1-EAJSA WWTP Sludge Canopy Repairs IFB Drawings.pdf

PDF 568 KB Posted

Attached to
Sludge Canopy Repairs
Solicitation number
US.263475
Issued by
Northampton County, Pennsylvania

About this file

This file contains the technical drawings for the Sludge Canopy Repairs project issued by the Easton Area Joint Sewer Authority (EAJSA) in Pennsylvania. The project encompasses structural repairs to the sludge canopy at the Easton Wastewater Treatment Plant, including roof framing demolition, parapet rehabilitation, installation of new roof panels and gutters, drainage system improvements, structural steel cleaning and recoating, roof framing leveling, and associated repairs to canopy support components. The contract is for general construction work with an expected project duration of 140 days. A non-mandatory pre-bid meeting is scheduled for 10:00 AM on Tuesday, December 1, 2026, at the Administration Building at the WWTP. Site visits by appointment only are available until 3:00 PM on Tuesday, December 15, 2026, at 50 South Delaware Drive, Easton, PA 18042. Bidding documents are available through the designated website at https://pennbid.bonfirehub.com, where prospective bidders are urged to register as plan holders to receive official notifications and addenda.

The drawings serve as technical documentation supporting the bid submission process and provide the engineering specifications and details necessary for contractors to prepare accurate cost estimates and construction plans. Pricing terms, funding sources, and award details are not specified within this drawings document. Interested bidders should consult the complete bidding documents and specifications available through the PennBid portal for comprehensive project requirements, contract terms, and submission instructions.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EX

ST

C R

O

SS

BE

AM

EXST PURLIN

BEAM

EX

ST

C R

O

SS

BE

AM

EXST PURLIN

BEAM

EXST PURLIN

BEAM

EXST PURLIN

BEAM

EXST PURLIN

BEAM

EXST PURLIN

BEAM

ROOF FRAMING DEMOLITION PLAN

SCALE: 3/8"=1'-0"

30'-2"

12'-0"1"± 6'-0" 12'-0" 1"±

'-2

2' -0

1"

1"

5'

-3

5' -3

2'

-6

2' -6

5'

-3

5' -3

2'

-0

DEMO PERIMETER

GAGE METAL BASE

OF PARAPET

ANGLE, ALL 4 SIDES

DEMO INTERNAL

GUTTER AND

COLUMN

COLLECTOR

BOXES

DEMO ROOF /

CEILING PANELS

DEMO HORIZ GAGE

METAL CEE STUDS

AND FASTENERS

LAID FLAT ACROSS

ROOF PANEL HIGH

RIBS, TYPICAL

BASE BID:

SALVAGE ADJUSTABLE

DIAGONAL BRACES

FROM FLAT STUD

MEMBER TO TOP OF

PARAPET. CLEAN,

COAT AND RE-INSTALL

BASE BID:

SALVAGE ADJUSTABLE

DIAGONAL BRACES

FROM TOP OF EXST

PURLIN BEAMS TO TOP

OF PARAPET. CLEAN,

COAT AND RE-INSTALL

AT ALL BEAM TO BEAM

AND BEAM TO COLUMN

CAP PLATES, BOLT

CONDITION TO BE FIELD

EVALUATED. ANTICIPATE

REPLACEMENT OF ALL

BOLTS IN-KIND

AFTER REMOVAL OF ALL DEMO AND SALVAGED COMPONENTS,

CLEAN ALL STRUCTURAL STEEL, DOWN TO BASE OF COLUMNS

EMBEDDED IN CONCRETE TO MEET SSPC-SP3 STANDARDS.

PREPARE STEEL FOR COATING SYSTEM, SEE COATING NOTES

CUT FLUSH AND SEAL EXIST

2" INTERNAL DOWNSPOUT

w/ 3/16" STEEL PLATE FIELD

WELDED AND FINISHED

SMOOTH. SIMILAR AT

COLUMN BASE,

TYPICAL

BASE BID:

USE CARE AND SALVAGE

PARAPET PANELS, TRIM AND

HORIZONTAL HAT-TRACK

BRACING FOR

RE-INSTALLATION

BASE BID:

SALVAGE ALL ADJUSTABLE DIAGONAL BRACES (ALL 4 SIDES).

CLEAN TO MEET SSPC-SP3 STANDARDS.

PREPARE STEEL FOR COATING SYSTEM, SEE COATING NOTES

DEMO

SECTION

PA

N

EL

TH

IC

KN

ES

S

PA

N

EL

TH

IC

KN

ES

S

PANEL

THICKNESS

PANEL

THICKNESS

N

EXST PURLIN BEAM

BR-1

(BEYOND)

EXST

COLS

DEMO INTERNAL

GUTTER

DEMO ROOF / CEILING

PANELS

DEMOLITION SECTION

SCALE: 3/8"=1'-0"

SEE PLAN NOTES TO

CLEAN ALL

STRUCTURAL STEEL

COMPONENTS

SEE PLAN NOTE TO CUT

FLUSH AND SEAL EXIST

INTERNAL DOWNSPOUT

INTAKES AND EXITS

BASE BID:

USE CARE AND SALVAGE

PARAPET PANELS, TRIM AND

HORIZONTAL HAT-TRACK

BRACING FOR

RE-INSTALLATION

EXIST CONC ISLAND

AND BOLLARDS. NO

WORK THIS AREA

ALL STRUCTURAL STEEL AND

COLUMNS TO BE CLEANED

AND COATED, SEE

CONSTRUCTION PLANS AND

COATING NOTES

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE

ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL

ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND

SURVEYOR TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE

STAMP OF A LICENSED PROFESSIONAL IS ALTERED, THE ALTERING

ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND

SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE

NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE

DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION

OF THE ALTERATION.

Fi le

V:

\P

RO

JE

CT

S\

AN

Y\ K7

\1

3.

0\

_D

ES

IG

N \D

RA

W

IN

G

S\

ST

RU

C\

M O

DE

L-

.D

W G

Sa ve d:

/9 /2

4:

:0

PM

P lo tt ed

9/ 9/

:1

6:

P M

C ur re nt

U se r:

G ar la nd

Pe te

L as tS av ed By

Checked By:

Drawing No.:

Issue Date:

Designed By: Drawn By:

Project No.: Scale:

Sheet of 3

AS SHOWN

No. By DateSubmittal / Revision Apv

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

EASTON AREA JOINT

SEWER AUTHORITY

SLUDGE CANOPY

REPAIRS

DEMOLITION

PLAN AND

SECTION

PMGSGYNRC

1030239/10/26

SD-100

11/19/2026

EX

ST

C R

O

SS

B

EA

M

EXST PURLIN BEAM

EX

ST

C R

O

SS

B

EA

M

EXST PURLIN BEAM

EXST PURLIN BEAM

EXST PURLIN BEAM

EXST PURLIN BEAM

EXST PURLIN BEAM

MC-1

MC-2

MC-2

MC-1

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-1

MC-1 DENOTES 362S162-54 (G90) METAL STUD, 54"lg (OR AS REQ'D TO ENGAGE (4 MIN)

UP-TURNED PANEL STIFFENING RIBS. MC-1 ALSO INCLUDES ADJUSTABLE PARAPET

DIAGONAL BRACE, SIMILAR TO BR-1.

BASE BID: REUSE EXISTING DIAGONAL PARAPET BRACES

ALTERNATE BID: SEE 2/S102 AND 2A/S102 FOR DIAGONAL BRACE REQUIREMENTS

ROOF FRAMING PLAN

SCALE: 3/8"=1'-0"

BR

-1

BR

-1

BR

-1

BR

-1

BR

-1

BR

-1

BR

-1

BR

-1 BR

-1

BR

-1

BR

-1

BR

-1

BR

-1

BR

-1

30'-2"

12'-0"3/4"± 6'-0" 12'-0" 3/4"±

'-2

2' -0

3/

4"

3/ 4"

5'

-3

5' -3

2'

-6

2' -6

5'

-3

5' -3

2'

-0

3"x3"x16ga

GALV G-90

ANGLE, FULL

PERIMETER

3"x3"x16ga G-90

GALV PERIMETER

ANGLE, FASTEN

TO EACH MC-1

AND MC-2 w/ (2)

TEK SCREWS

(2) DOWNSPOUT

LOCATIONS AS SHOWN

SECTION

MC-2 DENOTES 362S162-54 (G90) METAL STUD, 54"lg (OR AS REQ'D TO ENGAGE (4 MIN)

UP-TURNED PANEL STIFFENING RIBS. MC-2 DOES NOT RECEIVE PARAPET

DIAGONAL BRACE (BR-1)

MC-1

MC-2

MC-2

MC-1

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-1

MC-2

MC-2

ROOF / CEILING

PANELS, SEE

NOTES

BR-1 DENOTES ADJUSTABLE PARAPET DIAGONAL BRACE:

BASE BID: SALVAGE CLEAN AND COAT DIAGONAL (BR-1) BRACES FOR RE-USE

WITH NEW FASTENING HARDWARE

ALTERNATE BID: PROVIDE NEW (BR-1) ADJUSTABLE PARAPET BRACES.

SEE 2/S102 AND 2A/S102 FOR DIAGONAL BRACE REQUIREMENTS

BASE BID:

RE-INSTALL PARAPET

PANELS, TRIM AND

HORIZONTAL BRACING

WITH NEW FASTENING

HARDWARE

LINED INTERNAL

GUTTER AND

COLUMN

COLLECTOR

BOXES

PANEL

THICKNESS

PANEL

THICKNESS

PA

N

EL

TH

IC

KN

ES

S

PA

N

EL

TH

IC

KN

ES

S

SEE 3/S102 FOR ISOMETRIC REFERENCE CONSTRUCTION DETAIL

N

LOOSEN BOLTS SECURING (2) CROSS

BEAMS TO COLUMN CAPS. INSTALL

TAPERED STEEL PLATE FINGER SHIMS

BETWEEN CAP PLATE AND BOTTOM OF

CROSS BEAMS TO ENSURE PURLIN BEAMS

ARE SET TO THE SAME LEVEL ELEVATION

AT THE (4) EXTREME CORNERS ( ) OF THE

CANOPY STEEL FRAMING, ENSURING

POSITIVE DRAINAGE TO INTERNAL GUTTER.

REPLACE LOOSENED BOLTS WITH NEW

A325 BOLTS MATCHING EXISTING DIAMETER.

PROVIDE TEMP SUPPORT OF ROOF

FRAMING DURING LEVELING AND UNTIL

BOLTS ARE FULLY TIGHTENED.

SEE ROOF

FRAMING

LEVELING

NOTE BELOW

ROOF FRAMING LEVELING

ALTERNATE BID:

INSTALL ALL NEW PARAPET

PANELS, TRIM, FASTENERS AND

BRACING.

SEE ALTERNATE PARAPET

SECTIONS 2/S102 AND 2A/S102

FOR PARAPET CONSTRUCTION

DETAILS

EXISTING LOCATIONS

BASE BID:

3'-0" o.c. MAX

ALTERNATE BID:

3' -0

" o .c

. M

AX

MC-2FL

AT

M

ET

AL

ST

U D

SP

AC

IN

G

3' -0

" o .c

. M

AX

DI

AG

O

NA

L

BR

AC

E

SP

AC

IN

G

SEE BASE BID /

ALT BID NOTES

OPP SIDE FOR

SPACING

EXST PURLIN BEAMMC-1, MC-2

BR-1

(BEYOND)

EXST

COLS

6" SCHED 80 PVC

DOWNSPOUTS AND

ELBOWS, FACE MOUNTED

WITH STRAPS TO

COLUMNS

INTERNAL

GUTTER

ROOF / CEILING

PANELS, SEE NOTES

ELBOW AND NIPPLE

TO INTERNAL GUTTER,

(2 LOCATIONS).

D.S. NIPPLE TO MATCH

INSIDE DIAMETER OF 6"

SCHED 80 PVC PIPE

SECTION

SCALE: 3/8"=1'-0"

BASE BID:

RE-INSTALL SALVAGED PARAPET

PANELS, TRIM AND HORIZONTAL

HAT-TRACK BRACING. INSTALL

WITH NEW FASTENING HARDWARE.

ALTERNATE BID:

INSTALL ALL NEW PARAPET

PANELS, TRIM, FASTENERS AND

BRACING.

SEE ALTERNATE PARAPET

SECTIONS 2/S102 AND 2A/S102

FOR PARAPET CONSTRUCTION

DETAILS

1/S102

EXIST CONC ISLAND

AND BOLLARDS. NO

WORK THIS AREA

CAP EXIST 21

2" INTERNAL

DOWNSPOUT OUTLETS w/ 3/16"

STEEL PLATE FIELD WELDED AND

FINISHED SMOOTH AT COLUMN

BASE, TYPICAL

DISCHARGE NEW SCHED 80 PVC

DOWNSPOUTS EACH END OF

CONC ISLAND AS SHOWN.

PROVIDE (2) MIN STRAPS AROUND

HORIZ PIPE TO CONC.

CONNECTION TO BE MADE WITH

STAINLESS STEEL FASTENERS

BR-1

ROOF / CEILING PANELS AND TRIM:

1. FORMED STEEL ROOF PANELS TO BE 12" (FLAT) x 1 3/4" HIGH, 22ga GALVALUME

COATED AND FINISHED w/ KYNAR 500, BOTH SIDES. FINISH COLOR TO MATCH

EXISTING, OR AS SPECIFIED BY OWNER. CONFIRM FINISH AND COLOR WITH

OWNER PRIOR TO ORDER AND FABRICATION.

BASIS OF DESIGN: METALWORKS 3"x12", 22GA PANEL AT 6'-0" SPAN LENGTH, 2

SPAN (MINIMUM) CONDITION.

2. THE STEEL PANEL SHALL BE SUPPLIED IN LENGTHS TO SPAN CONTINUOUS FROM

THE INTERNAL GUTTER TO THE PERIMETER. ALL PANELS MUST HAVE VARIOUS

TRIM COMPONENTS AND ALL OTHER ACCESSORIES AS NECESSARY FOR A

COMPLETE INSTALLATION AND SHALL HAVE KYNAR 500 FINISH.

3. STEEL PANELS SHALL BE FASTENED PER THE FASTENER PATTERN DETAILS AS

INDICATED ON THE DRAWINGS.

4. ALL HORIZONTAL, VERTICAL AND CORNER TRIM, CLOSURES, CLIPS AND

FASTENERS ARE TO BE PROVIDED FOR A COMPLETE AND FINISHED APPEARANCE.

COORDINATE WITH EXISTING CONDITIONS AND METAL PANEL MFR / SUPPLIER

FOR COMPATIBLE COMPONENTS AND INSTALLATION REQUIREMENTS.

5. SHOP DRAWINGS SHALL INDICATE THE FINISH, TYPE, GAGE, DIMENSIONS, AND

LAYOUT OF ALL DECK, TRIM, AND ACCESSORIES. DRAWINGS MUST BE SUBMITTED

TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION.

ALTERNATE BID

PARAPET PANELS AND TRIM:

1. FORMED STEEL ROOF PANELS TO BE 12" (FLAT) x 1 3/4" HIGH, 24ga GALVALUME

COATED AND FINISHED w/ SIGNATURE 300 FINISH, BOTH SIDES. FINISH COLOR TO

MATCH EXISTING, OR AS SPECIFIED BY OWNER. CONFIRM FINISH AND COLOR

WITH OWNER PRIOR TO ORDER AND FABRICATION.

BASIS OF DESIGN: MBCI PBU EXPOSED FASTENER PANEL, 36"x3/4", 24GA PANEL.

2. THE STEEL PANEL SHALL BE SUPPLIED IN LENGTHS TO SPAN CONTINUOUS IN

HEIGHT. ALL PANELS MUST HAVE VARIOUS ASSOCIATED BASE AND CAP TRIM

COMPONENTS, CORNER TRIM, AND ALL OTHER ACCESSORIES AS NECESSARY

FOR A COMPLETE AND FINISHED APPEARANCE INSTALLATION. ALL TRIM

COMPONENTS SHALL HAVE KYNAR 500 FINISH TO MATCH THE PANEL.

3. STEEL PANELS SHALL BE FASTENED PER THE MANUFACTURERS PANEL AND TRIM

INSTALLATION TYPICAL DETAILS.

4. SHOP DRAWINGS SHALL INDICATE THE FINISH, TYPE, GAGE, DIMENSIONS, AND

LAYOUT OF ALL DECK, TRIM, AND ACCESSORIES. DRAWINGS MUST BE SUBMITTED

TO THE ENGINEER FOR REVIEW PRIOR TO FABRICATION.

COATINGS FOR STEEL

1. SURFACE PREPARATION AND CLEANING: STRUCTURAL STEEL SHALL BE

CLEANED IN ACCORDANCE WITH THE STEEL STRUCTURES PAINTING COUNCIL

SPECIFICATION SSPC-SP3 FOR POWER TOOL CLEANING AS FOLLOWS:

· BEFORE POWER TOOL CLEANING, VISIBLE DEPOSITS OF OIL, GREASE, OR

OTHER MATERIAL THAT MAY INTERFERE WITH COATING ADHESION SHALL

BE REMOVED.

· USE ROTARY OR IMPACT POWER TOOLS TO REMOVE STRATIFIED RUST

(RUST SCALE).

· USE POWER WIRE BRUSHING, POWER ABRADING, POWER IMPACT, OR

OTHER POWER ROTARY TOOLS TO REMOVE ALL LOOSE MILL SCALE, ALL

LOOSE OR NON-ADHERENT RUST, AND ALL LOOSE PAINT. DO NOT BURNISH

THE SURFACE.

· OPERATE POWER TOOLS IN A MANNER THAT PREVENTS THE FORMATION OF

BURRS, SHARP RIDGES, AND SHARP CUTS.

· AFTER POWER TOOL CLEANING AND PRIOR TO PAINTING, REMOVE DIRT,

DUST, OR SIMILAR CONTAMINANTS FROM THE SURFACE. ACCEPTABLE

METHODS INCLUDE BRUSHING, BLOW OFF WITH CLEAN, DRY AIR, OR

VACUUM CLEANING.

2. CLEAN ALL NEW AND EXISTING STEEL AND COAT WITH MACROPOXY 646-100

HIGH BUILD, HIGH SOLIDS EPOXY COATING SYSTEM CONSISTING OF A PRIMER

AND FINISH COAT AS MANUFACTURED BY MAB PAINTS, OR APPROVED EQUAL.

PROVIDE DIFFERENT COLORS FOR PRIMER AND FINISH COAT.

3. OWNER MAY ENGAGE THE SERVICES OF A QUALIFIED TESTING AND INSPECTING

AGENCY TO INSPECT AND TEST COATINGS FOR DRY FILM THICKNESS AND

ADHESION.

CONTRACTOR / OWNER NOTES

1. JOB SITE SAFETY IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR,

REVIEW OF THE CONSTRUCTION BY THE ENGINEER IS FOR CONFORMANCE

WITH DESIGN ASPECTS ONLY, NOT TO REVIEW THE CONTRACTOR'S

PROVISIONS FOR JOB SITE SAFETY. GUIDELINES FOR CONSTRUCTION

SAFETY SHALL BE IN ACCORDANCE WITH, BUT NOT LIMITED TO, THE

CONSTRUCTION INDUSTRY OSHA SAFETY AND HEALTH STANDARDS (1926

STANDARDS), AND ANY LOCAL ORDINANCES OR CODES THAT MIGHT APPLY.

LACK OF COMMENT ON THE PART OF THE ENGINEER WITH REGARD TO JOB

SITE SAFETY IS NOT TO BE INTERPRETED AS APPROVAL OF JOB SITE

SAFETY ASPECTS.

2. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING PROTECTION,

INCLUDING ALL TEMPORARY BARRICADES, PLANK BRIDGES, SIGNAGE, ETC

AS REQUIRED TO PROTECT OWNER'S PERSONNEL AND GROUND

EQUIPMENT FROM INJURY OR DAMAGE DURING THE DEMOLITION AND

CONSTRUCTION PERIOD. IF PERMITS ARE REQUIRED BY THE LOCAL

JURISDICTION FOR THE ERECTION OF SIDEWALK PROTECTION, THE COST

OF SUCH PERMIT WILL BE BORNE BY THE OWNER.

3. ALL EXISTING CONDITIONS SHALL BE FIELD VERIFIED MEASURED AND

DOCUMENTED PRIOR TO BEGINNING ANY WORK. IF EXISTING CONDITIONS

DO NOT PERMIT THE INSTALLATION OF THE PROPOSED WORK IN

ACCORDANCE WITH THE DETAILS AS SHOWN, THE CONTRACTOR SHALL

NOTIFY THE ENGINEER OF RECORD IMMEDIATELY AND PROVIDE AN

ACCURATE SKETCH OF THE CONDITION, INCLUDING A PROPOSED

MODIFICATION OR CORRECTION, FOR REVIEW AND APPROVAL.

4. THE CONTRACTOR SHALL REVIEW THE NEED FOR TEMPORARY SHORING

AND BRACING PRIOR TO THE CUTTING AND/OR REMOVAL OF ANY EXISTING

CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR THE

DEVELOPMENT AND COORDINATION OF THE SEQUENCE OF TEMPORARY

VERTICAL AND LATERAL BRACING, SHORING, DEMOLITION, AND NEW

CONSTRUCTION AS PROJECT CONDITIONS REQUIRE TO MAKE SAFE ALL

STRUCTURAL ELEMENTS AND ADJACENT PROPERTY ELEMENTS IMPACTED

BY THE PROJECT SCOPE OF WORK.

5. THIS STRUCTURE HAS BEEN DESIGNED TO BE SELF-SUPPORTING AND

STABLE AFTER THE REPLACEMENT OF THE CANOPY COMPONENTS HAS

BEEN COMPLETED. THE STABILITY OF THE STRUCTURE PRIOR TO

COMPLETION IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. THIS

RESPONSIBILITY EXTENDS TO ALL RELATED ASPECTS OF THE

CONSTRUCTION ACTIVITY INCLUDING, BUT NOT LIMITED TO, ERECTION

METHODS, ERECTION SEQUENCE, TEMPORARY BRACING, SHORING, USE OF

EQUIPMENT, AND SIMILAR CONSTRUCTION PROCEDURES, UNLESS

SPECIFICALLY INDICATED ON THE CONTRACT DOCUMENTS. LACK OF

COMMENT ON THE PART OF THE ENGINEER WITH REGARD TO

CONSTRUCTION PROCEDURES IS NOT TO BE INTERPRETED AS APPROVAL

OF THOSE PROCEDURES.

6. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR WORK

DISRUPTING THE ENTRANCES AND EXITS TO THE CANOPY. THE

RE-DIRECTION, BLOCKING AND REROUTING OF PEDESTRIAN AND STREET

TRAFFIC MUST BE IN PLACE AND COORDINATED PRIOR TO START OF WORK.

7. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER FOR TEMPORARY

DISCONNECTION AND RELOCATION OF ELECTRICAL SERVICE AND CONDUIT

THROUGHOUT THE CANOPY. ELECTRICAL SERVICE TO BE RESTORED BY

THE G.C. UPON COMPLETION OF CANOPY WORK.

POLYVINYL BUTYAL GUTTER LINER

1. GUTTER LINER: ONE PLY BONDED TO THE PREPARED SUBSTRATE IN GUTTER

LINER ADHESIVE. THE GUTTER LINER MEMBRANE MUST BE A PVB

(POLYVINYLBUTYRAL) WATERPROOFING MEMBRANE WITH A NOMINAL

THICKNESS OF 110 MILS. THE MEMBRANE MUST HAVE AN ALUMINUM SCRIM FOR

REINFORCEMENT GIVING IT THE STRENGTH, RIGIDITY AND CONFORMABILITY

FOR THE APPLICATION AS A GUTTER LINING MEMBRANE.

· BASIS OF DESIGN: GREENWELD PVB MEMBRANE BY THE GARLAND CO. /

VIKING PRODUCTS GROUP, INC., CLEVELAND OHIO.

2. GUTTER LINER ADHESIVE MUST BE A SINGLE COMPONENT, POLYETHER

STRUCTURAL ADHESIVE AS CONFIRMED BY ACTUAL ADHESION TESTING TO THE

EXISTING MEMBRANE.

· BASIS OF DESIGN: GREEN-LOCK STRUCTURAL ADHESIVE BY THE GARLAND

CO., CLEVELAND OHIO.

3. SEAM SEALER MUST BE A SYNTHETIC LIQUID RUBBER, BRUSH GRADE (BG), THAT

CURES TO A MONOLITHIC RUBBERY MEMBRANE WITH HIGH TENSILE STRENGTH

AND THE ABILITY TO ELONGATE AND RECOVER.

· BASIS OF DESIGN: CPR SEAM SEALER BY THE GARLAND CO., CLEVELAND

OHIO.

4. GUTTER LINER MEMBRANE INSTALLATION:

A. INSTALL UNDERLAYMENT AND FLASHING MEMBRANE CONTINUOUSLY IN THE

ENTIRE GUTTER ASSEMBLY.

B. HEAT WELD THE PVB MEMBRANE SEAMS TOGETHER USING HOT AIR WELDING

GUN AND A FLAT ANGLED TIP SET AT MANUFACTURER'S RECOMMENDED

HEAT SETTINGS. BASIS OF DESIGN MANUFACTURER RECOMMENDS USING A

LEISTER HEAT GUN OR EQUAL TOOL. USE A WEIGHTED HAND-ROLLER WHILE

HEAT WELDING THE SEAMS.

C. NO OPEN FLAME SHOULD BE USED WITH THIS PRODUCT TO WELD THE

SEAMS.

D. INSTALL IN GUTTER TO AVOID CREATING BACK WATER LAPS, INSTALLING TOP

MEMBRANE AT THE HIGHER SIDE OF THE GUTTER, HEAT WELDING THE

LOWER MEMBRANE TO THE TOP AND SEALING WITH APPROVED SEALANT UP

THE SIDES OF THE GUTTER AND AT TOP.

E. ROLL OR BRUSH MEMBRANE INTO ADHESIVE TO ENSURE FULL CONTACT TO

THE GUTTER. FORM MEMBRANE WITH ROLLER AND PUTTY KNIFE TO

CONFORM TO ALL ANGLES OF THE GUTTER.

F. SET THE PVB MEMBRANE IN BEADS OF SPECIFIED ADHESIVE / SEALANT AT 12"

O.C. TO ALL SURFACES.

G. SEAMS OF MEMBRANE SHALL BE HEAT WELDED AND SEAL ALL SEAMS OR

EDGES OF THE PRODUCT WITH APPROVED SEALANT.

H. THE MEMBRANE SHALL RUN CONTINUOUSLY OVER ALL INTERIOR SURFACES

OF THE GUTTER AND UNDER FLASHINGS AND/OR DRIP EDGES, COUNTER

FLASHINGS, EXPANSION JOINTS, ETC.; TO BE SANDWICHED BETWEEN NEW

PANEL LINE, SEALANTS, AND FASTENERS. MEMBRANE SHALL TERMINATE AS

PER THE PROJECT DETAILS AND MANUFACTURER'S

RECOMMENDATIONS/REQUIREMENTS AND SHALL NOT BE EXPOSED OR

VISIBLE FROM THE UNDERSIDE.

I. COORDINATE WITH, AND FOLLOW PRODUCT MFR FOR FULL INSTALLATION

INSTRUCTIONS AND INSTALLATION REQUIREMENTS IN ADDITION TO THE

ITEMS NOTED ABOVE.

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE

ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL

ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND

SURVEYOR TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE

STAMP OF A LICENSED PROFESSIONAL IS ALTERED, THE ALTERING

ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND

SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE

NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE

DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION

OF THE ALTERATION.

Fi le

V:

\P

RO

JE

CT

S\

AN

Y\ K7

\1

3.

0\

_D

ES

IG

N \D

RA

W

IN

G

S\

ST

RU

C\

M O

DE

L-

.D

W G

Sa ve d:

/9 /2

4:

:0

PM

P lo tt ed

9/ 9/

:1

6:

P M

C ur re nt

U se r:

G ar la nd

Pe te

L as tS av ed By

Checked By:

Drawing No.:

Issue Date:

Designed By: Drawn By:

Project No.: Scale:

Sheet of 3

AS SHOWN

No. By DateSubmittal / Revision Apv

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

EASTON AREA JOINT

SEWER AUTHORITY

SLUDGE CANOPY

REPAIRS

PLAN AND

SECTION

PMGSGYNRC

1030239/10/26

S-101

MC-1, MC-2 METAL STUD,

SEE PLAN AND NOTES.

(NOT AT PANEL SPANS 90° TO AS

DETAILED HERE, SEE PLAN)

DIAGONAL BRACE,

(BR-1). SEE PLAN

AND NOTES

CONT GAGE ANGLE w/

FASTENERS TO EACH "MC" METAL

STUD OR ROOF PANEL

OVERLAPPING RIB (AT PANEL

SPAN OPPOSITE DIRECTION),

AND TO PARAPET PANELS

INTERLOCKING ROOF / CEILING

PANELS w/ FASTENERS TO EACH

"MC" MEMBER AND STEEL

SUPPORT BEAMS

PURLIN BEAM

PARAPET PANEL, TOP, BOTTOM

AND CORNER TRIM, HORIZ

BRACING AND INSIDE CORNER

ANGLES. SEE PLAN NOTES FOR

BASE BID REQUIREMENTS

ENLARGED PARAPET SECTION

SCALE: 1 1/2"=1'-0"

S102

1/ 2"

BASE BID:

COLLECTOR BOX. FABRICATE

FROM 3/16" PLATE STEEL.

BRAKE BEND WHERE

POSSIBLE, WELD ALL SEAMS.

BOX TO EXTEND 4" MIN FROM

FACE OF COLUMN, ALL SIDES

COLLECTOR BOX MUST BE A

SPLIT DESIGN AND FIELD SEAMED.

PROVIDE 1/8" WELDS TO COLUMN

AND APPLY SEALANT PRIOR TO

LINER. SEE NOTES FOR GUTTER

LINER

3" LONG INTEGRAL FLANGE,

EACH SIDE OF COLLECTOR

BOX.

NOTE: FABRICATE EXTENSION

FLANGE TO ALLOW GUTTER TO

FIT TIGHT WITHIN FLANGE

BRAKE BENT 16ga GALV GUTTER w/ 1"x11

2"x0.120

RECTANGULAR TUBE EACH

SIDE.

16ga BRAKE BENT GUTTER

TO FIT WITHIN, AND LAP TO

COLUMN BOX FLANGES.

SEE NOTES FOR GUTTER

LINER

3"

1 1/2"

12"

3"

3" MIN

3"

(INSIDE)

FASTEN GUTTER TO

FLANGE WITH 3/16"

STAINLESS STEEL DOME

HEAD BLIND RIVETS AT 1"o.c.

CUT-OUT FOR DOWNSPOUT

NIPPLE TO FIT INSIDE 6" SCHED

80 PVC DOWNSPOUT. FIELD

LOCATE. EXTEND GUTTER

LINER INTO DOWNSPOUT

NIPPLE. SEAL ALL SEAMS PER

MFR

TOP OF COLUMN NOT SHOWN

FOR DETAIL CLARITY. SEE

FRAMING PLAN FOR BEAM

LEVELING NOTES

PURLIN BEAMS

BOLT CONDITION TO BE

FIELD EVALUATED.

ANTICIPATE REPLACEMENT

OF ALL BOLTS IN-KIND

(GRADE A325 MIN)

REPLACE EXISTING CEILING /

ROOF PANELS w/ 12" wide x 3" DEEP, 22ga INTERLOCKING

PANELS. SEE PANEL NOTES

FABRICATED CLOSED AND

SEALED BOX END GUTTER

CLOSURES, TYP

(NOT SHOWN)

FASTEN PANELS TO PURLINS

w/ CLIPS, OR FASTEN THRU

INTERLOCKING PANELS

DIRECTLY TO PURLINS AS

RECOMMENDED BY PANEL

MFR

FIELD TRIM / PROFILE AS REQ'D

S.S. CAP AND

GASKETED SELF

DRILLING

FASTENERS THRU

PANEL ENDS TO

RECTANGULAR TUBE

1 1/2"

LINER,

SEE NOTES

FASTEN 1"x11 2"x0.120

RECTANGULAR TUBES TO

BRAKE BENT GUTTER w/ 3/16"

STAINLESS STEEL DOME

HEAD BLIND RIVETS AT 4"o.c.

CUT FLUSH AND SEAL EXIST

2" INTERNAL DOWNSPOUT w/

3/16" STEEL PLATE FIELD

WELDED AND FINISHED

SMOOTH. SIMILAR AT

COLUMN BASE, TYPICAL

CROSS BEAMS

TURN UP AND

SEAL PANEL ENDS

OPPOSITE OF

GUTTER

ISOMETRIC REFERENCE DETAIL

SCALE: 3/4"=1'-0"

S102

2" WIDE PANEL FASTENING

FLANGE, TYP

MC-1, MC-2 METAL STUD,

SEE PLAN AND NOTES.

(NOT AT PANEL SPANS 90° TO

AS DETAILED HERE, SEE PLAN)

ADJUSTABLE (OR FIXED) LENGTH

DIAGONAL BRACE, "BR-1" ON PLAN. (2)

BRACES REQ'D AT EACH LOCATION AS

SHOWN ON PLAN (3'-0" o.c. MAXIMUM)

FOR ALTERNATE BID.

EACH BRACE MUST BE SELECTED TO

CAPABLE OF 450 lbs OF TENSION AND

COMPRESSION LOADING, MINIMUM

CONT 3"x3"x16ga GALV G-90 ANGLE w/

FASTENERS TO EACH "MC" METAL STUD

OR ROOF PANEL OVERLAPPING RIB

(AT PANEL SPAN OPPOSITE DIRECTION),

AND TO PARAPET PANELS

INTERLOCKING ROOF / CEILING

PANELS w/ FASTENERS TO EACH "MC"

MEMBER AND STEEL SUPPORT BEAMS

PURLIN BEAM, SEE PLAN

AND FIELD CONDITIONS

FOR SPACING

1/ 2"

ENLARGED PARAPET SECTION

SCALE: 3"=1'-0"

S102

ALTERNATE BID:

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO ANGLE

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. VERT AT

PANEL OVERLAPS

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU

PANEL, BASE TRIM, INTO CLG

PANEL

BASE DRIP TRIM

FASTEN BRACE TO FLAT

OF GA METAL STUD

SECTION w/ 12-14 TEK

SCREWS

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO EACH

FLANGE OF HAT TRACK

1 1/2", 16ga GALV G90 CONTINUOUS HAT

TRACK. IF TRACK IS NOT CONTINUOUS TO

CORNERS, LAPS MUST BE 12" MIN AND

OCCUR AT DIAGONAL BRACES. FASTEN

LAP LEGS w/ (3) SCREWS MIN EACH

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL, TOP "U" TRIM, AND INTO FLANGE OF HAT TRACK

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU

PANEL AND INTO FLANGE OF

HAT TRACK

450 lbsMIN

FASTEN BRACE TO ALL HAT

TRACK w/ 12-14 TEK SCREWS

450 lbsMIN

1/2" 2 11/16"

1/

2"1 1/4"

1/2"

EQ

EQ

1/

2"

℄ HAT

TRACK

℄ HAT

TRACK

ANGLE

BASE

CONT 3"x3"x16ga GALV G-90 ANGLE w/

FASTENERS TO ROOF PANELS AS

SPECIFIED BY CLG PANEL MFR

INTERLOCKING ROOF / CEILING PANELS

PURLIN BEAM, SEE PLAN

AND FIELD CONDITIONS

FOR SPACING

1/ 2"

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO ANGLE

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. VERT AT

PANEL OVERLAPS

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL, BASE TRIM, INTO CLG PANEL END CLOSURE

BASE DRIP

TRIM

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL TO EACH

FLANGE OF HAT TRACK

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU

PANEL AND INTO FLANGE OF

HAT TRACK

450 lbsMIN

CLG PANEL END CLOSURE,

COORD w/ CLG MFR / SUPPLIER

FOR TRIM REQUIREMENTS

12-24 TEKS/5 OR

1/4" THRU BOLT AT

BRACES TO BEAM

450 lbs

MIN

EXST BEAM

1/4-14x7/8" SELF DRILLING SCREWS AT 12"o.c. THRU PANEL, TOP "U" TRIM, AND INTO FLANGE OF HAT TRACK

FASTEN BRACE TO TRACK

w/ 12-14 TEK SCREWS

1 1/2", 16ga GALV G90 CONTINUOUS

HAT TRACK. IF TRACK IS NOT CONTINUOUS

TO CORNERS, LAPS MUST BE 12" MIN AND

OCCUR AT DIAGONAL BRACES. FASTEN LAP

LEGS w/ (3) SCREWS MIN EACH

FASTEN BRACE TO TRACK

w/ 12-14 TEK SCREWS

ENLARGED PARAPET SECTION

SCALE: 1 1/2"=1'-0"

2A S102

ALTERNATE BID:

EQ

EQ

1/

2"

℄ HAT

TRACK

℄ HAT

TRACK

ANGLE

BASE

ADJUSTABLE (OR FIXED) LENGTH

DIAGONAL BRACE, "BR-1" ON PLAN. (2)

BRACES REQ'D AT EACH LOCATION AS

SHOWN ON PLAN (3'-0" o.c. MAXIMUM)

FOR ALTERNATE BID.

EACH BRACE MUST BE SELECTED TO

CAPABLE OF 450 lbs OF TENSION AND

COMPRESSION LOADING, MINIMUM

IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE

ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL

ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND

SURVEYOR TO ALTER AN ITEM IN ANY WAY. IF AN ITEM BEARING THE

STAMP OF A LICENSED PROFESSIONAL IS ALTERED, THE ALTERING

ENGINEER, ARCHITECT, LANDSCAPE ARCHITECT OR LAND

SURVEYOR SHALL STAMP THE DOCUMENT AND INCLUDE THE

NOTATION "ALTERED BY" FOLLOWED BY THEIR SIGNATURE, THE

DATE OF SUCH ALTERATION, AND A SPECIFIC DESCRIPTION

OF THE ALTERATION.

Fi le

V:

\P

RO

JE

CT

S\

AN

Y\ K7

\1

3.

0\

_D

ES

IG

N \D

RA

W

IN

G

S\

ST

RU

C\

M O

DE

L-

.D

W G

Sa ve d:

/9 /2

4:

:0

PM

P lo tt ed

9/ 9/

:1

6:

P M

C ur re nt

U se r:

G ar la nd

Pe te

L as tS av ed By

Checked By:

Drawing No.:

Issue Date:

Designed By: Drawn By:

Project No.: Scale:

Sheet of 3

AS SHOWN

No. By DateSubmittal / Revision Apv

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

EASTON AREA JOINT

SEWER AUTHORITY

SLUDGE CANOPY

REPAIRS

NOTES,

SECTIONS AND

DETAILS

PMGSGYNRC

1030239/10/26

S-102

SD-100
SD-100
S-101
S-101
S-102
S-102