1-26 02 19 Tooele Co Landfill Water System BID DRAWINGS Approved.pdf
PDF 28 MB Posted
- Solicitation number
- DF26-22
- Issued by
- Tooele County, Utah
About this file
This is a construction bid drawing set for Tooele County, Utah, detailing a maintenance shed and water system project located at 2830 Bauer Road in Tooele, Utah. The project, identified as Project No. 05-24-0105, encompasses the construction of a pre-engineered metal building with concrete foundations, slabs, footings, interior water system infrastructure, site water piping, a 20,000-gallon underground water tank, and associated electrical power work. The building dimensions are 50 feet in nominal width with a 1.0:12 roof slope and 100-foot eave height. The construction set includes comprehensive civil and structural drawings with sixteen sheets covering boundary maps, site plans, grading plans, utility layouts, erosion control measures, civil and structural details, foundation plans, slab plans, and storage area framing specifications. All work shall conform to the 2021 International Building Code, APWA 2025 Standard Drawings and Specifications, and Tooele County Standards and Specifications.
The project specifications establish design criteria including allowable bearing capacity of 4,000 PSF, concrete strength of 4,000 PSI minimum, snow load of 30.1 PSF for flat roofs, basic wind speed of 115 MPH, and seismic design category D. Construction requirements detail concrete reinforcement specifications, anchor bolt installations, utility coordination procedures, erosion control protocols with stormwater pollution prevention measures, and special inspection requirements for concrete construction, soils placement, and adhesive anchors. The contractor assumes full responsibility for job site conditions, safety, utility location verification through Blue Stakes notification, and protection of existing utilities. Record drawings must be provided in electronic and printed formats with survey-grade GPS documentation of utility locations prior to final payment. Concrete exterior surfaces require curing and protective sealers applied within one year of placement, and all sidewalks and flatwork must maintain minimum 2 percent cross slopes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-DF26-22 IFB.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Source: Esri, Vantor, GeoEye, Earthstar Geographics, CNES/Airbus DS, USDA, USGS, AeroGRID, IGN, and the GIS User Community Powered by Esri
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
G
EN
ER
AL
\C -0
C O
VE
R
S H
EE
T.
dw g
- R
EB
EC
C
A.
C
R O
SM
AN
4/
8/
:0
PM
MAINTENANCE SHED & WATER SYSTEM
CONSTRUCTION SET
TOOELE, UT
FA PROJECT NO. 05-24-0105
FEBRUARY 2026
VICINITY MAPPROJECT LOCATION MAP
N.T.S.
LOCATION
PROJECT
N.T.S.
CIVIL & STRUCTURAL SHEET INDEX
PAGE SHEET TITLE
1 G-001 COVER SHEET
2 G-002 LEGEND AND GENERAL NOTES
3 G-003 GENERAL NOTES - CONTINUED
4 C-001 BOUNDARY MAP
5 C-100 SITE PLAN
6 C-200 GRADING PLAN
7 C-300 UTILITY PLAN
8 C-400 EROSION CONTROL PLAN
9 C-500 CIVIL DETAILS
10 C-501 CIVIL DETAILS
11 S-000 STRUCTURAL NOTES
12 S-001 STRUCTURAL NOTES
13 S-100 FOUNDATION PLAN
14 S-101 SLAB PLAN
15 S-102 STORAGE AREA
16 S-500 STRUCTURAL DETAILS
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
NN
Know what's
R
PAYSON
OREM
LEHI
LOGAN
BOUNTIFUL
SALINA
RICHFIELD
ESCALANTE
ARIZONA
36 73
15EUREKAELBERTA
UTAH
LAKE
ST. GEORGE
CEDAR CITY
MODENA
BEAVER
PANGUITCH
KANAB
DELTA
SEVIER
COVE FORT
FILLMORE
HOLDEN
MT. CARMEL JCT.
LONG VALLEY JCT.
JUNCTION
MILFORD
ZION NTL.
PARK
PARK
BRYCE NTL.
LAKE
N
EV
AD
A
TOOELE
SALT
LAKE
CITY
GREAT
SALT
LAKE
WENDOVER
SNOWVILLE
TREMONTON
BRIGHAM
OGDEN
CITY
IDAHO
UTAH
PROVO
SPRINGVILLE
FRUITLAND
DUCHESNE
ROOSEVELT
BLUFF
MONTICELLO
MOAB
HANKSVILLE
GREEN RIVER
PRICE
CANYONLANDS
NATL. PARK
GLEN CANYON NATL.
RECREATION AREA
FREMONT JCT.
CASTLE GATE
C O
LO
R
AD
O
UTAH
STATE OF
VERNAL
HEBER
PARK CITY
EVANSTON
ECHO
LAKE
BEAR
WYOMING
PROJECT AREA
BA
UER
R D
OLD BAUER RD
W BAUER RD
S O
U
TH
HW
Y
SHEET TITLE
1 COVER SHEET
2 ANCHOR BOLT PLAN
3 ANCHOR BOLT REACTIONS
4 RIGID FRAME ELEVATION
5 RIGID FRAME ELEVATION
6 ROOF DRAWING
7 SIDEWALK DRAWING
8 SIDEWALK DRAWING
9 ENDWALL FRAMING
10 ENDWALL FRAMING
11 DETAIL SHEET
12 DETAIL SHEET
13 DETAIL SHEET
CO BUILDING SYSTEMS DRAWINGS
HAL WATER SYSTEM DESIGN DRAWINGS
SHEET TITLE
1 COVER
2 GENERAL NOTES
3 LAYOUT
4 DETAILS 1
5 DETAILS 2
6 DETAILS 3
7 PLAN AN PROFILE
3/18/26 mili.pioquinto Approved
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
LEGEND CIVIL ABBREVIATIONS
CENTER LINE
PROPERTY OR R/W LINE
EASEMENT LINE
FENCE
CONTOUR LINE
SPOT ELEVATION
STORM DRAIN LINE
WATER LINE
TELEPHONE CABLE
ASPHALT PAVING
FIRE HYDRANT
WATER VALVE
WATER METER
STORM DRAIN CATCH BASIN
UTILITY POLE & ANCHOR
STRUCTURE
CURB & GUTTER
SIDEWALK
SIGN
POWER POLE
BOUNDARY BDRY
BEGINNING/BEGINBEG
ALTERNATE ALT
APPROXIMATELY APPROX
ASPHALTASP
4250 4250
EXISTING PROPOSED
L
LT
MAX
MKR
MH
MISC
MON
N
No
OD
PVMT
PL or P
PP
R
RD
REF
REQD
REV
RT
R/W
GRD GROUND
HORIZ HORIZONTAL
HYD HYDRANT
ID INSIDE DIAMETER
IE INVERT ELEVATION
IRR IRRIGATION
INV INVERT
TBC TOP BACK CURB
TEMP TEMPORARY
TEL TELEPHONE/TELEGRAM
TYP TYPICAL
VERT VERTICAL
VOL VOLUME
W WEST/WATER
WM WATER METER
XING CROSSING
XSEC CROSSING SECTION
S SOUTH
SD STORM DRAIN
SEC SECTION
SHT SHEET
SLB&M SALT LAKE BASE & MERIDIAN
SPECS SPECIFICATIONS
SQ SQUARE
SS SANITARY SEWER
ST STREET
STA STATION
STD STANDARD
RIGHT OF WAY
RIGHT/ROUTE
REVISION
REQUIRED
REFERENCE
ROAD
RANGE/RADIUS
POWER POLE
PROPERTY LINE
PAVEMENT
OUTSIDE DIAMETER
NUMBER
NORTH
MONUMENT
MISCELLANEOUS
MANHOLE
MARKER
MAXIMUM
LEFT
LENGTH
BKFL BACKFILL
GASG
BLDG BUILDING
BM BENCH MARK
BOT BOTTOM
BTWN BETWEEN
CB CATCH BASIN
C&G CURB AND GUTTER
CONC CONCRETE
CONST CONSTRUCT
COR CORNER
CEN CENTER
CU CUBIC
° DEGREE
DET DETAIL
DIA DIAMETER
E EAST
ELEV ELEVATION
ELEC ELECTRIC/ELECTRICAL
EOA EDGE OF ASPHALT
EST ESTIMATE
EXIST EXISTING
FEN FENCE
FL OR F FLOW LINE
FT FEET
IRRIGATION LINE
TH TEST HOLE
TOC TOP OF CONCRETE
C or CL CENTERLINE/CONTROL LINEL
L
FG FINISH GRADE
DRIVEWAY DRWY
EXISTING GROUNDEG
EQUIPMENT EQUIP
EXCAVATION EXC
GAS VALVE GV
JB JUNCTION BOX
NTS NOT TO SCALE
N/A NO ACCESS or NOT APPLICABLE
NIC NOT IN CONTRACT
L
WV WATER VALVE
YARDYd
@ AT
& AND
Ø ROUND or DIAMETER
W/ WITH
W/O WITHOUT
BW BACK OF WALK
LINEAR FEETLF
% PERCENT
MATCH LINE
EL=4354.63 EL=4354.66
OVERHEAD ELECTRIC
H
Y DH
Y D
GASGAS
WM WM
WV WV
DSTORM DRAIN MANHOLE D
SANITARY SEWER LINE
SANITARY SEWER CLEANOUT
SANITARY SEWER MANHOLE SS
CO CO
GAS VALVE
TELEPHONE BOX T T
P P
STREET LIGHT
LANDSCAPING (TREES ETC.)
HATCHING/PATTERNS
CONCRETE
ASPHALT PAVEMENT
SAND
UNDISTURBED SOIL
UNTREATED BASE COURSE
GRAVEL
DEMOLITION AREA
BACKFILL
REVISION TRIANGLE
DETAIL CALLOUT
KEYNOTE CALLOUT
DETAIL NAME
DETAIL #
KEYNOTE REFERENCEREVISION NO.
GENERAL CALLOUT PROPOSED CALLOUT
GENERAL NOTE CONSTRUCTION NOTE
1 ABC
SHEET NO.
SPEC # 00 00 00 1SCALE: N.T.S.
DETAIL NAME
DETAIL #
DETAIL NAME/
DESCRIPTION
ANNOTATION
SPECIFICATION NO.SCALE
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
G
EN
ER
AL
\C -0
LE
G
EN
D
A N
D N
O
TE
S.
dw g
4/ 8/
:0
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
2 OF 16MAR 2026
G-002 05-24-0105
LEGEND AND GENERAL NOTES
MAINTENANCE SHED & WATER SYSTEM3/18/26
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
UTILITY NOTES
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
G
EN
ER
AL
\C -0
LE
G
EN
D
A N
D N
O
TE
S.
dw g
4/ 8/
:0
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
3 OF 16MAR 2026
G-003 05-24-0105
GENERAL NOTES - CONTINUED
MAINTENANCE SHED & WATER SYSTEM
1. VERIFY DEPTH AND LOCATION OF ALL EXISTING UTILITIES PRIOR TO CONSTRUCTING ANY NEW UTILITY LINES. NOTIFY OWNER AND CIVIL ENGINEER OF ANY
DISCREPENCIES OR CONFLICTS PRIOR TO ANY CONNECTIONS BEING MADE.
2. ALL PIPING TO BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. REFER TO SPECIFICATIONS FOR MORE DETAILED INFORMATION.
3. ALL UTILITY WORK SHALL BE DONE IN ACCORDANCE WITH UTILITY OWNER'S SPECIFICATIONS. CONTRACTOR SHALL COORDINATE ALL SUCH WORK WITH UTILITY
OWNER.
4. CONTRACTOR SHALL NOT ALLOW ANY GROUNDWATER OR DEBRIS TO ENTER NEW PIPES DURING CONSTRUCTION.
5. CONTRACTOR SHALL PROVIDE DEWATERING OF GROUNDWATER. PROVIDE TRENCH SHORING AS NECESSARY.
GENERAL NOTES
1. CUT AND FILL SLOPES SHALL BE NO STEEPER THAN 3:1 HORIZONTAL TO VERTICAL.
2. AREAS TO RECEIVE FILL SHALL BE PROPERLY PREPARED AND APPROVED BY THE INSPECTOR PRIOR TO PLACING FILL.
3. FILLS SHALL BE BENCHED INTO COMPETENT MATERIAL AS PER THE SPECIFICATIONS.
4. THE CONTRACTOR SHALL COORDINATE INSPECTIONS & TESTING, AND SUBMIT A COMPLETE REPORT AND MAP UPON COMPLETION OF THE ROUGH GRADING. THE REPORT
AND MAP SHALL SHOW AREAS WHERE COMPACTION TESTS HAVE BEEN TAKEN, AND COMPACTION RESULTS.
5. DUST SHALL BE CONTROLLED BY WATERING. DO NOT OVER WATER OR SOFTEN THE SUBGRADE OR CAUSE EROSION DUE TO WATERING.
6. THE LOCATION AND PROTECTION OF ALL UTILITIES IS THE RESPONSIBILITY OF THE CONTRACTOR.
7. APPROVED PROTECTIVE MEASURES AND TEMPORARY DRAINAGE PROVISION MUST BE USED TO PROTECT ADJOINING DRAINAGE AREAS DURING THE CONSTRUCTION OF
THE PROJECT.
8. ALL PUBLIC ROADS MUST BE CLEANED DAILY OF ALL DIRT, MUD, AND DEBRIS DEPOSITED AS A RESULT OF THE CONSTRUCTION. THE CLEANING IS TO BE DONE TO THE
SATISFACTION OF THE PROJECT MANAGER, OWNER, AND COUNTY.
9. THE SITE SHALL BE CLEARED OF ALL VEGETATION AND DELETERIOUS MATER PRIOR TO BEGINNING THE GRADING OPERATION.
10. THE CONTRACTOR SHALL PROVIDE SHORING IN ACCORDANCE WITH OSHA REQUIREMENTS FOR TRENCH WALLS.
11. AGGREGATE BASE AND SUBGRADE SHALL BE COMPACTED AND PREPARED IN ACCORDANCE WITH THE GEOTECHNICAL REPORT FOR THIS PROJECT.
12. EROSION CONTROL: PROTECT ALL INLET BOXES, CATCH BASINS, STORM DRAIN MANHOLES, DRAINAGE DITCHES, AND WATERWAYS WITH APPROVED SWPPP PROTECTION
TO STRAIN THE STORM WATER DURING CONSTRUCTION. PROTECT ALSO FROM ILLICIT DISCHARGES. PROTECT SURROUNDING PROPERTIES AND STREETS FROM SITE
RUNOFF WITH SANDBAGS, EARTH BERMS, AND SILT FENCES. REFER TO THE SWPPP PLAN FOR ADDTIONAL INFORMATION.
SITE NOTES GRADING NOTES
1. ANY MODIFICATION TO THIS CONSTRUCTION PACKAGE SHALL BE APPROVED BY THE ENGINEER. PRIOR TO SAID APPROVAL, ALL IMPROVEMENT DRAWINGS SHALL BE
UPDATED AT THE CONTRACTOR'S EXPENSE, RESUBMITTED, AND APPROVED BY THE ENGINEER UNLESS NOTED OTHERWISE.
2. ALL WORK SHALL BE IN ACCORDANCE WITH APWA 2025 STANDARD DRAWINGS AND SPECIFICATIONS AND TOOELE COUNTY STANDARDS AND SPECIFICATIONS. IN THE
EVENT OF A CONFLICT, THE MOST STRINGENT SPECIFICATION WILL APPLY.
3. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY: THAT THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS;
AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD THE OWNER, AND ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED, ON
CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE OWNER, ARCHITECT, OR ENGINEER.
4. ALL SIDEWALKS AND BACK OF CURB SHALL BE GRADED AT 2% CROSS SLOPE OR LESS.
5. SITE CONCRETE SHALL BE 4000 PSI OR GREATER. ALL EXTERIOR CONCRETE WITH OR WITHOUT REINFORCEMENT SHALL HAVE FIBER MESH IN THE CONCRETE MIX.
SIDEWALKS AND CURB & GUTTER SHALL INCLUDE 0.5 LBS/CY OF MICRO FIBER. SLABS, PADS, AND RETAINING WALLS SHALL INCLUDE 3 LBS/CY OF MICRO FIBER.
6. PROOF ROLL SUBGRADE MATERIAL WITH FULLY LOADED WATER TRUCK OR OTHER SIMILARLY LOADED VEHICLE TO FIND SOFT SPOTS. PROOF ROLLING IS
CONSIDERED INCIDENTAL TO THE CONSTRUCTION AND NO ADDITIONAL PAYMENT FOR PROOF ROLLING WILL BE PAID TO THE CONTRACTOR. REMOVE AND REPLACE
SOFT SPOTS TO NOT LESS THAN 12-INCHES BELOW SUBGRADE OR DEEPER AS DIRECTED BY THE OWNER AND AS SPECIFIED IN THE SPECIFICATIONS. REPLACE SOFT
SPOTS WITH GRANULAR FILL, COMPACTED TO NOT LESS THAN 95% OF MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D 1557. SOFT SPOT REMOVAL WILL BE PAID
ACCORDING TO THE SPECIFICATIONS.
7. COMPACT ROAD BASE TO NO LESS THAN 95% OF MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D 1557.
8. UTILITIES SHOWN ON THE PROJECT PLANS ARE APPROXIMATE. CONTRACTOR SHALL NOTIFY BLUE STAKES 48 HOURS IN ADVANCE OF ANY CONSTRUCTION.
CONTRACTOR SHALL FIELD VERIFY ALL UTILITY LOCATIONS PRIOR TO CONSTRUCTION.
9. THE CONTRACTOR SHALL LOCATE, RETAIN AND PROTECT ALL EXISTING UTILITIES UNLESS OTHERWISE DIRECTED BY THE OWNER AND AS SHOWN ON THE PROJECT
PLANS. CONTRACTOR SHALL NOTIFY ENGINEER OF ALL UTILITY CONFLICTS UPON DISCOVERY.
10. CONTRACTOR IS RESPONSIBLE FOR REPAIR OR REPLACEMENTS OF ANY DAMAGE TO ADJACENT SURFACE IMPROVEMENTS IMPACTED BY CONSTRUCTION.
11. RECORD DRAWINGS ARE TO BE PROVIDED TO THE OWNER IN ELECTRONIC AND PRINTED FORMATS PRIOR TO FINAL PAYMENT. AS PART OF THE RECORD DRAWINGS, THE CONTRACTOR SHALL USE A SURVEY GRADE GPS DEVICE TO RECORD THE LOCATION OF DISCOVERED AND INSTALLED UTILITY LINES. THE SURVEY SHALL BE
PERFORMED AS LINES ARE FOUND AND LINES ARE INSTALLED AND SHALL BE DONE PRIOR TO THE LINE BEING COVERED. LINE NOT MEASURED WILL BE UNCOVERED, RE-BACKFILLED, AND RE-PAVED BY THE CONTRACTOR AT NO ADDITIONAL EXPENSE TO THE OWNER.
12. CONTRACTOR SHALL OBTAIN ALL PERMITS NECESSARY FOR CONSTRUCTION FROM CITY, COUNTY, STATE, AND OR FEDERAL AGENCIES AS REQUIRED.
13. ALL SIDEWALK SHALL BE GRADED AT 2% CROSS SLOPE OR LESS.
14. ASPHALT PAVING SHALL BE A MINIMUM OF 4-INCHES THICK. IF THICKER, THE PAVING SHALL BE DONE IN LIFTS OF UP TO 3-INCHES THICK AND AT LEAST 1.5" THICK
3/18/26
S
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
C
IV
IL
\C
-0
BO
U N
D
AR
Y M
AP
.d w g
4/
8/
:0
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
4 OF 16MAR 2026
C-001 05-24-0105
BOUNDARY MAP
MAINTENANCE SHED & WATER SYSTEM
N
279.9'
935.8'
3.5
7.7
PROPOSED BUILDING
PARCEL 06-017-C-9301
PARCEL
06-017-C-9302
PROPERTY LINE
MONUMENT FOUND
X: 54330.82 Y: 49641.26
MONUMENT FOUND
X: 54294.41 Y: 49571.44
MONUMENT FOUND
X: 54241.87 Y: 49577.97
MONUMENT FOUND
X: 52394.45 Y: 46599.76
MONUMENT FOUND
X: 52226.06 Y: 46555.50
3/18/26
15'TYP.
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
C
IV
IL
\C
-1
SI
TE
P
LA
N
.d w g
4/ 8/
:0
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
5 OF 16MAR 2026
C-100 05-24-0105
SITE PLAN
MAINTENANCE SHED & WATER SYSTEM
N
GRAPHIC SCALE
Scale: 1"=10'
30'20'10'5'0'
019BOLLARD TYP.
18' TYP.
8'
TY
P.
002 CONCRETE FLATWORK
5' TYP.
5'
TY
P.
004CONCRETE BAY APRON
004 CONCRETE BAY APRON
DIRECT ROOF DRAIN
DOWNSPOUTS TO
CONCRETE PAD
002CONCRETE FLATWORK
001GRAVEL SURFACE
001GRAVEL SURFACE
CONTRACTION JOINTS A
MINIMUM OF EVERY 6'
EXIS
TI
NG T
RANSFE
R S
TA
TI
ON
EQUIPMENT PAD. SEE
SHEET S-100 FOR
DIMENSIONS AND UTILITY
PENETRATION LOCATIONS.
50.7'
BOLLARDS PER S-100
5' 5'
7' 3.5'
3/18/26
S
D
D
WATER @ 4963.2
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
C
IV
IL
\C
-3
Er os io n C on tro l P la n.
dw g
4/ 8/
:1
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
8 OF 16MAR 2026
C-400 05-24-0105
EROSION CONTROL PLAN
MAINTENANCE SHED & WATER SYSTEM
N
GRAPHIC SCALE
Scale: 1"=10'
30'20'10'5'0'
TRACK OUT PAD PER
APWA PLAN 126
CONSTRUCTION ENTRANCE
3/18/26
1.5 INCH MINUS CRUSHED ROCK
COMPACT EXISTING SURFACE
PRIOR TO PLACING ROCK
SEE SITE PLAN FOR DIMENSIONS
5"
GRAVEL SURFACE
SCALE: N.T.S.
SANITARY SEWER MANHOLE
SCALE: N.T.S. SPEC # 03 70 00
2% MIN.
SLOPE
SEWER
MANHOLE RING AND COVER, D&L SUPPLY
MODEL A-1181 OR EQUAL, LID TO BE
NON-VENTED, LOW PROFILE WAFFLE
PATTERN COVER MARKED "SEWER"
PROVIDE POLY COATED STEEL MANHOLE
STEPS AT 12" O.C., SIMILAR TO AMCOR MODEL
HW1500.
VARIES FOR MANHOLES DESIGNATED AS A 5' OR
6' DIA. MANHOLE AND DEEPER THAN 16', STEPS
SHALL BE INSTALLED AT 16" O.C. AND SHALL
CONFORM TO ASTM C478
RUBBER BOOTED CONNECTORS TYPICAL FOR
PIPE CONNECTIONS, KOR-N-SEAL OR EQUAL
SEWER PIPING, SIZE
AS SHOWN ON PLANS
PRECAST CONCRETE MONOLITHIC
BASE, MINIMUM 4" THICK
PIPE
6" MIN. CONSOLIDATED GRAVEL
(1" MINUS)
PRECAST CONCRETE
MANHOLE, SIZE AS
SHOWN ON PLANS
ECCENTRIC CONE OPENING
ALIGNMENT, WHERE
APPLICABLE
SEAL FRAME TO CONE OR GRADE RINGS W/
HEATED MASTIC
MIN. 1 - 4" GRADE RINGS
MAX. 2 - 6" GRADE RINGS
ALLOWED FOR RIM ELEVATION ADJUSTMENT,
SEAL JOINTS WITH HEATED BITUMEN
SEALANT
GASKETED MANHOLE JOINTS
PRECAST CONCRETE MANHOLE
WALL SECTION
NON-SHRINK GROUT IN ANNULAR
SPACE BETWEEN MANHOLE, BOOT,
PIPE & BASE SECTION TO PIPE
SPRINGLINE
PRECAST CONCRETE CONCENTRIC MANHOLE
CONE SECTION. PROVIDE ECCENTRIC
MANHOLE CONE SECTION FOR MANHOLES
DESIGNATED ON THE DRAWINGS AS 5' OR 6'
DIAMETER MANHOLE
CONSOLIDATED GRAVEL
FG
6"
3' M
AX
2'-6"
3"
PLAN
A
B
ASECTION
SCALE: N.T.S.
BSECTION
SCALE: N.T.S.
3' SUMP
3' SUMP
TRENCH DRAIN
SCALE: N.T.S. SPEC # 33 02 01
TRENCH DRAIN SHALL BE ZURN MODEL Z-806
OR APPROVED EQUAL, ALL FIBERGLASS
CONSTRUCTION WITH FIBERGLASS GRATE
FINISHED FLOOR SLOPED
PER DRAINAGE PLAN
SET TOP OF TRENCH DRAIN
1/2" BELOW FINISHED FLOOR.
SLOPE FLOOR APPROXIMATELY
24"Ø AROUND TRENCH DRAIN
BOTTOM OUTLET
FLEXIBLE PIPE CONNECTION
FERNCO HD-4000 OR APPROVED EQUAL
2" VENT PIPE
2" 90° ELBOW
"P" TRAP
PIPE SIZE AS
SHOWN ON PLANS
TEE
CONCRETE FLATWORK
SCALE: N.T.S.
2% SLOPE AWAY FROM BUILDING
TOOLED
EDGE
VARIES - SEE SITE PLAN
4" 6"
4,000 PSI CONCRETE
UNTREATED BASE
COURSE
CONCRETE BAY APRON
SCALE: N.T.S.
2% SLOPE AWAY FROM BUILDING
TOOLED
EDGE
VARIES - SEE SITE PLAN
6" 6"
4,000 PSI CONCRETE
UNTREATED BASE
COURSE
PIPE & ENCASEMENT
UNDER STRUCTURE
SCALE: N.T.S. SPEC # 33 02 01
2'-0" TYP
STRUCTURE FOOTING
VA
R
IE
S
℄ PIPE
3" C
LR
3" CLR, TYP.
ALL AROUND
FOR PIPES 6" AND SMALLER
MIN. 3" TYP. CLEAR ALL
AROUND
FOR PIPES LARGER THAN 6"
MIN. 6" TYP. CLEAR ALL
AROUND
NOTE:
FOR PIPES SMALLER THAN 6", NO
ENCASEMENT REINFORCEMENT
REQUIRED
#5 @ 12" O.C.
#5 @ 12" O.C.
(1 AT EA. CORNER MIN.)A
ASECTION
N.T.S.
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
Know what'sbelow.
before you dig.Call
R
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
C
IV
IL
\C
-5
C
IV
IL
D
ET
AI
LS
.d w g
4/ 8/
:1
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
9 OF 16MAR 2026
C-500 05-24-0105
CIVIL DETAILS
MAINTENANCE SHED & WATER SYSTEM3/18/26
PRESSURE GAUGE TYPE 1
SCALE: N.T.S. SPEC # 40 91 20
SCH. 80
STAINLESS
STEEL NIPPLE
(TYP.)
1 1/4"x1" 3000 LB.
STAINLESS
STEEL BUSHING
1-1/4" 3000 LB. F.S. HALF
COUPLING, WELD TO
PIPE, OR 1 1/4" TAPPED
CONNECTION WHERE
CAST IRON.
COAT W/ EPOXY OR
COAL TAR ENAMEL
PIPE ID
STEEL SHELL
1" STAINLESS
STEEL BALL
VALVE
PRESSURE GAUGE (MIN.
3 1/2"Ø, CALIBRATED IN
APPLICABLE UNITS)
3/16"
PIPE PENETRATION TYPE 7
SCALE: N.T.S. SPEC # 33 02 01
POLYURETHANE
SEALANT
3/16
STEEL PIPE SLEEVE, 1/4"
THICK MIN.
1/4" PLATE WALL FLANGE,
MATERIAL SAME AS SLEEVE
3"
1" CLEARANCE
1"
THICKNESS
VARIES
FLOOR SLAB
TYPICAL PIPE TRENCH TYPE 1
SCALE: N.T.S. SPEC # 31 22 22
SLOPE PER O.S.H.A.
REQUIREMENTS
TRENCH ZONE MATERIAL,
SEE SPECIFICATIONS
IDENTIFICATION
TAPE, AS REQUIRED
PIPE ZONE MATERIAL,
SEE SPECIFICATION
MATCH EXISTING MATERIAL,
GRAVEL, TURF, OR EARTH
6" FOR PIPES 12" DIA. OR
SMALLER 12" FOR PIPES,
PIPES OVER 12" DIA.,
TOP AND BOTTOM
PIPE
0.D.+24"
1'-0"
MIN.
VA
R
IE
S
WHERE MULTIPLE
PIPES SEPARATE BY 9"
BURIED VALVE TYPE 1
SCALE: N.T.S. SPEC # 33 04 01
VALVE
8"
PVC SLEEVE TO
ACCOMODATE VALVE BOX
ADJUSTMENT
CLOW F-2450 VALVE
BOX OR APPROVED
EQUAL
CONCRETE RING
2'-0" DIAMETER,
6" THICK WITH
#4 BAR CONTINUOUS
AROUND BOX.
ADJUST TO FINISH
ELEVATION.
TOP OF PAVEMENT OR
GROUND SURFACE
STORM SEWER MANHOLE
SCALE: N.T.S. SPEC # 03 70 00
2% MIN.
SLOPE
SEWER
MANHOLE RING AND COVER, D&L SUPPLY
MODEL A-1181 OR EQUAL, LID TO BE
NON-VENTED, LOW PROFILE WAFFLE
PATTERN COVER MARKED "SEWER"
PROVIDE POLY COATED STEEL MANHOLE
STEPS AT 12" O.C., SIMILAR TO AMCOR MODEL
HW1500.
VARIES FOR MANHOLES DESIGNATED AS A 5' OR
6' DIA. MANHOLE AND DEEPER THAN 16', STEPS
SHALL BE INSTALLED AT 16" O.C. AND SHALL
CONFORM TO ASTM C478
RUBBER BOOTED CONNECTORS TYPICAL FOR
PIPE CONNECTIONS, KOR-N-SEAL OR EQUAL
STORM PIPING, SIZE
AS SHOWN ON PLANS
PRECAST CONCRETE MONOLITHIC
BASE
PIPE
6" MIN. CONSOLIDATED GRAVEL
(1" MINUS)
PRECAST CONCRETE
MANHOLE, SIZE AS
SHOWN ON PLANS
ECCENTRIC CONE OPENING
ALIGNMENT, WHERE
APPLICABLE
SEAL FRAME TO CONE OR GRADE RINGS W/
HEATED MASTIC
MIN. 1 - 4" GRADE RINGS
MAX. 2 - 6" GRADE RINGS
ALLOWED FOR RIM ELEVATION ADJUSTMENT,
SEAL JOINTS WITH HEATED BITUMEN
SEALANT
GASKETED MANHOLE JOINTS
PRECAST CONCRETE MANHOLE
WALL SECTION
NON-SHRINK GROUT IN ANNULAR
SPACE BETWEEN MANHOLE, BOOT,
PIPE & BASE SECTION TO PIPE
SPRINGLINE
PRECAST CONCRETE CONCENTRIC MANHOLE
CONE SECTION. PROVIDE ECCENTRIC
MANHOLE CONE SECTION FOR MANHOLES
DESIGNATED ON THE DRAWINGS AS 5' OR 6'
DIAMETER MANHOLE
CONSOLIDATED GRAVEL
FG
6"
3' M
AX
2'-6"
3" 3"
PLAN
A
ASECTION
SCALE: N.T.S.
BSECTION
SCALE: N.T.S.
B
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
Know what'sbelow.
before you dig.Call
R
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
F:
\S
LC
\P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
C
IV
IL
\C
-5
C
IV
IL
D
ET
AI
LS
.d w g
4/ 8/
:0
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
M. STENQUIST
M. STENQUIST
10 OF 16MAR 2026
C-501 05-24-0105
CIVIL DETAILS
MAINTENANCE SHED & WATER SYSTEM3/18/26
1. ALL DESIGN, CONSTRUCTION, AND INSPECTION SHALL BE IN CONFORMANCE WITH THE 2021 INTERNATIONAL
BUILDING CODE (IBC) AND REFERENCED STANDARDS.
2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS AT THE SITE.
3. ALL OMISSIONS OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING WITH ANY
WORK INVOLVED.
4. DRAWINGS INDICATE THE FINISHED PRODUCT. THEY DO NOT INDICATE A METHOD OF CONSTRUCTION.
CONTRACTOR SHALL TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE STRUCTURE DURING
CONSTRUCTION. SUCH PRECAUTIONS SHALL INCLUDE, BUT NOT BE LIMITED TO, BRACING, SHORING FOR
CONSTRUCTION EQUIPMENT, ETC..
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COMPENSATING THE OWNER FOR ANY CHANGES MADE AS A RESULT OF A DEVIATION FROM THE CONTRACT DOCUMENTS, FAULTY MATERIALS, OR FAULTY WORKMANSHIP.
6. OPTIONS ARE FOR THE CONTRACTOR'S CONVENIENCE. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL REQUIRED DESIGN CHANGES. COST ASSOCIATED WITH ANY DESIGN WORK INITIATED BY
THE OPTION SHALL BE BORN BY THE CONTRACTOR.
7. CONTRACTOR SHALL BE RESPONSIBLE FOR SAFETY AND PROTECTION WITHIN AND ADJACENT TO THE JOB SITE.
8. TEMPORARY SHORING AND BRACING SHALL BE PROVIDED WHEREVER NECESSARY TO TAKE CARE OF ALL LOADS TO WHICH THE STRUCTURE MAY BE SUBJECTED INCLUDING WIND. SUCH BRACING SHALL BE LEFT IN PLACE AS LONG AS MAY BE REQUIRED FOR SAFETY OR UNTIL ALL THE STRUCTURAL ELEMENTS ARE COMPLETE.
9. DURING AND AFTER CONSTRUCTION THE CONTRACTOR AND/OR OWNER SHALL KEEP LOADS ON THE
STRUCTURE WITHIN THE LIMITS OF THE DESIGN LOADS.
10. THE GENERAL CONTRACTOR SHALL HAVE SHOP DRAWINGS REVIEWED BY THE ENGINEER PRIOR TO
FABRICATION.
11. ALL DETAILS, SECTIONS, AND NOTES ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR SITUATIONS
UNLESS NOTED OR SHOWN OTHERWISE.
12. OBSERVATION VISITS TO THE JOB SITE BY THE OWNER, ENGINEER OR FIELD REPRESENTATIVES OF THE
ENGINEER SHALL NEITHER BE CONSTRUED AS INSPECTION NOR APPROVAL OF CONSTRUCTION.
13. SIZES, LOCATIONS, AND ANCHORAGE'S OF EQUIPMENT SHALL BE VERIFIED IN THE FIELD WITH EQUIPMENT
MANUFACTURERS (SUPPLIERS) PRIOR TO PLACING CONCRETE OR FABRICATING STEEL.
1. FOOTING ELEVATIONS WHERE SHOWN ARE TOP OF FOOTINGS AND PROVIDE MINIMUM COVER FOR FROST
DEPTH. DIFFERENT OR UNUSUAL CONDITIONS SHALL BE REPORTED TO THE ENGINEER.
2. EXTERIOR FOOTINGS SHALL BEAR AT A MINIMUM DEPTH OF 2'-6" BELOW FINISHED EXTERIOR GRADE.
3. NO FOOTINGS SHALL BE PLACED IN WATER OR ON FROZEN GROUND.
4. ANY SOIL CONDITION ENCOUNTERED DURING EXCAVATION THAT IS CONTRARY TO THE CONDITIONS USED FOR DESIGN OF FOOTINGS AS OUTLINED IN THE GEOTECHNICAL REPORT, OR ON THE DRAWINGS SHALL BE
BROUGHT TO THE ATTENTION OF THE ENGINEER BEFORE PROCEEDING.
5. WHERE 6" DIAMETER OR LARGER PIPE PASSES THROUGH AN INTERIOR OR EXTERIOR FOUNDATION WALL, STEP THE FOOTING DOWN TO PASS BELOW PIPE AND THEN STEP BACK UP TO INDICATED ELEVATION.
PROVIDE PIPE SLEEVE THROUGH FOUNDATION WALL. PLACE BOTTOM OF PIPE SLEEVE 12" ABOVE TOP OF
FOOTING.
6. PLACE GRANULAR STRUCTURAL FILL AND/OR AGGREGATE BASE COURSE AS REQUIRED BY THE GEOTECHNICAL REPORT IN MAXIMUM 8-INCH-THICK LOOSE LIFTS AND COMPACT FILLS TO 95% COMPACTION
TO ASTM D1557 (MODIFIED PROCTOR).
7. SHALLOW FOUNDATIONS SHALL BE PLACED ON UNDISTURBED NATIVE SOILS WHEN APPROVED BY THE GEOTECHNICAL ENGINEER. SEE RECOMMENDATIONS IN THE GEOTECHNICAL REPORT #26000121.001A BY KLEINFELDER DATED MAY 9, 2025. THE CONTRACTOR IS RESPONSIBLE FOR THE SUBGRADE PREPARATION
FOR STRUCTURES.
8. ALLOWABLE BEARING CAPACITY = 4000 PSF
1. ALL CONCRETE SHALL MEET THE REQUIREMENTS OF ACI-301, “SPECIFICATION FOR STRUCTURAL CONCRETE FOR BUILDINGS.” PROPORTIONING OF INGREDIENTS FOR EACH CONCRETE MIX SHALL BE BY METHOD 2 OR THE ALTERNATE PROCEDURE GIVEN IN ACI-301. PLACE CONCRETE PER ACI-304 AND CONFORM TO ACI-604 (306) FOR COLD WEATHER PLACEMENT AND ACI-605 (305) FOR HOT WEATHER PLACEMENT, USE INTERIOR MECHANICAL VIBRATORS WITH 7,000 RPM MINIMUM FREQUENCY. DO NOT OVER-VIBRATE. CONCRETE SHALL BE PLACED MONOLITHICALLY BETWEEN CONSTRUCTION AND CONTROL JOINTS. PROTECT ALL CONCRETE FROM PREMATURE
DRYING, EXCESSIVE HOT OR COLD TEMPERATURE FOR SEVEN DAYS AFTER PLACING.
2. STRENGTH
TWENTY-EIGHT DAY COMPRESSIVE STRENGTH SHALL BE: 4000 PSI
SLUMP: 4” + 1 INCH.
MAX. WATER/CEMENT RATIO: 0.45
3. STRUCTURAL CONCRETE EXPOSURE CLASS: S0
4. MATERIALS
CEMENT: ASTM C150, TYPE I OR ASTM C595 TYPE IL.
COARSE AND FINE AGGREGATE: ASTM C33.
WATER SHALL BE CLEAN AND POTABLE.
5. ADMIXTURES
WATER REDUCING ADMIXTURE: ASTM C494, ADMIXTURES SHALL BE USED IN EXACT ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
SYNERGIZED PERFORMANCE SYSTEMS: CONCRETE USING ADMIXTURES TO PRODUCE FLOWABLE CONCRETE
MAY BE USED SUBJECT TO ENGINEER'S APPROVAL.
6. AIR ENTRAINMENT:ASTM C260 AND ASTM C494, ENTRAIN 6% PLUS/MINUS 1 1/2% BY VOLUME IN ALL CONCRETE
EXPOSED TO THE EXTERIOR ENVIRONMENT.
7. NO OTHER ADMIXTURE PERMITTED UNLESS APPROVED BY THE ENGINEER OF RECORD.
8. THE FLATNESS AND LEVELNESS OF CONCRETE FLOORS SHALL BE MEASURED WITHIN 48 HOURS OF FINISHING PER ASTM E 1155: STANDARD TEST METHOD FOR DETERMINING FLOOR FLATNESS AND LEVELNESS USING THE
F-NUMBER SYSTEM.
GENERAL:
SPECIFIED OVERALL F-NUMBER FF 25/FL 20
MINIMUM LOCAL F-NUMBER FF 15/FL 12
9. A STATEMENT OF MIX DESIGN FOR ALL CONCRETE SHALL BE SUBMITTED TO AND REVIEWED BY THE ENGINEER
PRIOR TO COMMENCING WORK.
10. ALL CONCRETE WORK SHALL BE PLACED, CURED, STRIPPED, AND PROTECTED AS DIRECTED BY THE
SPECIFICATIONS AND ACI STANDARDS AND PRACTICES.
11. DOWEL VERTICAL BARS THE DEVELOPMENT LENGTH INTO STRUCTURE ABOVE AND FOOTINGS BELOW. PROVIDE 90 DEGREE HOOK WHERE DEVELOPMENT LENGTH IS NOT POSSIBLE. LAP ALL REINF. IN CONCRETE THE LISTED
LENGTH U.N.O.
12. BEFORE CONCRETE IS POURED CHECK WITH ALL TRADES TO ENSURE PROPER PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, ETC. RELATIVE TO WORK.
13. REFER TO DRAWINGS FOR TYPICAL CONSTRUCTION JOINT DETAILS. UNLESS NOTED IN DRAWINGS, ALL
REINFORCEMENT SHALL BE CONTINUOUS THROUGH JOINTS UNLESS NOTED OTHERWISE.
14. WHERE EXTERIOR SLABS ON GRADE ABUT FOUNDATIONS OR COLUMNS PROVIDE 3/8" PREFORMED EXPANSION
JOINT WITH SEALANT.
15. CONTRACTOR TO SEAL ALL EXTERIOR SLAB CONCRETE WITH CURING AND PROTECTIVE SEALERS. CURING SEALER SHALL BE USED UPON COMPLETION OF CONCRETE PLACEMENT. A SILANE 40 OR APPROVED EQUAL PROTECTIVE SEALER SHALL ALSO BE APPLIED TO ALL FINISHED CONCRETE WITHIN A YEAR OF PLACEMENT.
CONTRACTOR TO COORDINATE WITH THE PROJECT ENGINEER TO ENSURE THAT ADEQUATE TIME HAS BEEN ALLOWED FOR CURING SEALER TO WEAR OFF BEFORE THE PROTECTIVE SEALER SHALL BE APPLIED
1. ALL REINFORCEMENT SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH MNL-66(20): ACI DETAILING
MANUAL - 2004.
2. REINFORCING STEEL SHALL BE ASTM A615 GRADE 60. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A1064.
3. ALL REINFORCEMENT SHALL BE SECURELY TIED AND HELD IN PLACE.
4. REINFORCING BARS THAT ARE TO BE WELDED, INCLUDING DEFORMED BAR ANCHORS (D.B.A.) SHALL COMPLY WITH ASTM A706 OR ANOTHER APPROVED WELDABLE GRADE AND SHALL BE WELDED IN ACCORDANCE WITH
THE A.W.S. RECOMMENDATIONS.
5. ALL CONTINUOUS REINFORCEMENT SHALL TERMINATE WITH A 90 DEG. TURN OR A SEPARATE CORNER BAR.
ALL SPLICES IN CONCRETE SHALL LAP THE LISTED LAP LENGTH.
6. THE FOLLOWING CONCRETE COVER SHALL BE PROVIDED FOR REINFORCEMENT:
A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
B. ALL OTHER CONCRETE:2"
7. PRIOR TO FABRICATION AND PLACEMENT, SHOP DRAWINGS FOR ALL REINFORCING STEEL SHALL BE REVIEWED
BY THE ENGINEER.
8. REFER TO WALL CORNER AND WALL INTERSECTION REINFORCING DETAIL. IN GENERAL, THE WALL CORNER REINFORCING SIZES AND SPACING SHALL BE CALLED OUT ON THE PLANS AND REFERENCED TO THESE DETAILS AND THE TYPICAL HORIZONTAL WALL REINFORCING SHALL LAP WITH THE HORIZONTAL REINFORCING.
9. ALL BENDS, UNLESS OTHERWISE SHOWN, SHALL BE A 90 DEGREE STANDARD HOOK. REFER TO STANDARD
CONCRETE HOOK DETAILS.
10. ALL WALL CORNER AND WALL INTERSECTION REINFORCEMENT BARS SHALL BE CONTINUOUS AROUND CORNERS AND THROUGH COLUMNS OR PILASTERS. REINFORCEMENT SHALL BE EXTENDED INTO CONNECTING
WALLS AND LAPPED ON THE OPPOSITE FACE OF THE CONNECTING WALLS.
11. ALL REINFORCEMENT BENDS AND LAPS, UNLESS OTHERWISE NOTED, SHALL SATISFY THE REQUIREMENTS OF THE STD. CONCRETE HOOK SCHEDULE AND THE CONCRETE REINFORCEMENT LAP AND DEVELOPMENT
SCHEDULES.
THE FOLLOWING STRUCTURAL DESIGN LOADS APPLY U.N.O.:
ROOF LIVE LOAD . . . . . . . . . . . . . . . . . . . . . . . . . Lr = 20 PSF
STORAGE ROOM ROOF LIVE LOAD. . . . . . . . . . . L = 125 PSF
STRUCTURE RISK CATEGORY . . . . . . . . . . . . . . II
SNOW LOAD:
GROUND SNOW LOAD. . . . . . . . . . . . . . . . Pg = 35 PSF
SNOW IMPORTANCE FACTOR. . . . . . . . . Is = 1.0 SNOW EXPOSURE FACTOR. . . . . . . . . . . Ce = 1.0 SNOW THERMAL FACTOR . . . . . . . . . . Ct = 1.1 FLAT ROOF SNOW LOAD. . . . . . . . . . . . . Pf = 30.1 PSF SLOPED ROOF SNOW LOAD . . . . . . . . . . Ps = 30.1 PSF
WIND:
BASIC WIND SPEED . . . . . . . . . . . . . . . . . . V = 115 MPH
WIND EXPOSURE. . . . . . . . . . . . . . . . . . . . C
SEISMIC:
SEISMIC IMPORTANCE FACTOR. . . . . . . . . . . . IE = 1.0
SPECTRAL RESPONSE ACCELERATION. . . . . SS = 0.698
SPECTRAL RESPONSE ACCELERATION. . . . . S1 = 0.251
SEISMIC SOIL SITE CLASS . . . . . . . . . . . . . . . . D
SPECTRAL RESPONSE COEFFICIENT . . . . . . SDS = 0.578
SPECTRAL RESPONSE COEFFICIENT . . . . . . SD1 = N/A
SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . D
GENERAL CONCRETE REINFORCING STEEL
FOOTINGS
DESIGN CRITERIA
1. EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL CONSIST OF THE FOLLOWING ANCHOR TYPES AS PROVIDED BY HILTI, INC. CONTACT HILTI AT (800) 879-8000 FOR PRODUCT
RELATED QUESTIONS.
2. REBAR DOWELING INTO CONCRETE
2.1. ADHESIVE ANCHORS FOR CRACKED AND UNCRACKED CONCRETE USE:
2.1.1. HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HOLLOW DRILL BIT AND VACUUM
2.1.2. HILTI HIT-HY 500v3 SAFE SET SYSTEM WITH HILTI HOLLOW DRILL BIT AND VACUUM
2.1.3. HILTI HIT-RE 500v3 SAFE SET SYSTEM WITH HILTI ROUGHENING TOOL IN DIAMOND CORED HOLES
3. ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED BY HILTI OR
OTHER SUCH METHOD AS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. SUBSTITUTION
REQUESTS FOR ALTERNATE PRODUCTS OR DRILLING METHODS MUST BE APPROVED IN WRITING BY THE
STRUCTURAL ENGINEER OF RECORD PRIOR TO USE.
4. USE OF DIAMOND CORE BIT WITH ROUGHENING TOOL FOR ANCHOR HOLES REQUIRES APPROVAL FROM ENGINEER OF RECORD PRIOR TO DRILLING. UNLESS OTHERWISE SHOWN IN THE DRAWINGS, ALL HOLES
SHALL BE DRILLED PERPENDICULAR TO THE CONCRETE SURFACE.
5. INSTALL ANCHORS PER THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, AS INCLUDED IN
THE ANCHOR PACKAGING.
6. THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL ANCHOR PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL PERSONNEL WHO INSTALL ANCHORS
ARE TRAINED PRIOR TO THE COMMENCEMENT OF ANCHOR INSTALLATION.
7. ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF
ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE
CLEARANCES INDICATED ON THE DRAWINGS.
POST-INSTALLED ANCHORS
SHOP DRAWINGS
1. CONCRETE MIX DESIGN
2. CONCRETE REINFORCING STEEL
NON-SHRINK GROUT
1. F'C = 7,000 PSI MINIMUM IN 28 DAYS. FILL UP ENTIRE SPACE AVOIDING AIR POCKETS.
2. GROUT SHALL BE HIGH STRENGTH, NON-METALLIC, NON-SHRINKING SLURRY GROUT.
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
Know what'sbelow.
before you dig.Call
R
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
f:\
SL
C \P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
ST
R
U C
TU
R
AL
\S tru ct ur al p la ns .d w g
4/
8/
:2
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
B. MARSH
K. BENSON
11 OF 16MAR 2026
S-000 05-24-0105
STRUCTURAL NOTES
MAINTENANCE SHED & WATER SYSTEM
1. REFER TO STRUCTURAL DRAWINGS AND SPECIFICATIONS FOR DETAILS, ADDITIONAL NOTES AND
SCHEDULES PERTAINING TO PLYWOOD ROOF.
2. STRUCTURAL FRAMING LUMBER SHALL BE CLEARLY MARKED AND MEET THE FOLLOWING MINIMUM GRADES
AS DEFINED BY THE 2018 EDITION OF THE NATIONAL DESIGN SPECIFICATION:
A. 2" TO 4" THICK
5" AND WIDER: DOUGLAS FIR-LARCH GRADE NO.2
B. LVL: Fb = 2,600 PSI MIN., E=2,000,000 PSI
3. ALL ROOF AND FLOOR JOISTS SHALL BE SUPPORTED LATERALLY AT THE ENDS AND AT EACH SUPPORT BY SOLID BLOCKING 2" THICK AND THE FULL DEPTH OF THE JOIST, EXCEPT WHERE THE END OF THE JOIST IS
ATTACHED TO A HEADER OR BOND BEAM WITH METAL ANCHORS OR HANGERS.
4. ALL NAILS SPECIFIED ON DETAILS OR SCHEDULED SHALL BE COMMON STEEL WIRE NAILS (COATED) UNLESS NOTED OTHERWISE AND SHALL COMPLY WITH REQUIREMENTS OF ASTM F 1667 AND IBC SECTION 2303.6.
MIN. PENETRATION
NAIL SIZE SHANK DIAMETER INTRO SUPPORTED MEMBER
6d 0.113" 1.25" 8d 0.131" 1.50" 10d 0.148" 1.63" 12d 0.148" 1.63" 16d 0.162" 1.75"
5. HOLES FOR NAILS, WHERE NECESSARY TO PREVENT SPLITTING, SHALL BE BORED OF A DIAMETER SMALLER
THAN THAT OF THE NAILS.
6. ALL JOISTS AND BEAM HANGERS, FRAMING ANCHORS, STRAP TIES, AND OTHER METAL FASTENERS FOR
WOOD FRAMING SHALL BE SIMPSON BRAND (OR EQUIV.).
7. UNLESS NOTED OTHERWISE, ANCHOR ALL TRUSSES, RAFTERS AND JOISTS TO SUPPORTS WITH GALVANIZED
FRAMING ANCHORS.
8. UNLESS NOTED OTHERWISE, PROVIDE 2 X CONTINUOUS BLOCKING BETWEEN MAIN MEMBERS AT ALL
RIDGES, HIPS AND VALLEYS.
9. CUTTING AND NOTCHING OF STUDS. IN EXTERIOR WALLS AND BEARING PARTITIONS, ANY WOOD STUD IS PERMITTED TO BE CUT OR NOTCHED TO A DEPTH NOT EXCEEDING 25% OF ITS WIDTH. CUTTING OR NOTCHING OF STUDS TO A DEPTH NOT GREATER THAN 40% OF THE WIDTH IS PERMITTED IN NONBEARING
PARTITIONS SUPPORTING NO LOADS OTHER THAN THE WEIGHT OF THE PARTITION.
10. BORED HOLES IN STUDS. A HOLE NOT GREATER IN DIAMETER THAN 40% OF THE STUD WIDTH IS PERMITTED TO BE BORED IN ANY WOOD STUD. BORED HOLES NOT GREATER THAN 60% OF THE WIDTH OF THE STUD ARE PERMITTED IN NONBEARING PORTIONS OR IN ANY WALL WHERE EACH BORED STUD IS DOUBLED, PROVIDED
NOT MORE THAN TWO SUCH SUCCESSIVE DOUBLED STUDS ARE SO BORED.
11. IN NO CASE SHALL THE EDGE OF THE BORED HOLE BE NEARER THAN 5/8" TO THE EDGE OF THE STUD.
12. NAILING AND CONNECTION SHALL BE IN CONFORMANCE W/ IBC AND AITC. REFER TO IBC 2021, TABLE
2304.10.2 FOR FASTENING SCHEDULE.
13. ALL BOLTS FOR STRUCTURAL WOOD CONNECTIONS SHALL BE ASTM A307 BOLTS.
14. P.T. LUMBER SHALL BE IN CONFORMANCE WITH IBC SECTION 2303.1.9
15. NAILS IN CONTACT WITH P.T. LUMBER SHALL BE STAINLESS STEEL.
16. GLUE-LAMINATED BEAMS SHALL CONFORM TO I.B.C COMBINATION 24F-V4 FOR SIMPLE SPANS, 24F-V8 FOR
MULTIPLE SPANS OR CANTILEVERED BEAMS PER ICBO REPORT 2519 (UNLESS SHOWN OR NOTED
OTHERWISE ON DRAWINGS). LUMBER SHALL BE DOUGLAS FIR 2400 PSI. CAMBER FOR DEAD LOAD AS SHOWN
ON DRAWINGS. WATERPROOF GLUE ALL BEAMS.
17. WOOD SHEATHING SHALL MEET THE RATING REQUIREMENTS OF THE APA FOR EXPOSURE 1 AND SHALL CONFORM TO THE REQUIREMENTS FOR ITS TYPE IN USDOC PC1 OR USDOC PS2. THE PANELS MUST BE IDENTIFIED BY THE TRADEMARKS OF THE APPROVING TESTING AND INSPECTION AGENCY. WOOD SHEATHING SPAN RATINGS FOR THE CORRESPONDING THICKNESS ARE LISTED BELOW. SEE NOTES AND
SCHEDULES FOR SHEATHING THICKNESS REQUIREMENTS.
7/16" THICK - 24/16 SPAN RATING
15/32" THICK - 32/16 SPAN RATING
19/32" THICK - 40/20 SPAN RATING
23/32" THICK - 48/24 SPAN RATING
WOOD FRAMING
3/18/2026
1. SPECIAL INSPECTION SHALL BE PROVIDED ACCORDING TO IBC CHAPTER 17 FOR THE ITEMS IDENTIFIED IN
THIS SECTION AND ON THE CONTRACT DOCUMENTS.
2. THE NAMES AND CREDENTIALS OF SPECIAL INSPECTORS TO BE USED SHALL BE SUBMITTED TO THE
BUILDING DEPARTMENT WHEN APPLYING FOR A BUILDING PERMIT.
3. SPECIAL INSPECTION REPORTS SHALL BE DELIVERED TO THE OWNER BI-WEEKLY OR MORE FREQUENTLY AS
REQUIRED BY THE INSPECTOR OR BUILDING OFFICIAL.
4. OFF-SITE FABRICATION: WHERE FABRICATION OF STRUCTURAL LOAD-BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED ON THE PREMISES OF A FABRICATORS SHOP, SPECIAL INSPECTION OF THE FABRICATED ITEMS SHALL BE IN ACCORDANCE WITH IBC SECTION 1704.2.5 UNLESS THE FABRICATOR IS
APPROVED ACCORDING TO IBC SECTION 1704.2.5.1.
5. CONCRETE CONSTRUCTION: SPECIAL INSPECTIONS AND VERIFICATIONS SHALL BE PROVIDED IN
ACCORDANCE WITH TABLE 1705.3.
8. SOILS: SPECIAL INSPECTION SHALL BE PROVIDED FOR PLACEMENT OF FILL 12 INCHES OR MORE DEEP IN
ACCORDANCE WITH SECTION 1705.6.
9. ADHESIVE ANCHORS: PRIOR TO AND DURING ADHESIVE INJECTION TO ENSURE PROPER INSTALLATION AS PER MANUFACTURERS REQUIREMENTS. CONTRACTOR SHALL REVIEW AND SUBMIT PROPOSED ADHESIVE
MANUFACTURERS ICC OR IAPMO REPORT TO ENGINEER PRIOR TO INSTALLATION.
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A SEISMIC-FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM, OR COMPONENT LISTED IN THE QUALITY ASSURANCE PLAN SHALL SUBMIT A WRITTEN CONTRACTOR'S STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND TO THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT IN ACCORDANCE WITH IBC SECTION 1704.4.
THE CONTRACTOR'S STATEMENT OF RESPONSIBILITY SHALL CONTAIN THE FOLLOWING:
A. ACKNOWLEDGMENT OF AWARENESS OF THE SPECIAL REQUIREMENTS CONTAINED IN THE QUALITY
ASSURANCE PLAN.
B. ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED TO OBTAIN CONFORMANCE WITH THE
CONSTRUCTION DOCUMENTS APPROVED BY THE BUILDING OFFICIAL.
C. PROCEDURES FOR EXERCISING CONTROL WITHIN THE CONTRACTOR'S ORGANIZATION, THE METHOD AND
FREQUENCY OF REPORTING, AND THE DISTRIBUTION OF REPORTS.
D. IDENTIFICATION AND QUALIFICATIONS OF THE PERSON(S) EXERCISING SUCH CONTROL AND THE POSITION(S)
IN THE ORGANIZATION.
QUALITY ASSURANCE
CONTRACTOR RESPONSIBILITY
QUALITY ASSURANCE PLAN
ALL GRADES OF STEEL (MIN. YIELD STRENGTHS)
D = FINISHED INSIDE BEND DIAMETER
d = BAR DIAMETER
D = 6d FOR #3 THROUGH #8 D = 8d FOR #9, #10 AND #11 D = 10d FOR #14 AND #18
RECOMMENDED END HOOKS
BAR
SIZE D
180° HOOKS
A B
90° HOOKS
A
#3 21 4" 5" 3" 6"
#4 3" 6" 4" 8"
NOTES:
1. ALL REINFORCEMENT LAPS, UNLESS OTHERWISE NOTED, SHALL SATISFY THE MINIMUM
REQUIREMENTS SHOWN IN THE TABLE "REINFORCEMENT LAP LENGTHS."
2. TOP BARS SHALL BE DEFINED AS ANY HORIZONTAL BARS PLACED SUCH THAT MORE THAN 12"
OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE BAR, IN ANY SINGLE POUR.
HORIZONTAL WALL BARS ARE CONSIDERED TOP BARS.
CONCRETE REINFORCEMENT LAP & DEVELOPMENT SCHEDULES
NTS
HOOK EMBED
DEPTH
7"
9"
#5 33 4" 7" 5" 10"
#6 41 2" 8" 6" 1'-0"
1'-7"113 4"1'-3"91
2"#9
1'-4"8"11"6"#8
1'-2"7"10"51 4"#7
1'-10"1'-11 4"1'-5"103
4'#10
#11 12" 1'-7" 1'-23 4" 2'-0"
#14 181 4" 2'-3" 1'-93
4" 2'-7"
#18 24" 3'-0" 2'-41 2" 3'-5"
(IN ACCORDANCE WITH ACI 318-14)NTS
STD. CONCRETE HOOK SCHEDULE
12"
14"
23"
21"
18"
26"
31"
41"
16"
NOTE: EMBED BARS WITH HOOKS TO THE DEPTH
SHOWN.
VERIFICATION AND INSPECTION CONTINUOUS DURING
TASK LISTED
PERIODICALLY DURING
TASK LISTED
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY.
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER
MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS.
-- X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND VERIFY THAT SITE
HAS BEEN PREPARED PROPERLY.
-- X
-- X
X --
-- X
TABLE 1705.6 REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC REFERENCED
STANDARD
IBC
REFERENCE
1. INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, AND
VERIFY PLACEMENT.
3. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS.
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS.
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a.
4. VERIFYING USE OF REQUIRED DESIGN MIX.
-- X ACI 318 CH. 20,
25.2, 25.3, 26.6.1-26.6.3
1908.4
--X ACI 318:17.8.2.4 --
-- X ACI 318: CH. 19,
26.4.3, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
5. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH
TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE
TEMPERATURE OF THE CONCRETE.
X -- ASTM C172,
ASTM C31,
ACI 318: 26.4, 26.12
1908.10
6. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES. X -- ACI 318: 26.5
1908.6, 1908.7, 1908.8
7. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES.
-- X ACI 318:
26.5.3-26.5.5 1908.9
8. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED. -- X
ACI 318:
26.11.1.2(b) --
TABLE 1705.3 REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION
2. INSPECT ANCHORS CAST IN CONCRETE.
-- X ACI 318:17.8.2 --
-- X ACI 318: 17.8.2 --
5'-7"5'-1"4'-6"4'-0"3'-6"2'-5"2'-0"1'-7"1'-3"
7'-3"6'-7"5'-10"5'-2"4'-6"3'-1"2'-7"2'-1"1'-7"
#11#10#9#8#7#6#5#4#3
OTHER BAR
TOP BAR
BAR SIZE
REINFORCEMENT LAP LENGTHS
CONCRETE DESIGN STRENGTH - 4000 PSI
EQ EQ
TYPE A
HORZ
REINF
VERT
REINF
TYPE B
E.F. = EACH FACE
O.F. = OUTSIDE FACE (AGAINST SOIL)
I.F. = INSIDE FACE
3L = THREE LAYERS
TYPE C
MARK THICK
CW-1 8"
CONCRETE FOUNDATION WALL SCHEDULE
HORIZONTAL VERTICAL
REINFORCING
#4 @ 12" O.C.
REINFORCING
#4 @ 12" O.C.
PLACEMENT
TYPE A
NOTES:
1. HORIZONTAL WALL REINFORCING SHALL BE CONTINUOUS THRU CONSTRUCTION & CONTROL JOINTS.
2. SPLICES IN HORIZONTAL WALL REINFORCING SHALL BE TYPE Lsb, STAGGERED SUCH THAT SPLICES
DO NOT OVERLAP. SPLICES IN TWO CURTAINS SHALL NOT OCCUR IN THE SAME LOCATION.
PLACEMENT TYPE
HORZ
REINF
VERT
REINF
TYPE D
CONCRETE WALL
WALL CORNERS WALL INTERSECTIONS
M
AXS/
HORIZ CONCRETE
WALL REINF
VERT CONCRETE
WALL REINF
DOWEL W/ ACI
90°HOOK
TYPICAL CONCRETE WALL REINFORCING, CORNERS AND INTERSECTIONS PLAN VIEW
d
B
4d or
2 1/2" MIN
D
HOOK ADETAILING
DIMENSION
180° HOOK
d dA
D
DETAILING
DIMENSION
90° HOOK
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
Know what'sbelow.
before you dig.Call
R
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
f:\
SL
C \P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
ST
R
U C
TU
R
AL
\S tru ct ur al p la ns .d w g
4/
8/
:2
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
B. MARSH
K. BENSON
12 OF 16MAR 2026
S-001 05-24-0105
STRUCTURAL NOTES
MAINTENANCE SHED & WATER SYSTEM
Lsb
Ls b
Ls b
CW-2 6" #4 @ 18" O.C. #4 @ 18" O.C. TYPE A
STRUCTURAL KEY NOTES#
1. RECESS CONCRETE WALL AT HATCHED ENTRY WAY, TYPICAL.
2. FOUNDATION WALL, TYPICAL
3. CONCRETE PIER, TYPICAL
4. CONTINUOUS FOOTING, TYPICAL
5. SPREAD FOOTING, TYPICAL
6. #4 HAIRPIN BAR AROUND ANCHORS EXTEND INTO FLOOR SLAB,
TYP. SEE DETAIL 3/S500
7. STEP IN FOUNDATION WALL
8. CONCRETE SLAB ON GRADE SEE SHEET S101
9. FLOOR DRAIN 1" BELOW FINISHED FLOOR ELEVATION. GRADE
FLOOR IN STORAGE ROOM TO FLOOR DRAIN.
10. TRENCH DRAIN PER 20/S500
11. DROP FOOTING 1'-6" FOR PLUMBING LINE SEE DETAIL 18/S500
12. BOLLARD, SEE DETAIL 19/S500
13. CONCRETE FOUNDATION WALLS ON GRIDS A AND C EXTEND
ABOVE FINISHED FLOOR
14. GRADE BEAM PER 12 AND 14 ON S500
15. FLOOR SLAB RIDGE IS AT GRID 3 AND SLOPES TOWARD TRENCH
DRAINS
16. FOR FRAMED STORAGE SEE SHEET S102
17. 6" HOUSEKEEPING PAD SEE DETAIL 7/S500. MATCH TOP OF CURB
WALL ELEVATION.
18. CURBWALL FOR FRAMED WALL
LEGEND
FOUNDATION WALL
FOOTING
RECESSED WALL
FOUNDATION STEP
s s
FS2.6
AB2
CP1
FS3.6
AB3
CP3
1 2 3 4
C
B
A
'-0
'-0
25'-0" 25'-0" 25'-0" 25'-0"
12 TYP.
FS3.6
AB3
CP3
FS2.9
AB3
CP2
FS4.3
AB1
CP2
FS4.3
AB1
CP1
FS2.0
AB1
CP2
FS2.9
AB3
CP2
FS3.6
AB3
CP3
FS2.0
AB2
CP2
FS3.6
AB3
CP3
TOP OF PIER =
4967.27 TYP.
TOP OF WALL =
4967.27
FINISHED
FLOOR =
4967.27
S
S
S
S
5'-4"
FC
1.
FINISHED FLOOR
= 4967.24
FINISHED FLOOR
= 4967.45
TOP OF WALL
= 4970.27 FC1.6
FC
1.
FC1.6
FC
1.
TOP OF WALL
= 4967.27
FINISHED
FLOOR =
4967.27
FINISHED FLOOR =
4967.24
TOP OF PIER =
4967.27 TYP.
FC1.6
TOP OF WALL
= 4970.27
C W
-1
141414
CW-1
CW-1
C W
-116
4' -0
'-0
4' -0
'-0
AB4
AB4
AB4
AB4
4' -0
'-0
AB4
AB4
FINISHED FLOOR
= 4967.45
FINISHED
FLOOR =
4967.45
FC1.6
FC
1.
CW-2
CW-2
C W
-2C W
-2
36'
3'
6'3'
4'-3"
S
S
S
S11 5'-6" 4'-6"4'-6"
9'-0" 5'-0"
TOP OF WALL
= 4967.95
TOP OF WALL
= 4967.95
SLOPE TO DRAIN SLOPE TO DRAIN
FINISHED FLOOR
= 4967.35
32'-0"
FS2.0
AB2
CP2
FOUNDATION PLAN NOTES:
1. THIS FOUNDATION PLAN IS BASED ON THE COLUMN BASE ANCHOR REACTIONS
FROM CO BUILDING SYSTEMS FOR PROJECT NUMBER: 25104840 STAMPED
JANUARY 20, 2026.
2. VERIFY ALL DIMENSIONS WITH METAL BUILDING SYSTEM.
3. PLACEMENT LOCATION OF ANCHOR RODS SHALL BE IN ACCORDANCE WITH METAL
BUILDING DRAWINGS. ALL METAL BUILDING ANCHORS TO BE PER SCHEDULE
BELOW.
4. FOR REINFORCING SPLICES PROVIDE LAP LENGTHS AS FOUND IN THE
REINFORCING LAP LENGTHS SCHEDULE ON SHEET S001 WALL HORIZONTAL BARS
REQUIRE TOP BAR LAP LENGTHS, SEE SCHEDULE.
5. CENTER FOOTINGS UNDER WALLS AND STEEL COLUMNS. UNO.
S500
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
Know what'sbelow.
before you dig.Call
R
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
SCALE: 3/16"=1'-0"
FOUNDATION PLAN
FOOTING SCHEDULE
FC1.6 1'-6"x12"xCONT, (3) #5 BARS CONT.
FS2.0 2'-0"x2'-0"x1'-0" (3) #4 BARS EACH WAY
FS2.6 2'-6"x2'-6"x1'-0" (4) #4 BARS EACH WAY
FS2.9 2'-9"x2'-9"x1'-0" (4) #4 BARS EACH WAY
FS3.6 3'-6"x3'-6"x1'-0" (3) #5 BARS EACH WAY TOP AND BOTTOM
FS4.3 4'-3"x4'-3"x1'-0" (4) #5 BARS EACH WAY TOP AND BOTTOM
PIER SCHEDULE
CP1 1'-0"x1'-0" (8) #4 VERTICAL BARS, SEE DETAIL 6/S500
CP2 1'-0"x1'-9" (10) #4 VERTICAL BARS, SEE DETAIL 8/S500 AND 10/S500
CP3 1'-6"x2'-0" (12) #4 VERTICAL BARS, SEE DETAIL 9/S500
NOTES:
1. ALL PIERS REQUIRE #3 PIER TIES AT 6" O.C. FULL HEIGHT OF PIER.
2. FOR ADDITIONAL PIER ANCHOR REINFORCING, REFER TO ANCHOR REINFORCING
DETAILS 11,15,16, AND 17 ON S500
ANCHOR BOLT SCHEDULE
MARK ANCHOR SIZE AND EMBEDMENT
AB1 (4) 5/8"Ø W/ 16" EMBEDMENT
AB2 (4) 3/4"Ø W/ 16" EMBEDMENT
AB3 (4) 7/8"Ø W/ 16" EMBEDMENT
AB4 (2) 1/2" Ø W/ 16" EMBED
NOTES:
1. ALL ANCHOR BOLTS ARE ASTM F1554 GRADE 36 ANCHORS W/ 1/4" x 2" x 2" PLATE
BETWEEN (2) HEAVY HEX NUTS TIGHTENED TOGETHER AT EMBEDDED END.
N f:\
SL
C \P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
ST
R
U C
TU
R
AL
\S tru ct ur al p la ns .d w g
4/
8/
:2
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
B. MARSH
K. BENSON
13 OF 16MAR 2026
S-100 05-24-0105
FOUNDATION PLAN
MAINTENANCE SHED & WATER SYSTEM
S500
S500
S500 TYP.
S500 TYP.
S500 TYP.
S500 TYP.
S500 TYP.
S500
10&17 S500
6&16 S500
S500
8&15 S500
8&15 S500
9&11 S500
9&11 S500
9&11 S500
9&11 S50010
S500
S500
S500
S500
LEGEND
FOUNDATION WALL
CONTROL/
CONSTRUCTION JOINT
RECESSED WALL
FOUNDATION STEP
s s
STRUCTURAL KEY NOTES#
1. (2) #4 BARS x 48" TO MITIGATE SLAB CRACKING AS SHOWN
2. CONTROL/CONSTRUCTION JOINTS, TYPICAL
3. RECESS CONCRETE WALL AT HATCHED ENTRY WAY, TYPICAL.
4. TRENCH DRAIN, TYPICAL
5. 6" CONCRETE SLAB ON GRADE W/ #4 BARS AT 18" O.C. EACH WAY
CENTERED IN SLAB.
6. FOR FRAMED STORAGE ROOM SEE SHEET S102
7. HOUSE KEEPING PAD
1 2 3 4
C
B
A
1 TYP.
4 4
N
SLAB PLAN NOTES:
1. THIS SLAB PLAN IS BASED ON THE COLUMN BASE ANCHOR REACTIONS FROM
CO BUILDING SYSTEMS FOR PROJECT NUMBER: 25104840 STAMPED JAN 20,
2026.
2. VERIFY ALL DIMENSIONS WITH METAL BUILDING SYSTEM.
3. FOR REINFORCING SPLICES PROVIDE LAP LENGTHS AS FOUND IN THE
REINFORCING LAP LENGTHS SCHEDULE ON SHEET S001 WALL HORIZONTAL
BARS REQUIRE TOP BAR LAP LENGTHS, SEE SCHEDULE.
4. REFER TO S000 FOR CONCRETE SLAB FLATNESS REQUIREMENTS. REFER TO
ACI 302.1R FOR ADDITIONAL GUIDANCE FOR MEETING FLOOR FLATNESS
REQUIREMENTS.
5. CONTROL JOINTS (CJ) IN THE FLOOR SLAB ARE TO BE PROVIDED AT
COORDINATED EQUAL SPACE INCREMENTS NOT EXCEEDING 14'-0" O.C. SEE
SLAB PLAN FOR APPROXIMATE LOCATIONS. SEE DETAIL 1/S-500
6. DIAMOND-SHAPED DOWEL PLATE CONSTRUCTION JOINTS ARE TO BE
PROVIDED AT COORDINATED EQUAL SPACING INCREMENTS AT THE END OF
EACH SLAB PLACEMENT PERIOD AND SHALL BE ALIGNED WITH CONTROL
JOINTS SHOWN ON THE PLAN. CONTRACTOR SHALL COORDINATE
DIAMOND-SHAPED DOWEL PLATE CONSTRUCTION JOINT LOCATIONS BASED
ON PRACTICAL WORK LOAD PLACEMENT REQUIREMENTS. SEE DETAIL 2/S500
7. PROVIDE 1/2" EXPANSION MATERIAL AT SLAB INTERFACE TO EXTERIOR
CONCRETE WALL AT ALL LOCATIONS.
8. FOR THICKENED SECTIONS OF THE SLAB ON GRADE AND GRADE BEAMS THAT
ARE INTEGRAL WITH THE SLAB ON GRADE SEE SHEET S100
QA
This document or any part thereof in detail or design concept is the property of Forsgren Associates Inc.
and shall not be copied without the written authorization of Forsgren Associates Inc.
APPROVEDNO. REVISIONS
DESIGNED
DRAWN
DATEBY
(IF NOT 2"- SCALE ACCORDINGLY)
AT FULL SIZE
LINE IS 2 INCHES
ATTENTION
PAGE NO:DATE:
SHEET NO:
PROJECT NO:
Know what'sbelow.
before you dig.Call
R
370 EAST 500 SOUTH, STE 200, SALT LAKE CITY, UT 84111
PH: 801.364.4785 FAX: 801.364.4802
AN APEX COMPANY
SCALE: 3/16"=1'-0"
SLAB PLAN
f:\
SL
C \P ro je ct s\
\0 to oe le c ou nt y so lid w as te \C
AD
\S he et s\ m ai nt en an ce s he d\
ST
R
U C
TU
R
AL
\S tru ct ur al p la ns .d w g
4/
8/
:2
PM
CONSTRUCTION SET
T. BROWN
M. STENQUIST
B. MARSH
K. BENSON
14 OF 16MAR 2026
S-101 05-24-0105
SLAB PLAN
MAINTENANCE SHED & WATER SYSTEM
15'-0"
15'-…