This document package includes construction drawings and specifications for a cold storage room retrofit project at the Wellington Barn facility for the USDA Agricultural Research Service. Key project elements include demolishing an existing wall to install a new door; constructing new walls to enclose an electrical room; installing a pre-manufactured cold room within the existing barn structure; providing a concrete pad for new mechanical equipment; and optional generator installation. The project solicitation number is 12305B23R0013. The construction drawings provide floor plans, sections, and details of proposed demolition and new construction work. Mechanical drawings show specifications for refrigeration system components including evaporators, condensing units, humidifiers, and associated piping. Electrical drawings include plans for power distribution and lighting, along with panel schedules and notes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUFFALO
ROCHESTER WORCESTER
SYRACUSE
NEW YORK
SPRINGFIELD
HARTFORD
SHEET SHEET NAME
010-GENREAL
G-001 COVER SHEET
080-ARCHITECTURAL
A-001 ABBREVIATIONS AND GENERAL NOTES
AD101 DEMOLITION PLAN
A-101 FLOOR PLAN
A-301 BUILDING SECTION
A-401 DETAILS AND SCHEDULES
150-MECHANICAL
M-001 ABBREVIATIONS AND LEGEND
M-101 MECHANICAL PLAN
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
160-ELECTRICAL
E-001 ELECTRICAL LEGEND
E-100 ELECTRICAL PLAN
E-101 LIGHTING PLAN
E-500 SINGLE LINE DIAGRAM
PROJECT LOCATION
PROJECT LOCATION GENEVA, NEW YORK
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
LOCATION MAPVICINITY MAP
12305B21D0013/12305B22F0108
2939 PRE-EMPTION ROAD
GENEVA, NEW YORK 14456
WELLINGTON BARN COLD STORAGE RETROFIT
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
NO. DATE BY DESCRIPTION
REVISIONS
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
XXX
01/10/2023
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
U
S
D
A
DRAWING INDEX
WELLINGTON BARN COLD STORAGE
OF
BID OPTIONS
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
TMC COVER SHEET
G-001
NORTH
NEW YORK
BUFFALO
SYRACUSE
ROCHESTER
NEW YORK
WORCHESTER
SPRINGFIELD
HARTFORD
BASE BID:
TO INCLUDE: LIMITED DEMOLITION AND REMOVAL OF A WALL FOR INSTALLATION OF A NEW DOOR. CONSTRUCTION OF NEW WALLS
TO ENCLOSE THE ELECTRICAL ROOM. CONSTRUCT A NEW CONCRETE PAD FOR NEW EQUIPMENT. PROVIDE A PRE-MANUFACTURED
COLD ROOM WITHIN THE EXISTING BARN.
BID OPTION A:
TO INCLUDE: NEW ELECTRICAL GENERATOR.
Attachment 2. Drawings: Jan 2023: Pages 15.
tcrenshaw
TMC 20230110
ANGLE
@ AT
AB ANCHOR BOLT
AC ACOUSTIC
ACC ACCESS
ACT ACOUSTIC CEILING TILE
ACP ACOUSTIC CEILING PANEL
AD AREA DRAIN
ADD ADDITIONAL
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASPH ASPHALT
BB BOND BEAM
BD BOARD
BF BOTH FACES
BFC BELOW FINISH CEILING
BG BUMPER GUARD
BIT BITUMINOUS
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BM BEAM/BENCH MARK
BLK BLOCK
BOT BOTTOM
BRG BEARING
BRKR BREAKER
BRK BRICK
BRKT BRACKET
BS BACK SPLASH
BSMT BASEMENT
BTWN BETWEEN
CHANNEL
CAB CABINET
CER CERAMIC
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CG CORNER GUARD
CH COAT HOOK
CIP CAST IN PLACE
CJ CONTROL JOINT/
CONSTRUCTION JOINT
CLG CEILING
CLO CLOSET/CLOSURE
CLR CLEAR
COL COLUMN
COMB COMBINATION
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION/CONNECT
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPT CARPET
CR COAT RACK/CURTAIN ROD
CSG CASING
CT CERAMIC TILE
CTR CENTER/COUNTER
CTSK COUNTERSUNK
CUH CABINET UNIT HEATER
CW COLD WATER
D DEPTH
DBL DOUBLE
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIR DIRECTION
DIV DIVISION
FA FIELD ADJUSTABLE
FV FIELD VERIFY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FLEX FLEXIBLE
FLR FLOOR
FLRG FLOORING
FP FIREPROOF/FIRE PROTECTION
FR FIRE RETARDANT
FS FULL SIZE/FULL SCALE
FT FEET
FTG FOOTING
FURG FURRING
GA GAUGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GEN GENERAL
GFCI GOVERNMENT FURNISHED,
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED,
GOVERNMENT INSTALLED
GFRC GLASS FIBER REINFORCED CONCRETE
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GMU GLAZED MASONRY UNIT
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HEIGHT
HDBD HARDBOARD
HDCP HANDICAPPED
HDWD HARDWOOD
HDWE HARDWARE
HK HOOK
HM HOLLOW METAL
HP HIGH POINT
HR HANDRAIL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NONSHRINK
NTS NOT TO SCALE
NWC NORMAL WEIGHT CONCRETE
SOG SLAB ON GRADE
SPEC SPECIFICATION
SPR SPRINKLER
SQ SQUARE
SR SHOWER ROD
SS STAINLESS STEEL
ST STREET
STD STANDARD
STL STEEL
STO STORAGE
STRU STRUCTURAL/STRUCTURE
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
TB TACKBOARD/TOWEL BAR
TBR TO BE REMOVED
TCP THIN COAT PLASTER
TD TOWEL DISPENSER
TDW TOWEL DISPENSER AND WASTE
TEMP TEMPERATURE/TEMPERED
TER TERRAZZO
TEX TEXTURE
TFC TROWELED FLOOR COVERING
T & G TONGUE AND GROOVE
THK THICK
TOB TOP OF BEAM
TOC TOP OF CURB/TOP OF CONCRETE
TOD TOP OF DECK/TOP OF DUCT ELEVATION
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOP TOP OF PIPE ELEVATION
TOS TOP OF SLAB/TOP OF STEEL
TOW TOP OF WALL
TPG TOPPING
TPH TOILET PAPER HOLDER
TRAN TRANSOM
TRANS TRANSVERSE
TS TUBE STEEL
TWS THREADED WELDED STUD
TYP TYPICAL
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
UR URINAL
ABBREVIATIONS ABOVE ARE FOR
ARCHITECTURAL SHEETS ONLY.
DM DEMOUNTABLE PARTITION
DN DOWN
DO DITTO
DR DOOR
DRWR DRAWER
DS DOWNSPOUT
DWG DRAWING
DWL DOWEL
DWS DEFORMED WELDED STUD
EA EACH
EC ELECTRICAL CONTRACTOR
EF EACH FACE
EH ELECTRICAL HEATER/EXHAUST HOOD
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR/ELEVATION
EMBED EMBEDDED
EMER EMERGENCY
ENT ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ES EMERGENCY SHOWER
ESR ELASTOMERIC SHEET ROOFING
ETR EXISTING TO REMAIN
EVC ELASTIC VINYL COATING
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVATE
EXP EXPANSION
EXPD EXPOSED
EXPF EXPLOSION PROOF
EXT EXTERIOR
HT HEIGHT
HVAC HEATING VENTILATION &
AIR CONDITIONING
HWS HEAD WELDED STUDS
ID INSIDE DIAMETER
IMP INSULATED METAL PANEL
IN INCHES
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
IPW INSULATED PLENUM WALL
IRF INSULATED ROOF FILL
JAN JANITOR
JS JANITOR SINK
JST JOIST
JT JOINT
KD KNOCKED DOWN
KO KNOCK-OUT / KNEE OPENING
L LENGTH
LAB LABORATORY
LAM LAMINATED
LB POUND
LBS POUNDS
LD LINEAR DIFFUSER
LDG LANDING
LF LINEAR FOOT
LG LONG
LGT LIGHT
LKR LOCKER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LP LOW POINT
LSH LONG SLOTTED HOLE
LTG LIGHTING
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
MACH MACHINE
MAN MANUAL
MAR MARBLE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBW MASONRY BEARING WALL
MC MECHANICAL CONTRACTOR
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MK MARK
ML METAL LATH
MLDG MOLDING
MO MASONRY OPENING
MP METAL PARTITION
MS MACHINE SCREW
MTD MOUNTED
MTG MOUNTING
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
/OVERFLOW DRAIN
OFF OFFICE
OPNG OPENING
OPP OPPOSITE
OZ OUNCE
PART PARTITION
PC PIECE
PCC PRECAST CONCRETE
PCPL PORTLAND CEMENT PLASTER
PDWR PAPER TOWEL DISPENSER &
WASTE RECEPTACLE
PH PHILLIPS HEAD/PHASE
PL PLASTIC LAMINATE
/PLATE/PROPERTY LINE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PM PROTECTED METAL
PNL PANEL
PNLG PANELING
POL POLISHED
PR PAIR
PRE FAB PREFABRICATED
PRE FIN PRE-FINISHED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT/PAINT
PTM PAINT TO MATCH
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
QTY QUANTITY
RAD RADIUS
RAH ROOFTOP AIR
HANDLING UNIT
RB RUBBER BASE
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REINF REINFORCING
REL RELOCATE
REM REMAINDER
REQD REQUIRED
RES RESILIENT
RET RETURN
RI ROUGH IN
RM ROOM
RO ROUGH OPENING
RT RUBBER TILE
RUB RUBBER
SAT STANDARD AGGREGATE
TOPPING
SB SOIL BEARING
SC SEAMLESS COATING
SCF SPECIAL CONCRETE FINISH
SCHD SCHEDULE
SD SOAP DISPENSER
SE SHELF EDGE
SECT SECTION
SF SAND FLOAT
SG SUPPLY AIR GRILLE
SGL SINGLE
SH SHELF
SHD SHOWER DOOR
SHT SHEET
SIM SIMILAR
SJ STEEL JOIST
SLV SHORT LEG VERTICAL
SM SMOOTH
SND SANITARY NAPKIN DISPENSER
SNV SANITARY NAPKIN VENDOR
V VINYL
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VOL VOLUME
VWC VINYL WALL COVERING
W WIDE FLANGE STEEL BEAM
W/ WITH
WAF WELDED ANGLE FRAME
WC WATER CLOSET
WD WOOD
WDW WINDOW
WF WIDE FLANGE
WG WIRE GLASS
W/O WITHOUT
WP WEATHERPROOF
WPFG WATERPROOFING
WR WASTE RECEPTACLE
WSCT WAINSCOT
WSTP WEATHERSTRIP
WTR WATER
WWF WELDED WIRE FABRIC
ABBREVIATIONS LIST
GENERAL NOTES - ARCHITECTURAL:
1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF THE WORK. THE DRAWINGS ARE NOT INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE AND COMPLETION OF THE REQUIREMENTS OF
THE CONTRACT DOCUMENTS.
2. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN ONE PORTION OF THE CONTRACT DOCUMENTS SHALL NOT
BE CONSTRUED TO EXCLUDE OTHER ITEMS NECESSARY OR IMPLIED THEREFROM.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL PARTS OF THE WORK SO THAT NO WORK
SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION.
4. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, ALL REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE
CONTRACTING OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.
5. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.
6. ALL WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF THE CONSTRUCTION SCOPE OF WORK AGREEMENT.
7. THE CONTRACTOR SHALL PAY FOR AND COORDINATE THE REMOVAL AND LEGAL DISPOSAL OF MATERIALS AND
RUBBISH.
8. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SHALL VERIFY ALL NEW AND EXISTING
CONDITIONS, SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IN
WRITING OF ANY DIFFERING CONDITIONS BEFORE THE COMMENCEMENT OF WORK.
9. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN, LARGE SCALE DETAILS GOVERN OVER SMALL SCALE DETAILS.
THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IN WRITING OF ANY DIFFERING CONDITIONS
BEFORE THE COMMENCEMENT OF WORK.
10. UNLESS NOTED OTHERWISE, ALL GYPSUM BOARD SURFACES ARE TO RECEIVE ONE PRIMER COAT AND TWO COATS
OF PAINT.
11. DIMENSIONS NOTED AS 'HOLD' SHALL NOT VARY BY MORE THAN 1/8" FROM SIDE TO SIDE OR FROM FRONT TO BACK, FINISHED SURFACE TO FINISHED SURFACE.
12. NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, AND ALTERATION OPERATIONS SHALL BE APPLIED.
13. DIMENSIONS SHOWN ARE TO THE FACE OF THE STUD OR CMU (U.N.O.).
14. PROVIDE EXPANSION AND CONTROL JOINTS IN ALL WORK AS PER PRODUCT MANUFACTURER'S STANDARDS.
15. THE CONTRACTOR SHALL PERFORM ALL WORK IN ACCORDANCE WITH ALL APPLICABLE CODES, ORDINANCES AND
REGULATORY AGENCIES AND SHALL OBTAIN NECESSARY BUILDING AND FIRE PERMITS FROM ALL AUTHORITIES
HAVING JURISDICTION.
16. ALL INTERIOR FINISH MATERIALS SHALL COMPLY WITH THE REQUIREMENTS OF ALL APPLICABLE CODES, ORDINANCES AND REGULATORY AGENCIES.
17. ALL DISSIMILAR METALS SHALL BE ISOLATED FROM EACH OTHER TO AVOID GALVANIC CORROSION.
18. NOTES APPEAR ON VARIOUS SHEETS FOR DIFFERENT SYSTEMS AND MATERIALS. SHEETS ARE TO BE REVIEWED
AND NOTES ON INDIVIDUAL SHEETS SHALL BE APPLIED TO RELATED DRAWINGS AND DETAILS.
19. A FINISH INDICATION ON A WALL SHALL MEAN THE ENTIRE LENGTH AND HEIGHT OF THE WALL IS TO BE FINISHED OR
FIRE-RATED AS INDICATED.
20. WHEN NON-DIMENSIONED PARTITIONS APPEAR IN CONJUNCTION WITH DOOR OPENINGS, THE DOOR WIDTH AND THE
DOOR FRAME DETAILS DETERMINE THE LOCATION OF ADJACENT WALLS AND FRAMES.
21. WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, CONSULT THE CONTRACTING
OFFICER BEFORE PROCEEDING WITH THE WORK.
22. THE CONTRACTOR SHALL COORDINATE ALL MECHANICAL AND ELECTRICAL FLOOR AND WALL SLEEVES INCLUDING CONDUITS WITH ALL MECHANICAL, ELECTRICAL PLUMBING AND ARCHITECTURAL DRAWINGS.
23. PROVIDE ACCESS PANELS AS REQUIRED BY APPLICABLE CODES AND AS REQUIRED FOR MECHANICAL EQUIPMENT AND PLUMBING WORK. ALL ACCESS PANELS SHALL BE CONCEALED AND LOCATIONS SHALL BE
REVIEWED WITH THE CONTRACTING OFFICER PRIOR TO PROCEEDING.
24. ALL PIPE DUCTS AND BUS DUCTS THAT PENETRATE FLOOR SLABS OR WALL PARTITIONS SHALL BE INSTALLED IN A MANNER THAT WILL PRESERVE THE MOISTURE RESISTIVENESS, FIRE RATING, AND STRUCTURAL
INTEGRITY OF THE BUILDING.
25. DO NOT CUT INTO, REMOVE OR ALTER ANY STRUCTURAL MEMBER OR PORTION OF THE FLOOR SYSTEM
UNLESS IT IS SPECIFICALLY APPROVED BY CONTRACTING OFFICER.
26. INTERIOR PARTITION MOVEMENT CONTROL:
A. VERTICAL CONTROL JOINTS FOR ANY WALL LENGTH ARE TO OCCUR AT NOT MORE THAN 30'-0" O.C. IN
THE HORIZONTAL DIRECTION, UNLESS NOTED OTHERWISE.
B. PROVISIONS SHALL BE MADE IN THE DESIGN, FABRICATION, AND INSTALLATION OF INTERIOR PARTITIONS
FOR TYPICAL FLOOR DEFLECTIONS OF THE STRUCTURE UNDER SUPERIMPOSED LOADS AS FOLLOWS:
a. TYPICAL ROOF/FLOOR MEMBERS: SPAN/360 BUT NOT LESS THAN 1/2”.
27. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR PERSONS AND PROPERTY AT ALL TIMES, AND EXECUTE THE WORK IN SUCH A MANNER TO AVOID ANY HAZARD TO PERSONS
AND PROPERTY AS NECESSARY.
28. THE CONTRACTOR SHALL COORDINATE THE SEQUENCING OF THE WORK TO BE PERFORMED IN OR ABOUT EXISTING FACILITIES, IF APPLICABLE, WITH THE CONTRACTING OFFICER PRIOR TO THE START OF SUCH
WORK.
EARTHWORK
GRAVEL
PLASTER, SAND,
GROUT
CONCRETE
CONCRETE
MASONRY
CLAY
MASONRY
PRECAST
CONCRETE
METAL
PLYWOOD
FINISH
LUMBER
WOOD STUDS,
BLOCKING
STEEL STUDS
GYPSUM
WALLBOARD
ACOUSTICAL
TILE
BATT
INSULATION
RIGID
INSULATION
MATERIALS - SECTION HATCH SYMBOLS
APPLICABLE CODES AND STANDARDS:
ABBREVIATIONS TITLE EDITION
IBC INTERNATIONAL BUILDING CODE 2021
NORTH
1i
ROOM NAME
A
View Name 1/8" = 1'-0"
A-100
NORTH ARROW
SECTION
MARKER
ELEVATION
ROOM TAG
KEY TAG
WALL TYPE
WINDOW TYPE
VIEW NAME, NUMBER
AND SCALE
STAIR TAG
DOOR NUMBER
EXTERIOR
ELEVATION
INTERIOR
ELEVATION
A101
GRID LOCATION
ARCHITECTURAL SYMBOLS:
A101
LOUVER
A
A101
A
A A-101
DETAIL MARK
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TMC
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
A-001
ABBREVIATIONS AND GENERAL NOTES
CUT OPENING IN EXISTING
METAL WALL PANEL FOR
NEW DOOR & FRAME.
MODIFY EXISTING
FRAMING AND PROVIDE
NEW FRAMING AS
REQUIRED.
EXISTING
FORKLIFT
GFGI
TRACTOR STORAGE
STORAGE
EXISTING
COOLER
SEEDS
PROCESSING
CONDITIONED
SPACE
BOILER ROOM
RESTROOM
RESTROOM
CABBAGE
STORAGE
2'
9" 3'
4"
SAWCUT AND REMOVE
PORTITION OF SLAB FOR
NEW PIPE BOLLARDS
+/- 47' - 0"
- 5
8'
GENERAL NOTES - DEMOLITION:
1. FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PERFORMING
WORK OR FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES,
BRING ANY DISCREPANCIES TO THE ATTENTION OF THE CONTRACTING OFFICER FOR
FINAL DETERMINATION.
2. CONTRACTOR MUST PROVIDE TEMPORARY STRUCTURAL SUPPORT FOR EXISTING
CONSTRUCTION DURING THE PROJECT (AS REQUIRED).
3. CONTRACTOR TO ENSURE THE MEANS OF EGRESS REMAIN CLEAR OF DEBRIS
THROUGHOUT THE ENTIRETY OF THE PROJECT SCOPE.
4. THE DEMOLITION PLANS APPROXIMATE THE EXTENT OF THE DEMOLITION. CONTRACTOR
IS REQUIRED TO PROVIDE DEMOLITION AND REMOVE ALL MATERIALS AS REQUIRED TO
PROVIDE NEW WORK. ANY DISCREPANCY IS TO BE VERIFIED WITH THE ACTIVITY PRIOR
TO COMMENCEMENT IN WRITING.
5. THE FACILITY WILL REMAIN OPERATIONAL DURING THE WORK HOURS. THE
CONTRACTOR SHALL COORDINATE WORK ACTIVITIES AND UTILITY OUTAGES WITH THE
GOVERNMENT. THE GOVERNMENT WILL MOVE AND STORE ALL STORAGE RACKS AND
PALLETS PRIOR TO CONSTRUCTION. THE GOVERNMENT WILL MOVE ALL OF THE RACKS
AND PALLLETS BACK IN THE SPACE AFTER CONSTRUCTION IS COMPLETE.
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TMC
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
AD101
DEMOLITION PLAN
1/8" = 1'-0"AD101
FLOOR PLAN - DEMOLITION1
PLAN NORTH
SCALE: = 1'-0"
0 8 168
1/8"
KEYED NOTES - DEMOLITION
5 DEMO AND DISPOSE OF WALL, AS REQUIRED FOR INSTALLATION OF THE NEW DOOR AND
FRAME.
EXISTING BUILDING
SHELVING RACKS TO BE REMOVED AND STORED BY GOVERNMENT, TYPICAL IN ROOM 101.
STORAGE PALLETS TO BE REMOVED AND STORED BY GOVERNMENT, TYPICAL IN ROOM 101.
4 PROTECT EXISTING ELECTRICAL PANELS , SEE ELECTRICAL
A L
IG
N
GENERAL NOTES - FLOOR PLAN:
1. REFER TO SHEET A-001 FOR ARCHITECTURAL ABBREVIATIONS AND SYMBOLS.
+/- 47' - 0"
- 5
8'
7' - 7"
C U
-1 G
E N
E R
A T
O R
FORKLIFT
GFGI
A-301
6' - 8"
N E
W E
X
IS
T
IN
G
6"
46' - 0"
6"
NEW EXISTING
BOILER ROOM
RESTROOM
RESTROOM
CONDITIONED
SPACE
SEEDS
PROCESSING
STORAGE
TRACTOR
STORAGE
102 EXISTING
COOLER
COLD ROOM
ELEC
CABBAGE
STORAGE
A
B
D
1 2 3
A-101
3'x7' INSULATED
PERSONAL DOOR
A-401
DOORS ARE
PART OF
THE
PREFAB
COOLER
UNIT
STRUCTURAL SUPPORT BY
COLD ROOM MANUFACTURER.
INTERMEDIATE COLUMNS ARE
NOT ALLOWED WITHOUT THE
WRITTEN APPROVAL OF THE
CONTRACTING OFFICER.
GENERATOR
BID OPTION A
SEE ELEC.
3'
11' - 3"
8" 6'
8"
8"
10"
10"
C
8" 7' - 8" 37' - 0" 8"
44' - 8"
8'
9"
20' - 7"
6'
5"
C U
-2
A-401
A
B
1 2
7' - 7"
NEW 2x6 WOOD STUD WALLS 7/A-401
A
A
3" 8"
ELEC
COLD ROOM
EXISTING
WALLS
4'
5"1'
6" 5'
0"
5' - 5"
CONCRETE PAD
AT NEW DOOR
7' - 3"
4" 8"
6'
8"
8' - 2"
6" 8" 7' - 8"
6'
5"
STRUCTURAL FRAME MUST
BE AT A MINIMUM HSS6x6x1/4
COLUMNS, W12X53 BEAMS,
LATERAL BRACED AS
REQUIRED FOR STABILITY
AND ALLOWABLE
DEFLECTION = L/240 MAX AND
PER VENDOR REQIREMENTS
(FINAL SIZES AS
DETERMINEDBY COLD ROOM
MANUFACTURER).
SCALE: = 1'-0"
0 8 168
1/8"
1/8" = 1'-0"A-101
RETROFIT FLOOR PLAN1
PLAN NORTH
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TMC
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
A-101
FLOOR PLAN
KEYED NOTES - FLOOR PLAN
EXISTING BUILDING
PROVIDE A PRE-MANUFACTURED, COLD STORAGE, ROOM - 46'-0"W x 50'-0"L x 12'-0"H
SHELVING RACK REUSED (GFGI)
STORAGE PALLET REUSED (GFGI)
NOT USED
10'x10' FAST-CLOSE OVERHEAD HIGH SPEED INSULATED DOOR BY COLD ROOM
MANUFACTURER
PIPE BOLLARD
CONCRETE PAD - COORDINATE SIZE WITH EQUIPMENT (MIN. SIZE SHOWN)8
BUILDING AREA RETROFIT
COLD ROOM +/- 2240 SF
TOTAL 2240 SF
NOTE:
THE COLD ROOM MANUFACTURER MUST PROVIDE A COMPLETE SYSTEM
OF INSULATED WALL AND CEILING PANELS, STRUCTURAL MEMBERS TO
SUPPORT THE COLD ROOM SYSTEM INCLUDING ANCHORING TO THE
EXISTING CONCRETE SLAB, INSULATED MAN-DOOR AND HARDWARE,
INSULATED OVERHEAD DOOR AND HARDWARE, REFRIGERATION SYSTEM,
LIGHTING SYSTEM, CONVINCE OUTLETS, LIGHT SWITCHES, AND
MISCELLANEOUS COMPONENTS FOR A COMPLETE AND OPERABLE SYSTEM.
EXISTING CONSTRUCTION, INCLUDING CEILINGS, SHALL BE REMOVED AND
REPLACED LIKE-IN-KIND AS REQUIRED TO PROVIDE THE COLD ROOM WITHIN
THE EXISTING BUILDING. SHOP DRAWINGS MUST BE PROVIDED AND
APPROVED PRIOR TO PURCHASE OF THE COLD ROOM.
1/4" = 1'-0"A-101
ELECTRICAL ROOM - ENLARGED FLOOR PLAN2
NOTE:
THE COLD ROOM AND RELATED PRE-FABRICATED COMPONENTS ARE PROPRIETARY
SYSTEMS AND SHALL BE A DELEGATED ENGINEERING DESIGN. THE MANUFACTURER SHALL
SUBMIT SHOP DRAWINGS THAT ARE SEALED BY A LICENSED ENGINEER, EMPLOYED BY THE
CONTRACTOR/MANUFACTURER, INDICATING THAT THE SUPPLIED COMPONENTS ARE IN
COMPLIANCE WITH THE CONTRACT DOCUMENTS AND THE SPECIFIED CRITERIA. PROVIDE A
COMPLETE DESIGN ANALYSIS SHOWING ALL CALCULATIONS FOR THE SUPPLEMENTAL
FRAMING AND MODIFIED FOUNDATION REQUIREMENTS, LAYOUT OF ANCHOR BOLTS AND
OTHER EMBEDDED ITEMS. DELEGATED DESIGNS MUST COMPLY WITH THE REQUIREMENTS
OF AIA A201-2017 SECTION 3.12.10 AND THE INTERNATIONAL BUILDING CODE. ALL
SUBMITTALS MUST BE APPROVED BY THE CONTRACTING OFFICER PRIOR TO ANY
FABRICATION OR RELATED FIELD CONSTRUCTION.
DETAILS SHOWN ON THESE CONSTRUCTION DRAWINGS ARE THE DESIGNER OF RECORD'S
ESTIMATE OF REQUIREMENTS BASED ON ANTICIPATED SYSTEMS AND
CONFIGURATION. ITEMS SPECIFIED IN THESE CONTRACT DOCUMENTS, SUCH AS THICKNESS
AND GAUGES, SHALL BE INCORPORATED AS THE MINIMUM ALLOWED.
FOUNDATIONS SHALL BE ASSUMED TO HAVE A BEARING CAPACITY OF 1500 PSF UNLESS THE
CONTRACTOR PROVIDES ADDITIONAL TESTING TO VERIFY OTHERWISE.
GENERAL NOTES - SECTIONS:
1. FIELD VERIFY ALL DIMENSIONS AND BRING ANY DISCREPANCIES TO THE ATTENTION OF
THE ARCHITECT/ENGINEER FOR FINAL DETERMINATION.
2. REFER TO SHEET A-001 FOR ARCHITECTURAL ABBREVIATIONS AND SYMBOLS.
LEVEL 01
0' - 0"
CEILING, EXIST
13' - 5"
PREMANUFACTURED
COOD ROOM PANEL
SYSTEM
HVAC - EVAP
SEE MECHANICAL
COLD ROOM
A B D
EXISTING INSULATED
CEILING OF ROOM
SHALL REMAIN
LEVEL 04
12' - 0"
C
COLD ROOM SYSTEM :
ROOF IS 5 1/2" WOOD FRAME HIGH DENSITY URETHANE (R-30)
WALLS ARE 4" WOOD FRAME HIGH DENSITY URETHANE (R-22)
STRUCTURAL FRAME MUST BE
AT A MINIMUM HSS6x6x1/4
COLUMNS, W12X53 BEAMS,
LATERAL BRACED AS
REQUIRED FOR STABILITY AND
ALLOWABLE DEFLECTION =
L/240 MAX AND PER VENDOR
REQIREMENTS (FINAL SIZES
AS DETERMINED BY COLD
ROOM MANUFACTURER).
C L R
SCALE: = 1'-0"
0 4 84
1/4"
KEYED NOTES-BUILDING SECTION
EXISTING METAL ROOF SYSTEM
EXISTING METAL WALL PANELS AND WOOD FRAMED WALLS
NEW COLD ROOM ENCLOSURE, ENCLOSURE - 46'-0"W x 50'-0"L x 12'-0"H
SHELVING RACKS (GFGI)
STORAGE PALLETS (GFGI)
EXISTING BUILDING
EXISTING CONCRETE SLAB
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TMC
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
A-301
BUILDING SECTION
1/4" = 1'-0"A-301
BUILDING SECTION1
S E
E S
C H
E D
2"
2"
SCHED.
SEE 2"
F1
SCHED.
SEE
A
HOLLOW
METAL
S E
E S
C H
E D
ABBREVIATION LEGEND:
PT - PAINT (P-1)
HM - HOLLOW METAL
NOTE:
SEE SPECIFICATIONS FOR HARDWARE AND KEYING WILL FOLLOW PROTOCOL OF EXISTING FUNCTIONALITY.
PAINT LEGEND
FINISH NO. FINISH DESCRIPTION MANUFACTURER MODEL NUMBER STYLE COLOR SIZE REMARKS
P-1 PAINT SHERWIN WILLIAMS LIGHT FRENCH GRAYSW 0055 - EPOXY PAINT
DOOR AS SCHEDULED
AND SPECIFIED
SEALANT CONT. BOTH SIDES
HOLLOW METAL FRAME
AS SCHEDULED
METAL FLASHING
W/ HEMMED EDGES
EXISTING METAL WALL PANEL
7"
EXISTING WOOD
WALL FRAMING
FRAME
ANCHOR
2"
2X6 STUDS
EXISTING INSULATION
2X4 STUDS
JAMB
OUTSIDEINSIDE
HEAD
DOOR AS SCHEDULED
AND SPECIFIED
SEALANT CONT. BOTH
SIDES
HOLLOW METAL FRAME
AS SCHEDULED
METAL FLASHING
W/ HEMMED EDGES
EXISTING METAL WALL PANEL
7"
EXISTING WOOD
STRUCTURE
BEYOND
FRAME ANCHOR
2" 2x8 WOOD
HEADER, SPAN
ACROSS
OPENING TO
EXISTING
STUDS
1/2" PLYWOOD
EXISTING INSULATION
OUTSIDEINSIDE
2X6 WOOD STUD @ 16" O.C.
6" R-19 BATT INSUL.
5/8" TYPE X MOISTURE
RESISTANT
GYP. BD.
SECTION
6" R-19 BATT INSUL.
5/8" TYPE X MOISTURE
RESISTANT GYP. BD.
2X6 WOOD STUD
@ 16" O.C.
PLAN
EXISTING CONC. SLAB.
5/8" TYPE X MOISTURE
RESISTANT
GYP. BD.
5/8" TYPE X MOISTURE RESISTANT GYP. BD.
(2) TOP PLATE
EXISTING CEILING
±1 3'
-5
GENERAL NOTES - PARTITIONS:
1. PROVIDE 5/8" TYPE "X" MOISTURE-RESISTANT GYPSUM BOARD (UNLESS NOTED
OTHERWISE).
2' - 4" x 2' - 4"
2'
0" 2"
4'
0"
MOUND
CONCRETE
TOP OF SLAB AND CONCRETE
FINISH SHALL MATCH EXISTING
SLAB.
#6 x2'-0" REBAR THROUGH
BOLLARD, TYP. OF (2) ORIENT 90
DEGREES TO EACH OTHER WELD
REBAR TO BOLLARD
NEW 8" SCHEDULE 40 STEEL
BOLLARD CONCRETE
FILLED. PAINT SAFETY
YELLOW
WRAP WITH 4" WHITE
ENGINEERING GRADE TAPE
SAW CUT EXISTING SLAB
ALONG STRAIGHT LINES
AND REMOVE
EXISTING CONC. SLAB
EXISTING CONC. SLAB
1/2" EXP. JT. MATERIAL
THRESHOLD SET IN
FULL BED OF SEALANT
CONTINUOUS ALUMINUM
RAIN DRIP AT EXTERIOR
DOOR THRESHOLD -
REFER TO DOOR
HARDWARE SPECS
NEOPRENE DOOR SHOE AT
THRESHOLD - REFER TO
DOOR HARDWARE SPECS
1/2" PAVING JOINT FILLER
DOOR AS SCHEDULED
SLOPE
OUTSIDEINSIDE
SILL
EXISTING CONCTERE SLAB
2" 2"
2" 2"
9"
9"
1' - 0"
1'
0" HSS6x6x1/4"
3/4" A36 PL
5/16"
TYP.
5/8" ⌀ ANCHOR BOLT,
W/ 4" EPOXY EMBED., TYP.
STRUCTURAL
SUPPORT TO BE
DESIGNED AND
SIZED BY THE
COLD ROOM
MANUFACTURER
PRIME AND PAINT ALL
EXPOSED STRUCTURAL STEEL
NOTE: INFORMATION
SHOWN IS MINUMINUM
REQUIREMENT (FINAL SIZE
AS DETERMINED BY COLD
ROOM MANUFACTURER).
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TMC
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
A-401
DETAILS AND SCHEDULES
DOOR AND HARDWARE SCHEDULE
DOOR
NUMBER
DOOR FRAME
FIRE
RATING
STC
RATING HARDWARE COMMENTSTYPE
SIZE
MATERIAL FINISH
UNDER
CUT TYPE MATERIAL FINISH
DETAILS
WIDTH HEIGHT THICK HEAD JAMB SILL
105 A 3' - 0" 7' - 0" 0' - 1 3/4" HM PT F1 HM PT 8/A-401 6/A-401 1/A-401 HW-1 INSULATED, 1
SCALE: = 1'-0"
0 4 84
1/4"
1/4" = 1'-0"A-401
FRAME TYPE5
1/4" = 1'-0"A-401
DOOR TYPES4
DOOR AND HARDWARE SCHEDULE COMMENTS
NO COMMENTS
1. ALL EXTERIOR DOORS AND FRAMES ARE TO BE INSULATED.
ROOM FINISH SCHEDULE
ROOM NO ROOM NAME
WALL FINISH BASE FINISH FLOOR CEILING
NOTES & REMARKS (SEE NOTES)NORTH EAST SOUTH WEST NORTH EAST SOUTH WEST MATERIAL FINISH MATERIAL FINISH HEIGHT
105 ELEC P-1 P-1 P-1 P-1 NONE NONE NONE NONE NONE NONE OPEN NONE 13'-5"
3" = 1'-0"A-401
HOLLOW METAL FRAME DETAIL - JAMB6
3" = 1'-0"A-401
HOLLOW METAL FRAME DETAIL - HEAD8
1 1/2" = 1'-0"A-401
PARTITION WALL - TYPE A - WOOD STUD7
SCALE: = 1'-0"1 1/2"
01 1
SCALE: = 1'-0"3"
WALL TYPE SCHEDULE
NUMBER STUD SIZE STUD SPACING
WALL
THICKNESS COMMENTS
A 0' - 5 1/2" 16" 0' - 6 3/4" 5/8" TYPE-X MOISTURE RESISTANT GYPSUM BOARD EACH SIDE, PAINTED FINISH
3/4" = 1'-0"A-401
BOLLARD DETAIL3
SCALE: = 1'-0"3/4"
0 1 2 31
HARDWARE SET
SET NAME STC RATING TYPE (SEE SPECS) COMMENTS
HW-1 - STOREROOM LOCKSET LEVER HANDLE
3" = 1'-0"A-401
HOLLOW METAL FRAME DETAIL - SILL1
1 1/2" = 1'-0"A-401
BASE PLATE DETAIL (TYP. EACH COLUMN)9
GENERAL NOTES
1. THIS PROJECT IS A RENOVATION OF AN EXISTING FACILITY. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES.
ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICERS ATTENTION FOR RESOLUTION BEFORE
PROCEEDING WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. ALL WORK SHALL BE PERFORMED SO THAT IT MINIMIZES DISRUPTION OF THE OPERATION OF THE FACILITY.
3. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS
(DO NOT SCALE FOR LOCATIONS). THE CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONAL REFRIGERATION SYSTE AS INDICATED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS AS
INDICATED.
4. REMOVE CONNECTING UTILITIES (WATER, DRAINAGE, POWER, GAS, ETC.) AS INDICATED OR NECESSARY FOR
FUTURE RECONNECTION IF REQUIRED.
5. CONTRACTOR SHALL EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO
PERFORM THE WORK IDENTIFIED HERIN.
6. CONTRACTOR SHALL USE APPROPRIATE TOOLS AND SHALL NOT IMPART EXCESSIVE VIBRATIONS TO THE
EXISTING STRUCTURE OR OTHER BUILDING COMPONENTS.
7. COORDINATE PIPING AND EQUIPMENT INSTALLATION WITH EXISTING STRUCTURAL, ELECTRICAL, PLUMBING, AND COMMUNICATION. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER. CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS OF TRADES.
8. PRESSURE TEST NEW REFRIGERANT LINES TO A MINIMUM OF 450 PSIG WITH NO LOSS IN PRESSURE FOR A PERIOD OF 24 HOURS. RECORD TEMPERATURE BEFORE AND AFTER TEST; NOTE -0.3 PSI IS ALLOWED FOR EACH DECREASE IN DEGREE °F. PURGE, EVACUATE LINES TO ABSOLUTE PRESSURE OF 300 MICROMETERS FOR ONE HOUR WITHOUT INCREASE IN PRESSURE. CHARGE SYSTEM IN COMPLIANCE WITH REFRIGERATION SYSTEM AND
REFRIGERANT MANUFACTURER CHARGING INSTRUCTIONS.
9. ALL NEW REFRIGERANT PIPING SHALL BE INSULATED COMPLETELY.
10. ALL PIPING PENETRATIONS SHALL BE FULLY SEALED WATERTIGHT.
ACCU
AD
A.F.F.
A.F.G.
AHU
AP
APPROX.
ARCH
BTUH
CD
CL
C.O.
C.V.
CFM
CLG
CONC.
CONT.
CP
CHWR
CHWS
CWP
CWR
CWS
CT
CTE
CU
dB
DIFF.
DN.
DET.
DIA.
DIM.
DWG.
EA.
E/A
EAG
EAT
EF
EWT
ECC
EFF
ELEC.
ELEV.
ET
F
FLR
FDC
F/SD
FPM
FCO
FCU
FT.
FIN.
G
GA.
GAL.
GALV.
AIR COOLED CONDENSING UNIT
ACCESS DOOR
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
ACCESS PANEL
APPROXIMATE
ARCHITECTURAL
BRITISH THERMAL UNIT PER HOUR
CEILING DIFFUSER
CENTER LINE
CLEAN OUT
CHECK VALVE
CUBIC FEET PER MINUTE
CEILING
CONCRETE
CONTINUATION
CONDENSER WATER PUMP
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER PUMP
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
COOLING TOWER
CONNECT TO EXISTING
CONDENSING UNIT
DECIBELS
DIFFUSER
DOWN
DETAIL
DIAMETER
DIMENSION
DRAWING
EACH
EXHAUST AIR
EXHAUST AIR GRILLE
ENTERING AIR TEMPERATURE
EXHAUST FAN
ENTERING WATER TEMPERATURE
ECCENTRIC
EFFICIENCY
ELECTRICAL
ELEVATION
EXPANSION TANK
FAHRENHEIT
FLOOR
FIRE DEPARTMENT CONNECTION
FIRE/SMOKE DAMPER
FEET PER MINUTE
FLOOR CLEAN OUT
FAN COIL UNIT
FOOT OR FEET
FINISHED
NATURAL GAS PIPING
GAUGE
GALLONS
GALVANIZED
ABBREVIATIONS
COMMON TERMS
GEN.
G.P.H.
G.P.M.
HP
HR.
I.D.
IN,
kW, K.W.
L
LB
LBS
LD
LAT
LWT
MAU
MAX.
MCA
MFR.
MECH.
MIN.
MOCP
NC
NO
NPT
O/A O.D.
PH
PRV
PSI
R/A
RAD
RAR
RED.
REINF.
REQ'D.
RPM
RTU
S/A
SAG
SD
SEN
SF
SQ.
TA
TEMP
TH
TYP.
U.N.P.
UC
UH
VA
VAV
V V.T.R.
W/
WT
GENERAL
GALLONS PER HOUR
GALLONS PER MINUTE
HORSEPOWER
HOUR
INSIDE DIMENSION
INCHES
KILOWATT
LOUVER
POUND
POUNDS
LINEAR DIFFUSER
LEAVING AIR TEMPERATURE
LEAVING WATER TEMPERATURE
MAKEUP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MANUFACTURER
MECHANICAL
MINIMUM OR MINUTE
MAXIMUM OVERCURRENT PROTECTION
NORMALLY CLOSED
NORMALLY OPENED
NATIONAL PIPE THREAD
DIAMETER
OUTSIDE AIR
OUTSIDE DIMENSION, OUTSIDE DIAMETER
PHASE
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
RETURN AIR
RADIUS
RETURN AIR REGISTER
REDUCER
REINFORCING
REQUIRED
REVOLUTIONS PER MINUTE
ROOF TOP UNIT
SUPPLY AIR
SUPPLY AIR GRILLE
SMOKE DETECTOR
SENSIBLE
SQUARE FEET
SQUARE
TRANSFER AIR
TEMPERATURE
THERMOMETER
TYPICAL
UNLESS NOTED OTHERWISE
UNIT COOLER
UNIT HEATER
VALVE
VARIABLE AIR VOLUME (BOX)
VOLTS
VENT THRU ROOF
WITH
WEIGHT
COMMON TERMS
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TEL
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
M-001
ABBREVIATIONS AND LEGEND01/10
/202 jditty Toms TN Stamp jditty Toms Signature
A
B
D
1 2 3
C
EVAP-1 EVAP-2
CU-1
H-1
GENERATOR, BID OPTION A
(REFER TO ELECTRICAL
DRAWINGS)
1/2"
3/4"
CU-2
BOILER ROOM
RESTROOM
RESTROOM
CONDITIONED
SPACE
SEEDS
PROCESSING
STORAGE
EXISTING
COOLER
TRACTOR
STORAGE
COLD ROOM
CABBAGE
STORAGE
ELEC
H-2
1/2"
PROVIDE CONCRETE
EQUIPMENT PAD. SEE
DETAIL 4/M-502.
POINT OF CONNECTION
1-1/2" LPG
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TEL
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
M-101
MECHANICAL PLAN
1/8" = 1'-0"M-101
MECHANICAL PLAN1
SCALE: = 1'-0"
0 8 168
1/8"
PLAN NORTH
KEYED NOTES - FLOOR PLAN
COORDINATE LOCATION OF EVAPORATORS WITH STORAGE RACKS. REFER TO
ARCHITECTURAL PLANS.
TIE NEW 1-1/2" LPG PIPING INTO EXISTING LPG PIPING IN BOILER ROOM.
PROVIDE 1/2" WATER LINE WITH SHUTOFF BALL VALVE TO HUMIDIFIER.
PROVIDE 3/4" DRAIN LINES FROM HUMIDIFIER TO OUTDOORS.
PROVIDE 1" CONDENSATE DRAIN LINE FROM EVAPORATORS TO OUTDOORS.
OVERHEAD COLD WATER PIPING FROM EXISTING RESTROOMS TO NEW FREEZE
PROOF WALL HYDRANT AND COOLER HUMIDIFIERS. CONNECT TO WATER
SYSTEM FED FROM EXISTING WATER SOFTENER. (SIZE AS INDICATED). INSTALL
WITHIN HEATED ENVELOPE OF THE BUILDING TO PROTECT FROM FREEZING.
MOUNT HUMIDIFIER ON COOLER ENCLOSURE WALL PER DETAIL 3/M-502.
PROVIDE EQUIPMENT PLATFORM FOR CONDENSING INITS CU-1 AND CU-2. SEE
DETAIL 2/M-502.
1 3
01/10/ jditty Toms TN Stamp
6' - 11 3/32"
2' - 4 3/4"
3'
3/
8"
2'
3/
4" 3'
3/ 8"
3'
5"
REFRIGERANT
CONNECTION END
ELECTRICAL
CONNECTION END
AIR FLOW
DRAIN CONNECTION
ACCEPTS 1/2" HANGER ROD
5' - 11 23/32" 3' - 5 3/8"
3'
/4
13-3/4"
6- 3/
4"
19-3/8"
-3
/4
STEAM HUMIDIFIER
(SDU) SPACE DISTRIBUTION UNIT
1/4
1/4
1/4 3'
CONDENSING UNIT
CONDENSING UNIT
HSS 4x4x1/4"
ELEVATED
STEEL
PLATFORM
HSS 2x2x1/4"
COLUMN, TYP
1-1/2" SCH 40
BRACE, TYP
1/4" THICK BASE PLATE WITH
(2) WEDGE ANCHORS, TYP
WITH MINIMUM 3 1/2" EMBED
HSS 4x4x1/4"
EQUIPMENT PAD PER
DETAIL 4/M-502
2" MIN. 18" MIN. 2" MIN.
CONDENSING UNIT
2" MIN. 2" MIN.
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TEL
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
M-501
MECHANICAL DETAILS
NOT TO SCALEM-501
EVAPORATOR UNIT (EVAP-1 & EVAP-2) DETAIL1
NOT TO SCALEM-501
CONDENSING UNIT (CU-1 & CU-2) DETAIL3
12" = 1'-0"M-501
HUMIDIFIER (H-1 & H-2) DETAIL4
NOT TO SCALEM-501
ELEVATED STRUCTURAL STEEL EQUIPMENT PLATFORM DETAIL2
01/10 /202 jditty Toms TN Stamp
EVAPORATOR UNIT
PER SCHEDULE.
LOCATE PER MFR
RECOMMENDATIONSREFRIGERANT PIPING PER
MFR RECOMMENDATIONS
1" CONDENSATE DRAIN PIPING
SLOPE 1/4" PER FOOT MINIMUM
CLEANOUT
TRAP TO BE LOCATED OUTDOORS
WITHIN 2 FT OF GRADE. HEAT
TRACE AND INSULATE.
SECURE PIPING TO EXTERIOR
WALL. INSULATE AND HEAT TRACE
TO PROTECT FROM FREEZING.
SEAL PENETRATION OF COOLER
ENCLOSURE AIR TIGHT
SEAL EXTERIOR PENETRATIONS
WEATHER TIGHT.
THREADED ROD
AIR FLOW
SUPPORT
HUMIDIFIER PER SCHEDULE
1/2" PAN DRAIN PIPING
3/4" MAIN DRAIN PIPING. SLOPE
1/4" PER FOOT MINIMUM. HEAT
TRACE AND INSULATE.
SPACE DISTRIBUTION UNIT
1/2" WATER SUPPLY
TO HUMIDIFIER
1/2" BALL VALVE
MOUNT UNIT TO COOLER ENCLOSURE
WALL PER MFR INSTRUCTIONS USING
APPROVED BRACKET
SEAL PENETRATION OF COOLER
ENCLOSURE AIR TIGHT
SEAL EXTERIOR PENETRATIONS
WEATHER TIGHT.
1/2" WATER SUPPLY
ROUTE IN HEATED SPACE
CONDENSING UNIT
REFRIGERANT GAUGE
CONNECTION
BACK-SEATED REFRIGERANT VALVE
REFRIGERANT SUCTION LINE
WITH INSULATION
REFRIGERANT LIQUID LINE
CONDUIT - POWER AND CONTROL
FILTER - DRYER
SIGHT GLASS WITH
MOISTURE INDICATOR
ELEVATED STRUCTURAL
STEEL EQUIPMENT PLATFORM.
SEE DETAIL 2/M-501
FAN GUARD
4"
REFER TO ARCHITECTURAL PLANS
M
IN
IM
U
M
M
IN
IM
U
M
GRADE
CHAMFER ALL EDGES
BROOM FINISH
ATTACH EQUIPMENT TO PAD PER MFR INSTRUCTIONS.
PAD TO PROJECT A MINIMUM OF 6" BEYOND EQUIPMENT.
NO. 4 RE-BAR
CONTINUOUS
NO. 3 RE-BAR 16" O.C.
EACH WAY
4" CRUSHED
STONE BASE
M
IN
IM
U
M T
H
IC
K N
E S
S
SAWCUT OR SCORE CRACK CONTROL JOINTS EVERY 10'.
12" MINIMUM
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TEL
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
M-502
MECHANICAL DETAILS
NOT TO SCALEM-502
EVAPORATOR INSTALLATION DETAIL1
NOT TO SCALEM-502
HUMIDIFIER INSTALLATION DETAIL3
NOT TO SCALEM-502
CONDENSING UNIT INSTALLATION DETAIL2
NOT TO SCALEM-502
CONCRETE EQUIPMENT PAD DETAIL4
01/10/ jditty Toms TN Stamp
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural
Research
Service
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
TEL
WELLINGTON BARN COLD STORAGE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
M-601
MECHANICAL SCHEDULES
CU-2 EMERSON XFAM-060D-TFC-081 51,750 R449A 208-230/3/60 1 6 22.5 156 2 1/3 2.7 30.2 50 1045 ALL
CU-1 EMERSON XFAM-060Z-TFC-081 51,750 R449A 208-230/3/60 1 6 23.9 156 2 1/3 2.7 31.9 50 1045 ALL
QTY
POWER
(HP)
RLA
(AMPS)
LRA
(AMPS)
QTY
POWER
(HP)
FLA
(AMPS)
MCA
(AMPS)
MOCP
(AMPS)
MANUFACTURER MODEL NO.
COOLING
CAPACITY
(BTUH)
REFRIGERANT
VOLTS/
PHASE/
HERTZ
COMPRESSOR DATA FAN DATA UNIT
MARK
BASIS OF DESIGN REFRIGERATION DATA ELECTRICAL DATA
UNIT
WT
(LBS)
REMARKS
COOLER CONDENSING UNIT SCHEDULE
EVAP-2 LARKIN LEM0575BS8AMB 6,650 45 2 18 625 51,750 R448A/R449A 208-230/1/60 566 ALL
EVAP-1 LARKIN LEM0575BS8AMB 6,650 45 2 18 625 51,750 R448A/R449A 208-230/1/60 566 ALL
MANUFACTURER MODEL NO.
AIRFLOW
(CFM)
THROW
(FT.)
SPEEDS
FAN
DIA
(IN.)
FAN
POWER
(WATTS)
MARK
BASIS OF DESIGN AIRFLOW DATA
COOLING
CAPACITY
(BTUH)
REFRIGERANT
VOLTS/
PHASE/
HERTZ
UNIT
WT
(LBS)
REMARKS
COOLER EVAPORATOR SCHEDULE
NOTES:
1. HANG UNITS FROM COOLER ENCLOSURE PER MANUFACTURER'S RECOMMENDATIONS WITH PROPER UNIT CLEARANCES.
2. SIZE AND INSTALL REFRIGERANT TUBING ACCORDING TO ALL MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL
NECESSARY TUBING, FITTINGS AND REFRIGERATION SPECIALTY ITEMS.
3. PROVIDE 1" CONDENSATE DRAIN TO EXTERIOR OF BUILDING.
NOTES:
1. CU-2 SHALL BE EQUIPPED WITH A DIGITAL SCROLL COMPRESSOR WITH CAPABILITY TO MODULATE DOWN TO 10% OF RATED
CAPACITY.
2. SIZE AND INSTALL REFRIGERANT TUBING ACCORDING TO ALL MANUFACTURER'S RECOMMENDATIONS.
3. PROVIDE ALL NECESSARY TUBING, FITTINGS AND REFRIGERATION SPECIALTY ITEMS.
4. PROVIDE FACTORY INSTALLED LOW AMBIENT OPERATION.
5. PROVIDE INSULATED AND HEATED RECIEVER.
H-2 NEPTRONIC SKE4-N06 18 208-230/1/60 16.5 115 ALL
H-1 NEPTRONIC SKE4-N06 18 208-230/1/60 16.5 115 ALL
MANUFACTURER MODEL NO.
VOLTS/
PHASE/
HERTZ
MOCP
(AMPS)
MARK
BASIS OF DESIGN
STEAM
OUTPUT
(LB/HR)
ELECTRICAL DATA
UNIT
WT
(LBS)
REMARKS
HUMIDIFIER SCHEDULE
NOTES:
1. RESISTIVE TYPE HEATING ELEMENT.
2. STAINLESS STEEL EVAPORATION CHAMBER.
3. PROVIDE SPACE DISTRIBUTION UNIT EQUAL TO NEPTRONIC SDU4-1. MOUNT ON UNIT PER MANUFACTURER'S SPECIFICATIONS.
01/10/20 jditty Toms TN Stamp
NO. DATE BY DESCRIPTION
REVISIONS
PROJECT NO.
DATE
USDA AGRICULTURAL RESEARCH SERVICE
PLANT GENETICS RESEARCH UNIT
SHEET
OF
XXX
01/10/2023
A-E FIRM USDA
WELLINGTON BARN COLD STORAGE
AGRICULTURE RESEARCH SERVICE
USDA ARS NEA AAO ACQ/PER PROP
10300 BALTIMORE AVENUE
BLDG 003, RM 223, BARC-WEST
BELTSVILLE, MD 20705
PROJECT MANAGEREPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
TMC
2122-M
V. EDWARDS
T. VIGIL
JGM B. DISALVO
P. BORDELON
BSN
FIRM
P.A.Johnson M AdamscTHE
ARCHITECTS / ENGINEERS PLANNING SURVEYING MANAGEMENT
Agricultural Research Service
U S D A
2939 PRE-EMPTION ROAD
GENEVA, NY 14456
ELECTRICAL LEGEND
E-001
1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF WORK. THE DRAWINGS ARE NOT
INTENDED TO INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE
AND COMPLETION OF THE REQUIREMENTS OF THE CONTRACT.
2. THE CONTRACTOR IS RESPONSIBLE FOR THE COORDINATION OF ALL PARTS OF THE WORK SO THAT NO WORK SHALL BE LEFT IN AN UNFINISHED OR INCOMPLETE CONDITION. INSTALLATION
OF ELECTRICAL WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY
INSTALLATION IS DONE. CONDUIT AND DEVICES SHOWN ON PLANS ARE SCHEMATIC.
3. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY AND MANUFACTURER'S PUBLISHED
STANDARDS FOR QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL AS, ALL
REQUIREMENTS IN THESE DRAWINGS AND SPECIFICATIONS. ANY CONFLICTING
REQUIREMENTS OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT TO THE CONTACTING
OFFICER'S ATTENTION PRIOR TO PROCEEDING WITH THE WORK.
4. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-PLACE, AND NEW WORK.
5. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND SHALL VERIFY ALL
NEW AND EXISTING CONDITIONS SHOWN ON THESE DRAWINGS. THE CONTRACTOR SHALL
NOTIFY THE CONTRACTOR IN WRITING OF ANY DIFFERING CONDITIONS BEFORE
COMMENCEMENT OF WORK.
6. THE CONTRACTOR SHALL PLAN HIS/HER WORK TO PROVIDE ADEQUATE PROTECTION FOR
PERSONS AND PROPERTY AT ALL TIMES, AND EXECUTE THE WORK IN SUCH A MANNER TO
AVOID ANY HAZARD TO PERSONS AND PROPERTY AS NECESSARY.
7. MINIMUM RACEWAY SIZE SHALL BE 3/4-IN. INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT
RACEWAY FILL RATIO TO LESS THAN 40% FULL.
8. ALL CONDUCTORS COPPER.
9. ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND
CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH
DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE
A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTTIPLE BRANCH
CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
10. ALL SAFETY DISCONNECTS SHALL BE HEAVY DUTY 240V NEMA 3R NON-FUSED TYPE.
11. PROVIDE SAFETY DISCONNECTS FOR ALL MECHANICAL EQUIPMENT.
12. NEW WORK SHALL BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS
OF NEW WORK SHALL BE CHECKED AGAINST EXISTING WORK.
13. REFER TO ONE-LINE DIAGRAMS, SCHEDULES, AND RISER DIAGRAMS FOR CONDUCTOR AND
CONDUIT SIZES NOT SHOWN ON PLANS.
14. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY
SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL AND CIRCUIT(S). TEXT
SHALL BE BLACK 1/4-IN IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE
NOT PERMITTED.
15. COORDINATE WALL, FLOOR AND ROOF PENETRATIONS WITH THE CONTRACTOR.
16. SUPPLEMENTAL STEEL MEMBERS REQUIRED TO SUPPORT ELECTRICAL EQUIPMENT FROM
MAIN STRUCTURE SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR UNLESS
SPECIFICALLY NOTED OTHERWISE.
17. EXACT LOCATIONS OF PANELBOARDS, DISCONNECTS, TIMERS, AND SWITCHES SHALL BE
COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND
MECHANICAL EQUIPMENT. MOUNT DISCONNECTS AND SWITCHES MINIMUM 48" AFF. MOUNT
TIMERS MINIMUM 40" AFF.
18. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN
FOR INFORMATION ONLY. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
19. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON
DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE.
IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER
SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.
20. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN
ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF
QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER
MANUFACTURER IS ACCEPTABLE
21. PROVIDE GFCI PROTECTION AND FOR ALL NON-LIGHTING RECEPTACLES.
22. PROVIDE WEATHERPROOF IN USE COVERS FOR ALL RECEPTACLES.
23. PROVIDE WEATHERPROOF COVERS FOR ALL SWITCHES.
GENERAL PROJECT NOTES:ABBREVIATIONS:
DSHP
DSS
DWBP
DX
EC
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
A OR AMP AMPERE(S)
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR CONDITIONING UNIT
CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING
CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER
SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR
TEMPERATURE
CLOSED CIRCUIT
TELEVISION
CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CHILLER
CHILLED WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS
MANHOLE
CONDENSATE PUMP
CONTROL POWER
TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING
UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER
CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR
SYSTEM (UNIT)
DOUBLE POLE SINGLE
THROW
DOUBLE POLE DOUBLE
THROW
DUCTLESS SPLIT
CONDENSING UNIT
(POWERS THE DSS INDOOR
UNIT)
DUCTLESS SPLIT HEAT
PUMP (POWERS THE DSS
INDOOR UNIT)
DUCTLESS SPLIT SYSTEM
(INDOOR UNIT)
DOMESTIC WATER
BOOSTER PUMP
DIRECT EXPANSION (DX)
COOLING COIL
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC
TUBING
EMERGENCY
EFFECTIVE PROJECTED
AREA
EQUIPMENT
ENERGY RECOVERY
VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
NFPA
NC
NESC
NL
NO
NTS
P
PA
HWP
HWRP
HWSP
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LM
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
HT
HVU
HWCP
GUH
GWH
H or HT
HAC
HOA
HP
HP
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFCI
GRS
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL
PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH
EQUIPMENT
GROUND
GOVERNMENT FURNISHED
GOVERNMENT INSTALLED
GROUND FAULT
INTERRUPTER
GALVANIZED RIGID STEEL
CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR
PORTION OF SPLIT SYSTEM
HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR
UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER
CIRCULATING PUMP IN A
PRIMARY-SECONDARY
SYSTEM
HEATING WATER SUPPLY IN
A PRIMARY-ONLY SYSTEM
HOT WATER
RECIRCULATION PUMP
HEATING WATER SUPPLY
PUMP IN A PRIMARY-
SECONDARY SYSTEM
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION
SYSTEM
INTERMEDIATE METAL
CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE
INTERRUPTING CAPACITY
KCM OR KCMIL THOUSAND OF CIRCULAR
MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LOCKHEED MARTIN
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING
HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL
CODE
NATIONAL ELECTRICAL
MANUFACTURER'S
ASSOCIATION
NATIONAL FIRE
PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL
SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
SPEC
SPST
SWBD
SWGR
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
XFMR
Z
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH
PARALLEL OR SERIES FAN
(PRIMARY INDUCTION UNIT)
PAD MOUNTED
TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR
CONDITIONER
POLYVINYL CHLORIDE
RECEPT or RECP RECEPTACLE
RF
RH
RETURN FAN
RADIANT HEATERS
(ELECTRIC)
RMC
RMS
RTU
RVNR
SA
SCCR
SD
SF
S/N
SP
SPD
SPDT
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-
REVERSING
SURGE ARRESTOR
SHORT CIRCUIT CURRENT
RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE
THROW
SPECIFICATIONS
SINGLE POLE SINGLE
THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED
OTHERWISE
UNDERWRITERS
LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT
FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT
PUMP
WEATHERPROOF
TRANSFORMER
IMPEDANCE
NOTE: ABBREVIATIONS ABOVE
ARE FOR ELECTRICAL SHEETS
ONLY. NOT ALL ABBREVIATIONS
SHOWN WILL BE USED ON THIS
PROJECT.
MDP MAIN DISTRIBUTION PANEL
xx
PANELBOARD.
NAME OF PANELBOARD
GEAR
LA-1
LA-1 HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH
CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS
LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT
NUMBERS AT THE HOMERUN ARROWS.
PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL
PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN
A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.
10 THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF
THE CONDUCTORS THAT SHALL BE RUN IN THE CONDUIT.
THE ABSENCE OF TEXT SIGNIFIES THAT THE
CONDUCTORS SHOULD BE #12 AWG.
CONDUIT AND WIRING
CONDUCTORS IN CONDUIT SURFACE MOUNTED TO WALL OR
CEILING. LONG TIC MARKS INDICATE NUMBER OF
CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR
IS SHOWN AS A SHORT TIC MARK. SIZE THE
EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES
THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE
MARKINGS TO THE LEFT SIGNIFY THAT THREE
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED.
UNDERGROUND DUCT. DASHED LINE INDICATES CONDUIT IS
TO BE TRENCHED AND BURIED. REFER TO ?/E-??? FOR
DETAIL.
ELECTRICAL LEGEND:
DUPLEX NEMA 5-20R. GFCI. PROVIDE WITH WEATHERPROOF IN USE COVER.
NE
W
EX
IS
TI
NG
NEW EXISTING
BOILER ROOM
RESTROOM
RESTROOM
CONDITIONED
SPACE
SEEDS
PROCESSING
STORAGE
TRACTOR
STORAGE
102 EXISTING
COOLER
COLD ROOM
ELEC
CABBAGE
STORAGE
EVAP-1 EVAP-2
H-1
H-2
C U
-1 G
EN
ER
AT
O
R C
U -2
SCALE: = 1'-0"
0 8 168
1/8"
PLAN NORTH
EXISTING
VENTILATION
CONTROLS
EXISTING PANEL "EP-2"
EXISTING 200A DISCONNECT
EXISTING IRRIGATION CONTROLS
EXISTING PANEL "EP1"
EXISTING PANEL "MDP"
EXISTING METER BASE
EXISTING WATER HEATER
EXISTING BOILER7
NEW TRANSFER SWITCH "ATS"
NEW PANEL "EP-4"
KEYED NOTES - ELECTRICAL PLAN
EXISTING EQUIPMENT. PROTECT AND PRESERVE.
BID OPTION A: NEW GENERATOR.
PROVIDE NEW GROUNDING AT GENERATOR.
BID OPTION A: 300A NEMA 3R 120/208V 4-POLE AUTOMATIC TRANSFER SWITCH
300A NEMA 1 120/208V 3-PHASE PANEL.
NEW CONDENSER UNIT. PROVIDE FEEDER CONSISTING OF THREE #6 AWG
CONDUCTORS AND #10 GROUND IN 1-IN RMC. PROVIDE A 90A CIRCUIT BREAKER
FROM PANEL EM. FEED CONDENSER FROM NEW CIRCUIT BREAKER. TYPICAL OF
TWO UNITS.
NEW EVAPORATOR UNITS. PROVIDE 15A FEEDER FOR FAN CIRCUIT FROM PANEL
EP-4 CONSISTING OF TWO #12 AWG CONDCUTORS AND #12 GROUND IN 0.75-IN
RMC. TYPICAL OF TWO UNITS.
EXISTING MECHANICAL EQUIPMENT. PROVIDE DEDICATED 20A 120V CIRCUIT AND
NEMA 5-20R RECEPTACLE FROM NEW PANEL EM CONSISTING OF TWO #6 AWG
CONDUCTORS AND #6 AWG GROUND IN 1-IN RMC WHERE EXPOSED AND EMT
WHERE CONCEALED IN ATTIC. ROUTE THROUGH ATTIC SPACE. PIGTAIL TO #12
AWG AT NEW SURFACE MOUNTED JUNCTION BOX ABOVE RECEPTACLE.
PROVIDE 15A 208V 1-PHASE 3-WIRE CIRCUIT TO POWERED DOOR FROM PANEL EP-2
CONSISTING OF THREE #12 AWG CONDUCTORS AND #12 GROUND IN 0.75-IN EMT.
SCALE:
ELECTRICAL PLAN
1/8" = 1'-0"
E-100
NEW CONDENSERS
NEW
GENERATOR
"GEN"
9 NEW HUMIDIFICATION UNITS. PROVIDE CIRCUITS FROM PANEL EM CONSISTING OF
THREE #10 THWN, #10G IN 0.75-IN RMC. TYPICAL OF TWO UNITS.