1-2026 UCA MODULAR SHELTER RFQ.docx
DOCX document 109 KB Posted
- Solicitation number
- GJ27-8
- Issued by
- Utah
About this file
This is a Request for Quotation (RFQ) issued by the Utah Communications Authority (UCA) for a modular shelter to be constructed at Birch Creek for radio communications purposes. The solicitation seeks qualified contractors to provide design, fabrication, and installation services for a modular radio communications shelter meeting UCA's specifications and requirements. Questions regarding the solicitation must be submitted by August 2, 2026, no later than 3:00 PM Mountain Time via the U3P submission portal. Quotations are due by August 5, 2026, no later than 3:00 PM Mountain Time, also submitted via U3P. The solicitation does not indicate a specific contract award date or contract term length, though vendors should expect evaluation and award decisions to follow standard procurement timelines.
Specific pricing terms, set-aside provisions, funding sources, and budget amounts are not detailed in the available RFQ summary documentation. The Utah Communications Authority is the issuing office and will conduct the procurement independently; this posting serves as a courtesy advertisement only, and the actual contract award will not be posted on the Division of Purchasing website. Interested vendors must review the complete solicitation documents to understand all technical specifications, pricing requirements, insurance obligations, and other compliance requirements necessary to submit a responsive quotation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-UCA Standard Terms and Conditions.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UTAH COMMUNICATIONS AUTHORITY Request for Quotation
REQUEST FOR QUOTATION
Modular Radio Communications Shelter Solicitation Posted via U3P
1. Introduction Utah Communications Authority (UCA) supports public safety communications for Utah’s first responders and citizens. UCA operates and maintains critical radio, microwave, and data infrastructure at remote sites throughout the state.
UCA is soliciting competitive quotes for one (1) modular radio communications shelter for deployment at the Birch Creek radio site, in accordance with the specifications, terms, and conditions set forth in this document. The shelter shall be of two-room modular construction suitable for housing radio equipment and a generator at a remote, unstaffed site. This solicitation is for the shelter and its steel skid as supplied products only. UCA will perform all on-site assembly and installation; no vendor labor is being solicited.
UCA intends to award a purchase agreement to the lowest-priced responsive bidder who demonstrates full compliance with all mandatory requirements.
2. Key Dates & Delivery The following table summarizes the solicitation timeline, delivery information, and shelter configuration. It contains eight rows, each pairing a key date or detail with its value. All times shown are Mountain Daylight Time (MDT).
| KEY DATE / DETAIL |
| VALUE |
| Issue Date |
| July 29, 2026, 3:00 PM MDT |
| Questions Due |
| August 2, 2026, 3:00 PM MDT |
| Quotes Due |
| August 5, 2026, 3:00 PM MDT |
| Required Delivery |
| On or before September 7, 2026 |
| Ship-To Address |
| 31 N Cutler Drive, North Salt Lake, UT 84054 |
| Installation Site |
| Birch Creek |
| Quantity |
| One (1) shelter |
| Configuration |
| Two-room modular shelter |
3. Pricing Offerors shall provide a total quoted price, inclusive of all costs, delivered to the ship-to address identified in Section 2. Quotes may be submitted on the vendor’s own letterhead or quote form, provided they clearly address each of the cost elements listed below.
1. Base price for one (1) complete modular shelter and steel skid meeting the specifications in Section 4
1. Shipping and delivery to 31 N Cutler Drive, North Salt Lake, UT 84054
1. Any additional charges, fees, or surcharges
Pricing that omits any of the elements above, or that bundles costs without sufficient detail for UCA to evaluate them, may be deemed non-responsive.
Note: UCA intends to award to the lowest-priced responsive bidder meeting all mandatory specifications. Partial bids will not be considered.
4. Technical Specifications The shelter must meet all of the minimum mandatory specifications set out in this section. A shelter that does not meet every requirement listed below will be deemed non-responsive. Detailed shelter drawings are provided in Exhibit B, beginning after Section 8.
4.1 Dimensions and Structural Requirements
The table below lists seven mandatory requirements covering overall dimensions, the interior divider wall, and wind, snow, and floor load ratings.
| REQUIREMENT |
| SPECIFICATION |
| Overall Length |
| 23′-1″ |
| Overall Width |
| 11′-1½″ |
| Overall Height |
| 9′-2″ |
| Interior Divider Wall |
| 10′-5¼″ × 8′-6″ |
| Wind Load Rating |
| 115 MPH minimum |
| Snow Load Rating |
| 40 PSF minimum |
| Floor Load Rating |
| 250 PSF minimum |
4.2 Steel Skid Base
The shelter shall be built on a bolt-together steel skid. The table below lists six mandatory requirements covering the skid, its foundation, field assembly, and handling provisions.
| COMPONENT |
| REQUIREMENT |
| Skid Type |
| Bolt-together steel skid; shelter shall be built on the skid |
| Foundation |
| Skid shall be set directly on grade; no concrete foundation or pier system will be provided |
| Assembly |
| Bolt-together design suitable for field assembly on site by UCA personnel |
| Forklift Slots |
| Required |
| Lifting Brackets |
| Required |
| Load Capacity |
| Skid shall support the fully loaded shelter at the floor load rating specified in Section 4.1 |
4.3 Construction Specifications
The table below lists six mandatory requirements covering panel construction, field assembly, and the roofing system.
| COMPONENT |
| REQUIREMENT |
| Panel Type |
| Cam lock style panels |
| Panel Core |
| 4-inch high-density foam insulation |
| Panel Facings |
| 26-gauge steel sheets, both interior and exterior |
| Assembly |
| Field-assembled modular design |
| Roofing Material |
| Single-ply PVC membrane |
| Roofing Warranty |
| 20-year limited warranty required |
4.4 Door Specifications
The table below lists seven mandatory requirements covering the equipment room entrance, the generator room entrance, and door security hardware.
| DOOR / FEATURE |
| REQUIREMENT |
| Equipment Room Entrance — Size |
| 3′-0″ × 6′-8″ |
| Equipment Room Entrance — Configuration |
| Left inswing |
| Equipment Room Entrance — Construction |
| 24-gauge steel with complete frame assembly |
| Generator Room Entrance — Size |
| 4′-0″ × 6′-8″ |
| Generator Room Entrance — Configuration |
| Right outswing |
| Generator Room Entrance — Construction |
| 24-gauge steel with complete frame assembly |
| Door Security Hardware |
| Two (2) deadbolt locks per door; commercial-grade hardware |
4.5 Floor System
The table below lists six mandatory requirements covering floor dimensions, assembly, facings, reinforcement, and finish.
| COMPONENT |
| REQUIREMENT |
| Dimensions |
| 23′-1″ × 11′-1½″ |
| Assembly |
| Locking floor assembly system |
| Exterior Facing |
| 26-gauge steel minimum |
| Interior Facing |
| 20-gauge steel |
| Reinforcement |
| ½″ plywood substrate |
| Finish |
| Cove base molding at all wall intersections |
4.6 Damper Openings
The two square openings shown in the Exhibit B elevation drawings are damper openings, not cable entry ports. They must be framed to receive motorized control dampers. The table below lists five mandatory requirements covering the quantity, size, framing, and intended damper for these openings.
| COMPONENT |
| REQUIREMENT |
| Openings Required |
| Two (2) |
| Opening Size |
| 37″ × 37″ square, each |
| Opening Type |
| Framed openings with weatherproof sealing capability |
| Intended Damper |
| Grainger item 3C131 — Dayton square aluminum motorized control damper, 100–240 VAC, normally open |
| Damper Dimensions |
| 39″ × 39″ overall flanged frame, 13¼″ long; requires a 37″ × 37″ square wall opening |
4.7 Shipping and Documentation
UCA will assemble the shelter on site using its own personnel. The documentation listed below must therefore be complete enough for assembly by UCA staff without vendor support.
Shipping Requirements
1. Shelter shall be shipped disassembled and palletized for transport
1. All components shall be securely wrapped and protected against damage in transit
1. All components shall be clearly identified and labeled Required Documentation
1. Detailed installation instructions
1. Assembly drawings and diagrams
1. Component inventory list
1. Recommended tool list
5. Terms & Conditions Any contract resulting from this solicitation will incorporate the Utah Communications Authority’s Standard Terms and Conditions for Goods and Services (“Standard Terms and Conditions”), a copy of which is attached hereto as Exhibit A.
1. The Authority may refuse to negotiate exceptions and/or additions that are excessive; inconsistent with similar contracts; that compromise warranties, insurance, or indemnification provisions necessary to protect the Authority; where the solicitation specifically prohibits exceptions and/or additions; or that are not in the best interest of the Authority.
1. The Authority reserves the right to negotiate exceptions and/or additions in a manner resulting in expeditious resolution. This process may include beginning negotiations with the Offeror having the fewest exceptions and concluding with the Offeror submitting the greatest number. Contracts may be executed and become effective as negotiations are completed.
1. If negotiations are required, the Offeror must provide all documents in Microsoft Word format for redline editing and must provide the name, contact information, and availability of the person(s) who will be directly involved in legal negotiations.
1. Any mandatory requirement to accept an Offeror’s terms and conditions may result in the proposal being determined non-responsive.
1. An award is subject to successful contract negotiation (if required). The Authority, at its sole discretion, will determine when negotiations become unproductive and may terminate the award to that Offeror and proceed to the next eligible Offeror.
6. Evaluation Criteria Quotes will be evaluated against the following criteria. Total delivered price is the primary factor.
1. Compliance with all mandatory technical specifications in Section 4
1. Total delivered price (primary factor)
1. Demonstrated ability to deliver within the required timeframe
1. Vendor experience and qualifications
7. Submittal Instructions Deadline: All quotes must be received by August 5, 2026, at 3:00 PM MDT.
Quotes must be submitted electronically via U3P and uploaded to the Vendor Attachments section of the solicitation. Each submission must include the following:
1. Company name and address
1. Contact name, phone number, and email address
1. Formal vendor quote addressing every cost element in Section 3
1. Manufacturer, brand, and model number of the shelter proposed
1. Confirmation of compliance with all mandatory technical specifications in Section 4
1. Product data sheets, cut sheets, or shop drawings for the proposed shelter
1. Estimated lead time and delivery schedule
1. Confirmation that the assembly documentation required by Section 4.7 will be provided
Questions: All questions regarding this solicitation must be submitted through U3P and received no later than August 2, 2026, at 3:00 PM MDT. Questions received after that time may not be answered.
8. Attachments The table below lists the two exhibits that accompany this solicitation.
| ATTACHMENT |
| DESCRIPTION |
| Exhibit A |
| UCA Standard Terms and Conditions for Goods and Services (provided separately in U3P) |
| Exhibit B |
| Shelter technical drawings (included in this document, immediately following this section) |
Exhibit B — Shelter Technical Drawings This exhibit contains five technical drawings of the modular radio communications shelter: one floor plan and four elevation views. All dimensions shown on the drawings are nominal and shall be read together with the mandatory specifications in Section 4. Where a drawing and Section 4 conflict, Section 4 governs. The two 37″ × 37″ square openings shown in the elevation drawings are the framed damper openings described in Section 4.6.
Figure 1. Two-Room Shelter Floor Plan The drawing below shows the floor plan of the two-room shelter as viewed from above, with overall dimensions and panel labels.
Figure 1. Two-room shelter floor plan, 23′-1″ × 11′-1½″.
Figure 2. Front Elevation The drawing below shows the front elevation of the shelter, including both entrance doors.
Figure 2. Front elevation showing both entrance doors.
Figure 3. Back Elevation The drawing below shows the back elevation of the shelter, including one of the two damper openings specified in Section 4.6.
Figure 3. Back elevation with a 37″ × 37″ framed damper opening.
Figure 4. Left Elevation The drawing below shows the left end elevation of the shelter, including the second damper opening specified in Section 4.6.
Figure 4. Left elevation with a 37″ × 37″ framed damper opening.
Figure 5. Right Elevation The drawing below shows the right end elevation of the shelter.
Figure 5. Right elevation — plain paneled wall, no openings.