATIONS AND MOUNTING CONDITIONS PRIOR TO FABRICATION OF
REPLACEMENT BAFFLE.
2. MATERIAL TO BE REPLACED IN-KIND.
GATE No. CLEAR OPENING TYPE MOUNTING OPENING SEATED HEAD UNSEATED HEAD OPERATOR G-1.1 30"x30" 4-SIDED WALL MOUNT UPWARD 5' 5' NON-GEARED LIFT MOUNTED YOKE
G-1.2 30"x30" 4-SIDED WALL MOUNT UPWARD 5' 5' NON-GEARED LIFT MOUNTED YOKE
G-1.3 30"x30" 4-SIDED WALL MOUNT UPWARD 5' 5' NON-GEARED LIFT MOUNTED YOKE
G-1.4 30"x30" 4-SIDED WALL MOUNT UPWARD 5' 5' NON-GEARED LIFT MOUNTED YOKE
G-1.5 30"x30" 4-SIDED WALL MOUNT UPWARD 5' 5' NON-GEARED LIFT MOUNTED YOKE
G-1.6 30"x30" 4-SIDED WALL MOUNT UPWARD 5' 5' NON-GEARED LIFT MOUNTED YOKE
G-2.1 72"x36" 3-SIDED WEIR WALL MOUNT DOWNWARD 2.5' 2.5' NON-GEARED LIFT MOUNTED TO PEDESTAL
G-2.2 72"x36" 3-SIDED WEIR WALL MOUNT DOWNWARD 2.5' 2.5' NON-GEARED LIFT MOUNTED TO PEDESTAL
G-2.3 72"x36" 3-SIDED WEIR WALL MOUNT DOWNWARD 2.5' 2.5' NON-GEARED LIFT MOUNTED TO PEDESTAL
G-2.4 72"x36" 3-SIDED WEIR WALL MOUNT DOWNWARD 2.5' 2.5' NON-GEARED LIFT MOUNTED TO PEDESTAL
G-2.5 72"x36" 3-SIDED WEIR WALL MOUNT DOWNWARD 2.5' 2.5' NON-GEARED LIFT MOUNTED TO PEDESTAL
G-2.6 72"x36" 3-SIDED WEIR WALL MOUNT DOWNWARD 2.5' 2.5' NON-GEARED LIFT MOUNTED TO PEDESTAL
1. FIELD VERIFY EXISTING ANCHOR STUD PATTERN PRIOR TO FABRICATION.
2. ALL GATE CONFIGURATIONS SHALL CONFORM TO THE GATE SCHEDULE AND SECTION 40 05
59.24 - ALUMINUM SLIDE GATES.
| Sheets and Views |
| G-001 COVER SHEET |
| C-101 SITE PLAN |
| C-501 DETAILS |
File details come from the government source that posted it. Updated .