1-2026-11-17 2026-0639 Jessup Township Building Alterations Issued for Bid.pdf
PDF 9 MB Posted
- Attached to
- Jessup Township Building Alterations
- Solicitation number
- US.263394
- Issued by
- Somerset County, Pennsylvania
About this file
This is a set of issued-for-bid construction documents for the Jessup Township Municipal Building Alterations project located at 10175 State Route 706, Montrose, Pennsylvania 18801, in Susquehanna County. The project consists of structural repairs and improvements to the existing wood-framed township building, including temporary bracing, installation of a new steel structural system on a concrete foundation, masonry crack repairs, wood siding repairs and painting, roof and drainage improvements, replacement of an overhead and swinging door, and installation of a new galvanized steel stair and guardrail system. Sealed bids must be submitted by 2:00 PM on Tuesday, December 28, 2026, via PennBid, with bids to be read aloud at the regular scheduled Township Meeting on December 30, 2026. A mandatory pre-bid conference will be held at 9:00 AM on Tuesday, December 8, 2026, at the project site, with attendance required for prospective bidders. Award notification is expected by Wednesday, February 10, 2027. The contract documents include architectural, structural, and as-existing demolition plans and elevations with detailed notes and specifications prepared by JHA Companies (Ryan Lee, RA).
Bid security equal to ten percent of the total bid amount must accompany each bid, in the form of a bid bond naming Jessup Township as obligee or a cashier's check or certified check payable to Jessup Township. Performance and payment bonds in the amount of one hundred percent of the contract amount shall be provided by the successful bidder within fifteen days of notice of award. Prevailing wage rates apply to this project. The bidding documents include comprehensive general project notes, demolition key notes, design load criteria, and detailed specifications for concrete work, structural steel, wood framing, foundation design and construction, site preparation, shoring and bracing, post-installed anchors, and special inspection requirements in accordance with the 2021 International Building Code and applicable standards including ACI, AISC, and AWS specifications. Jessup Township reserves the right to reject any or all bids or parts thereof and to waive any defects or irregularities in the bids.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AERIAL LOCATION MAP
LOCATION MAP
Pennsylvania One Call System, Inc.
CALL BEFORE YOU DIG!
a.
b.
c.
Pennsylvania Law Requires:
3 working days for construction phase 10 working days in design state Stop Call
GENERAL PROJECT NOTES:
1.1.
2.2.
3.3.
4.4.
5.5.
6.6.
7.7.
8.8.
9.9.
All codes having jurisdiction shall be observed strictly in the construction of the project, including all applicable All codes having jurisdiction shall be observed strictly in the construction of the project, including all applicable township and state, zoning, building codes. contractor to verify all codes before commencing construction and township and state, zoning, building codes. contractor to verify all codes before commencing construction and bring all discrepancies between code requirements and the contract documents to the attention of the bring all discrepancies between code requirements and the contract documents to the attention of the Architect / Engineer.Architect / Engineer.
The contractor shall verify and protect all service and utility lines and existing site area from deterioration or The contractor shall verify and protect all service and utility lines and existing site area from deterioration or damage.damage.
The Architect / Engineer shall not be responsible for the safety and construction, procedures, techniques, or The Architect / Engineer shall not be responsible for the safety and construction, procedures, techniques, or the failure of the builder to carry out the work in accordance with the drawings, specifications, or required the failure of the builder to carry out the work in accordance with the drawings, specifications, or required codes, including all OSHA regulations.codes, including all OSHA regulations.
Contractor shall bring errors and omissions, which may occur, in the Contract Documents to the attention of Contractor shall bring errors and omissions, which may occur, in the Contract Documents to the attention of the Architect / Engineer and Owner in writing and written instructions shall be obtained before proceeding with the Architect / Engineer and Owner in writing and written instructions shall be obtained before proceeding with the work. The contractor will be held responsible for the results of any errors, discrepancies, or omissions in the work. The contractor will be held responsible for the results of any errors, discrepancies, or omissions in the Contract Documents of which the Contractor failed to notify the Engineer before construction and/or the Contract Documents of which the Contractor failed to notify the Engineer before construction and/or fabrication of the work.fabrication of the work.
The contractor shall verify all dimensions and job conditions at the job site sufficiently in advance of work, to The contractor shall verify all dimensions and job conditions at the job site sufficiently in advance of work, to be performed to assure the orderly progress of the work.be performed to assure the orderly progress of the work.
Contractors shall maintain the premises clean and free of trash, debris and shall protect all adjacent work from Contractors shall maintain the premises clean and free of trash, debris and shall protect all adjacent work from damage. All finished work shall be ready for use at the conclusion of project.damage. All finished work shall be ready for use at the conclusion of project.
All manufacturer's printed warnings and/or directions for handling products must be strictly observed. Any All manufacturer's printed warnings and/or directions for handling products must be strictly observed. Any items not compatible with substrate shall be isolated as per manufactures' recommendations.items not compatible with substrate shall be isolated as per manufactures' recommendations.
All codes, trade standards, and manufacturer's instructions referenced in the Contract Documents shall be the All codes, trade standards, and manufacturer's instructions referenced in the Contract Documents shall be the latest edition.latest edition.
The Contractor shall make no structural changes without approval of the Architect / Engineer.The Contractor shall make no structural changes without approval of the Architect / Engineer.
Project Contacts:
PA - NY - OH - WV
JHA Companies
Property Location:
Project Location:
Sheet Title:
Project No:
Sheet Issue Date:
Project Issue Date:
Checked By:
Plan Status:
Scale:
Seal:
Project Notes:
3939 Birney Ave Moosic, Pennsylvania 18507
844-542-4757
Th es e D ra w in gs s ha ll no t b e ut iliz ed b y an y Pe rs on
, F irm
, o r C or po ra tio n w ith ou t t he s pe ci fic w rit te n pe rm is si on o f J H
A C om pa ni es
ISSUED FOR BIDISSUED FOR BID
As Indicated
Tax Map Number:
G-1.0
REPAIRS & ALTERATIONSREPAIRS & ALTERATIONS
JESSUP TOWNSHIP
MUNICIPAL BUILDING
Contact: JESSUP TWP SUPERVISORSContact: JESSUP TWP SUPERVISORS
10175 STATE ROUTE 70610175 STATE ROUTE 706
MONTROSE, PA 18801MONTROSE, PA 18801
JESSUP TOWNSHIP
MUNICIPAL
BUILDING
Attn:JESSUP TWP SUPERVISORS
10175 STATE ROUTE 706
MONTROSE, PA 18801
REPAIRS &
ALTERATIONS
COVER SHEET/ DRAWING
INDEX
2026-0639 11/17/2026 11/17/2026
RJL
Ryan Lee, RA 3939 Birney Avenue Moosic, PA 18507 Phone: 570-229-1768 email: rlee@jhacompanies.com
ISSUED FOR BID
SUSQUEHANNA COUNTYSUSQUEHANNA COUNTY
Project Notes
141.00-1,008.00141.00-1,008.00
G DRAWING INDEX - GENERAL
Sheet Number Sheet Name Sheet Issue Date Revision # Revision Date Revision
Description
G-1.0 COVER SHEET/ DRAWING INDEX 11/17/2026
G-1.1 CODE COMPLIANCE REVIEW/ PROJECT INFO. 11/17/2026
S DRAWING INDEX - STRUCTURAL
Sheet Number Sheet Name Sheet Issue Date Revision # Revision Date Revision
Description
S-0.1 GENERAL STRUCTURAL NOTES 11/17/2026
S-0.2 GENERAL STRUCTURAL NOTES 11/17/2026
S-1.0 FOUNDATION PLANS, ELEVATIONS, & DETAILS 11/17/2026
S-5.0 STRUCTURAL DETAILS 11/17/2026
S-5.2 STRUCTURAL PLANS, ELEVATIONS, & DETAILS FOR STAIRS 11/17/2026
S-5.3 STRUCTURAL PLANS, ELEVATIONS, & DETAILS FOR STAIRS & K-BRACE 11/17/2026
A DRAWING INDEX - ARCHITECTURAL
Sheet Number Sheet Name Sheet Issue Date Revision # Revision Date Revision
Description
A-1.0 PROPOSED FLOOR PLAN 11/17/2026
A-1.1 PROPOSED FLOOR PLAN 11/17/2026
A-2.1 EXTERIOR ELEVATIONS 11/17/2026
A-2.2 EXTERIOR ELEVATIONS 11/17/2026
AE DRAWING INDEX - AS EXISTING
Sheet Number Sheet Name Sheet Issue Date Revision # Revision Date Revision
Description
AE-1.1 DEMOLITION PLANS 11/17/2026
AE-2.1 DEMOLITION ELEVATIONS 11/17/2026
THE PROJECT CONSISTS OF STRUCTURAL
REPAIRS AND IMPROVEMENTS TO THE EXISTING
WOOD-FRAMED TOWNSHIP BUILDING,
INCLUDING TEMPORARY BRACING, INSTALLATION
OF A NEW STEEL STRUCTURAL SYSTEM ON A
CONCRETE FOUNDATION, AND A NEW HEADER
FOR THE GARAGE DOOR OPENING. ADDITIONAL
WORK INCLUDES MASONRY CRACK REPAIRS,
WOOD SIDING REPAIRS AND PAINTING, ROOF
AND DRAINAGE IMPROVEMENTS, REPLACEMENT
OF AN OVERHEAD AND SWINGING DOOR, AND
INSTALLATION OF A NEW GALVANIZED STEEL
STAIR AND GUARDRAIL SYSTEM.
Rev # Revision Description Date
ALIGN
PLAN SYMBOLOGY LEGEND:
PLAN
NORTH TRUE
NORTH
WALL:
BASE:
FLOOR:
WC1
B1
CPT1
ROOM NAMEROOM NAME
# # S.F.
MATCHLINE
REFER TO DETAIL 1 / A101
LEVEL NAME
EL 0'-0"
0' 4' 8' 16' 24'
SCALE: 1/8" = 1'-0"
GRAPHIC SCALE
NORTH ARROW
11 OVERALL FLOOR PLANOVERALL FLOOR PLAN
SCALE: 1/4"=1'-0" -NOTESCALE: 1/4"=1'-0" -NOTEA1.1A1.1
A-1.1
SHEET NUMBERS
SHEET TYPE SUB SERIES
DISCIPLINE/SERIES
DETAIL NUMBER VIEW TITLE
DETAIL / SHEET SCALE
VIEW NOTE
PLAN, ELEVATION, SECTION OR DETAIL TITLE
A
EXISTING GRIDS
A
NEW GRIDS
A-1.1
MATCHLINE REFERENCE
FLOOR ELEVATION
8'-0" [A]
CEILING TAG
HEIGHT ABOVE
FLOOR LEVEL
CEILING TYPE
"X"
A-2.1
ELEV.
A-2.1
"X"
"X"3/0
"X" #"#"
ALIGN FACE OF
OBJECTS/SURFACES
A-3.1
SIM
ROOM FINISH TAG
CASEWORK TAG
ROOM NAME, NUMBER & AREA
EXTERIOR ELEVATION REFERENCE
DETAIL NUMBER
SHEET NUMBER
INTERIOR ELEVATION REFERENCE
DETAIL NUMBERS
SHEET NUMBER
SECTION REFERENCE
DETAIL NUMBER
SHEET NUMBER
A101
SIM
DETAIL NUMBER
SHEET NUMBER
DETAIL REFERENCE
WALL TAG
PARTITION
TYPE
DOOR/OPENING TAG
CALLOUT REFERENCE
DETAIL
NUMBER
SHEET
NUMBER
WINDOW TAG
REVISION TAG
KEYNOTE
SHEET/DRAWING NUMBERSSHEET/DRAWING NUMBERS
DISCIPLINE/SERIES
A = ARCHITECTURAL
AE= AS-EXISTING
C = CIVIL
E = ELECTRICAL
G= GENERAL
M= HVAC
L = LANDSCAPE
LS= LIFE SAFETY
P = PLUMBING
S = STRUCTURAL
SHEET TYPE SUB SERIES (ARCHITECTURAL)
A = ARCHITECTURAL PLANS, SECTIONS AND ELEVATIONS
1 = FLOOR PLANS
2 = EXTERIOR ELEVATIONS
3 = BUILDING SECTIONS
4 = ENLARGED ROOM DETAILS
5 = SCHEDULES & DETAILS
6 = REFLECTED CEILING
7 = FINISHES
"X"
CURTAINWALL TAG
ABBREVIATIONS:
A.B. Anchor Bolt A/C Air Conditioning ACC. Accessible/Accessibility ACOUST. Acoustical ADJ. Adjacent AFF or A.F.F. Above Finish Floor AFG or A.F.G Above Finish Grade ALUM. Aluminium ANGL. Angle APPROX. Approximate ARCH. Architect(ural) ASPH. Asphalt ATTN. Attention
B/O Bottom of BD. Board BIT. Bituminous BLDG. Building BLK. Block BLKG. Blocking BM. Beam BOT. Bottom BRG. Bearing BRK. Brick BRKMTL. Break Metal B.U.R. Built-Up Roofing
C or CH. Channel C.F. Communication Features CAB. Cabinet CB or C.B. Cement Board C\C or C.C Center to Center CCTV or C.C.T.V. Closed Circut Television Cer. Ceramic CFS Clear Floor Space CFSF Cold Form Steel Framing CL or C.L. or Centerline CLG. or CLNG. Ceiling CMU or C.M.U. Concrete Masonry Unit C.O. Closed Opening COL. Column COMB. Combination or Combine COMP. Compact(ed) CONC. Concrete CONST. Construction CONT. Continuous CORR. Corridor C.W. Cold Water CJ or C.J. Control Joint CLR. Clear
DN. Down DBL. Double DEPT. Department DETL. Detail DIA. or Ø Diameter D.F. Drinking Fountain DIV. Division DR. or DRN. Drain DS. or D.S. Downspout DWG(S). Drawing(s)
EA. Each EJ or EJ. or E.J. Expansion Joint ELEV. Elevation ELEC. or ELECT Electrical ELE. Elevator EMER. or EMERG. Emergency ENCL. Enclosure ENG. Engineer EP or E.P. Electrical Panel EQ. Equal EQUIP. Equipment EWC or E.W.C. Electrical Water Cooler E.W. Each Way EX. Existing EXP. Expansion EXT. Exterior
F.A. Fire Alarm FD. or F.D. Floor Drain FDN. Foundation F.E. Fire Extinguisher F.E.C. Fire Extinguisher FIN. Finish FL. or FLR. Floor FLUOR. Fluorescent FRM. Frame F.R. Fire Resistant F.R.C. Fiber reinforced concrete F.R.T. Fire Retardant Treated F.R.P. Fiber Reinforced Plastic FT. Foot (feet) FTG. Footing FUT. or FUTR. Future FV. or F.V. Field Verify
Ga. Gauge GALV. Galvanized G.B. Gypsum Board GEN. General GFRC Glass Fiber Reinforced Concrete GFRG Glass Fiber Reinforced GL. Glass GLAZ. Glazing GRAN. Granular G.S.M. Galvanized Sheet Metal G.V. Gas Valve GYP. Gypsum GYP. BD. Gypsum Board
HC. or H.C. Handicapped H.B. Hose Bib HDWD. Hardwood Floors HDWR. Hardware HM. OR H.M. Hollow Metal HORIZ. Horizontal H.P. High Point HSS Hollow Structural Section HT. Height HTG. Heating HR. or Hr. Hour HVAC Heating, Ventilation and A/C H.W. Hot water
ID. Inside Diameter IN. Inch(es) INCL. Include INSUL. Insulation INT. Interior INV. Invert
JC or J.C. Janitor's Closet JAN. Janitor(ial) JT. or JNT. Joint
KIT. Kitchen K.O. Knock out
LAV. Lavatory LAM. Laminate LB. or LBS. Pound(s) LGMF Light Gauge Metal Framing LT. WT. Light Weight L.L.H or LLH Long Leg Horizontal L.L.V. or LLV Long Leg Vertical
MAS. Masonry MAX. Maximum MED. Medium MDO or M.D.O. Medium Density Overlay MECH. Mechanical OPNG. Opening OPP. Opposite
PART Particle, Partial or Partition PL Plate P. LAM or P.L. Plastic Laminate PLAS. Plaster PLBG. Plumbing PLWD. or PLYWD. Plywood PNL. Panel PORC. Porcelain PR. Pair P.S.F. Pounds per Square Foot P.T. Pressure Treated POST TEN. Post Tensioned PTN. or PARTN. Partition PWR. Power
R Riser R.A. Return Air RAD. Radius RD Roof Drain REC. Recessed REC'V or REC'VD Receive or Received RE Refer or Referenced REF. Refrigerator REG. Regular or Register REINF. Reinforce REQ'D Required REQ'S Requirements RES. Resilient RM. Room R.O. Rough Opening
SCHED. Schedule SECT. Section SF or S.F. Square Feet SIM. Similar SM. or S.M. Surface Mounted SPEC. Specification SQ. Square SS OR S.S. Stainless Steel STD. Standard ST. Steel STOR. Storage STR. Structural SUSP. Suspended SYM. Symmetrical
TEL. Telephone TEMP. Temporary or Tempered T&B Top and Bottom T&G Tongue and Groove THRU Through TS or T.S. Tube Steel TV OR T.V. Television TYP. Typical
U.N.O. Unless Noted Otherwise UR. or URNL. Urinal
VAR. Varies/ Variable VCT or V.C.T. Vinyl Composition Tile VB. Vertical Bracing VERT. Vertical VIF. or V.I.F. Verify in Field
W/ With W/O Without WD. Wood WF. Wide Flange W.O. Work Order WIN Window
ADA SYMBOLOGY LEGEND:
DOOR CLEARANCES.
FRONT APPROACHES
INDICATED, SEE PLANS AND
CODES FOR SIDE
APPROACHES.
TURNING RADIUS
5'-0"
2'-6"
4' -0
1'-0"
1'-6"
CLEAR FLOOR SPACE
1'-0" 3'-0" 1'-0"
5'-0"
2' -0
3'
-0
IF BOTH CLOSER AND
LATCH PROVIDED
THESE CODE REQUIRED CLEARANCE MUST BE MET.
PHYSICAL ACCESSIBLE
DESIGNATED ROOM.
HEARING ACCESSIBLE
DESIGNATED ROOM
WITH COMMUNICATION
ELEMENTS AND
FEATURES.
PUSH SIDE
PULL SIDE
30x48 LAV
5'-0"
4' -8
56x60 TOILET
DOOR CLEARANCES
7' -0
7'-0"
HANDICAP PARKING SYMBOL
NOTES:
1. SYMBOL TO BE CENTERED ON WIDTH OF PARKING STALL.
SYMBOL IS REQUIRED TO CONTRAST WITH BACKGROUND. USE
WHITE ON BLUE (COLOR #105090 IN FEDERAL STANDARD 5952)
DOUBLE COAT.
GENERAL PROJECT:
1. ALL DRAWINGS SHALL BE READ IN CONJUNCTION W/ ALL OTHER DRAWINGS, PROJECT
MANUAL/SPECIFICATION, PROJECT PRODUCT MANUAL, THESE NOTES, DRAWING
SYMBOLS, MATERIAL LEGEND, REFLECTED CEILING LEGEND AND GENERAL INFORMATION
ON THIS SHEET AND ABBREVIATIONS.
2. DO NOT SCALE DRAWINGS, USE FIGURED DIMENSIONS ONLY. VERIFY ALL DIMENSIONS
PRIOR TO COMMENCEMENT OF ANY WORK. VERIFY ALL DISCREPANCIES BETWEEN FIELD
CONDITIONS AND THE CONTRACT DOCUMENTS. IN THE EVENT OF DISCREPANCY, NOTIFY
THE ARCHITECT AND OBTAIN RESOLUTION BEFORE PROCEEDING. FAILURE TO NOTIFY
THE ARCHITECT WILL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY TO PERFORM
THE WORK AS INTENDED BY THE CONTRACT DOCUMENTS. CONTRACTOR SHALL BE
RESPONSIBLE FOR ANY AND ALL WORK ARISING FROM SUCH FAILURE TO COORDINATE
DISCREPANCIES TO THE SATISFACTION OF THE ARCHITECT.
SPECIFICATIONSPECIFICATION S:
1. WHEN/ IF PROVIDED PER PROJECT SEE SPECIFICATION FOR GENERAL BUILDING
ELEMENTS, FINISHES, MATERIALS, BUILDING ACCESSORIES, TOILET AND BATHROOM
ACCESSORIES, TOILET PARTITIONS AND URINAL SCREENS, ETC. UNLESS NOTED
OTHERWISE (U.N.O.).
DRAWINGSDRAWINGS ::
1. PLANS, SECTIONS, AND ELEVATIONS INDICATE SPECIFIC INFORMATION. SEE TYPICAL
MOUNTING HEIGHTS, PARTITION DETAILS, DOOR DETAILS, CASEWORK TYPES AND
DETAILS, TOP TYPES, SHELF TYPES, NOTES AND TYPICAL DETAILS FOR TYPICAL
INFORMATION, INSTALLATION AND CONSTRUCTION UNLESS INDICATED OTHERWISE.
DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD UNLESS NOTED OTHERWISE
(U.N.O.)
VERIFY CONDITIONSVERIFY CONDITIONS ::
1. VERIFY ALL EXISTING FIELD CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK.
VERIFY ALL DISCREPANCIES BETWEEN FIELD CONDITIONS AND THE CONTRACT
DOCUMENTS. IN THE EVENT OF DISCREPANCY, NOTIFY THE ARCHITECT AND OBTAIN
RESOLUTION BEFORE PROCEEDING FAILURE TO NOTIFY THE ARCHITECT WILL NOT
RELIEVE THE CONTRACTOR OF RESPONSIBILITY TO PERFORM THE WORK AS INTENDED
BY THE CONTRACT DOCUMENTS. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND
ALL WORK ARISING FROM SUCH FAILURE TO COORDINATE DISCREPANCIES TO THE
SATISFACTION OF THE ARCHITECT.
COORDINATIONCOORDINATION ::
1. THE GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE THE ENTIRE PROJECT
INCLUDING ALL BUILDING ELEMENTS, SITE, EQUIPMENT, FITTINGS, FIXTURES, FURNITURE,
MECH. AND ELEC. ITEMS.
2. VERIFY AND COORDINATE THE FOLLOWING W/ THE RESPECTIVE DISCIPLINES AND
TRADES:
2A. VERIFY ALL EXISTING CONDITIONS, SIZES AND LOCATIONS OF MECH. AND/OR ELEC.
PENETRATIONS PRIOR TO COMMENCEMENT OF ANY WORK.
2B. LOCATIONS FOR BACKING/BLOCKING REQUIRED FOR MOUNTING ARCH, MECH.
AND/OR ELEC. EQUIPMENT, OWNER FURNISHED EQUIPMENT, FURNITURE, ARTWORK AND
SYSTEMS.
2C. CUTTING AND PATCHING FOR WORK REQUIRED BY MECH. AND/OR ELEC.
2D. SIZES AND LOCATIONS OF MECH. AND/OR ELEC. CONCRETE CURBS AND HOUSE
KEEPING PADS. SEE ALSO TYPICAL INTERIOR CONCRETE DETAILS U.N.O.
2E. SIZES AND LOCATIONS OF MECH.AND/OR ELEC. EXTERIOR WALL, CEILING AND ROOF
EQUIPMENT, DEVICES AND PENETRATIONS.
LIFE SAFETYLIFE SAFETY ::
1. LIFE SAFETY PLANS INDICATES FIRE AND SMOKE RATED PARTITIONS. SEE LIFE SAFETY
PLANS FOR PARTITION RATING AND FLOOR PLANS FOR PARTITION TYPES AND
CONSTRUCTION.
2. ALL SLEEVES, OPENINGS, PENETRATIONS, ETC. FOR CONDUITS, CABLE TRAYS, PIPES
AND DUCTS, ETC. THROUGH RATED PARTITIONS, FLOORS AND ROOF SLABS ARE TO BE
FIRE STOPPED IN ACCORDANCE W/ THE REQUIRED FIRE RATED ASSEMBLY DESIGN,
APPLICABLE CODES AND LOCAL FIRE AUTHORITY REQUIREMENTS. SEE "HILTI" FIRE
STOPPING SPECIFICATIONS FOR CORRECT APPLICATION.
3. ALL FIRE EXITS SHALL BE KEPT CLEAR AND ACCESSIBLE AT ALL TIMES.
SPRINKLER SYSTEMSPRINKLER SYSTEM : (When Applicable): (When Applicable)
1. SPRINKLER HEADS SHOWN ON THE RCP'S ARE THOSE OF DESIGN CONCERN. ALL
AREAS ARE REQUIRED TO BE SPRINKLERED. SPRINKLER HEADS AT GYPSUM BOARD
CEILINGS MUST BE FULLY RECESSED AND COVERED W/ METAL PLATES FINISHED TO
MATCH ADJACENT SURFACE.
ROOM OPENINGSROOM OPENINGS ::
1. FLOOR PLANS INDICATE ROOM OPENING NUMBERS FOR DOOR AND BORROWED LIGHT
FRAME TYPES, FRAME PROFILES, NOTES AND TYPICAL DETAILS. SEE DOOR SCHEDULE.
2. LOCATE DOORS AND OTHER OPENINGS IN PARTITIONS ADJACENT TO PERPENDICULAR
WALLS. MAINTAIN MINIMUM ACCESSIBILITY DOOR LATCH SIDE CLEARANCE
REQUIREMENTS, PUSH SIDE 12" MIN. 4'-0" DEEP IF DOOR IS PROVIDED W/ A CLOSER AND
PULL SIDE 1'-6" MIN. 4'-0" DEEP IF DOOR IS PROVIDED W/ A CLOSER.
CASEWORK AND MILLWORKCASEWORK AND MILLWORK ::
1. CASEWORK TYPES, TOP TYPES, SHELF TYPES, NOTES AND SPECIFIC DETAILS ARE AS
SHOWN ON PLANS AND INTERIOR ELEVATIONS, TYPES, UNDERCOUNTER TASK LIGHTING,
SUPPORT BRACKET TYPES, COUNTER TOP CORNER, GROMMETS, GYP. BD./ PLAM SOFFIT
TYPES, NOTES AND DETAILS, ROOM FINISHES SCHEDULE AND/OR FINISHES PLANS.
2. CASEWORK FINISHES, SEE ROOM FINISHES SCHEDULE AND NOTES.
ROOM FINISHESROOM FINISHES ::
1. FINISHES ARE INDICATED IN THE FINISH SCHEDULE AND/OR FINISH PLANS.
SEE TYPICAL FINISH TRANSITION DETAILS.
FLOOR DRAINSFLOOR DRAINS ::
1. SET FLOOR DRAINS AND FLOOR SINKS W/ TOP OF FINISH TILE/ POURED FLOOR. SEE
PLUMBING DRAWINGS FOR LOCATIONS
2. SLOPE CONCRETE FLOOR AT 1/8" PER FOOT TOWARDS FLOOR DRAINS AND AWAY
FROM ALL WALLS.
FURNITURE, EQUIPMENT, FIXTURES AND ACCESSORIESFURNITURE, EQUIPMENT, FIXTURES AND ACCESSORIES
1. FURNITURE, EQUIPMENT, FITTING, FIXTURES AND ACCESSORIES INSTALLATION SHALL
BE IN ACCORDANCE W/ MANUFACTURERS INSTRUCTIONS AND THE TYPICAL MOUNTING
HEIGHTS.
CURBS AND PADSCURBS AND PADS ::
1. CONCRETE CURBS AND PADS FOR EQUIPMENT. LOCATIONS MAY BE NOTED ON THE
ARCHITECTURAL DRAWINGS. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR
LOCATIONS AND SPECIFIC SIZE AND CONFIGURATION OF THEIR EQUIPMENT.
PARTITIONSPARTITIONS ::
1. PLAN DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD OR CMU PARTITIONS
EXCLUDING DIRECTLY APPLIED FINISH MATERIAL SUCH AS GYP.BD. AND CERAMIC TILE
UNLESS NOTED OTHERWISE (U.N.O.)
2. ALIGN PARTITIONS W/ FACE OF OTHER PARTITIONS OR COLUMNS, UNLESS NOTED
OTHERWISE. THE FACE OF EVERY PARTITION SHALL BE FLUSH W/OUT OFFSETS.
CHANGES IN PARTITION THICKNESS SHALL OCCUR AT CORNERS, PARTITION
INTERSECTIONS OR OTHER FEATURES WHICH INTERRUPT THE PLANE OF THE PARTITION.
FACE OF CORRIDOR PARTITIONS SHALL BE FLUSH FOR THE ENTIRE LENGTH OF THE
CORRIDOR REGARDLESS OF CHANGES IN PARTITION THICKNESS, ALL ADJUSTMENTS
SHALL BE MADE TO THE ROOM SIDE OF THE CORRIDOR PARTITION AND AT CORNERS.
WALL BLOCKING AND ANCHORAGEWALL BLOCKING AND ANCHORAGE ::
1. PROVIDE PLYWOOD WALL BLOCKING WHERE ARTWORK, MARKER-BOARDS (MBD) AND
TACK-BOARDS (TBD) ARE SHOWN. EXTENT OF BLOCKING TO MATCH SIZE OF ARTWORK,
MARKER-BOARDS (MBD) AND TACK-BOARDS (TBD). SEE PARTITION BLOCKING DETAILS.
2. PROVIDE WALL BLOCKING FOR FURNITURE, EQUIPMENT, FITTINGS, FIXTURES AND
ACCESSORIES IN ACCORDANCE W/ MANUFACTURER RECOMMENDATIONS AND
REQUIREMENTS. SEE PARTITION BLOCKING DETAILS. DESIGN LOAD FOR FITTINGS AND
FIXTURES MUST INCLUDED MIN, 250 LB VERTICAL AND HORIZONTAL FORCES.
WALL PROTECTIONWALL PROTECTION ::
1. CORNER GUARDS AND OTHER WALL PROTECTION TYPES AS INDICATED ON THE
DRAWINGS.
2. CORNER GUARDS ARE MOUNTED ABOVE FLOOR FINISH BASE AND UP TO UNDERSIDE
OF CEILING OR CEILING BULKHEAD, WHICH EVER IS APPLICABLE.
3. FOR INSTALLATION OF CORNER GUARDS, WALL PROTECTION, HANDRAILS, CRASH
RAILS, ETC, SEE MANUFACTURERS INSTRUCTIONS.
CEILINGSCEILINGS ::
1. CEILING HEIGHT SHALL BE MIN. 7'-6" IN ALL HABITABLE ROOMS, LOBBIES, CORRIDORS, PASSAGES, ETC. ABOVE FLOOR LEVEL UNLESS OTHERWISE NOTED. SEE ALSO
REFLECTED CEILING PLANS AND ROOM FINISH SCHEDULE.
2. COORDINATE AND VERIFY ALL CEILING ACCESS PANEL SIZES AND LOCATIONS W/
MECH. AND ELEC. CONTRACTORS. PROVIDE FLUSH ACCESS PANELS AT ALL EQUIPMENT,
VALVES, DAMPERS, CONTROLS, CLEANOUTS, ETC. PAINT TO MATCH CEILING FINISH.
3. CENTER CEILING GRID IN ROOM UNLESS NOTED OTHERWISE.
4. CENTER SPRINKLER HEADS, DIFFUSERS, LIGHT FIXTURES, AND OTHER RECESSED OR
SURFACE MOUNTED ITEMS IN CEILING TILES UNLESS NOTED OTHERWISE (U.N.O.).
DESCRIPTION F.E. +C
NOTES :
FE+C
INTERCOM
DOOR
CCTV CAMERA OUTLETS
FINISHED CEILING
JB
JBVD VD
VD
H
FA
ALARM ANNUNCIATOR PANEL
T
DOOR
LIGHT SWITCH
VD
WALL SCONCE THERMOSTAT/HUMIDISTAT FIRE ALARM
JB
CARD READER
ABOVE COUNTER/DESK
ABOVE FLOOR
ELECT/COMM OUTLETS
WS
WALL MOUNTED AT DOOR LOCATION
EO
MOUNT HEIGHTS SHOWN
FOR
ABOVE FLOOR AND ABOVE
COUNTER UNO.,
REFER TO ELEVATIONS FOR
LOCATIONS.
- CENTERLINE AT 18" A.F.F.
REFER
ELECTRICAL
AND
COMMUNICATION
DRAWINGS.
FIXTURES CAN
NOT
PROJECT INTO
CORRIDOR MORE
THAN 4"
SW
LT
EO
EOEO
EO
AT DOOR LOCATION
- 48" MAX. TOP OF
DEVICE
AAP IC
T
SW
LT H
TYP.
TYP. DOOR
LATCH
SIDE
MIN.
MOUNTING
HEIGHT.
MAX. DIM.
TO
TOP OF
FIXTURE
8'-0".
TYPICAL MOUNTING HEIGHTS AND LOCATIONS:
PORTABLE FIRE
EXTINGUISHER - U.L.
LABELED MIN.
4A-80BC
10LB RATED - WALL
MTD. W/ HANDLE @
48" A.F.F. - F.E.+C = W/
RECESSED WALL
CABINET
U .N
.O
4' -0
" 6' -0
3"
3"
1' -0
3"
1' -6
" CCLL
CCLL
CCLL
4' -0
6"
CCLL
4' -0
" 6" 6"
CCLLCCLL U
.N
.O
3' -0
CCLL6" 6" 6"
CCLLCCLLCCLL
4' -0
6' -8
" CCLL
3' -6
4' -0
MATERIAL PATTERNS:
CONCRETE
EARTH (UNDISTURBED)
EARTH (DISTURBED)
METAL
WOOD
CMU
RIGID INSULATION
BATT INSULATION
GRAVEL / SUB-BASE
SAND / GROUT
GYPSUM BOARD / PLASTER
DEFINITIONS:
WHERE ADDITIONAL ABBREVIATIONS, OR WORD DEFINITIONS, ARE DEFINED BY ANOTHER DISCIPLINE AND
A CONFLICT OCCURS, THEIR DEFINITION SHALL TAKE PRECEDENCE OVER THE FOLLOWING:
NECESSARY: WORK NEEDED TO COMPLETE THE WORK. TO: "MAKE IT OPERATIONAL".
REQUIRED: WORK NEEDED TO BE IN COMPLIANCE WITH BUILDING CODE, GOVERNING CODE, OR JURISDICTION HAVING AUTHORITY.
PROVIDE: RESPONSIBLE FOR PURCHASE, DELIVERY, RECEIVING, INSPECTION, STORAGE, PREPARATION, AND INSTALLATION OF ITEM(S).
FURNISH: RESPONSIBLE FOR PURCHASE AND DELIVERY OF ITEM(S)
INSTALL: RESPONSIBLE FOR RECEIVING, INSPECTION, STORAGE, PREPARATION AND INSTALLATION OF ITEM(S).
Project Contacts:
PA - NY - OH - WV
JHA Companies
Project Location:
Sheet Title:
Project No:
Sheet Issue Date:
Project Issue Date:
Checked By:
Plan Status:
Scale:
Seal:
Project Notes:
3939 Birney Ave Moosic, Pennsylvania 18507
844-542-4757
Th es e D ra w in gs s ha ll no t b e ut iliz ed b y an y Pe rs on
, F irm
, o r C or po ra tio n w ith ou t t he s pe ci fic w rit te n pe rm is si on o f J H
A C om pa ni es
ISSUED FOR BIDISSUED FOR BID
As Indicated
G-1.1
JESSUP TOWNSHIP
MUNICIPAL
BUILDING
Attn:JESSUP TWP SUPERVISORS
10175 STATE ROUTE 706
MONTROSE, PA 18801
REPAIRS &
ALTERATIONS
CODE COMPLIANCE
REVIEW/ PROJECT INFO.
2026-0639 11/17/2026 11/17/2026
RJL
Ryan Lee, RA 3939 Birney Avenue Moosic, PA 18507 Phone: 570-229-1768 email: rlee@jhacompanies.com
ISSUED FOR BID
Project Notes
DEMOLITION LEGEND:
ABOVE FINISHED FLOOR
FINISHED FLOOR
FIRE RATED - TYPE & RATINGS AS INDICATED
MOLD RESISTANT
UNLESS NOTED OTHERWISE
VERIFY IN FIELD
CENTERLINE
HANDICAP ACCESSIBLE
- PER PA UNIVERSAL ACCESSIBILITY STANDARDS
WEATHER PROOF
A.F.F.A.F.F.
F.F.F.F.
F.R.F.R.
M.R.M.R.
U.N.O.U.N.O.
V.I.F.V.I.F.
CC
H.C.A. H.C.A.
WPWP
EXISTING, TO REMAIN
DEMOLISHED, TO BE REMOVED OR ALTERED
DEMOLITION KEY NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
REMOVE EXISTING T-1-11 SIDING INCLUDING ALL FASTENERS. PREPARE EXISTING
WALL SUBSTRATE FOR NEW SIDING INSTALLATION.
DISCONNECT AND TEMPORARILY REMOVE EXISTING MINI-SPLIT REFRIGERANT
LINE SETS AS REQUIRED. PROTECT AND STORE FOR REINSTALLATION.
DISCONNECT AND REMOVE EXISTING OUTDOOR MINI SPLIT UNIT AND
ASSOCIATED REFRIGERANT LINE SETS AS REQUIRED. PROTECT AND STORE FOR
REINSTALLATION.
REMOVE PORTION OF EXISTING WALL, INCLUDING FRAMING, FASTENERS,
INSULATION, AND ASSOCIATED MATERIALS, AS REQUIRED FOR NEW DOOR
INSTALLATION. VERIFY ROUGH OPENING DIMENSIONS WITH DOOR
MANUFACTURER. REFER TO STRUCTURAL DRAWINGS FOR FRAMING
REQUIREMENTS.
REMOVE EXISTING WINDOWS AND ASSOCIATED FRAMES, TRIM, AND HARDWARE
AS REQUIRED, EXCEPT WHERE NOTED TO REMAIN OR BE REINSTALLED.
EXISTING WINDOW TO REMAIN. PROVIDE NEW FLASHING AT WINDOW PERIMETER
AS REQUIRED TO INTEGRATE WITH NEW SIDING INSTALLATION.
REMOVE EXISTING WALL INCLUDING ALL FRAMING, FASTENERS AND FINISHES..
REFER TO STRUCTURAL DRAWINGS FOR LIMITS OF REMOVAL, TEMPORARY
BRACING, DIMENSIONS, AND DETAILS.
REMOVE EXISTING DOORS AND ASSOCIATED FRAMES, HARDWARE, AND TRIM AS
REQUIRED.
REMOVE EXISTING FIRE EXTINGUISHER AND ASSOCIATED MOUNTING HARDWARE
AS REQUIRED. PROTECT AND STORE FOR REINSTALLATION. RETAIN AND
REINSTALL SIGNAGE
DISCONNECT AND REMOVE EXISTING WATER AND SANITARY LINES AS REQUIRED.
PROTECT AND STORE FOR REINSTALLATION.
REMOVE EXISTING HOSE BIBS AND ASSOCIATED CONNECTIONS AS REQUIRED.
PROVIDE AND INSTALL NEW HOSE BIBS IN KIND. COORDINATE LOCATIONS WITH
EXISTING CONDITIONS.
COORDINATE DISCONNECTION AND TEMPORARY REMOVAL OF EXISTING
CIRCUITRY FROM STORAGE BUILDING TO SUB PANEL .
COORDINATE DISCONNECTION AND TEMPORARY REMOVAL OF EXISTING
TELECOMMUNICATIONS SERVICE AND ASSOCIATED COMPONENTS WITH SERVICE
PROVIDER. PROTECT AND STORE FOR REINSTALLATION.
REMOVE EXISTING RECEPTACLES AND ASSOCIATED MOUNTING HARDWARE AS
REQUIRED. PROVIDE AND INSTALL NEW RECEPTACLES IN KIND.
REMOVE EXISTING WIRING, CONDUIT, DEVICES, SWITCHES, RECEPTACLES, AND
EQUIPMENT WITHIN LIMITS OF WALL DEMOLITION. TRACE EXISTING WIRING BACK
TO SOURCE AND REMOVE AS REQUIRED. RELOCATE AND RECONNECT EXISTING
ELECTRICAL COMPONENTS AS REQUIRED TO MAINTAIN SERVICE. PROVIDE NEW
COMPONENTS IN KIND WHERE EXISTING COMPONENTS CANNOT BE REUSED.
REMOVE EXISTING INTERIOR CONCRETE SLAB-ON-GRADE AS REQUIRED FOR
INSTALLATION OF NEW FOOTING. REFER TO STRUCTURAL DRAWINGS FOR
FOOTING LOCATION, DIMENSIONS, AND DETAILS.
REMOVE EXISTING EXTERIOR CONCRETE SLAB-ON-GRADE AS REQUIRED FOR
INSTALLATION OF NEW FOOTING. REFER TO STRUCTURAL DRAWINGS FOR
FOOTING LOCATION, DIMENSIONS, AND DETAILS.
REMOVE EXISTING UTILITY SINK AND ASSOCIATED PLUMBING CONNECTIONS AS
REQUIRED. PROTECT AND TURN OVER TO OWNER FOR RETENTION.
DISCONNECT AND REMOVE EXISTING WELL PRESSURE TANK AS REQUIRED.
PROTECT EXISTING WELL SERVICE LINE. PROTECT AND STORE TANK FOR
REINSTALLATION.
DISCONNECT AND REMOVE EXISTING WATER HEATER AS REQUIRED. PROTECT
AND STORE FOR REINSTALLATION.
REMOVE EXISTING JERSEY BARRIER. PROTECT AND STORE FOR OWNER
RETENTION.
EXISTING FOUNDATION CRACK TO BE PREPPED FOR REPAIR. SEE STRUCTURAL
DRAWINGS FOR MORE INFORMATION.
REMOVE EXISTING WOOD SIDING TO FRAMING INCLUDING ALL TRIM AND
FASTENERS. PREP FOR INSTALLATION OF NEW SHEATHING, FURRING, AND
SIDING.
BOTTOM FLIGHT OF EXISTING WOOD STAIR TO BE REMOVED IN PREPARATION OF
EXCAVATION FOR NEW FOOTING AND RETAINING WALL.
AE-2.1
EL
EV
AE-2.1
2 ELEV.
AE-2.1
ELEV.
AE-2.1
EL
EV
EX. BASEMENTEX. BASEMENT
EX. RESTROOMEX. RESTROOM
EX. HALLEX. HALL
EX. STAIR AEX. STAIR A
A
UP
UP
UP
ENTIRE WALL TO BE REMOVED AND REBUILT.
SEE STRUCTURAL FOR LIMITS, DETAILS, AND
TEMPORARY BRACING, TYP.
48'-10 3/4" +/-
'-0
NOTE: COORDINATE UTILITIES TO BE
DISCONNECTED AND UNINSTALLED
BEFORE WORK BEGINS.
EX.
DR.
EX.
DR. EX.
DR.
EX.
DR.
EX.
DR.
EX.
WIN.
AE-2.1
EL
EV
AE-2.1
2 ELEV.
AE-2.1
ELEV.
AE-2.1
EL
EV
EX. MEETING ROOMEX. MEETING ROOM
EX. STORAGEEX. STORAGE
EX. ENTRANCEEX. ENTRANCE
EX. OFFICEEX. OFFICE
EX. RESTROOMEX. RESTROOM
EX. SHOWER RMEX. SHOWER RM
EX. CLOS.EX. CLOS. EX. CLOS.EX. CLOS.
DN.
DN.
DN.
DN.DN.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
EX.
DR.
7'-8"
48'-10 3/4" +/-
EX. WIN.
TO REMAIN
EX. WIN.
TO REMAIN
'-0
1 1
Project Contacts:
PA - NY - OH - WV
JHA Companies
Project Location:
Sheet Title:
Project No:
Sheet Issue Date:
Project Issue Date:
Checked By:
Plan Status:
Scale:
Seal:
Project Notes:
3939 Birney Ave Moosic, Pennsylvania 18507
844-542-4757
Th es e D ra w in gs s ha ll no t b e ut iliz ed b y an y Pe rs on
, F irm
, o r C or po ra tio n w ith ou t t he s pe ci fic w rit te n pe rm is si on o f J H
A C om pa ni es
ISSUED FOR BIDISSUED FOR BID
As Indicated
AE-1.1
JESSUP TOWNSHIP
MUNICIPAL
BUILDING
Attn:JESSUP TWP SUPERVISORS
10175 STATE ROUTE 706
MONTROSE, PA 18801
REPAIRS &
ALTERATIONS
DEMOLITION PLANS
2026-0639 11/17/2026 11/17/2026
Checker
Ryan Lee, RA 3939 Birney Avenue Moosic, PA 18507 Phone: 570-229-1768 email: rlee@jhacompanies.com
ISSUED FOR BID
Project Notes
PLAN
NORTH TRUE
NORTH
0' 2' 4' 8' 16'1' 12'
SCALE: 3/16" = 1'-0"
AE-1.1AE-1.1
11 LOWER LEVEL DEMOLITION PLANLOWER LEVEL DEMOLITION PLAN
SCALE: 3/16" = 1'-0"SCALE: 3/16" = 1'-0"
AE-1.1AE-1.1
22 UPPER LEVEL DEMOLITION PLANUPPER LEVEL DEMOLITION PLAN
SCALE: 3/16" = 1'-0"SCALE: 3/16" = 1'-0"
DEMOLITION LEGEND:
ABOVE FINISHED FLOOR
FINISHED FLOOR
FIRE RATED - TYPE & RATINGS AS INDICATED
MOLD RESISTANT
UNLESS NOTED OTHERWISE
VERIFY IN FIELD
CENTERLINE
HANDICAP ACCESSIBLE
- PER PA UNIVERSAL ACCESSIBILITY STANDARDS
WEATHER PROOF
A.F.F.A.F.F.
F.F.F.F.
F.R.F.R.
M.R.M.R.
U.N.O.U.N.O.
V.I.F.V.I.F.
CC
H.C.A. H.C.A.
WPWP
EXISTING, TO REMAIN
DEMOLISHED, TO BE REMOVED OR ALTERED
DEMOLITION KEY NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
REMOVE EXISTING T-1-11 SIDING INCLUDING ALL FASTENERS. PREPARE EXISTING
WALL SUBSTRATE FOR NEW SIDING INSTALLATION.
DISCONNECT AND TEMPORARILY REMOVE EXISTING MINI-SPLIT REFRIGERANT
LINE SETS AS REQUIRED. PROTECT AND STORE FOR REINSTALLATION.
DISCONNECT AND REMOVE EXISTING OUTDOOR MINI SPLIT UNIT AND
ASSOCIATED REFRIGERANT LINE SETS AS REQUIRED. PROTECT AND STORE FOR
REINSTALLATION.
REMOVE PORTION OF EXISTING WALL, INCLUDING FRAMING, FASTENERS,
INSULATION, AND ASSOCIATED MATERIALS, AS REQUIRED FOR NEW DOOR
INSTALLATION. VERIFY ROUGH OPENING DIMENSIONS WITH DOOR
MANUFACTURER. REFER TO STRUCTURAL DRAWINGS FOR FRAMING
REQUIREMENTS.
REMOVE EXISTING WINDOWS AND ASSOCIATED FRAMES, TRIM, AND HARDWARE
AS REQUIRED, EXCEPT WHERE NOTED TO REMAIN OR BE REINSTALLED.
EXISTING WINDOW TO REMAIN. PROVIDE NEW FLASHING AT WINDOW PERIMETER
AS REQUIRED TO INTEGRATE WITH NEW SIDING INSTALLATION.
REMOVE EXISTING WALL INCLUDING ALL FRAMING, FASTENERS AND FINISHES..
REFER TO STRUCTURAL DRAWINGS FOR LIMITS OF REMOVAL, TEMPORARY
BRACING, DIMENSIONS, AND DETAILS.
REMOVE EXISTING DOORS AND ASSOCIATED FRAMES, HARDWARE, AND TRIM AS
REQUIRED.
REMOVE EXISTING FIRE EXTINGUISHER AND ASSOCIATED MOUNTING HARDWARE
AS REQUIRED. PROTECT AND STORE FOR REINSTALLATION. RETAIN AND
REINSTALL SIGNAGE
DISCONNECT AND REMOVE EXISTING WATER AND SANITARY LINES AS REQUIRED.
PROTECT AND STORE FOR REINSTALLATION.
REMOVE EXISTING HOSE BIBS AND ASSOCIATED CONNECTIONS AS REQUIRED.
PROVIDE AND INSTALL NEW HOSE BIBS IN KIND. COORDINATE LOCATIONS WITH
EXISTING CONDITIONS.
COORDINATE DISCONNECTION AND TEMPORARY REMOVAL OF EXISTING
CIRCUITRY FROM STORAGE BUILDING TO SUB PANEL .
COORDINATE DISCONNECTION AND TEMPORARY REMOVAL OF EXISTING
TELECOMMUNICATIONS SERVICE AND ASSOCIATED COMPONENTS WITH SERVICE
PROVIDER. PROTECT AND STORE FOR REINSTALLATION.
REMOVE EXISTING RECEPTACLES AND ASSOCIATED MOUNTING HARDWARE AS
REQUIRED. PROVIDE AND INSTALL NEW RECEPTACLES IN KIND.
REMOVE EXISTING WIRING, CONDUIT, DEVICES, SWITCHES, RECEPTACLES, AND
EQUIPMENT WITHIN LIMITS OF WALL DEMOLITION. TRACE EXISTING WIRING BACK
TO SOURCE AND REMOVE AS REQUIRED. RELOCATE AND RECONNECT EXISTING
ELECTRICAL COMPONENTS AS REQUIRED TO MAINTAIN SERVICE. PROVIDE NEW
COMPONENTS IN KIND WHERE EXISTING COMPONENTS CANNOT BE REUSED.
REMOVE EXISTING INTERIOR CONCRETE SLAB-ON-GRADE AS REQUIRED FOR
INSTALLATION OF NEW FOOTING. REFER TO STRUCTURAL DRAWINGS FOR
FOOTING LOCATION, DIMENSIONS, AND DETAILS.
REMOVE EXISTING EXTERIOR CONCRETE SLAB-ON-GRADE AS REQUIRED FOR
INSTALLATION OF NEW FOOTING. REFER TO STRUCTURAL DRAWINGS FOR
FOOTING LOCATION, DIMENSIONS, AND DETAILS.
REMOVE EXISTING UTILITY SINK AND ASSOCIATED PLUMBING CONNECTIONS AS
REQUIRED. PROTECT AND TURN OVER TO OWNER FOR RETENTION.
DISCONNECT AND REMOVE EXISTING WELL PRESSURE TANK AS REQUIRED.
PROTECT EXISTING WELL SERVICE LINE. PROTECT AND STORE TANK FOR
REINSTALLATION.
DISCONNECT AND REMOVE EXISTING WATER HEATER AS REQUIRED. PROTECT
AND STORE FOR REINSTALLATION.
REMOVE EXISTING JERSEY BARRIER. PROTECT AND STORE FOR OWNER
RETENTION.
EXISTING FOUNDATION CRACK TO BE PREPPED FOR REPAIR. SEE STRUCTURAL
DRAWINGS FOR MORE INFORMATION.
REMOVE EXISTING WOOD SIDING TO FRAMING INCLUDING ALL TRIM AND
FASTENERS. PREP FOR INSTALLATION OF NEW SHEATHING, FURRING, AND
SIDING.
BOTTOM FLIGHT OF EXISTING WOOD STAIR TO BE REMOVED IN PREPARATION OF
EXCAVATION FOR NEW FOOTING AND RETAINING WALL.
UPPER LEVEL
14'-4"
LOWER LEVEL
0'-0"
T/O FDN.
3'-0"
LEVEL 0.5
1'-8"
6 6
UPPER LEVEL
14'-4"
LOWER LEVEL
0'-0"
T/O FDN.
3'-0"
22 22
UPPER LEVEL
14'-4"
NOTE: NO WORK PLANNED FOR THIS ELEVATION
BEYOND REPAIR AND REPLACEMENT OF DAMAGED
SIDING AND PREPARATION FOR NEW PAINT.
UPPER LEVEL
14'-4"
LOWER LEVEL
0'-0"
T/O FDN.
3'-0"
LEVEL 0.5
1'-8"
8 9 3
4" 1'
-0
5/
6 6
14 21
Project Contacts:
PA - NY - OH - WV
JHA Companies
Project Location:
Sheet Title:
Project No:
Sheet Issue Date:
Project Issue Date:
Checked By:
Plan Status:
Scale:
Seal:
Project Notes:
3939 Birney Ave Moosic, Pennsylvania 18507
844-542-4757
Th es e D ra w in gs s ha ll no t b e ut iliz ed b y an y Pe rs on
, F irm
, o r C or po ra tio n w ith ou t t he s pe ci fic w rit te n pe rm is si on o f J H
A C om pa ni es
ISSUED FOR BIDISSUED FOR BID
As Indicated
AE-2.1
JESSUP TOWNSHIP
MUNICIPAL
BUILDING
Attn:JESSUP TWP SUPERVISORS
10175 STATE ROUTE 706
MONTROSE, PA 18801
REPAIRS &
ALTERATIONS
DEMOLITION
ELEVATIONS
2026-0639 11/17/2026 11/17/2026
Checker
Ryan Lee, RA 3939 Birney Avenue Moosic, PA 18507 Phone: 570-229-1768 email: rlee@jhacompanies.com
ISSUED FOR BID
Project Notes
0' 4' 8' 12'
SCALE: 1/4" = 1'-0"
0' 2' 4' 8' 16'1' 12'
SCALE: 3/16" = 1'-0"
AE-2.1AE-2.1
33 PLAN EAST EXISTINGPLAN EAST EXISTING
SCALE: 3/16" = 1'-0"SCALE: 3/16" = 1'-0"
AE-2.1AE-2.1
22 PLAN NORTH EXISTINGPLAN NORTH EXISTING
SCALE: 3/16" = 1'-0"SCALE: 3/16" = 1'-0"
AE-2.1AE-2.1
11 PLAN SOUTH EXISTINGPLAN SOUTH EXISTING
SCALE: 3/16" = 1'-0"SCALE: 3/16" = 1'-0"
AE-2.1AE-2.1
44 PLAN WEST EXISTINGPLAN WEST EXISTING
SCALE: 3/16" = 1'-0"SCALE: 3/16" = 1'-0"
GENERAL DEMOLITION NOTE:
PREPARE ENTIRE EXTERIOR OF BUILDING FOR PAINTING.
PRESSURE WASH EXTERIOR SURFACES AS APPROPRIATE,
REMOVE LOOSE AND PEELING PAINT, SCRAPE AND SAND
EXISTING WOOD SIDING AND TRIM, AND REMOVE DIRT, MILDEW,
AND OTHER SURFACE CONTAMINANTS. REPAIR MINOR
SURFACE DEFECTS, FILL NAIL HOLES AND GAPS, AND CAULK
JOINTS AS REQUIRED. REPLACE OR REPAIR DETERIORATED
WOOD AS NECESSARY. LEAVE ALL SURFACES CLEAN, DRY,
SOUND, AND PROPERLY PREPARED TO RECEIVE NEW PAINT.
GENERAL PROJECT INFORMATION
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
a.
b.
4.
5.
6.
"LOADS" INDICATED IN THE DESIGN LOAD CRITERIA TABLE ARE THOSE USED IN DESIGN OF THE BUILDING SUPERSTRUCTURE.
DESIGN LOADS AND CRITERIA USED IN THE DESIGN OF SPECIALTY STRUCTURAL SYSTEMS (i.e. CURTAIN WALL, FIRESTAIRS, COLD- FORMED METAL FRAMING, ARCHITECTURAL PRECAST CONCRETE, METAL PANELS, ETC ) ARE TO BE DETERMINED BY A THIRD PARTY ENGINEER WHO HAS BEEN CONTRACTED BY THE SPECIALTY STRUCTURAL SYSTEM MANUFACTURER AND IN ACCORDANCE WITH THE CODE REQUIREMENTS OF THE GOVERNING JURISDICTION. THE SPECIALTY STRUCTURAL ENGINEER IS RESPONSIBLE FOR ALL CONNECTIONS OF THESE SYSTEMS TO THE SUPERSTRUCTURE. THE SPECIALTY STRUCTURAL SYSTEMS CONNECTIONS INCLUDE, BUT ARE NOT LIMITED TO, ENGINEERING, DETAILING, AND INSTALLATION IF ALTERATION TO THE SUPERSTRUCTURE IS REQUIRED AS DETERMINED BY THE ENGINEER OF RECORD (E.O.R) TO REINFORCE FOR HIGH CONCENTRATED FORCES APPLIED BY THE SPECIALTY SYSTEM CONNECTION, THE REINFORCEMENT AND COST SHALL BE BORNE BY THE SPECIALTY SUBCONTRACTOR AND SHALL BE
CONSIDERED A PART OF THE SPECIALTY CONNECTION.
THE CONTRACTOR SHALL SUBMIT, FOR REVIEW, DRAWINGS AND CALCULATIONS FOR ALL PERFORMANCE ASSEMBLIES IDENTIFIED IN THE GENERAL NOTES AND LISTED BELOW: THE DESIGN OF THESE ASSEMBLIES IS THE RESPONSIBILITY OF THE CONTRACTOR'S ENGINEER LICENSED IN THE COMMONWEALTH OF PENNSYLVANIA. ALL SUBMITTALS SHALL BEAR THIS ENGINEER'S SEAL AND SIGNATURE. THE SUBMITTAL REVIEW SHALL BE FOR GENERAL CONFORMANCE WITH THE PROJECT REQUIREMENTS AS INDICATED ON
THE DRAWINGS AND IN THE GENERAL NOTES.
NON-LOAD BEARING STUD WALL AND CURTAIN WALL SYSTEMS AND RELATED CONNECTIONS: DESIGNS SHALL TAKE INTO ACCOUNT ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING CODES. BACK UP SYSTEM AND CURTAIN WALL SHALL BE DESIGNED FOR A DEFLECTION AS SPECIFIED IN THE PROJECT SPECIFICATIONS PREPARED BY THE ARCHITECT.
METAL STAIRS AND METAL RAILINGS: DESIGNS SHALL TAKE INTO ACCOUNT ALL VERTICAL AND LATERAL LOADS REQUIRED BY APPLICABLE BUILDING CODES. WHERE HEADERS OR OTHER TYPES OF STRUCTURAL MEMBERS HAVE BEEN DESIGNATED BY THE STRUCTURAL ENGINEER OF RECORD TO SUPPORT THE STAIRS, THE CONNECTIONS FROM THE STAIRS SHALL BE DESIGNED SO THAT NO ECCENTRIC OR TORSIONAL FORCES ARE INDUCED IN THESE STRUCTURAL MEMBERS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING HARDWARE AS REQUIRED BY THE STAIR DESIGN.
ALL DETAILS MARKED "TYPICAL" IN THE SET OF STRUCTURAL DRAWINGS SHALL BE APPLIED THROUGHOUT THE PROJECT AS REQUIRED TO SATISFY THE REQUIREMENTS OF THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL COORDINATE REQUIREMENTS FOR
QUANTITY AND LOCATION WHERE THE "TYPICAL" DETAILS APPLY.
FAILURE ON THE PART OF THE CONTRACTOR TO REVIEW THE STRUCTURAL DRAWINGS OR THE DRAWINGS OF OTHER DISCIPLINES (i.e.)
ARCHITECTURAL, CIVIL, M E P , ETC ) TOGETHER WITH THE FULL EXTENT OF THE PROJECT SPECIFICATIONS DOES NOT RELIEVE THEM OF THE RESPONSIBILITY TO FURNISH AND INSTALL ITEMS THAT ARE PART OF THEIR WORK AS INDICATED BY THE DRAWINGS AND SPECIFICATIONS OF OTHER TRADES. ALL STRUCTURAL TRADE CONTRACTORS AND SUBCONTRACTORS ARE PROHIBITED FROM EXCLUDING STRUCTURAL WORK FROM THEIR CONTRACT NOT SHOWN IN THE STRUCTURAL DRAWINGS.
THE STRUCTURAL DRAWINGS FOR THIS PROJECT ARE NOT ISSUED FOR BID OR CONSTRUCTION UNLESS THE INDIVIDUAL SHEETS ARE
IDENTIFIED AS "ISSUED FOR BID" OR "ISSUED FOR CONSTRUCTION."
EXISTING CONDITIONS
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
4.
5.
DIMENSIONS AND ELEVATIONS OF EXISTING CONDITIONS SHOWN ON THE STRUCTURAL DRAWINGS ARE BASED ON LIMITED AVAILABLE INFORMATION CONTAINED IN EITHER VARIOUS ORIGINAL DESIGN AND CONSTRUCTION DOCUMENTS OR FIELD SURVEY. ACTUAL FIELD
CONDITIONS NEED TO BE CONFIRMED BY THE CONTRACTOR PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS BY ACTUAL MEASUREMENT PRIOR TO BEGINNING WORK, AND WHEN FEASIBLE, PRIOR TO SHOP DRAWING SUBMITTALS. ANY AND ALL DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO COORDINATE SAID
DISCREPANCIES WITH ALL SUBCONTRACTORS AND MATERIAL SUPPLIERS.
DURING CONSTRUCTION THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS WHICH ARE NOT KNOWN OR ARE AT VARIANCE WITH THE PROJECT DOCUMENTS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ALL UNFORESEEN AND DEVIATING CONDITIONS INCLUDING, BUT NOT LIMITED TO: SIZES OR DIMENSIONS OTHER THAN THOSE SHOWN, DAMAGE OR DETERIORATION TO
MATERIALS AND COMPONENTS AND CONDITIONS OF INSTABILITY OR LACK OF SUPPORT.
THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING AND MAKE SAFE ALL EXISTING BUILDING CONSTRUCTION AND/OR ADJACENT PROPERTY AS PROJECT CONDITIONS REQUIRE. DESIGN OF TEMPORARY SHORING AND BRACING SHALL BE
PERFORMED AND OVERSEEN BY A LICENSED ENGINEER (PA) EMPLOYED BY THE CONTRACTOR.
WHERE NEW CONSTRUCTION IS REQUIRED TO SUPPORT THE EXISTING FRAMING AND/OR CONSTRUCTION, THE CONTRACTOR IS TO ENSURE ALL EXISTING FRAMING IS SHORED AND BRACED PRIOR TO INSTALLATION OF THE NEW STRUCTURAL SUPPORT SYSTEM.
SITE PREPARATION GENERAL NOTES
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
4.
5.
6.
7.
8.
THE SURFACE OF THE EXPOSED SUB-GRADE SHALL BE INSPECTED BY PROBING OR TESTING TO CHECK FOR POCKETS OF SOFT OR UNSUITABLE MATERIAL. EXCAVATE UNSUITABLE SOIL AS DIRECTED BY THE ON-SITE GEOTECHNICAL ENGINEER AND/OR TESTING
AGENCY.
FILL ALL EXCAVATED AREAS WITH APPROVED CONTROLLED FILL. PLACE IN 12 INCH (12 ”) MAXIMUM LOOSE LIFTS AND COMPACT TO A
MINIMUM OF 95% OF THE MAXIMUM DRY DENSITY IN ACCORDANCE WITH ASTM D-1557.
ALL CONTROLLED FILL MATERIAL SHALL BE A SELECT GRANULAR MATERIAL FREE FROM ALL ORGANICS OR OTHERWISE DELETERIOUS MATERIAL WITH NO MORE THAN 20% BY WEIGHT PASSING A NO. 200 SIEVE (CLASSIFIED AS SC, SM, SP OR BETTER IN ACCORDANCE WITH THE UNIFIED SOIL CLASSIFICATION SYSTEM) AND WITH A PLASTICITY INDEX NOT EXCEEDING 6%.
PROVIDE FIELD DENSITY TESTS FOR EACH 3,000 S.F. OF BUILDING AREA FOR EACH LIFT OF CONTROLLED FILL.
EXCAVATIONS SHALL BE KEPT DRY BY PUMPING UNTIL UNDERGROUND CONSTRUCTION IS COMPLETE.
LOOSENED BEARING SOILS SHALL BE RE-COMPACTED WITH A SMALL VIBRATORY PLATE COMPACTOR PRIOR TO PLACEMENT OF
REINFORCING BARS.
ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED BY THE GEOTECHNICAL ENGINEER PRIOR TO CONCRETE PLACEMENT. ALL SOFTENED OR OTHERWISE UNSUITABLE BEARING MATERIALS SHALL BE REMOVED AND REPLACED WITH LOAD-BEARING FILL OR WITH
LEAN CONCRETE (2,000 PSI).
THE CONTRACTOR SHALL LAYOUT THE ENTIRE BUILDING AND FIELD VERIFY ALL DIMENSIONS PRIOR TO EXCAVATION.
SHORING AND BRACING GENERAL NOTES
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
4.
5.
THE CONTRACTOR SHALL PROVIDE LAYOUT DRAWINGS AND CALCULATIONS FOR SHORING AND BRACING SYSTEM AND OTHER DATA, AS REQUIRED, PREPARED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER LICENSED IN THE COMMONWEALTH OF
PENNSYLVANIA. SUBMIT TO E.O.R. ONE WEEK PRIOR TO THE START OF WORK.
SHORING AND BRACING SHALL COMPLY WITH THE LOCAL BUILDING CODE AND ORDINANCES OF THE LOCAL GOVERNING
AUTHORITIES.
INSPECTION FOR STRUCTURAL STABILITY SHALL BE PROVIDED BY AN APPROVED LICENSED ENGINEER (PA) EMPLOYED BY THE CONTRACTOR, AS REQUIRED BY LOCAL GOVERNING AUTHORITIES. SUBMIT WEEKLY FIELD OBSERVATION REPORTS TO ENGINEER OF
RECORD DURING THE DURATION OF THE SHORING OPERATION.
SUBMIT WEEKLY FIELD OBSERVATION REPORTS TO E.O.R. DURING THE DURATION OF THE SHORING OPERATION BENCHMARKS ARE T0 BE ESTABLISHED BEF0RE EXCAVATI0NS AND RE-SURVEYED WEEKLY BY A LICENSED LAND SURVEY0R EMPLOYED BY THE
CONTRACTOR.
BRACING SHALL BE LOCATED TO CLEAR NEW CONSTRUCTION AND OTHER PERMANENT WORK. MAINTAIN SHORING AND BRACING UNTIL. STRUCTURAL ELEMENTS ARE RE-BRACED BY OTHER BRACING OR UNTIL PERMANENT CONSTRUCTION IS IN PLACE.
FOUNDATION DESIGN AND CONSTRUCTION CRITERIA
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
4.
5.
6.
7.
8.
9.
THE FOUNDATION FOR THIS STRUCTURE HAS BEEN DESIGNED FOR A 2,500 PSF ASSUMED ALLOWABLE SOIL BEARING PRESSURE AT A BEARING DEPTH OF APPROXIMATELY 48" BELOW EXTERIOR GRADE ELEVATION, WITH APPROPRIATE GROUND INSULATION.
THE OWNER SHALL RETAIN THE SERVICES OF A PROFESSIONAL GEOTECHNICAL ENGINEER, SUBJECT TO THE APPROVAL OF THE ENGINEER OF RECORD, TO PERFORM SOIL TESTING AND INSPECTION. THE GEOTECHNICAL ENGINEER SHALL INSPECT THE SUBGRADE TO VERIFY BEARING LEVELS AND ENSURE THAT THE SAFE ASSUMED BEARING CAPACITY MEETS OR EXCEEDS THE DESIGN VALUE INDICATED ON THE CONTRACT DOCUMENTS. FIELD REPORTS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD OUTLINING THE
WORK PERFORMED AND TEST RESULTS.
IF CONDITIONS PROVE TO BE UNACCEPTABLE AT THE BEARING ELEVATIONS SHOWN, THE FOOTING BEARING ELEVATIONS MAY NEED TO BE LOWERED BASED ON THE RECOMMENDATIONS OF THE GEOTECHNICAL ENGINEER. FINAL BEARING ELEVATIONS AND BACKFILL RECOMMENDATIONS MUST BE APPROVED BY THE ENGINEER OF RECORD PRIOR TO FIELD MODIFICATION.
SLAB-ON-GRADE HAS BEEN DESIGNED USING A SUBGRADE MODULUS OF k=100 PCI AND DESIGN LOADING OF 100 PSF LIVE LOAD.
THE GEOTECHNICAL ENGINEER SHALL ENSURE SUBGRADE IS PREPARED TO MINIMUM SPECIFICATION, OTHERWISE THE DESIGNER IS NOT RESPONSIBLE FOR DIFFERENTIAL SETTLEMENT, SLAB CRACKING, OR OTHER FUTURE DEFECTS RESULTING FROM UNREPORTED
CONDITIONS MITIGATING THE ABOVE ASSUMPTIONS.
CONCRETE FOR FOUNDATIONS SHALL BE POURED ON THE SAME DAY THE SUBGRADE IS APPROVED BY THE GEOTECHNICAL
ENGINEER.
MINIMUM DEPTH BELOW GRADE REQUIRED FOR FROST PROTECTION TO BOTTOM OF FOUNDATION = (-X'-X") APPLIES TO ALL PERIMETER WALL FOOTINGS. FOUNDATION SHALL BE PROPERLY INSULATED PER CONSTRUCTION DRAWINGS.
BACKFILL SHALL BE BROUGHT UP EQUALLY ON BOTH SIDES OF FOUNDATION WALLS UNTIL THE FINAL ELEVATION IS ACHIEVED.
VARIATIONS SHALL NOT EXCEED 2'-0" BETWEEN BACKFILL ELEVATIONS ON EITHER SIDE WITHOUT ENGINEER OF RECORD'S APPROVAL.
WHEN STEPPING WALL FOUNDATIONS, THE MAXIMUM STEP SHALL BE ONE UNIT VERTICALLY TO TWO UNITS HORIZONTALLY WHERE
ELEVATIONS CHANGE.
LOCATIONS OF FOOTING STEPS SHOWN ON THE FOUNDATION PLAN ARE APPROXIMATE, IF SHOWN. WHETHER FOOTING STEPS ARE SHOWN ON THE DRAWINGS OR NOT, THE GENERAL CONTRACTOR SHALL FIELD VERIFY EXACT GRADE LOCATIONS AROUND THE BUILDING AND LOCATE ANY FOOTING STEPS IN ORDER TO MAINTAIN A PROPER FROST DEPTH COVER AT ALL LOCATIONS, UNLESS OTHERWISE NOTED ON THE DRAWINGS. CONTRACTOR IS RESPONSIBLE TO ENSURE ALL FOOTINGS HAVE APPROPRIATE FROST DEPTH
COVER. CONTACT ENGINEER OF RECORD IF COURSE OF ACTION IS UNCLEAR.
POST-INSTALLED ANCHOR GENERAL NOTES
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
POST INSTALLED ANCHORS ARE ONLY PERMITTED TO BE USED WHERE INDICATED ON PLANS, DETAILS, OR SCHEDULES.
ALL POST-INSTALLED ANCHORS SHALL BE FROM THE FOLLOWING APPROVED MANUFACTURERS: HILTI, DEWALT, AND REDHEAD. THE MANUFACTURER, DIAMETER, TYPE, SPACING, ETC. SPECIFIED IN THE SECTIONS AND DETAILS OF THIS PROJECT CONTROL. ALL
SUBSTITUTIONS MUST BE PRE-APPROVED BY THE ENGINEER OF RECORD (JHA COMPANIES).
ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED BY HILTI, DEWALT, OR SUCH OTHER METHOD AS APPROVED BY THE ENGINEER OF RECORD. SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY THEIR HAVING AN ICC ESR SHOWING COMPLIANCE WITH THE RELEVANT BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY OF COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER CREEP, IN-SERVICE TEMPERATURE, AND INSTALLATION TEMPERATURE.
INSTALL ANCHORS PER THE MANUFACTURER ’S INSTRUCTIONS, AS INCLUDED IN THE ANCHOR PACKAGING.
OVERHEAD ADHESIVE ANCHORS MUST BE EVALUATED USING THE "HILTI PROFIS" SYSTEM OR "DEWALT DDA" SYSTEM.
THE CONTRACTOR SHALL ARRANGE ANCHOR MANUFACTURER'S REPRESENTATIVE TO PROVIDE ON-SITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. THE ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR'S PERSONNEL WHO WILL INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF INSTALLING
ANCHORS.
ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF ANCHORS TO EDGE OF CONCRETE, AMONG OTHER FACTORS. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON
THE DRAWINGS. DO NOT STRAY FROM STATED DIMENSIONS ON SECTIONS AND DETAILS.
EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS OTHERWISE NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS. HILTI PS 200 FERROSCAN, HILTI PS 1000 X-SCAN, GPR SCAN, X-RAY, CHIPPING, OR OTHER MEANS MAY ALSO BE USED.
DESTRUCTIVE INVESTIGATIVE METHODS MUST BE APPROVED BY THE ENGINEER OF RECORD. REINFORCING BARS SHALL NOT BE CUT
WITHOUT THE APPROVAL OF THE ENGINEER OF RECORD.
ADHESIVE ANCHORS INSTALLED IN HORIZONTAL TO VERTICAL OVERHEAD ORIENTATION TO SUPPORT SUSTAINED TENSION LOADS SHALL BE DONE BY A CERTIFIED ADHESIVE ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI/CRSI (ACI 318-11 D9 2 2)/(ACI 318-14-14 D922). PROOF OF CURRENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO
COMMENCEMENT OF INSTALLATION.
ADHESIVE ANCHORS MUST BE INSTALLED IN CONCRETE AGED A MINIMUM OF 21 DAYS (ACI 318-11 D.2.2)/(ACI318-14 17.1.2).
FIELD CONDITIONFIELD CONDITION ANCHOR SYSTEM (OR EQUIVALENT) ANCHOR SYSTEM (OR EQUIVALENT)
ADHESIVE ANCHOR INTO SOLID MASONRY:
GROUT FILLED CONCRETE BLOCK AND SOLID BRICK
ADHESIVE DOWELING FOR ANCHORING REINFORCEMENT
BARS INTO EXISTING CONCRETE
HILTI HIT-HY 270 SYSTEM (ESR-2682)/(ESR-3342) WITH
HILTI HAS- E THREADED ROD
HILTI HIT-HY 200 SAFE SET SYSTEM (ESR-3187) WITH
HOLLOW DRILL BIT HILTI HIT RE 500 V3 (ESR-3814)
SAFESET SYSTEM (ESR-2322) WITH REBAR AND HOLLOW
DRILL BIT (ESR-2322) SYSTEM
CAST-IN-PLACE CONCRETE GENERAL NOTES
(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)(UNLESS OTHERWISE NOTED OR SHOWN ON PLAN, THE FOLLOWING NOTES SHALL APPLY)
1.
2.
3.
A.
B.
C.
D.
E.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
34.
35.
a.
b.
c.
d.
e.
f.
g.
h.
i.
CONCRETE WORK SHALL CONFORM WITH THE REQUIREMENTS OF THE AMERICAN CONCRETE INSTITUTE ACI 318-14.
UNLESS OTHERWISE INDICATED, ALL CAST-IN-PLACE CONCRETE SHALL DEVELOP A STRENGTH OF 4,000 PSI AT 28 DAYS.
CONCRETE MIXTURES SHALL MEET THE FOLLOWING CRITERIA:
MAXIMUM WATER-CEMENTITIOUS MATERIAL RATIO 0.50.
SLUMP LIMIT:
FOOTINGS, FOUNDATIONS & GRADE BEAMS: 4" TO 8" FOR CONCRETE WITH VERIFIED SLUMP OF 2" TO 4" BEFORE ADDING HIGH-RANGE
WATER-REDUCING ADMIXTURE OR PLASTICIZING ADMIXTURE, PLUS OR MINUS 1".
SLABS-ON-GRADE: 4" PLUS OR MINUS 1".
SUSPENDED SLABS, BEAMS, COLUMNS AND WALLS: 4" TO 8" FOR CONCRETE WITH VERIFIED SLUMP OF 2" TO 4" BEFORE ADDING
HIGH-RANGE WATER-REDUCING ADMIXTURE OR PLASTICIZING ADMIXTURE, PLUS OR MINUS 1".
AIR CONTENT:
FOOTINGS, FOUNDATIONS & GRADE BEAMS: 6%, PLUS OR MINUS 1.5% AT POINT OF DELIVERY.
SLABS-ON-GRADE: DO NOT ALLOW AIR CONTENT OF TROWEL-FINISHED FLOORS TO…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .