1-EAJSA WWTP Sludge Canopy Repairs IFB Drawings.pdf
PDF 568 KB Posted
- Attached to
- Sludge Canopy Repairs
- Solicitation number
- US.263475
- Issued by
- Northampton County, Pennsylvania
About this file
This file contains the technical drawings for the Sludge Canopy Repairs project issued by the Easton Area Joint Sewer Authority (EAJSA) in Pennsylvania. The project encompasses structural repairs to the sludge canopy at the Easton Wastewater Treatment Plant, including roof framing demolition, parapet rehabilitation, installation of new roof panels and gutters, drainage system improvements, structural steel cleaning and recoating, roof framing leveling, and associated repairs to canopy support components. The contract is for general construction work with an expected project duration of 140 days. A non-mandatory pre-bid meeting is scheduled for 10:00 AM on Tuesday, December 1, 2026, at the Administration Building at the WWTP. Site visits by appointment only are available until 3:00 PM on Tuesday, December 15, 2026, at 50 South Delaware Drive, Easton, PA 18042. Bidding documents are available through the designated website at https://pennbid.bonfirehub.com, where prospective bidders are urged to register as plan holders to receive official notifications and addenda.
The drawings serve as technical documentation supporting the bid submission process and provide the engineering specifications and details necessary for contractors to prepare accurate cost estimates and construction plans. Pricing terms, funding sources, and award details are not specified within this drawings document. Interested bidders should consult the complete bidding documents and specifications available through the PennBid portal for comprehensive project requirements, contract terms, and submission instructions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-EAJSA WWTP Sludge Canopy Repairs IFB Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EX
ST
C R
O
SS
BE
AM
EXST PURLIN
BEAM
EX
ST
C R
O
SS
BE
AM
EXST PURLIN
BEAM
EXST PURLIN
BEAM
EXST PURLIN
BEAM
EXST PURLIN
BEAM
EXST PURLIN
BEAM
ROOF FRAMING DEMOLITION PLAN
SCALE: 3/8"=1'-0"
30'-2"
12'-0"1"± 6'-0" 12'-0" 1"±
'-2
2' -0
1"
1"
5'
-3
5' -3
2'
-6
2' -6
5'
-3
5' -3
2'
-0
DEMO PERIMETER
GAGE METAL BASE
OF PARAPET
ANGLE, ALL 4 SIDES
DEMO INTERNAL
GUTTER AND
COLUMN
COLLECTOR
BOXES
DEMO ROOF /
CEILING PANELS
DEMO HORIZ GAGE
METAL CEE STUDS
AND FASTENERS
LAID FLAT ACROSS
ROOF PANEL HIGH
RIBS, TYPICAL
BASE BID:
SALVAGE ADJUSTABLE
DIAGONAL BRACES
FROM FLAT STUD
MEMBER TO TOP OF
PARAPET. CLEAN,
COAT AND RE-INSTALL
BASE BID:
SALVAGE ADJUSTABLE
DIAGONAL BRACES
FROM TOP OF EXST
PURLIN BEAMS TO TOP
OF PARAPET. CLEAN,
COAT AND RE-INSTALL
AT ALL BEAM TO BEAM
AND BEAM TO COLUMN
CAP PLATES, BOLT
CONDITION TO BE FIELD
EVALUATED. ANTICIPATE
REPLACEMENT OF ALL
BOLTS IN-KIND
AFTER REMOVAL OF ALL DEMO AND SALVAGED COMPONENTS,
CLEAN ALL STRUCTURAL STEEL, DOWN TO BASE OF COLUMNS
EMBEDDED IN CONCRETE TO MEET SSPC-SP3 STANDARDS.
PREPARE STEEL FOR COATING SYSTEM, SEE COATING NOTES
CUT FLUSH AND SEAL EXIST
2" INTERNAL DOWNSPOUT
w/ 3/16" STEEL PLATE FIELD
WELDED AND FINISHED
SMOOTH. SIMILAR AT
COLUMN BASE,
TYPICAL
BASE BID:
USE CARE AND SALVAGE
PARAPET PANELS, TRIM AND
HORIZONTAL HAT-TRACK
BRACING FOR
RE-INSTALLATION
BASE BID:
SALVAGE ALL ADJUSTABLE DIAGONAL BRACES (ALL 4 SIDES).
CLEAN TO MEET SSPC-SP3 STANDARDS.
PREPARE STEEL FOR COATING SYSTEM, SEE COATING NOTES
DEMO
SECTION
PA
N
EL
TH
IC
KN
ES
S
PA
N
EL
TH
IC
KN
ES
S
PANEL
THICKNESS
PANEL
THICKNESS
N
EXST PURLIN BEAM
BR-1
(BEYOND)
EXST
COLS
DEMO INTERNAL
GUTTER
DEMO ROOF / CEILING
PANELS
DEMOLITION SECTION
SCALE: 3/8"=1'-0"
SEE PLAN NOTES TO
CLEAN ALL
STRUCTURAL STEEL
COMPONENTS
SEE PLAN NOTE TO CUT
FLUSH AND SEAL EXIST
INTERNAL DOWNSPOUT
INTAKES AND EXITS
BASE BID:
USE CARE AND SALVAGE
PARAPET PANELS, TRIM AND
HORIZONTAL HAT-TRACK
BRACING FOR
RE-INSTALLATION
EXIST CONC ISLAND
AND BOLLARDS. NO
WORK THIS AREA
ALL STRUCTURAL STEEL AND
COLUMNS TO BE CLEANED
AND COATED, SEE
CONSTRUCTION PLANS AND
COATING NOTES
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE
ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL
ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND
SURVEYOR TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED, THE ALTERING
ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND
SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION
OF THE ALTERATION.
Fi le
V:
\P
RO
JE
CT
S\
AN
Y\ K7
\1
3.
0\
_D
ES
IG
N \D
RA
W
IN
G
S\
ST
RU
C\
M O
DE
L-
.D
W G
Sa ve d:
/9 /2
4:
:0
PM
P lo tt ed
9/ 9/
:1
6:
P M
C ur re nt
U se r:
G ar la nd
Pe te
L as tS av ed By
Checked By:
Drawing No.:
Issue Date:
Designed By: Drawn By:
Project No.: Scale:
Sheet of 3
AS SHOWN
No. By DateSubmittal / Revision Apv
Drawing Copyright © 2026
One East Broad Street Suite 310
Bethlehem, PA. 18018 610.865.3000
EASTON AREA JOINT
SEWER AUTHORITY
SLUDGE CANOPY
REPAIRS
DEMOLITION
PLAN AND
SECTION
PMGSGYNRC
1030239/10/26
SD-100
11/19/2026
EX
ST
C R
O
SS
B
EA
M
EXST PURLIN BEAM
EX
ST
C R
O
SS
B
EA
M
EXST PURLIN BEAM
EXST PURLIN BEAM
EXST PURLIN BEAM
EXST PURLIN BEAM
EXST PURLIN BEAM
MC-1
MC-2
MC-2
MC-1
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-1
MC-1 DENOTES 362S162-54 (G90) METAL STUD, 54"lg (OR AS REQ'D TO ENGAGE (4 MIN)
UP-TURNED PANEL STIFFENING RIBS. MC-1 ALSO INCLUDES ADJUSTABLE PARAPET
DIAGONAL BRACE, SIMILAR TO BR-1.
BASE BID: REUSE EXISTING DIAGONAL PARAPET BRACES
ALTERNATE BID: SEE 2/S102 AND 2A/S102 FOR DIAGONAL BRACE REQUIREMENTS
ROOF FRAMING PLAN
SCALE: 3/8"=1'-0"
BR
-1
BR
-1
BR
-1
BR
-1
BR
-1
BR
-1
BR
-1
BR
-1 BR
-1
BR
-1
BR
-1
BR
-1
BR
-1
BR
-1
30'-2"
12'-0"3/4"± 6'-0" 12'-0" 3/4"±
'-2
2' -0
3/
4"
3/ 4"
5'
-3
5' -3
2'
-6
2' -6
5'
-3
5' -3
2'
-0
3"x3"x16ga
GALV G-90
ANGLE, FULL
PERIMETER
3"x3"x16ga G-90
GALV PERIMETER
ANGLE, FASTEN
TO EACH MC-1
AND MC-2 w/ (2)
TEK SCREWS
(2) DOWNSPOUT
LOCATIONS AS SHOWN
SECTION
MC-2 DENOTES 362S162-54 (G90) METAL STUD, 54"lg (OR AS REQ'D TO ENGAGE (4 MIN)
UP-TURNED PANEL STIFFENING RIBS. MC-2 DOES NOT RECEIVE PARAPET
DIAGONAL BRACE (BR-1)
MC-1
MC-2
MC-2
MC-1
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-1
MC-2
MC-2
ROOF / CEILING
PANELS, SEE
NOTES
BR-1 DENOTES ADJUSTABLE PARAPET DIAGONAL BRACE:
BASE BID: SALVAGE CLEAN AND COAT DIAGONAL (BR-1) BRACES FOR RE-USE
WITH NEW FASTENING HARDWARE
ALTERNATE BID: PROVIDE NEW (BR-1) ADJUSTABLE PARAPET BRACES.
SEE 2/S102 AND 2A/S102 FOR DIAGONAL BRACE REQUIREMENTS
BASE BID:
RE-INSTALL PARAPET
PANELS, TRIM AND
HORIZONTAL BRACING
WITH NEW FASTENING
HARDWARE
LINED INTERNAL
GUTTER AND
COLUMN
COLLECTOR
BOXES
PANEL
THICKNESS
PANEL
THICKNESS
PA
N
EL
TH
IC
KN
ES
S
PA
N
EL
TH
IC
KN
ES
S
SEE 3/S102 FOR ISOMETRIC REFERENCE CONSTRUCTION DETAIL
N
LOOSEN BOLTS SECURING (2) CROSS
BEAMS TO COLUMN CAPS. INSTALL
TAPERED STEEL PLATE FINGER SHIMS
BETWEEN CAP PLATE AND BOTTOM OF
CROSS BEAMS TO ENSURE PURLIN BEAMS
ARE SET TO THE SAME LEVEL ELEVATION
AT THE (4) EXTREME CORNERS ( ) OF THE
CANOPY STEEL FRAMING, ENSURING
POSITIVE DRAINAGE TO INTERNAL GUTTER.
REPLACE LOOSENED BOLTS WITH NEW
A325 BOLTS MATCHING EXISTING DIAMETER.
PROVIDE TEMP SUPPORT OF ROOF
FRAMING DURING LEVELING AND UNTIL
BOLTS ARE FULLY TIGHTENED.
SEE ROOF
FRAMING
LEVELING
NOTE BELOW
ROOF FRAMING LEVELING
ALTERNATE BID:
INSTALL ALL NEW PARAPET
PANELS, TRIM, FASTENERS AND
BRACING.
SEE ALTERNATE PARAPET
SECTIONS 2/S102 AND 2A/S102
FOR PARAPET CONSTRUCTION
DETAILS
EXISTING LOCATIONS
BASE BID:
3'-0" o.c. MAX
ALTERNATE BID:
3' -0
" o .c
. M
AX
MC-2FL
AT
M
ET
AL
ST
U D
SP
AC
IN
G
3' -0
" o .c
. M
AX
DI
AG
O
NA
L
BR
AC
E
SP
AC
IN
G
SEE BASE BID /
ALT BID NOTES
OPP SIDE FOR
SPACING
EXST PURLIN BEAMMC-1, MC-2
BR-1
(BEYOND)
EXST
COLS
6" SCHED 80 PVC
DOWNSPOUTS AND
ELBOWS, FACE MOUNTED
WITH STRAPS TO
COLUMNS
INTERNAL
GUTTER
ROOF / CEILING
PANELS, SEE NOTES
ELBOW AND NIPPLE
TO INTERNAL GUTTER,
(2 LOCATIONS).
D.S. NIPPLE TO MATCH
INSIDE DIAMETER OF 6"
SCHED 80 PVC PIPE
SECTION
SCALE: 3/8"=1'-0"
BASE BID:
RE-INSTALL SALVAGED PARAPET
PANELS, TRIM AND HORIZONTAL
HAT-TRACK BRACING. INSTALL
WITH NEW FASTENING HARDWARE.
ALTERNATE BID:
INSTALL ALL NEW PARAPET
PANELS, TRIM, FASTENERS AND
BRACING.
SEE ALTERNATE PARAPET
SECTIONS 2/S102 AND 2A/S102
FOR PARAPET CONSTRUCTION
DETAILS
1/S102
EXIST CONC ISLAND
AND BOLLARDS. NO
WORK THIS AREA
CAP EXIST 21
2" INTERNAL
DOWNSPOUT OUTLETS w/ 3/16"
STEEL PLATE FIELD WELDED AND
FINISHED SMOOTH AT COLUMN
BASE, TYPICAL
DISCHARGE NEW SCHED 80 PVC
DOWNSPOUTS EACH END OF
CONC ISLAND AS SHOWN.
PROVIDE (2) MIN STRAPS AROUND
HORIZ PIPE TO CONC.
CONNECTION TO BE MADE WITH
STAINLESS STEEL FASTENERS
BR-1
ROOF / CEILING PANELS AND TRIM:
1. FORMED STEEL ROOF PANELS TO BE 12" (FLAT) x 1 3/4" HIGH, 22ga GALVALUME
COATED AND FINISHED w/ KYNAR 500, BOTH SIDES. FINISH COLOR TO MATCH
EXISTING, OR AS SPECIFIED BY OWNER. CONFIRM FINISH AND COLOR WITH
OWNER PRIOR TO ORDER AND FABRICATION.
BASIS OF DESIGN: METALWORKS 3"x12", 22GA PANEL AT 6'-0" SPAN LENGTH, 2
SPAN (MINIMUM) CONDITION.
2. THE STEEL PANEL SHALL BE SUPPLIED IN LENGTHS TO SPAN CONTINUOUS FROM
THE INTERNAL GUTTER TO THE PERIMETER. ALL PANELS MUST HAVE VARIOUS
TRIM COMPONENTS AND ALL OTHER ACCESSORIES AS NECESSARY FOR A
COMPLETE INSTALLATION AND SHALL HAVE KYNAR 500 FINISH.
3. STEEL PANELS SHALL BE FASTENED PER THE FASTENER PATTERN DETAILS AS
INDICATED ON THE DRAWINGS.
4. ALL HORIZONTAL, VERTICAL AND CORNER TRIM, CLOSURES, CLIPS AND
FASTENERS ARE TO BE PROVIDED FOR A COMPLETE AND FINISHED APPEARANCE.
COORDINATE WITH EXISTING CONDITIONS AND METAL PANEL MFR / SUPPLIER
FOR COMPATIBLE COMPONENTS AND INSTALLATION REQUIREMENTS.
5. SHOP DRAWINGS SHALL INDICATE THE FINISH, TYPE, GAGE, DIMENSIONS, AND
LAYOUT OF ALL DECK, TRIM, AND ACCESSORIES. DRAWINGS MUST BE SUBMITTED
TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION.
ALTERNATE BID
PARAPET PANELS AND TRIM:
1. FORMED STEEL ROOF PANELS TO BE 12" (FLAT) x 1 3/4" HIGH, 24ga GALVALUME
COATED AND FINISHED w/ SIGNATURE 300 FINISH, BOTH SIDES. FINISH COLOR TO
MATCH EXISTING, OR AS SPECIFIED BY OWNER. CONFIRM FINISH AND COLOR
WITH OWNER PRIOR TO ORDER AND FABRICATION.
BASIS OF DESIGN: MBCI PBU EXPOSED FASTENER PANEL, 36"x3/4", 24GA PANEL.
2. THE STEEL PANEL SHALL BE SUPPLIED IN LENGTHS TO SPAN CONTINUOUS IN
HEIGHT. ALL PANELS MUST HAVE VARIOUS ASSOCIATED BASE AND CAP TRIM
COMPONENTS, CORNER TRIM, AND ALL OTHER ACCESSORIES AS NECESSARY
FOR A COMPLETE AND FINISHED APPEARANCE INSTALLATION. ALL TRIM
COMPONENTS SHALL HAVE KYNAR 500 FINISH TO MATCH THE PANEL.
3. STEEL PANELS SHALL BE FASTENED PER THE MANUFACTURERS PANEL AND TRIM
INSTALLATION TYPICAL DETAILS.
4. SHOP DRAWINGS SHALL INDICATE THE FINISH, TYPE, GAGE, DIMENSIONS, AND
LAYOUT OF ALL DECK, TRIM, AND ACCESSORIES. DRAWINGS MUST BE SUBMITTED
TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION.
COATINGS FOR STEEL
1. SURFACE PREPARATION AND CLEANING: STRUCTURAL STEEL SHALL BE
CLEANED IN ACCORDANCE WITH THE STEEL STRUCTURES PAINTING COUNCIL
SPECIFICATION SSPC-SP3 FOR POWER TOOL CLEANING AS FOLLOWS:
· BEFORE POWER TOOL CLEANING, VISIBLE DEPOSITS OF OIL, GREASE, OR
OTHER MATERIAL THAT MAY INTERFERE WITH COATING ADHESION SHALL
BE REMOVED.
· USE ROTARY OR IMPACT POWER TOOLS TO REMOVE STRATIFIED RUST
(RUST SCALE).
· USE POWER WIRE BRUSHING, POWER ABRADING, POWER IMPACT, OR
OTHER POWER ROTARY TOOLS TO REMOVE ALL LOOSE MILL SCALE, ALL
LOOSE OR NON-ADHERENT RUST, AND ALL LOOSE PAINT. DO NOT BURNISH
THE SURFACE.
· OPERATE POWER TOOLS IN A MANNER THAT PREVENTS THE FORMATION OF
BURRS, SHARP RIDGES, AND SHARP CUTS.
· AFTER POWER TOOL CLEANING AND PRIOR TO PAINTING, REMOVE DIRT,
DUST, OR SIMILAR CONTAMINANTS FROM THE SURFACE. ACCEPTABLE
METHODS INCLUDE BRUSHING, BLOW OFF WITH CLEAN, DRY AIR, OR
VACUUM CLEANING.
2. CLEAN ALL NEW AND EXISTING STEEL AND COAT WITH MACROPOXY 646-100
HIGH BUILD, HIGH SOLIDS EPOXY COATING SYSTEM CONSISTING OF A PRIMER
AND FINISH COAT AS MANUFACTURED BY MAB PAINTS, OR APPROVED EQUAL.
PROVIDE DIFFERENT COLORS FOR PRIMER AND FINISH COAT.
3. OWNER MAY ENGAGE THE SERVICES OF A QUALIFIED TESTING AND INSPECTING
AGENCY TO INSPECT AND TEST COATINGS FOR DRY FILM THICKNESS AND
ADHESION.
CONTRACTOR / OWNER NOTES
1. JOB SITE SAFETY IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR,
REVIEW OF THE CONSTRUCTION BY THE ENGINEER IS FOR CONFORMANCE
WITH DESIGN ASPECTS ONLY, NOT TO REVIEW THE CONTRACTOR'S
PROVISIONS FOR JOB SITE SAFETY. GUIDELINES FOR CONSTRUCTION
SAFETY SHALL BE IN ACCORDANCE WITH, BUT NOT LIMITED TO, THE
CONSTRUCTION INDUSTRY OSHA SAFETY AND HEALTH STANDARDS (1926
STANDARDS), AND ANY LOCAL ORDINANCES OR CODES THAT MIGHT APPLY.
LACK OF COMMENT ON THE PART OF THE ENGINEER WITH REGARD TO JOB
SITE SAFETY IS NOT TO BE INTERPRETED AS APPROVAL OF JOB SITE
SAFETY ASPECTS.
2. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING PROTECTION,
INCLUDING ALL TEMPORARY BARRICADES, PLANK BRIDGES, SIGNAGE, ETC
AS REQUIRED TO PROTECT OWNER'S PERSONNEL AND GROUND
EQUIPMENT FROM INJURY OR DAMAGE DURING THE DEMOLITION AND
CONSTRUCTION PERIOD. IF PERMITS ARE REQUIRED BY THE LOCAL
JURISDICTION FOR THE ERECTION OF SIDEWALK PROTECTION, THE COST
OF SUCH PERMIT WILL BE BORNE BY THE OWNER.
3. ALL EXISTING CONDITIONS SHALL BE FIELD VERIFIED MEASURED AND
DOCUMENTED PRIOR TO BEGINNING ANY WORK. IF EXISTING CONDITIONS
DO NOT PERMIT THE INSTALLATION OF THE PROPOSED WORK IN
ACCORDANCE WITH THE DETAILS AS SHOWN, THE CONTRACTOR SHALL
NOTIFY THE ENGINEER OF RECORD IMMEDIATELY AND PROVIDE AN
ACCURATE SKETCH OF THE CONDITION, INCLUDING A PROPOSED
MODIFICATION OR CORRECTION, FOR REVIEW AND APPROVAL.
4. THE CONTRACTOR SHALL REVIEW THE NEED FOR TEMPORARY SHORING
AND BRACING PRIOR TO THE CUTTING AND/OR REMOVAL OF ANY EXISTING
CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR THE
DEVELOPMENT AND COORDINATION OF THE SEQUENCE OF TEMPORARY
VERTICAL AND LATERAL BRACING, SHORING, DEMOLITION, AND NEW
CONSTRUCTION AS PROJECT CONDITIONS REQUIRE TO MAKE SAFE ALL
STRUCTURAL ELEMENTS AND ADJACENT PROPERTY ELEMENTS IMPACTED
BY THE PROJECT SCOPE OF WORK.
5. THIS STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND
STABLE AFTER THE REPLACEMENT OF THE CANOPY COMPONENTS HAS
BEEN COMPLETED. THE STABILITY OF THE STRUCTURE PRIOR TO
COMPLETION IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. THIS
RESPONSIBILITY EXTENDS TO ALL RELATED ASPECTS OF THE
CONSTRUCTION ACTIVITY INCLUDING, BUT NOT LIMITED TO, ERECTION
METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, SHORING, USE OF
EQUIPMENT, AND SIMILAR CONSTRUCTION PROCEDURES, UNLESS
SPECIFICALLY INDICATED ON THE CONTRACT DOCUMENTS. LACK OF
COMMENT ON THE PART OF THE ENGINEER WITH REGARD TO
CONSTRUCTION PROCEDURES IS NOT TO BE INTERPRETED AS APPROVAL
OF THOSE PROCEDURES.
6. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR WORK
DISRUPTING THE ENTRANCES AND EXITS TO THE CANOPY. THE
RE-DIRECTION, BLOCKING AND REROUTING OF PEDESTRIAN AND STREET
TRAFFIC MUST BE IN PLACE AND COORDINATED PRIOR TO START OF WORK.
7. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR TEMPORARY
DISCONNECTION AND RELOCATION OF ELECTRICAL SERVICE AND CONDUIT
THROUGHOUT THE CANOPY. ELECTRICAL SERVICE TO BE RESTORED BY
THE G.C. UPON COMPLETION OF CANOPY WORK.
POLYVINYL BUTYAL GUTTER LINER
1. GUTTER LINER: ONE PLY BONDED TO THE PREPARED SUBSTRATE IN GUTTER
LINER ADHESIVE. THE GUTTER LINER MEMBRANE MUST BE A PVB
(POLYVINYLBUTYRAL) WATERPROOFING MEMBRANE WITH A NOMINAL
THICKNESS OF 110 MILS. THE MEMBRANE MUST HAVE AN ALUMINUM SCRIM FOR
REINFORCEMENT GIVING IT THE STRENGTH, RIGIDITY AND CONFORMABILITY
FOR THE APPLICATION AS A GUTTER LINING MEMBRANE.
· BASIS OF DESIGN: GREENWELD PVB MEMBRANE BY THE GARLAND CO. /
VIKING PRODUCTS GROUP, INC., CLEVELAND OHIO.
2. GUTTER LINER ADHESIVE MUST BE A SINGLE COMPONENT, POLYETHER
STRUCTURAL ADHESIVE AS CONFIRMED BY ACTUAL ADHESION TESTING TO THE
EXISTING MEMBRANE.
· BASIS OF DESIGN: GREEN-LOCK STRUCTURAL ADHESIVE BY THE GARLAND
CO., CLEVELAND OHIO.
3. SEAM SEALER MUST BE A SYNTHETIC LIQUID RUBBER, BRUSH GRADE (BG), THAT
CURES TO A MONOLITHIC RUBBERY MEMBRANE WITH HIGH TENSILE STRENGTH
AND THE ABILITY TO ELONGATE AND RECOVER.
· BASIS OF DESIGN: CPR SEAM SEALER BY THE GARLAND CO., CLEVELAND
OHIO.
4. GUTTER LINER MEMBRANE INSTALLATION:
A. INSTALL UNDERLAYMENT AND FLASHING MEMBRANE CONTINUOUSLY IN THE
ENTIRE GUTTER ASSEMBLY.
B. HEAT WELD THE PVB MEMBRANE SEAMS TOGETHER USING HOT AIR WELDING
GUN AND A FLAT ANGLED TIP SET AT MANUFACTURER'S RECOMMENDED
HEAT SETTINGS. BASIS OF DESIGN MANUFACTURER RECOMMENDS USING A
LEISTER HEAT GUN OR EQUAL TOOL. USE A WEIGHTED HAND-ROLLER WHILE
HEAT WELDING THE SEAMS.
C. NO OPEN FLAME SHOULD BE USED WITH THIS PRODUCT TO WELD THE
SEAMS.
D. INSTALL IN GUTTER TO AVOID CREATING BACK WATER LAPS, INSTALLING TOP
MEMBRANE AT THE HIGHER SIDE OF THE GUTTER, HEAT WELDING THE
LOWER MEMBRANE TO THE TOP AND SEALING WITH APPROVED SEALANT UP
THE SIDES OF THE GUTTER AND AT TOP.
E. ROLL OR BRUSH MEMBRANE INTO ADHESIVE TO ENSURE FULL CONTACT TO
THE GUTTER. FORM MEMBRANE WITH ROLLER AND PUTTY KNIFE TO
CONFORM TO ALL ANGLES OF THE GUTTER.
F. SET THE PVB MEMBRANE IN BEADS OF SPECIFIED ADHESIVE / SEALANT AT 12"
O.C. TO ALL SURFACES.
G. SEAMS OF MEMBRANE SHALL BE HEAT WELDED AND SEAL ALL SEAMS OR
EDGES OF THE PRODUCT WITH APPROVED SEALANT.
H. THE MEMBRANE SHALL RUN CONTINUOUSLY OVER ALL INTERIOR SURFACES
OF THE GUTTER AND UNDER FLASHINGS AND/OR DRIP EDGES, COUNTER
FLASHINGS, EXPANSION JOINTS, ETC.; TO BE SANDWICHED BETWEEN NEW
PANEL LINE, SEALANTS, AND FASTENERS. MEMBRANE SHALL TERMINATE AS
PER THE PROJECT DETAILS AND MANUFACTURER'S
RECOMMENDATIONS/REQUIREMENTS AND SHALL NOT BE EXPOSED OR
VISIBLE FROM THE UNDERSIDE.
I. COORDINATE WITH, AND FOLLOW PRODUCT MFR FOR FULL INSTALLATION
INSTRUCTIONS AND INSTALLATION REQUIREMENTS IN ADDITION TO THE
ITEMS NOTED ABOVE.
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE
ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL
ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND
SURVEYOR TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED, THE ALTERING
ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND
SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION
OF THE ALTERATION.
Fi le
V:
\P
RO
JE
CT
S\
AN
Y\ K7
\1
3.
0\
_D
ES
IG
N \D
RA
W
IN
G
S\
ST
RU
C\
M O
DE
L-
.D
W G
Sa ve d:
/9 /2
4:
:0
PM
P lo tt ed
9/ 9/
:1
6:
P M
C ur re nt
U se r:
G ar la nd
Pe te
L as tS av ed By
Checked By:
Drawing No.:
Issue Date:
Designed By: Drawn By:
Project No.: Scale:
Sheet of 3
AS SHOWN
No. By DateSubmittal / Revision Apv
Drawing Copyright © 2026
One East Broad Street Suite 310
Bethlehem, PA. 18018 610.865.3000
EASTON AREA JOINT
SEWER AUTHORITY
SLUDGE CANOPY
REPAIRS
PLAN AND
SECTION
PMGSGYNRC
1030239/10/26
S-101
MC-1, MC-2 METAL STUD,
SEE PLAN AND NOTES.
(NOT AT PANEL SPANS 90° TO AS
DETAILED HERE, SEE PLAN)
DIAGONAL BRACE,
(BR-1). SEE PLAN
AND NOTES
CONT GAGE ANGLE w/
FASTENERS TO EACH "MC" METAL
STUD OR ROOF PANEL
OVERLAPPING RIB (AT PANEL
SPAN OPPOSITE DIRECTION),
AND TO PARAPET PANELS
INTERLOCKING ROOF / CEILING
PANELS w/ FASTENERS TO EACH
"MC" MEMBER AND STEEL
SUPPORT BEAMS
PURLIN BEAM
PARAPET PANEL, TOP, BOTTOM
AND CORNER TRIM, HORIZ
BRACING AND INSIDE CORNER
ANGLES. SEE PLAN NOTES FOR
BASE BID REQUIREMENTS
ENLARGED PARAPET SECTION
SCALE: 1 1/2"=1'-0"
S102
1/ 2"
BASE BID:
COLLECTOR BOX. FABRICATE
FROM 3/16" PLATE STEEL.
BRAKE BEND WHERE
POSSIBLE, WELD ALL SEAMS.
BOX TO EXTEND 4" MIN FROM
FACE OF COLUMN, ALL SIDES
COLLECTOR BOX MUST BE A
SPLIT DESIGN AND FIELD SEAMED.
PROVIDE 1/8" WELDS TO COLUMN
AND APPLY SEALANT PRIOR TO
LINER. SEE NOTES FOR GUTTER
LINER
3" LONG INTEGRAL FLANGE,
EACH SIDE OF COLLECTOR
BOX.
NOTE: FABRICATE EXTENSION
FLANGE TO ALLOW GUTTER TO
FIT TIGHT WITHIN FLANGE
BRAKE BENT 16ga GALV GUTTER w/ 1"x11
2"x0.120
RECTANGULAR TUBE EACH
SIDE.
16ga BRAKE BENT GUTTER
TO FIT WITHIN, AND LAP TO
COLUMN BOX FLANGES.
SEE NOTES FOR GUTTER
LINER
3"
1 1/2"
12"
3"
3" MIN
3"
(INSIDE)
FASTEN GUTTER TO
FLANGE WITH 3/16"
STAINLESS STEEL DOME
HEAD BLIND RIVETS AT 1"o.c.
CUT-OUT FOR DOWNSPOUT
NIPPLE TO FIT INSIDE 6" SCHED
80 PVC DOWNSPOUT. FIELD
LOCATE. EXTEND GUTTER
LINER INTO DOWNSPOUT
NIPPLE. SEAL ALL SEAMS PER
MFR
TOP OF COLUMN NOT SHOWN
FOR DETAIL CLARITY. SEE
FRAMING PLAN FOR BEAM
LEVELING NOTES
PURLIN BEAMS
BOLT CONDITION TO BE
FIELD EVALUATED.
ANTICIPATE REPLACEMENT
OF ALL BOLTS IN-KIND
(GRADE A325 MIN)
REPLACE EXISTING CEILING /
ROOF PANELS w/ 12" wide x 3" DEEP, 22ga INTERLOCKING
PANELS. SEE PANEL NOTES
FABRICATED CLOSED AND
SEALED BOX END GUTTER
CLOSURES, TYP
(NOT SHOWN)
FASTEN PANELS TO PURLINS
w/ CLIPS, OR FASTEN THRU
INTERLOCKING PANELS
DIRECTLY TO PURLINS AS
RECOMMENDED BY PANEL
MFR
FIELD TRIM / PROFILE AS REQ'D
S.S. CAP AND
GASKETED SELF
DRILLING
FASTENERS THRU
PANEL ENDS TO
RECTANGULAR TUBE
1 1/2"
LINER,
SEE NOTES
FASTEN 1"x11 2"x0.120
RECTANGULAR TUBES TO
BRAKE BENT GUTTER w/ 3/16"
STAINLESS STEEL DOME
HEAD BLIND RIVETS AT 4"o.c.
CUT FLUSH AND SEAL EXIST
2" INTERNAL DOWNSPOUT w/
3/16" STEEL PLATE FIELD
WELDED AND FINISHED
SMOOTH. SIMILAR AT
COLUMN BASE, TYPICAL
CROSS BEAMS
TURN UP AND
SEAL PANEL ENDS
OPPOSITE OF
GUTTER
ISOMETRIC REFERENCE DETAIL
SCALE: 3/4"=1'-0"
S102
2" WIDE PANEL FASTENING
FLANGE, TYP
MC-1, MC-2 METAL STUD,
SEE PLAN AND NOTES.
(NOT AT PANEL SPANS 90° TO
AS DETAILED HERE, SEE PLAN)
ADJUSTABLE (OR FIXED) LENGTH
DIAGONAL BRACE, "BR-1" ON PLAN. (2)
BRACES REQ'D AT EACH LOCATION AS
SHOWN ON PLAN (3'-0" o.c. MAXIMUM)
FOR ALTERNATE BID.
EACH BRACE MUST BE SELECTED TO
CAPABLE OF 450 lbs OF TENSION AND
COMPRESSION LOADING, MINIMUM
CONT 3"x3"x16ga GALV G-90 ANGLE w/
FASTENERS TO EACH "MC" METAL STUD
OR ROOF PANEL OVERLAPPING RIB
(AT PANEL SPAN OPPOSITE DIRECTION),
AND TO PARAPET PANELS
INTERLOCKING ROOF / CEILING
PANELS w/ FASTENERS TO EACH "MC"
MEMBER AND STEEL SUPPORT BEAMS
PURLIN BEAM, SEE PLAN
AND FIELD CONDITIONS
FOR SPACING
1/ 2"
ENLARGED PARAPET SECTION
SCALE: 3"=1'-0"
S102
ALTERNATE BID:
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO ANGLE
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. VERT AT
PANEL OVERLAPS
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU
PANEL, BASE TRIM, INTO CLG
PANEL
BASE DRIP TRIM
FASTEN BRACE TO FLAT
OF GA METAL STUD
SECTION w/ 12-14 TEK
SCREWS
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO EACH
FLANGE OF HAT TRACK
1 1/2", 16ga GALV G90 CONTINUOUS HAT
TRACK. IF TRACK IS NOT CONTINUOUS TO
CORNERS, LAPS MUST BE 12" MIN AND
OCCUR AT DIAGONAL BRACES. FASTEN
LAP LEGS w/ (3) SCREWS MIN EACH
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL, TOP "U" TRIM, AND INTO FLANGE OF HAT TRACK
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU
PANEL AND INTO FLANGE OF
HAT TRACK
450 lbsMIN
FASTEN BRACE TO ALL HAT
TRACK w/ 12-14 TEK SCREWS
450 lbsMIN
1/2" 2 11/16"
1/
2"1 1/4"
1/2"
EQ
EQ
1/
2"
℄ HAT
TRACK
℄ HAT
TRACK
ANGLE
BASE
CONT 3"x3"x16ga GALV G-90 ANGLE w/
FASTENERS TO ROOF PANELS AS
SPECIFIED BY CLG PANEL MFR
INTERLOCKING ROOF / CEILING PANELS
PURLIN BEAM, SEE PLAN
AND FIELD CONDITIONS
FOR SPACING
1/ 2"
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO ANGLE
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. VERT AT
PANEL OVERLAPS
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL, BASE TRIM, INTO CLG PANEL END CLOSURE
BASE DRIP
TRIM
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO EACH
FLANGE OF HAT TRACK
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU
PANEL AND INTO FLANGE OF
HAT TRACK
450 lbsMIN
CLG PANEL END CLOSURE,
COORD w/ CLG MFR / SUPPLIER
FOR TRIM REQUIREMENTS
12-24 TEKS/5 OR
1/4" THRU BOLT AT
BRACES TO BEAM
450 lbs
MIN
EXST BEAM
1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL, TOP "U" TRIM, AND INTO FLANGE OF HAT TRACK
FASTEN BRACE TO TRACK
w/ 12-14 TEK SCREWS
1 1/2", 16ga GALV G90 CONTINUOUS
HAT TRACK. IF TRACK IS NOT CONTINUOUS
TO CORNERS, LAPS MUST BE 12" MIN AND
OCCUR AT DIAGONAL BRACES. FASTEN LAP
LEGS w/ (3) SCREWS MIN EACH
FASTEN BRACE TO TRACK
w/ 12-14 TEK SCREWS
ENLARGED PARAPET SECTION
SCALE: 1 1/2"=1'-0"
2A S102
ALTERNATE BID:
EQ
EQ
1/
2"
℄ HAT
TRACK
℄ HAT
TRACK
ANGLE
BASE
ADJUSTABLE (OR FIXED) LENGTH
DIAGONAL BRACE, "BR-1" ON PLAN. (2)
BRACES REQ'D AT EACH LOCATION AS
SHOWN ON PLAN (3'-0" o.c. MAXIMUM)
FOR ALTERNATE BID.
EACH BRACE MUST BE SELECTED TO
CAPABLE OF 450 lbs OF TENSION AND
COMPRESSION LOADING, MINIMUM
IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE
ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL
ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND
SURVEYOR TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE
STAMP OF A LICENSED PROFESSIONAL IS ALTERED, THE ALTERING
ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND
SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE
NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE
DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION
OF THE ALTERATION.
Fi le
V:
\P
RO
JE
CT
S\
AN
Y\ K7
\1
3.
0\
_D
ES
IG
N \D
RA
W
IN
G
S\
ST
RU
C\
M O
DE
L-
.D
W G
Sa ve d:
/9 /2
4:
:0
PM
P lo tt ed
9/ 9/
:1
6:
P M
C ur re nt
U se r:
G ar la nd
Pe te
L as tS av ed By
Checked By:
Drawing No.:
Issue Date:
Designed By: Drawn By:
Project No.: Scale:
Sheet of 3
AS SHOWN
No. By DateSubmittal / Revision Apv
Drawing Copyright © 2026
One East Broad Street Suite 310
Bethlehem, PA. 18018 610.865.3000
EASTON AREA JOINT
SEWER AUTHORITY
SLUDGE CANOPY
REPAIRS
NOTES,
SECTIONS AND
DETAILS
PMGSGYNRC
1030239/10/26
S-102
| SD-100 |
| SD-100 |
| S-101 |
| S-101 |
| S-102 |
| S-102 |