1-Bid Drawings - 2026 43 Digester Tank Façade Rehabilitation Construction.pdf

PDF 4 MB Posted

Attached to
2026 43 Digester Tank Façade Rehabilitation Construction
Solicitation number
US.262832
Issued by
Pennsylvania

About this file

This document comprises bid drawings for the 2026 43 Digester Tank Façade Rehabilitation Construction project at the Bethlehem Wastewater Treatment Plant, located at 144 Shimersville Road, Bethlehem, Pennsylvania 18015. The project involves construction repairs to the brick and concrete facades of four digester tanks: South Primary Digester (PD-1), North Primary Digester (PD-2), South Primary Digester (PD-3), and North Secondary Digester (SD), along with repairs to an associated control building. Work includes concrete crack repair via epoxy injection, brick mortar repointing, removal and replacement of loose or broken brick, sealant joint replacement, stainless steel flashing installation, parapet reconstruction, through-wall scupper replacement, roof coating repairs, gutter repairs and verification, capstone patching and resetting, and pressure washing of select areas. Specific quantities identified in the repair legend include repointing areas ranging from 5 to 475 square feet across the four tanks, sealant replacement of 60 to 135 linear feet, concrete crack injection of 36 to 250 linear feet, loose brick replacement of 1 to 8 pieces, and gutter repairs of 190 linear feet. The drawings are dated August 6, 2026, with a revision date of November 16, 2026, and are supplemented by detailed technical specifications.

All contractors must field-verify existing conditions, dimensions, and elevations prior to submitting proposals and beginning work, as the drawings may not depict all existing piping, conduits, equipment, and fixtures requiring relocation. The contractor bears sole responsibility for jobsite safety, development of temporary shoring and bracing sequences, and protection of owner personnel and the public through temporary barricades. All work must comply with the International Building Code 2021. Damaged finishes and materials must be restored to pre-construction condition or better, and all phases of work, including temporary service outages, require coordination with the owner. The contractor must immediately notify the engineer of any existing conditions that prevent installation in accordance with the design details and must submit accurate sketches of conditions with proposed modifications for approval. Additional engineering fees for defective work may be withheld from contractor payments.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-001

COVER SHEET

AND

GENERAL NOTES

SGY PMG

106246

NOTED

8/6/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

BETHLEHEM WASTEWATER TREATMENT PLANT

JUNE 2026

PRIMARY AND SECONDARY DIGESTER TANKS

144 SHIMERSVILLE RD

BETHLEHEM, PA 18015

CHA PROJECT NO. 106246

PROJECT DRAWING LIST

S-001 COVER SHEET & GENERAL NOTES

S-100 SOUTH PRIMARY DIGESTER PD-1 ELEVATIONS

S-101 NORTH PRIMARY DIGESTER PD-2 ELEVATIONS

S-102 SOUTH PRIMARY DIGESTER PD-3 ELEVATIONS

S-103 NORTH SECONDARY DIGESTER SD ELEVATIONS

S-104 CONTROL BUILDING ELEVATIONS

S-500 SECTIONS AND DETAILS

GENERAL NOTES

1. THESE DRAWINGS SHOW THE WORK ASSOCIATED WITH REPAIRS AND RESTORATION OF FOUR (4)

DIGESTER TANKS AT THE WASTE WATER TREATMENT PLANT BETHLEHEM, PA.

2. THE WORK SHOWN ON THESE DRAWINGS HAS BEEN DESIGNED IN ACCORDANCE WITH THE STRUCTURAL

REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE, 2021.

3. ALL EXISTING CONDITIONS SHALL BE FIELD VERIFIED PRIOR TO BEGINNING ANY WORK. IF EXISTING CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE WORK IN ACCORDANCE WITH THE DETAILS AS SHOWN, THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD IMMEDIATELY AND PROVIDE AN ACCURATE SKETCH OF THE CONDITION, INCLUDING A PROPOSED MODIFICATION OR CORRECTION, FOR REVIEW AND

APPROVAL.

4. THE CONTRACTOR SHALL REVIEW THE NEED FOR TEMPORARY SHORING AND BRACING PRIOR TO THE CUTTING AND/OR REMOVAL OF ANY EXISTING CONSTRUCTION. THE CONTRACTOR IS RESPONSIBLE FOR THE DEVELOPMENT AND COORDINATION OF THE SEQUENCE OF TEMPORARY VERTICAL AND LATERAL BRACING, SHORING, DEMOLITION, AND NEW CONSTRUCTION AS PROJECT CONDITIONS REQUIRE TO MAKE SAFE ALL

STRUCTURAL ELEMENTS AND ADJACENT ELEMENTS IMPACTED BY THE PROJECT SCOPE OF WORK.

5. JOBSITE SAFETY IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. REVIEW OF THE CONSTRUCTION BY THE ENGINEER IS FOR CONFORMANCE WITH DESIGN ASPECTS ONLY, NOT TO REVIEW THE CONTRACTOR'S PROVISIONS FOR JOBSITE SAFETY. LACK OF COMMENT ON THE PART OF THE ENGINEER WITH REGARD TO

JOBSITE SAFETY IS NOT TO BE INTERPRETED AS APPROVAL OF JOBSITE SAFETY ASPECTS.

6. IF FAULTY CONSTRUCTION PROCEDURES, OR MATERIAL, RESULT IN DEFECTIVE WORK THAT REQUIRES ADDITIONAL ENGINEERING TIME TO DEVISE CORRECTIVE MEASURES, PROFESSIONAL FEES MAY BE CHARGED TO THE CONTRACTOR AT THE STANDARD HOURLY RATE OF ADDITIONAL SERVICES. SUCH FEES

MAY BE WITHHELD FROM THE CONTRACTOR'S PAYMENT.

7. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL TEMPORARY BARRICADES

AS REQUIRED TO PROTECT THE OWNER'S PERSONNEL AND THE GENERAL PUBLIC FROM INJURY DURING THE CONSTRUCTION PERIOD. DRIVEWAYS AND ENTRANCES SERVING THE PREMISES ARE TO BE KEPT CLEAR AND

AVAILABLE TO THE OWNER AND THE OWNER'S EMPLOYEES AT ALL TIMES.

8. THESE DRAWINGS ARE SUPPLEMENTED BY A DETAILED TECHNICAL SPECIFICATION. THE NOTES SHOWN ON

THESE DRAWINGS UNDER CERTAIN CATEGORIES OF WORK ARE INTENDED TO SUMMARIZE BASIC

REQUIREMENTS AND ARE ON THE DRAWINGS FOR CONVENIENCE.

SPECIAL NOTES TO THE CONTRACTOR:

1. REPAIR QUANTITIES IDENTIFIED ON THESE DRAWINGS WERE BASED UPON FIELD OBSERVATIONS MADE

BY THE ENGINEER.

2. ALL CONTRACTORS MUST REVIEW THE WORK AREA PRIOR TO SUBMITTING CONSTRUCTION PROPOSALS TO DETERMINE THE FULL SCOPE OF THE WORK INVOLVED. THE DRAWINGS MAY NOT SHOW ALL PIPING, CONDUITS, EQUIPMENT, AND FIXTURES THAT MAY HAVE TO BE RE-ROUTED OR TEMPORARILY

DISLOCATED TO PERFORM THE STRUCTURAL WORK SHOWN.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND ELEVATIONS OF THE EXISTING CONDITIONS

BEFORE PROCEEDING WITH ANY WORK.

4. THE SCHEDULING OF ALL PHASES OF THE WORK, INCLUDING ANY TEMPORARY SERVICE OUTAGES, SHALL

BE COORDINATED WITH THE OWNER.

5. ALL FINISHES OR MATERIALS DAMAGED IN THE PERFORMANCE OF THE WORK SHALL BE RESTORED TO

PRE CONSTRUCTION CONDITION, OR BETTER.

6. THE CONTRACTOR SHALL REPORT TO THE ENGINEER ANY AND ALL CONDITIONS WHICH DIFFER FROM

THOSE SHOWN ON THESE DRAWINGS, OR WHICH PREVENT HIM FROM PERFORMING THE WORK IN

ACCORDANCE WITH THE CONTRACT DOCUMENTS.

AREA OF WORK

11/16/2026

ELEVATION - 1

SCALE: 3/8"=1'-0"

ELEVATION - 2

SCALE: 3/8"=1'-0"

ELEVATION - 3

SCALE: 3/8"=1'-0"

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

3.0

PATCH CAPSTONE

PER DETAIL 1/S-500

5.0

9.0

ROOF

9.0

ROOF

9.0

ROOF

25'-0" ±25'-0" ±25'-0" ±

APPROX EXTENTS OF FOREGROUND STRUCTURE

11.011.011.0

ELEVATION - 4

SCALE: 3/8"=1'-0"

ELEVATION - 5

SCALE: 3/8"=1'-0"

ELEVATION - 6

SCALE: 3/8"=1'-0"

7.0

5.0

5.0

INSTALL NEW S.S. FLASHING PER

DETAIL 6/S-500.RE-SET CAP STONES

AND REPAIR ROOF COATING AT

REBUILT PARAPET AREA

RE-SET THRU WALL SCUPPER

AND RESTORE ALL FLASHING,

REFER TO DETAIL 8/S-500

NO CAP STONE

WORK

9.0

ROOF

9.0

ROOF

9.0

ROOF

11.0

25'-0" ± 25'-0" ± 25'-0" ±

11.011.0

ELEVATION - 7

SCALE: 3/8"=1'-0"

ELEVATION - 8

SCALE: 3/8"=1'-0"

1.0

CORNER

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

7.0

4.0

1.0

3.0

4.0

3.0

7.0

1.0

9.0

ROOF

9.0

ROOF

25'-0" ± 28'-11" ±

INSTALL NEW S.S. FLASHING PER

DETAIL 6/S-500.RE-SET CAP STONES

AND REPAIR ROOF COATING AT

REBUILT PARAPET AREA

INSTALL NEW S.S. FLASHING PER

DETAIL 6/S-500.RE-SET CAP STONES

AND REPAIR ROOF COATING AT

REBUILT PARAPET AREA

AFTER

RE-SETTING,

TYP

11.0

AFTER

RE-SETTING,

TYP

11.0

KEY PLAN

SCALE: NONE

24 23

29 30

9 10

4 3

N

CONTROL

BLDG

PD-1 PD-2

PD-3 SD

W

N

E

S

DESCRIPTION

1.0

3.0

4.0

MARK

REPAIR LEGEND FOR SOUTH PD-1 ONLY

DENOTATION

CUT BACK EXISTING MORTAR JOINTS AND REPOINT WITH NEW

MORTAR WITHIN DEFINED AREA. REF DETAIL 4/S-500. (30 SQ FT )

SEE ELEVATION VIEW FOR ADDITIONAL REQUIRED WORK NOT NOTED HERE

EXISTING CRACKS, FAILING, MISSING OR OPEN MORTAR JOINTS.

OR

REMOVE LOOSE BRICK, BROKEN BRICK OR MISSING BRICK AND RESET

AS NECESSARY. ANY NEW BRICK TO MATCH EXISTING SIZE, SHAPE, AND

COLOR. (2 BRICK )

ADDITIONAL SPOT REPOINTING TO BE DETERMINED BY

ENGINEER DURING CONSTRUCTION PHASE

(300 SQ FT)

SEE ELEVATION DRAWINGS FOR ADDITIONAL REPAIRS NOT SCHEDULED HERE

5.0 REMOVE EXISTING SEALANT AND REPLACE. (60 LF )

REF 2/S-500

6.0

7.0 DEMO EXISTING 2 WYTHE BRICK AND RECONSTRUCT. COORD w/

SECTION 3/S-500 (130 SF )

8.0

CUT BACK EXISTING MORTAR JOINT AND REPOINT WITH NEW MORTAR.

REF DETAIL 4/S-500. (12 LF )

2.0

9.0 NOT SHOWNINJECTION PORTS AND INJECT ROOF CRACKS (250 LF).

REF DETAIL 5/S-500. ROOF LOCATIONS TO BE FIELD DETERMINED BY ENGINEER

NOT APPLICABLE THIS DIGESTER

NOT APPLICABLE THIS DIGESTER

NOT APPLICABLE THIS DIGESTER

ON ELEVATIONS

REMOVE ALL EXST JT MATERIAL, CLEAN JOINT AND INSTALL

NEW SEALANT PER 2/S-500 (135 LF )

10.0 NOT APPLICABLE THIS DIGESTER

11.0 Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-100

SOUTH PRIMARY

DIGESTER PD-1

ELEVATIONS

SGY PMG

106246

NOTED

8/6/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

ELEVATION - 9

ELEVATION - 10

SCALE: 3/8"=1'-0"

ELEVATION - 11

SCALE: 3/8"=1'-0"

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

1.0

8.0

1.0

8.0

1.0

8.0

3.0

5.0

9.0

ROOF

9.0

ROOF

9.0

ROOF

25'-0" ±25'-0" ±25'-0" ±

ELEVATION - 12

SCALE: 3/8"=1'-0"

ELEVATION - 13

SCALE: 3/8"=1'-0"

ELEVATION - 14

SCALE: 3/8"=1'-0"

2.0

1.0

8.0

1.01.0

8.0

1.0

8.0

5.0

9.0

ROOF

9.0

ROOF

9.0

ROOF

25'-0" ±25'-0" ±25'-0" ±

ELEVATION - 15

SCALE: 3/8"=1'-0"

ELEVATION - 16

SCALE: 3/8"=1'-0"

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

2.0

1.0

8.0

2.0

1.0

8.0

1.0

2.0

4.0

REMOVE AND

RE-SET BRICK

1.0

5.0

9.0

ROOF

9.0

ROOF

29'-5" ±25'-0" ±

KEY PLAN

SCALE: NONE

24 23

29 30

9 10

4 3

N

CONTROL

BLDG

PD-1 PD-2

PD-3 SD

W

N

E

S

DESCRIPTION

1.0

3.0

4.0

MARK DENOTATION

CUT BACK EXISTING MORTAR JOINTS AND REPOINT WITH NEW

MORTAR WITHIN DEFINED AREA. REF DETAIL 4/S-500. (5 SQ FT )

EXISTING CRACKS, FAILING, MISSING OR OPEN MORTAR JOINTS.

OR

ADDITIONAL SPOT REPOINTING TO BE DETERMINED BY

ENGINEER DURING CONSTRUCTION PHASE

(300 SQ FT)

SEE ELEVATION DRAWINGS FOR ADDITIONAL REPAIRS NOT SCHEDULED HERE

5.0 REMOVE EXISTING SEALANT AND REPLACE. (60 LF )

REF 2/S-500

6.0

7.0

8.0

CUT BACK EXISTING MORTAR JOINT AND REPOINT WITH NEW MORTAR.

REF DETAIL 4/S-500. (60 LF )

2.0 PRESSURE WASH AND CLEAN SURFACE (80 SQ FT )

REPAIR LEGEND FOR NORTH PD-2 ONLY

INJECTION PORTS AND INJECT ROOF CRACKS (250 LF).

REF DETAIL 5/S-500. LOCATIONS TO BE FIELD DETERMINED BY ENGINEER9.0

NOT APPLICABLE THIS DIGESTER

NOT APPLICABLE THIS DIGESTER

REMOVE LOOSE BRICK, BROKEN BRICK OR MISSING BRICK AND RESET

AS NECESSARY. ANY NEW BRICK TO MATCH EXISTING SIZE, SHAPE, AND

COLOR. (2 BRICK )

SEE ELEVATION VIEW FOR ADDITIONAL REQUIRED WORK NOT NOTED HERE

INJECTION PORTS, REF DETAIL 5A/S-500 (205 MIN REQ'D)

AND APPLY SEALANTANT TO HORIZ JOINT, REF 2/S-500 (190 LF )

Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-101

NORTH PRIMARY

DIGESTER PD-2

ELEVATIONS

SGY PMG

106246

NOTED

8/6/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

ELEVATION - 25

ELEVATION - 26

SCALE: 3/8"=1'-0"

ELEVATION - 27

SCALE: 3/8"=1'-0"

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

6.0

3.0

2.0

3.0

2.0

1.0

3.0

5.0

10.0 10.0 10.0

25'-0"+- 25'-0"+- 25'-0"+-

ELEVATION - 28

SCALE: 3/8"=1'-0"

ELEVATION - 29

SCALE: 3/8"=1'-0"

ELEVATION - 30

SCALE: 3/8"=1'-0"

REMOVE INSERT AND

PATCH BRICK

6.0 6.06.0

REMOVE (2)

INSERTS AND

PATCH BRICK

1.0

1.0

1.0

3.0

2.0

1.0

1.0

3.0

2.0

3.0

2.0

5.0

10.0 10.0 10.0

25'-0"+- 25'-0"+- 25'-0"+-

ELEVATION - 31

SCALE: 3/8"=1'-0"

ELEVATION - 32

SCALE: 3/8"=1'-0"

4.0

REMOVE INSERT

AND PATCH BRICK

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

6.0 6.01.0

1.0

1.0

1.0

3.0

3.0

2.0

5.0

10.0 10.0

25'-0"+- 29'-4 1/2"+-

KEY PLAN

SCALE: NONE

24 23

29 30

9 10

4 3

N

CONTROL

BLDG

PD-1 PD-2

PD-3 SD

W

N

E

S

DESCRIPTION

1.0

3.0

4.0

MARK DENOTATION

CUT BACK EXISTING MORTAR JOINTS AND REPOINT WITH NEW

MORTAR WITHIN DEFINED AREA. REF DETAIL 4/S-500. (170 SQ FT )

EXISTING CRACKS, FAILING, MISSING OR OPEN MORTAR JOINTS.

OR

ADDITIONAL SPOT REPOINTING TO BE DETERMINED BY

ENGINEER DURING CONSTRUCTION PHASE

(300 SQ FT)

SEE ELEVATION DRAWINGS FOR ADDITIONAL REPAIRS NOT SCHEDULED HERE

5.0 REMOVE EXISTING SEALANT AND REPLACE. (60 LF )

REF 2/S-500

6.0

7.0

8.0

CUT BACK EXISTING MORTAR JOINT AND REPOINT WITH NEW MORTAR.

REF DETAIL 4/S-500. (115 LF )

2.0 PRESSURE WASH AND CLEAN SURFACE (325 SQ FT )

REPAIR LEGEND FOR SOUTH PD-3 ONLY

9.0

REMOVE LOOSE BRICK, BROKEN BRICK OR MISSING BRICK AND RESET

AS NECESSARY. ANY NEW BRICK TO MATCH EXISTING SIZE, SHAPE,

AND COLOR. (2 BRICK )

SEE ELEVATION VIEW FOR ADDITIONAL REQUIRED WORK NOT NOTED HERE

NOT APPLICABLE THIS DIGESTER

10.0 VERIFY INTEGRITY OF TERM BAR AND FASTENERS SECURING GUTTER,

REPAIR OR REPLACE DAMAGED OR MISSING COMPONENTS, RE-SEAL

TERM BAR / GUTTER TO TANK WALL. (190LF)

CONCRETE CRACK REPAIR. REF DETAIL 5/S-500. (36LF)

NOT APPLICABLE THIS DIGESTER

NOT APPLICABLE THIS DIGESTER

Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-102

SOUTH PRIMARY

DIGESTER PD-3

ELEVATIONS

SGY PMG

106246

NOTED

8/6/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

ELEVATION - 17

ELEVATION - 18

SCALE: 3/8"=1'-0"

ELEVATION - 19

SCALE: 3/8"=1'-0"

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

3.0

1.0

3.0

3.0

1.0

3.0

2.0

3.0

3.0

3.0

3.03.0

4.0

VERIFY PROPER DRAINAGE.

REPAIR, STRAIGHTEN, RE-SUPPORT

AND RESTORE SLOPE TO EXISTING

GUTTER THIS AREA

VERIFY PROPER DRAINAGE.

REPAIR, STRAIGHTEN, RE-SUPPORT

AND RESTORE SLOPE TO EXISTING

GUTTER THIS AREA

VERIFY PROPER DRAINAGE.

REPAIR, STRAIGHTEN, RE-SUPPORT

AND RESTORE SLOPE TO EXISTING

GUTTER THIS AREA

10.0 10.0 10.0

25'-0"+-25'-0"+-30'±

ELEVATION - 20

SCALE: 3/8"=1'-0"

ELEVATION - 21

SCALE: 3/8"=1'-0"

ELEVATION - 22

SCALE: 3/8"=1'-0"

3.0

3.03.0

3.0

5.0

3.0

VERIFY PROPER DRAINAGE.

REPAIR, STRAIGHTEN, RE-SUPPORT

AND RESTORE SLOPE TO EXISTING

GUTTER THIS AREA

10.0 10.0 10.0

25'-0"+- 25'-0"+- 25'-0"+-

ELEVATION - 23

SCALE: 3/8"=1'-0"

ELEVATION - 24

SCALE: 3/8"=1'-0"

C O

N

TR

O L

BL

D

G

CLEAN DEBRIS FROM

ALL WEEP JOINTS,

TYPICAL ALL

LOCATIONS AROUND

TANKS

3.0

3.0

1.0

3.0

5.0

3.0

VERIFY PROPER DRAINAGE.

REPAIR, STRAIGHTEN, RE-SUPPORT

AND RESTORE SLOPE TO EXISTING

GUTTER THIS AREA

10.0 10.0

25'-0"+-25'-0"+-

KEY PLAN

SCALE: NONE

24 23

29 30

9 10

4 3

N

CONTROL

BLDG

PD-1 PD-2

PD-3 SD

W

N

E

S

DESCRIPTION

1.0

3.0

4.0

MARK DENOTATION

CUT BACK EXISTING MORTAR JOINTS AND REPOINT WITH NEW

MORTAR WITHIN DEFINED AREA. REF DETAIL 4/S-500. (475 SQ FT )

EXISTING CRACKS, FAILING, MISSING OR OPEN MORTAR JOINTS.

OR

ADDITIONAL SPOT REPOINTING TO BE DETERMINED BY

ENGINEER DURING CONSTRUCTION PHASE

(300 SQ FT)

SEE ELEVATION DRAWINGS FOR ADDITIONAL REPAIRS NOT SCHEDULED HERE

5.0 REMOVE EXISTING SEALANT AND REPLACE. (60 LF )

REF 2/S-500

6.0

7.0

8.0

CUT BACK EXISTING MORTAR JOINT AND REPOINT WITH NEW MORTAR.

REF DETAIL 4/S-500. (8 LF )

2.0 PRESSURE WASH AND CLEAN SURFACE (70 SQ FT )

REPAIR LEGEND FOR NORTH SD-2 ONLY

9.0

REMOVE LOOSE BRICK, BROKEN BRICK OR MISSING BRICK AND RESET

AS NECESSARY. ANY NEW BRICK TO MATCH EXISTING SIZE, SHAPE, AND

COLOR. ( 1 BRICK )

SEE ELEVATION VIEW FOR ADDITIONAL REQUIRED WORK NOT NOTED HERE

NOT APPLICABLE THIS DIGESTER

10.0

NOT APPLICABLE THIS DIGESTER

NOT APPLICABLE THIS DIGESTER

NOT APPLICABLE THIS DIGESTER

VERIFY INTEGRITY OF TERM BAR AND FASTENERS SECURING GUTTER,

REPAIR OR REPLACE DAMAGED OR MISSING COMPONENTS, RE-SEAL

TERM BAR / GUTTER TO TANK WALL. (190LF) Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-103

NORTH SECONDARY

DIGESTER SD

ELEVATIONS

SGY PMG

106246

NOTED

8/6/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

SOUTH ELEVATION

NORTH ELEVATION

SCALE: 3/8"=1'-0"

WEST ELEVATION

SCALE: 3/8"=1'-0"

3.0 1.0

REMOVE

BROKEN

CAPSTONE

PIECE AND

PATCH PER

DETAIL 1/S-500

INSIDE

CORNER

RE-SET

DISPLACED CAP

STONE, RE-SEAL

JOINT PER 2/S-500

REPLACE (3)

BROKEN BRICK.

CLEAN AND COAT

ALL PORTIONS OF

EXPOSED STEEL

LINTEL. REPOINT

ADJACENT BRICK

JOINTS. SIM OPP

SIDE OF WINDOW

REPLACE (5)

BROKEN BRICK,

THIS WINDOW.

CLEAN AND

COAT ALL

PORTIONS OF

EXPOSED STEEL

LINTEL. REPOINT

ADJACENT

BRICK JOINTS

REMOVE BED

JOINT MORTAR AT

LINTEL BEARING,

CLEAN AND COAT

ALL PORTIONS OF

EXPOSED STEEL

LINTEL. REPOINT

JOINT. TYP BOTH

SIDES OF WINDOW

REMOVE BED

JOINT MORTAR AT

LINTEL BEARING,

CLEAN AND COAT

ALL PORTIONS OF

EXPOSED STEEL

LINTEL. REPOINT

JOINT. TYP BOTH

SIDES OF WINDOW

1.0

3.0

3.0

1.0

4.0

EAST ELEVATION

SCALE: 3/8"=1'-0"

3.0 3.0

1.0

RE-SEAL JOINT

PER 2/S-500

KEY PLAN

SCALE: NONE

24 23

29 30

9 10

4 3

N

CONTROL

BLDG

PD-1 PD-2

PD-3 SD

W

N

E

S

DESCRIPTION

1.0

3.0

4.0

MARK DENOTATION

CUT BACK EXISTING MORTAR JOINTS AND REPOINT WITH NEW

MORTAR WITHIN DEFINED AREA. REF DETAIL 4/S-500. (30 SQ FT )

EXISTING CRACKS, FAILING, MISSING OR OPEN MORTAR JOINTS.

OR

ADDITIONAL SPOT REPOINTING TO BE DETERMINED BY

ENGINEER DURING CONSTRUCTION PHASE

(100 SQ FT)

SEE ELEVATION DRAWINGS FOR ADDITIONAL REPAIRS NOT SCHEDULED HERE

5.0

6.0

7.0

8.0

CUT BACK EXISTING MORTAR JOINT AND REPOINT WITH NEW MORTAR.

REF DETAIL 4/S-500. (25 LF )

2.0

REPAIR LEGEND FOR CONTROL BUILDING ONLY

9.0

SEE ELEVATION VIEW FOR ADDITIONAL REQUIRED WORK NOT NOTED HERE

NOT APPLICABLE THIS BUILDING

10.0 NOT APPLICABLE THIS BUILDING

NOT APPLICABLE THIS BUILDING

NOT APPLICABLE THIS BUILDING

NOT APPLICABLE THIS BUILDING

NOT APPLICABLE THIS BUILDING

NOT APPLICABLE THIS BUILDING

REMOVE LOOSE BRICK, BROKEN BRICK OR MISSING BRICK AND RESET

AS NECESSARY. ANY NEW BRICK TO MATCH EXISTING SIZE, SHAPE, AND

COLOR. (8 BRICK )

REMOVE ALL EXST JT MATERIAL, CLEAN JOINT AND INSTALL

NEW SEALANT PER 2/S-500 (6 LF )

11.0 Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-104

CONTROL BUILDING

ELEVATIONS

SGY PMG

106246

NOTED

8/6/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

PLAN

SECTION

TYPICAL PATCH REPAIR DETAIL

SCALE: NONE

S-500

TYPICAL SEALANT DETAIL

SCALE: NONE

S-500

TYPICAL BRICK VENEER RECONSTRUCTION

SCALE: NONE

S-500

EXTENTS OF

CONCRETE SPALL

SAW-CUT BEYOND

PERIMETER OF SPALL

TO A DEPTH OF 1/2"

MIN

PATCH AREA TO

MATCH SURROUNDING

EXISTING CONCRETE

ELEVATION w/ REPAIR

MATERIAL, SEE

OPTIONS

EXIST SLAB BONDING AGENT,

SEE NOTES

D

EP

TH

REPAIR COPING CAP - SIKATOP-123 PLUS REPAIR MORTAR

PREPARATION: REMOVE ALL DETERIORATED CONCRETE, DIRT, OIL, SURFACE

GREASE, AND ALL BOND-INHIBITING MATERIALS FROM SURFACE. BE SURE

REPAIR AREA IS NOT LESS THAN 1/8 INCH (3MM) IN DEPTH. PREPARATION WORK

SHOULD BE DONE BY HIGH PRESSURE WATER BLAST TO OBTAIN AN EXPOSED

AGGREGATE SURFACE PROFILE OF +/- 1/16 INCH. SUBSTRATE SHOULD BE

SATURATED SURFACE DRY (SSD) WITH NO STANDING WATER DURING

APPLICATION.

PRIMING: APPLY A SCRUB COAT OF SIKATOP-123 PLUS PRIOR TO PLACEMENT

OF THE MORTAR. THE REPAIR MORTAR HAS TO BE APPLIED INTO THE WET

SCRUB COAT BEFORE IT DRIES.

MIXING: POUR COMPONENT 'A' INTO MIXING CONTAINER. ADD COMPONENT 'B'

WHILE MIXING CONTINUOUSLY. MIX MECHANICALLY WITH LOW SPEED DRILL

(400-600 RPM) AND MIXING PADDLE OR MORTAR MIXER. MIX TO A UNIFORM

CONSISTANCY. MAXIMUM 3 MIINUTES. REFERENCE MANUFACTURER'S

INSTRUCTIONS FOR ADDITIONAL INFORMATION.

APPLICATION & FINISH: THE MIXED SIKATOP-123 PLUS MUST BE WORKED WELL

INTO THE PRIMED SUBSTRATE, FILLING ALL PORES AND VOIDS. COMPACT WELL.

FORCE MATERIAL AGAINST SAW-CUT OR FORMED EDGES OF REPAIR WORKING

TOWARDS THE CENTER. AFTER FILLING REPAIR, CONSOLIDATE, THEN SCREED.

FINISH WITH STEEL, WOOD, PLASTIC, FLOATES, OR DAMP SPONGES, AS

NECESSSARY TO MATCH THE EXISTING SURFACE TEXTURE. WHERE MULTIPLE

LIFTS ARE REQUIRED, SCORE TOP SURFACE ON EACH LIFT TO PRODUCE A

ROUGHENED SUBSTRATE FOR NEXT LIFT. ALLOW PRECEDING LIFT TO REACH

INITIAL SET BEFORE APPLYING FRESH MATERIAL. SATURATE SURFACE OF THE

LIFT WITH CEAN WATER. IF PREVIOUS LAYERS ARE OVER 48 HOURS OLD,

MECHANICALLY PREPARE THE SUBSTRATE AND DAMPEN.

CURING: MOIST CURE WITH WET BURLAP AND POLYETHYLENE OR A FINE MIST

OF WATER. MOST CURING SHOULD COMMENCE IMMEDIATELY AFTER FINISHING.

PROTECT FRESHLY APPLIED MORTAR FROM DIRECT SUNLIGHT, WIND, RAIN AND

FROST.

VERTICAL CONTROL JOINTS JOINT REPAIR - SIKAFLEX-15LM SEALANT

COPING CAP JOINT REPAIR - SIKAFLEX-1a SEALANT

PD-2 HORIZONTAL JOINT REPAIR-SIKAFLEX PRIMER 429

WITH SIKAFLEX-15LM SEALANT

DESCRIPTION: ONE PART, LOW-MODULUS POLYURETHANE SEALANTS.

PREPARATION: CLEAN ALL SURFACES. JOINT WALLS MUST BE SURFACE SOUND,

CLEAN, DRY, FROST-FREE, AND FREE OF OIL AND GREASE. CURING COMPOUND

RESIDUES AND MANY OTHER FOREIGN MATTERS MUST BE THOROUGHLY REMOVED.

CLEAN BY MECHANICAL METHODS TO EXPOSE A SOUND SURFACE. INSTALL BOD

BREAKER TAPE OR BACKER ROD TO PREVENT BOND AT BASE OF JOINT.

APPLICATION: RECOMMENDED APPLICATION TEMPERATURES, 40 DEG - 100 DEG F.

FOR COLD-WEATHER APPICATIONS, PRE-CONDITIONING UNITS TO APPROXIMATELY 70

DEG F IS RECOMMENDED. ONLY APPLY SEALANT TO CLEAN, SOUND, DRY, AND

FROST-FREE SUBSTRATES. WHEN APPLYING SEALANT, AVOID AIR ENTRAPMENT. DRY

TOOLING IS RECOMMENDED. DO NOT TOOL WITH DETERGENT OR SOAP SOLUTIONS.

DO NOT APPLY TO DAMP OR WET SURFACES. JOINT DIMENSION SHOULD ALLOW FOR

¼ INCH MINIMUM AND ½ INCH MAXIMUM THICKNESS FOR SEALANT. PROPER DESIGN

IS 2:1 WIDTH TO DEPTH RATIO.

ALL APPLICATIONS TO FOLLOW MANUFACTURERS PRODUCT INSTALLATION

INSTRUCTIONS.

NEW CLOSED CELL

W/ SURFACE SKIN

BACKER ROD

NEW SPECIFIED

SEALANT JOINT

COPING OR BRICK

TO

/2

STAINLESS STEEL 345-BT

FLEXIBLE TIE ANCHOR AS MFR

BY HOHMANN & BARNARD.

SPACE AT 16" o.c. HORIZ AND

VERT. SECURE TO CONCRETE

TANK WALL w/ (1) 1/4"Ø x 2 1/2"

S.S. TAPCON ANCHOR

(2) WYHT BRICK RECONSTRUCTION

TO MATCH EXISTING BRICK SIZE,

SHAPE, COLOR AND PATTERN.

MORTAR TO MATCH EXISTING.

TOOTH IN MASONRY AT SIDES OF

DEMO EXTENTS

8" MAX FROM TOP

OF VENEER OR

CONCRETE TANK

WALL, VIF

1/ 2"

M

IN

R

EP

AI

R

1/4

"o

.c

H O

R

IZ

V

ER

T

SEE DETAIL 6/S-500 AND DIGESTER

ELEVATION VIEWS FOR TOP OF

PARAPET RECONSTRUCTION

WHERE APPLICABLE, (NOT SHOWN

HERE).

VERTICAL CONTROL JOINTS AND

COPING CAP HEAD JOINTS

ROUT JOINT AFTER

CRACK INJECTION,

APPLY SPECIFIED

JOINT SEALANT

CONCRETE

PD-2 HORIZONTAL JOINT

INJECTED CONCRETE

COLD JOINT

TYPICAL REPOINTING DETAIL

SCALE: NONE

S-500

SAWCUT BACK EXST

JOINT (3/4" MIN), &

CLEAN OUT ALL

LOOSE MORTAR &

DEBRIS, & REPOINT

w/ NEW MORTAR. DO

NOT CUT OR DAMAGE

BRICK OR ENLARGE

JOINTS

LAP DRIP EDGE

INTACT, DO NOT

TRIM

LA

P

D R

IP

E

D G

E

IN

TA

C

T, D

O N

O T

TR

IM

EDGE OF PIECE

8" M

IN

EDGE OF PIECE 1

CUT / REMOVE HEMMED

DRIP EDGE OF

UNDERLYING S.S.

FLASHING THIS SIDE

1/8" x 1" ELASTIC BUTYL

TAPE CONTINUOUS,

EXTEND FROM DRIP EDGE

TO TRIMMED EDGE AT

HEM

SE

LF

AD

H

ER

ED

M

EM

BR

AN

E

PLAN VIEW A-A

6" 6"

ROOF

SIDE

BELOW LAP

ABOVE LAP

1" 1"

SEE PLAN VIEW FOR SELF

ADHERED MEMBRANE

AND BUTYL MASTIC NOT

SHOWN HERE

FULL MORTAR BED

8" LA

P

A

A

FABRICATED / CURVED

STAINLESS STEEL CAP

FLASHING

PROVIDE CONT SEALANT JOINT

BETWEEN TOP OF MASONRY AND

UNDERSIDE OF S.S. FLASHING ALONG

BOTH INTERIOR AND EXTERIOR

EDGES OF WALL USING SEALANT

CONC TANK

ROOF

INSIDE FACE OF

BRICK PARAPET

SEE DETAIL 7/S-500 FOR

CAP STONE SETTING

PINS, NOT SHOWN HERE

STAINLESS STEEL PARAPET FLASHING DETAILS

SCALE: NONE

S-500

DETAILS SHOWN FOR CONSTRUCTION REFERENCE ONLY, DO NOT

SCALE. FIELD VERIFY ALL CONDITIONS AND REQUIRED DIMENSION

PRIOR TO FABRICATING CURVED FLASHING SECTIONS.

FABRICATE S.S. FLASHING SECTIONS IN 4'-0" MINIMUM SECTIONS.

1.

2.

NO SCALE

FLASHING HEIGHT TO

MATCH EXST, OR A S REQ'D TO

LAP ROOF COATING SYSTEM.

FIELD VERIFY CONDITIONS

PRIOR TO FABRICATION OF

NEW FLASHING

NOTE: NOT SHOWN

CURVED HERE

EXTEND SIKADUR

COMBIFLEX SG

SYSTEM FULL

EXTENT OF

PARAPET

RECONSTRUCTION.

SEAL ALL EDGES w/

MFR. APPROVED

ADHESIVE.

ALSO COORDINATE

WITH 8/S-500

S-500

SETTING PIN COVER DETAIL

SCALE: NONE

CAP STONE STAINLESS STEEL

1/2"Ø x 4"lg S.S. DOWEL w/ 1/8"thk x 2 1/2"o.d. ROUND S.S.

PLATE WASHER WELDED AT

MID-HEIGHT

CMU SUBSTRATE

S.S. THROUGH WALL

FLASHING

M-1 SEALANT

SELF ADHERED

MEMBRANE

RE-USE EXISTING HOLES.

CLEAN OUT EXISTING HOLES

w/ COMPRESSED AIR. RE-DRILL

IF NECESSARY TO REMOVE

REMAINING MORTAR

1/8

EQ TY

P

7"

8"

SELF ADHERED

MEMBRANE

S.S. DOWEL AND

ROUND WASHER

PLAN VIEW

2 1/2"Ø

OUTSIDE

8"x7" SELF-ADHERED MEMBRANE w/ 3/4"Ø

PUNCHED HOLE OVER

DOWEL WASHER

CONTINUOUS

WELD

3/4"Ø HOLE IN

LIMESTONE

M-1 STRUCTURAL

ADHESIVE

INSTALL EXCESS MORTAR

AROUND BASE OF PIN

PRIOR TO SETTING COPING

STONE TO LOCK STONE

INTO PLACE AT BASE

LIMESTONE COPING

TYPICAL CRACK INJECTION DETAIL

SCALE: NONE

5, 5A S-500

REMOVE EXST SEALANT.

SEAL PORTS AND JOINT

WITH SIKADUR 31 HI-MOD

GEL.

EXST CONC

SEPARATION / CRACK

INJECTION

PORTS

INJECT / SEAL PORTS

AND CRACK WITH

MATERIAL NOTED BY

REPAIR TYPE

AFTER INJECTION AND PROPER CURE TIME, REMOVE INJECTION PORTS AND JOINT SEALANT. PREPARE JOINT PER MFR SPECIFICATIONS TO RECIEVE NEW SEALANT.

12"o.c. UNO

5/S-500:

CONCRETE CRACK REPAIR (EPOXY INJECTION):

1. CRACK REPAIR: SIKADUR 35 HI MOD LV (FOR APPLICATION WITH PNEUMATIC

PUMP).

2. SET INJECTION PORTS ALONG THE CRACK AND SEAL PORTS AND CRACK WITH

SIKADUR 31 HI-MOD GEL.

3. WHEN SIKADUR 31 EPOXY SEAL HAS CURED, INJECT SIKADUR 35 HI-MOD LV OR

SIKA CRACK WELD INTO PORTS WITH STEADY PRESSURE. START INJECTION

PROCESS INTO THE FIRST (LOWER) PORT. WHEN RESIN BEGINS TO FLOW FROM

THE ADJACENT PORT, CLOSE OFF THE FIRST PORT AND DISCONNECT THE HOSE.

RECONNECT TO THE SECOND PORT AND INJECT UNTIL RESIN STARTS TO FLOW

FROM THE THIRD PORT. REPEAT THIS PROCESS UNTIL THE WHOLE CRACK HAS

BEEN INJECTED.

4. AFTER THE RESIN HAS BEEN ALLOWED TO CURE, THE INJECTION PORTS AND

CAPSEAL SHOULD BE REMOVED AND ANY HOLES OR VOIDS SHOULD BE FILLED.

5. FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR SURFACE

PREPARATION, PRODUCT MIXING, APPLICATION, CLEAN UP AND CURING.

5A/S-500:

CONCRETE HORIZONTAL COLD JOINT INJECTION (PD-2):

PREPARATION:

MECHANICALLY CLEAN AND REMOVE ALL EXISTING MATERIAL ALONG ENTIRE LENGTH OF

HORIZONTAL CONCRETE COLD JOINT CEE NOTCH.

COLD JOINT INJECTION: SIKAFIX HH HYDROPHILIC, FOR APPLICATION WITH PNEUMATIC

PUMP.

MIXING:

PRIOR TO INSTALLATION THE MATERIAL SHOULD BE AGITATED VIGOROUSLY SHAKING THE 5

GALLON PAIL OR BY MIXING WITH A JIFFY MIXER, BUNG MIXER OR BY HAND.

APPLICATION METHOD / TOOLS:

1. BEGIN BY DRILLING 5/8” DIAMETER HOLES ALONG THE LENGTH OF THE CRACK THROUGH

THE SUBSTRATE. INSTALL INJECTION PACKERS IN THE HOLES AND TIGHTEN. SPACING OF

THE INJECTION PORTS TO BE 12"OC.

2. SEAL CONTINUOUS VEE NOTCH JOINT AND AROUIND INJECTION PORTS WITH SIKADUR 31

HI-MOD GEL. ALLOW TO CURE

3. FLUSH THE DRILLED HOLES WITH WATER TO REMOVE DEBRIS AND DRILL DUST FROM THE

HOLES AND CRACK. THIS WILL ALSO ENSURE THAT THE CRACK IS WET ENOUGH TO

REACT WITH THE GROUT WHEN IT IS INTRODUCED TO THE CRACK. BEGIN THE INJECTION

OF THE GROUT AT THE FIRST PACKER FLUSHED FOR A HORIZONTAL CRACK. DURING THE

INJECTION, THE SIKAFIX® HH HYDROPHILIC WILL DISPLACE WATER FROM THE

CRACK/ADJACENT PORTS. CONTINUE INJECTING UNTIL THE GROUT APPEARS AT THE

ADJACENT PACKER HOLE. STOP PUMPING AND REINSTALL THE PACKER IN THE ADJACENT

HOLE. TIGHTEN THE PACKER AND MOVE THE PUMP HOSE TO THE SECOND PACKER AND

BEGIN INJECTION. CONTINUE THE PROCESS UNTIL 3-4 PACKERS HAVE BEEN GROUTED.

DISCONNECT AND GO BACK TO THE FIRST PACKER AND INJECT ALL THE PORTS FOR THE

SECOND TIME IF NECESSARY. SOME PORTS MAY TAKE ADDITIONAL GROUT, WHICH WILL

FILL UP AND FURTHER DENSIFY THE MATERIAL IN THE CRACK. CONTINUE PROCESS UNTIL

THE LENGTH OF THE PREPARED CRACK IS INJECTED. NOTE: INJECTION PRESSURE WILL

VARY FROM 200 PSI TO 2500 PSI DEPENDING ON THE WIDTH OF THE CRACK, THICKNESS

OF CONCRETE AND CONDITION OF CONCRETE.

4. AFTER THE RESIN HAS BEEN ALLOWED TO CURE, THE INJECTION PORTS AND CAPSEAL

SHOULD BE REMOVED AND ANY HOLES OR VOIDS SHOULD BE FILLED.

5. FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR SURFACE PREPARATION,

PRODUCT MIXING, APPLICATION, CLEAN UP AND CURING.

6. AFTER INJECTION AND PROPER CURE TIME, REMOVE INJECTION PORTS AND JOINT

EPOXY. PREPARE JOINT PER MFR SPECIFICATIONS TO RECEIVE NEW SPECIFIED

SEALANT.

CONSULT AND FOLLOW MANUFACTURER FOR FULL INSTRUCTIONS AND PROCEDURES FOR ALL MATERIALS

THROUGH WALL SCUPPER DETAILS

SCALE: NONE

S-500

THRU WALL SCUPPER BOX DETAIL

3 SIDED FLANGE, INSIDE FACE OF

PARAPET. SET BOTTOM FLUSH TO

TOP OF CONCRETE TANK

TOP OF CONCRETE TANK

INSIDE VERT PARAPET WALL FACE

SLIP FIT OF INTERIOR SCUPPER

SECTION INTO EXTERIOR SECTION.

PROVIDE ADEQUATE URETHANE

CAULK ALL SIDES PRIOR TO SLIP FIT

ASSEMBLY TO ENSURE PERMANENT

WATERTIGHT SEAL

PROVIDE S.S. TAPCON ANCHORS

THRU SCUPPER FLANGES TO

PARAPET

6" (MIN.)

(M

IN

SCUPPER SECTIONS TO BE

CONSTRUCTED FROM 18ga. (MIN)

T304 STAINLESS STEEL.

ALL NON BRAKE BENT CORNERS,

FOLDS OR FLANGES TO BE

CONTINUOUS WELD.

CAULK ALL AROUND

S.S. THRU WALL SCUPPER

BOX. SEE DETAIL BELOW FOR

CONSTRUCTION

MASONRY PARAPET TO BE

RECONSTRUCTED, SEE

ELEVATIONS. FIELD VERIFY

AND MATCH EXISTING BRICK

RECONSTRUCT WALL

OPENING AS REQ'D FOR NEW

THRU WALL SCUPPER BOX AT

EXISTING LOCATION.

SET SCUPPER BOX FLANGE IN

CONTINUOUS BED OF

URETHANE CAULK PRIOR

TO FINAL INSTALLATION

SIKADUR COMBIFLEX SG SYSTEM. SEAL ALL EDGES w/ MFR.

APPROVED ADHESIVE. EXTEND SIKADUR COMBIFLEX SG

SYSTEM FULL EXTENT OF PARAPET RECONSTRUCTION.

CUT SIKADUR

COMBIFLEX 3 SIDES AT

SCUPPER, FOLD / LAP

BOTTOM PORTION INTO

FLOOR OF SCUPPER

BOX.

NEW CURVED S.S. THRU WALL

FLASHING, SEE DETAIL 6/S-500

EXIST COPING CAPS

TO BE RE-SET

NEW SCUPPER

GUTTER BOX AND

DOWNSPOUT

TUCK SCUPPER

GUTTER UNDER

SCUPPER BOX

FLANGE

3" (MIN)

ALL SIDES, TYP

4 SIDED FLANGE, OUTSIDE

FACE OF PARAPET.

SEAL PERIIMETER

VIEWS PROVIDED FOR CONSTRUCTION REFERENCE ONLY, DO NOT SCALE

CONC TANK WALL AND ROOF

TANK ROOF SEALED w/

SIKADUR BROADCAST EPOXY

OVERLAY SYSTEM, FIELD

VERIFY

4"

PERIMETER SEALANT

FL

AS

H

IN

G H

EI

G

H T

TO

M

AT

C

H E

XS

T, O R

A S

R

EQ

'D

TO

L

AP

R O

O F

C O

AT

IN

G

SY

ST

EM

. F

IE

LD

V

ER

IF

Y C

O N

D

IT

IO

N

S

PR

IO

R

T O

FA

BR

IC

AT

IO

N

O F

N

EW

FL

AS

H

IN

G

4"

EXTEND SIKADUR

COMBIFLEX 8" MIN PAST

BRICK RECONSTRUCTION

Scale:

BAR IS ONE (1) INCH LONG

ON ORIGINAL DRAWING

VERIFY SCALE

ISSUE FOR

BID

Job No.

Date:

Sheet:

Drawn: Appd:

N o.

D at e By

D es cr ip tio n

Sheet No:

Drawing Copyright © 2026

One East Broad Street Suite 310

Bethlehem, PA. 18018 610.865.3000

S-500

SECTIONS AND DETAILS

SGY PMG

106246

NOTED

6/26/2026

FA

CA

DE

R

EH

AB

IL

IT

AT

IO

N

PR

IM

AR

Y

AN

D

SE

CO

N

DA

RY

D

IG

ES

TE

R

TA

N

KS

fo r th e

BE

TH

LE

H

EM

W

AS

TE

W

AT

ER

T

RE

AT

M

EN

T

PL

AN

T

SH

IM

ER

SV

IL

LE

R D

BE

TH

LE

H

EM

PA

Sheets and Views
S-001
Sheets and Views
S-100
Sheets and Views
S-101
Sheets and Views
S-102
Sheets and Views
S-103
Sheets and Views
S-104
Sheets and Views
S-500