1-140P9721Q0047_OTHER-WRST-309504_Design_Drawings.pdf
PDF 2 MB Posted
- Attached to
- KENNECOTT MICROGRID UPGRADES Federal contract opportunity
- Solicitation number
- 140P9721Q0047
About this file
This combined synopsis and solicitation requests quotes for the Kennecott Microgrid Upgrades project located at Kennecott Mines National Historic Landmark in Kennecott, Alaska. The National Park Service requires replacement of the existing powerhouse and power production systems serving park facilities with a new self-contained powerhouse including a 25 kW propane generator, 72 kWh lithium battery bank, 28.8 kW solar PV array, clean agent fire suppression system, and all required hardware and software to provide a complete working hybrid power system. Quotes are due by 3:00 PM Alaska time on June 3, 2021 and must be submitted electronically to the contracting officer. This acquisition is set aside for small businesses. The contractor will furnish and install the solar panels, ground-mounting system, electrical cabling, and prefabricated power house module.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P9721Q0047_Amd_0001.pdf | ||
| Sol_140P9721Q0047.pdf | ||
| 0-140P9721Q0047_SOW-WRST-309504-Kennecott_Microgrid_Upgrades.pdf | ||
| 5-140P9721Q0047_OTHER-WRST-309504_Site_Photos.pdf | ||
| 2-140P9721Q0047_OTHER-WRST-309504_Design_Narrative___Specifications.pdf | ||
| 4-140P9721Q0047_OTHER-WRST-309504_General_Specs_01_00_00.pdf | ||
| 3-140P9721Q0047_OTHER-WRST-309504_CM-16_Submittal_Form.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CIRCLE
PRUDHOE
FAIRBANKS
BERING
SEA
PACIFIC
ANCHORAGE
HOMER
KODIAK
SEWARD
KOTZEBUE
NOME
U N
IT
ED
S
TA
TE
S
R U
S S
I A
NENANA
TANANA
ARCTIC
BAY
WHITEHORSE YT.
HAINES JCT.
OCEAN
CORDOVA
VALDEZ
SITKA
JUNEAU
EAGLE
TOK
GLENNALLEN
POLE
NORTH DAWSON Y.T.
C
AN
AD
A
ST
AT
ES
U
N
IT
ED
CIRCLE
OCEAN
BARROWARCTIC
HAINES
KENNECOTT, ALASKA
MICROGRID UPGRADES IN ALASKA PARKS
KENNICOTT (WRST)
NATIONAL PARK SERVICE
OWNERS REPRESENTATIVE
NATIONAL PARK SERVICE
AMANDA JORDAN
240 WEST 5TH AVENUE, ANCHORAGE, AK 99501
907 644-3311 amanda_jordan@nps.gov
LEAD DESIGNER
DESIGN ALASKA
ELIZABETH JOHNSTON
601 COLLEGE ROAD, FAIRBANKS, AK 99701
907 452-1241 elizabeth@designalaska.com
PROJECT
LOCATION
SEE DISCIPLINES FOR SPECIFIC SYMBOLS
GENERAL
G001 GENERAL INFORMATION
ELECTRICAL
E100 ELECTRICAL POWER SITE PLAN AND DETAILS KENNICOTT
E101 ELECTRICAL PLANS & DETAILS
E102 ELECTRICAL PLANS & DETAILS
E103 ELECTRICAL ADDITIONAL DETAILS
NUMBER
NAME
SHEET LOCATION
SCALE
TRUE NORTH
PLAN NORTH
GRID LINE
REVISION
ROOM NAME
ROOM NUMBER
1/8"=1'-0"
ROOM
NAME
A
GOVERNING CODES
NFPA 70 2017
AUTHORITY HAVING JURISDICTION
STATE OF ALASKA
3/10/2021 4:46 PM 402001 G001 KENNICOTT.DWG
402001
11 MAR 2021
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
MICROGRID
UPGRADES IN
ALASKA PARKS
KENNICOTT (WRST)
G001
DLH
DLH
GENERAL
INFORMATION
CONTRACT NO.: 140P2020Q0066
ORDER NO.: 140P9720F0034
KENNICOTT
PROJECT
LOCATION
PLAN SET NO.: WRST 190 #173741
4 4 4 42
4 4 4 4 4 4 4 4 4 4 4
44 4 4 4 4 4 4 4 4 4 4 4
2 2
4 4 4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4 4 4
2 2 2 2 2
2 2 2 2 2
4 4
JAN 13°
FEB 21°
MAR 29°
APR 37°
MAY 45°
JUL 45°
AUG 37°
SEP 29°
OCT 21°
NOV 13°
DEC 6°
JUN 52°
14'
13'-4"
10'-3"
KENNICOTT OPEN MAY-SEPT
23°
29°
KENNICOTT OPEN MAY (45°) -SEPT (29°)
SPACED TO NOT SHADE PV PANELS OF OTHER ARRAYS
2'-6"
35°
SEASONAL RANGE OF
SOLAR ANGLES 29° - 52°
JUL - DEC JAN - JUN
8'
8'-6"
2'
DOOR
DOOR
DOOR
DOOR DOOR DOOR
OPTION 1 - INLINE OPTION 2 - ANGLE OPTION 3 - SIDE-BY-SIDE
CABLES, TYPE SIZE
AND NUMBER AS
SHOWN ON DRAWINGS
TYPICAL)
STRUCTURAL
FILL
BEDDING MATERIAL
POWER CABLES
SURFACE FINISH TO MATCH
ADJACENT FINISH
MARKER
TAPE
FINISH GRADE
PER NEC
6"
6"
3/10/2021 4:43 PM 402001 E100 SITE PLANS DETAILS.DWG
402001
11 MAR 2021
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
MICROGRID
UPGRADES IN
ALASKA PARKS
KENNICOTT (WRST)
Donald L. Hopkins
No. EE10582
11-MAR-2021
E100
DLH
DLH
ELECTRICAL
POWER SITE PLANS
AND DETAILS
KENNICOTT
EXISTING
GENERATOR
MODULE
DAIRY BARN
DECON
XFMR
480V-208V
RECREATION
HALL
VISITOR CENTER
TRANSFORMER HOUSE
GENERAL STORE
REFRIGERATOR PLANT
WEST BUNK HOUSE
NEW SCHOOL
LEACHING PLANT
UTILIDUCT ON BRIDGE
POWER PLANT
MILL
GENERAL MANAGER'S OFFICE
2 2 2 2 208VAC 3-PHASE DISTRIBUTION FEEDER
4 4 4 4 480VAC 3-PHASE DISTRIBUTION FEEDER
PROPOSED
NEW ELECTRIC &
GENERATOR MODULES
NPS SYSTEM POWER DISTRIBUTION PLAN - KENNICOTT1
E100 128" = 1'-0"
480V - 208V 3-PHASE DRY TYPE TRANSFORMER
EXISTING 4 EA 1000 GALLON PROPANE
TANKS REVISE PROPANE PIPING TO NEW
GENERATOR MODULE AS NEEDED
PROPOSED
PV ARRAYS (4)
XFMR
480V-208V
XFMR
480V-208V
XFMR
480V-208V
XFMR
480V-208V
PRIVATE HOMES
MACHINE SHOP
KENNICOTT GLACIER LODGE SOUTH
KENNICOTT GLACIER LODGE
LOCATION OF POWER LINES ONLY SHOWN SCHEMATICALLY
ACTUAL LOCATIONS OF LINES TO BE FIELD VERIFIED IF NEEDED
14' 14'
14'
SEASONAL SOLAR ANGLE WITH PANEL TILT AND SEPARATION DISTANCES2
E100 NO SCALE
70'
EXISTING GENERATOR MODULE
PROPOSED
NEW ELECTRIC &
GENERATOR MODULES
(OPTION 1 SHOWN)
COORDINATE WITH NPS
FOR FINAL LOCATIONS
PROPOSED
PV ARRAYS (4)
SETS OF 6 PANELS PER EACH
FOUNDATION AND RACKING
12 FOUNDATIONS IN ARRAY
4 EA 1000 GALLON PROPANE TANKS
PV ADJUSTABLE RACKING & FOUNDATION4
E100 NO SCALE
PV PANEL
PV RAILRAIL CONNECTOR
TOP CAP
STOPPER SLEEVE
FASTENER
ANCHOR BASE
USED FOR
ADJUSTABILITY
2" SQUARE
SIGN POST
TUBING
CROSS
BRACING
REINFORCED CONCRETE
FOUNDATION FOOTING
ANCHOR BASE
(TYPICAL 4)
TRENCH DETAIL - TYPICAL3
E100 NO SCALE
DC COMBINER BOX (TYP)
2 - CIRCUITS PER ARRAY
(Vmpp ~ 365 VDC) (Voc ~ 442 VDC) (Impp ~ 10 Amps)
MPPT CHARGE
CONTROLLERS
(TYP)
SINGLE PHASE INVERTER
BANK OF THREE
3-PHASE 4-WIRE 208VAC
POWER
DISTRIBUTION
PANEL
MC-HL CABLES (TYP)
4 #6, 1 #8 GND
(2 CIRCUITS & GND)
PV ARRAY #1 - 18 PANELS 400W EACH = 7.2 kW
PV ARRAY COMBINED
72 PANELS 400W EACH = 28.8 kW
PANEL 'A'
200/3 MCB
208Y/120 V
3 PH, 4 W
200/3
AC OUT
AC IN
GENERATOR SET
31 kVA/25 kW STANDBY
208Y/120 V, 3 PH., 4 W.
100/3
G
AC OUT
AC IN
AC OUT
AC IN
DRY TYPE STEP-UP
30 kVA TRANSFORMER 208V
DELTA-PRI
480Y/277V WYE-SEC
POWER
TO SITE
BATTERY BANK
74 kWh LITHIUM
48VDC NOMINAL
TERMINAL BOXES
AT CABLE TRANSITION
NEW POWER SYSTEMS MODULE
30A 2-POLE
DISCONNECT
(TYP)
SCP
GATEWAY
(E) MC-HL CABLE(S) 3 #2, 1 #6
GND
PV ARRAY #2 - 18 PANELS 400W EACH = 7.2 kW
PV ARRAY #3 - 18 PANELS 400W EACH = 7.2 kW
PV ARRAY #4 - 18 PANELS 400W EACH = 7.2 kW
GSM
CTL
NEW GENERATOR MODULE
MANUAL TRANSFER
SWITCH
ROLL UP
GENERATOR
CONNECTION
OUTSIDE MODULE
LOAD
BY
PASS
GEN
POWER
DISTRIBUTION
PANEL
SBM
GSM - GENERATOR START MODULE (AUTOMATIC)
SCP - SYSTEM CONTROL PANEL
SBM - SYSTEM BATTERY MONITOR
GATEWAY - GATEWAY (FOR SYSTEM WIRELESS INTERFACE)
BATTERY MAIN
DISCONNECT SWITCH
SPLICE BOX ON
EXTERIOR OF MODULE
GROUNDING ELECTRODE SYSTEM TO CONSIST OF:
1 - 2 BARE CU CONNECTED TO 4-GROUND RODS 12" FROM CORNERS OF
LOCATION OF ENCLOSURE
PANEL 'G'
30/3 MCB
208Y/120 V
3 PH, 4 W
30/3
#6
#4
#2 #6
POWER CONNECTIONS
(ONE PER PANEL)
PV CABLES SERIES
CONNECTED 2-STRINGS
3/10/2021 4:23 PM 402001 E101 PLANS & DETAILS.DWG
402001
11 MAR 2021
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
MICROGRID
UPGRADES IN
ALASKA PARKS
KENNICOTT (WRST)
Donald L. Hopkins
No. EE10582
11-MAR-2021
E101
DLH
DLH
ELECTRICAL
PLANS & DETAILS
NPS SYSTEM POWER GENERATION PLAN - KENNICOTT1
E101 NO SCALE
GENERAL SHEET NOTES
1. EQUIPMENT ENCLOSURES ARE BASED ON 8' X 20' CONNEX SHIPPING CONTAINERS. TWO
MODULES TO SEPARATE THE ELECTRONICS FROM THE GENERATOR SYSTEMS.
2. POWER TO SITE CURRENTLY BY DIRECT BURIAL MC-HL TYPE CABLE ROUTED TO
GENERATOR MODULE. CONTRACTOR SHALL PROVIDE A LOCATE FOR THIS CABLE TO
ENSURE DURING TRANSITION THIS CABLE CAN BE RE-ROUTED TO NEW POWER SYSTEMS
MODULE FOR POWERING THE NPS SITE POWER DISTRIBUTION SYSTEMS.
3. POWER TO SITE CONFIGURED TO BE 480Y/277V GROUNDED WYE SYSTEM, HOWEVER THE
NEUTRAL CONDUCTOR MAY NOT BE AVAILABLE FOR THE FEEDER CABLES. IN THESE
INSTANCES THE PHASE AND EQUIPMENT CONDUCTORS WILL BE CONNECTED TO THE
EXISTING CABLES WHERE A NEUTRAL WILL NOT BE INCLUDED WITHIN THESE CONNECTIONS.
FEEDER SCHEDULE
CONDUCTORS, GND, CONDUIT AMPS
1 (4) #3/0 AWG, #6 GND, 2" C. 200
2 (3) #1 AWG, #6 GND, 1-1/4" C. 125
3 (4) #2 AWG, #8 GND, 1-1/4" C. 100
4 (3) #2 AWG, #6 GND, 1 1/4" C. 100
5 (4) #10 AWG, #10 GND, 1" C. 30
PLAN VIEWELEVATION VIEW - SIDE ELEC-ADOOR END ELEVATIONBATTERY BANK ELEVATION ELEVATION VIEW - SIDE ELEC-B SIDE ELEC-A
SIDE ELEC-B
PLAN VIEWELEVATION VIEW - SIDE GEN-ADOOR END ELEVATIONGENERATOR ELEVATION ELEVATION VIEW - SIDE GEN-B SIDE GEN-A
SIDE GEN-B
ACCESS DOOR FOR
OPERATOR PANEL AND
CIRCUIT BREAKER HANDLE
FUEL
CONNECT
A A
A A
(8) CHARGE
CONTROLLERS
(3) DC-AC
INVERTER/
CHARGERS
POWER DISTRIBUTION PANEL (PDP)
AND CABLE CABINETS (BELOW)
PANEL 'A'
TRANSFORMER
A AA A
A A A A
B
B B
B
PDP
B
B
PANEL 'A'
QUAD RECEPTACLE
(LOCATED UNDER PANELBOARD)
TRANSFORMER
A-1
A-4
G-2B
B
G-1
A-4
BATTERY BANK
74 kWh LITHIUM
48VDC NOMINAL
G-6
POWER & CONTROL
BATT CHARGER
BATTERY BANK
74 kWh LITHIUM
48VDC NOMINAL
A-2
G-3
D O
O R
C
LO
SE
D
DOOR OPEN
DOOR OPEN
DOOR OPEN
G-5
A-3
PANEL 'G'
EXHAUST AIR
INTAKE AIR M
EXHAUST FAN
1/4 HP 120VAC
& DAMPERS
CIRCUIT A-5
T
LINE VOLTAGE THERMOSTAT
ON WALL ADJACENT TO PANEL
EXHAUST AIR
INTAKE AIR
GENERATOR
EMERGENCY STOP
PUSHBUTTON
3/10/2021 4:23 PM 402001 E102 PLANS & DETAILS.DWG
402001
11 MAR 2021
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
MICROGRID
UPGRADES IN
ALASKA PARKS
KENNICOTT (WRST)
Donald L. Hopkins
No. EE10582
11-MAR-2021
E102
DLH
DLH
ELECTRICAL
PLANS & DETAILS
NPS POWER SYSTEM AND GENERATOR MODULE PLAN & ELEVATIONS - KENNICOTT1
E102 NO SCALE
GENERAL SHEET NOTES
1. EQUIPMENT ENCLOSURES ARE BASED ON 8' X 20' CONNEX SHIPPING CONTAINERS. TWO MODULES TO SEPARATE THE
ELECTRONICS FROM THE GENERATOR SYSTEMS.
2. POWER TO SITE CURRENTLY BY DIRECT BURIAL MC-HL TYPE CABLE ROUTED TO GENERATOR MODULE. CONTRACTOR SHALL PROVIDE A LOCATE FOR THIS CABLE TO ENSURE DURING TRANSITION THIS CABLE CAN BE RE-ROUTED TO NEW POWER
SYSTEMS MODULE FOR POWERING THE NPS SITE POWER DISTRIBUTION SYSTEMS.
3. POWER TO SITE CONFIGURED TO BE 480Y/277V GROUNDED WYE SYSTEM, HOWEVER THE NEUTRAL CONDUCTOR MAY NOT BE AVAILABLE FOR THE FEEDER CABLES. IN THESE INSTANCES THE PHASE AND EQUIPMENT CONDUCTORS WILL BE CONNECTED TO THE EXISTING CABLES WHERE A NEUTRAL WILL NOT BE INCLUDED WITHIN THESE CONNECTIONS.
SPECIFIC NOTES
CONSTRUCT WALL WITH 3'-0" MAN DOOR WITH RELIGHT WINDOW ON OPEN END OF CONNEX CONFIGURED AS THE ELECTRIC MODULE.
AN ADDITIONAL WINDOW TO BE SLIDER TYPE WITH SCREEN TO COVER OPENING OF WINDOW FRAME WHEN OPEN.
DOOR AND HANDLE TO ELECTRIC MODULE TO BE RESET TO ALLOW FOR CONNEX DOORS TO BE CLOSED/LOCKED SECURED FOR THE OFF
SEASON STORAGE.
CONNEX DOORS TO BE PROPPED OPEN DURING VISITOR SEASON OR OTHER PERIODS WHEN NPS PERSONNEL ARE AT SITE AND POWER
SYSTEMS ARE ACTIVE.
CONSTRUCT WALL WITH 3'-0" MAN DOOR WITH RELIGHT WINDOW ON OPEN END OF CONNEX CONFIGURED AS THE GENERATOR MODULE.
DOOR SIZE TO BE COORDINATED TO ALLOW GENERATOR TO BE MOVED THROUGH DOOR FRAME WITH DOOR PANEL REMOVED.
DOOR AND LOUVER TO BE RESET 18 INCHES TO ALLOW FOR CONNEX DOORS TO BE CLOSED/LOCKED SECURED FOR THE OFF SEASON
STORAGE.
CONNEX DOOR IN FRONT OF MAN DOOR TO BE PROPPED OPEN DURING VISITOR SEASON OR OTHER PERIODS WHEN NPS PERSONNEL ARE
AT SITE AND POWER SYSTEMS ARE ACTIVE.
OTHER DOOR IN FRONT OF LOUVERS TO REMAIN CLOSED TO MITIGATE SOUND TRANSMISSION FROM INSIDE OF THE ENCLOSURE TO THE
OUTSIDE ENVIRONMENT.
PROVIDE SHEET METAL DUCTWORK AND FLEXIBLE CONNECTION TO COVERED HOOD TO VENT ENGINE HEAT AND EXHAUST FROM THE
ENCLOSURE.
DUCTWORK TO BE PROVIDED WITH SOUND DEADENING INTERIOR MATERIAL TO MITIGATE SOUND TRANSMISSION TO THE OUTER
ENVIRONMENT.
PROVIDE ELECTRICALLY OPERATED LOUVERS IN OPENING OF THE ENCLOSURE TO OPEN UPON ENGINE START TO PROVIDE COOLING
INTAKE AND EXHAUST AIR TO THE GENERATOR MODULE.
ENCLOSURE DOOR ON VENT SIDE TO BE CLOSED TO REDUCE SOUND TO ENVIRONMENT WHEN GENERATOR RUNNING.
PROVIDE HEAVY DUTY SCREENING ON INTAKE LOUVER NEXT TO DOOR TO PREVENT INFILTRATION OF BUGS AND/OR FOREIGN MATERIAL
SUCH AS COTTONWOOD FIBERS FROM ENTRY INTO MODULE WHEN THE GENERATOR IS RUNNING.
AFFIX SCREEN WITH SNAPS OR MAGNETS TO ALLOW FOR THE SCREEN TO BE READILY CLEANED AND REPLACED.
PROVIDE ELECTRICALLY OPERATED LOUVERS IN OPENING OF THE ENCLOSURE ND LINE VOLTAGE THERMOSTAT TO OPEN UPON TEMPERATURES OVER 75 DEGREES F TO PROVIDE COOLING INTAKE AND EXHAUST HEATED AIR TO THE ELECTRIC MODULE.
PROVIDE HEAVY DUTY FIBERGLASS TYPE SCREENING ON INTAKE LOUVER NEXT TO DOOR TO PREVENT INFILTRATION OF BUGS AND/OR FOREIGN MATERIAL SUCH AS COTTONWOOD FIBERS FROM ENTRY INTO MODULE WHEN THE EXHAUST FAN IS RUNNING. SCREENING TO BE
ATTACHED WITH SNAPS OR WITH MAGNETS SO IS EASILY REMOVABLE AND CLEANABLE.
AFFIX SCREEN WITH SNAPS OR MAGNETS TO ALLOW FOR THE SCREEN TO BE READILY CLEANED AND REPLACED.
PROVIDE CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR GENERATOR AND ELECTRICAL MODULES FOR PROTECTION OF ENCLOSED SYSTEMS. WHERE LOUVERS ARE PRESENT IN THE ENCLOSURE, THE FIRE SUPPRESSION SYSTEM TO COMMAND THESE LOUVERS TO CLOSE
PRIOR TO DEPLOYMENT OF THE CLEAN AGENT SYSTEM.
BASIS OF DESIGN LIGHTING FIXTURE SCHEDULE
FIXTURE LUMEN DESCRIPTION MOUNTING MFR'S NO. MANUFACTURER
TYPE OUTPUT HEIGHT
A 4000 4' LED HIGH POWER STRIPLIGHT WITH
WIREGUARD AND MULTIVOLT DRIVER.
SURFACE
CEILING
CSS L48 4000LM MVOLT
80CRI WG
LITHONIA
B 880 SURFACE
WALL +7'-6"
LITHONIA
ELECTRIC AND GENERATOR MODULE VENTILATION SCHEMATIC DIAGRAMS2
E102 NO SCALE
M
M
TR
LINE
NEUTRAL
VENT DAMPER
ACTUATORS 120VAC
INTAKE AND EXHAUST
GENERATOR RUN RELAY
GENERATOR MODULE DAMPER CONTROL SCHEMATIC DIAGRAM
M
M
LINE
NEUTRAL
VENT DAMPER
ACTUATORS 120VAC
INTAKE AND EXHAUST
ELECTRIC MODULE FAN & DAMPER CONTROL SCHEMATIC DIAGRAM
LINE VOLTAGE
COOLING THERMOSTAT
M
EXHAUST FAN
NC CONTACTS IN FIRE SUPPRESSION SYSTEM
TO SHUT DOWN DAMPERS UPON RELEASE
NC CONTACTS IN FIRE SUPPRESSION SYSTEM
TO SHUT DOWN DAMPERS/FAN UPON RELEASE
TYPE 'B' LIGHT OPTIONAL. CONSULT WITH CONTRACTING OFFICER TO DETERMINE IF THIS LIGHT IS INCLUDED IN BID.
WALL MOUNT AMBER PHOSPHOR CONVERTED
WITH PHOTOCELL / MOTION SENSOR.
DSXW 10C 350 AMBPC
MVOLT PIR
3/10/2021 4:33 PM 402001 E103 ADDITIONAL DETAILS.DWG
402001
11 MAR 2021
COMM. NUMBER
ISSUE DATE
DESIGNED BY
DRAWN BY
1"0" SCALE
601 College Road Fairbanks AK 99701 907.452.1241
Architects SurveyorsEngineers
AECC511 designalaska.com
MICROGRID
UPGRADES IN
ALASKA PARKS
KENNICOTT (WRST)
Donald L. Hopkins
No. EE10582
11-MAR-2021
E103
DLH
DLH
ELECTRICAL
ADDITIONAL
DETAILS
UNIT SHELL CONSTRUCTION - COMMON TO BOTH EQUIPMENT MODULES
FLOORING: 3/4” OSB SUBFLOOR AND 80 MILS POLYUREA POLYSHIELD HT100
2X4'S ON 16” CENTER WITH 3/4” T&G PLYWOOD PAINTED WHITE
CEILING: 2X4'S ON 24” CENTER WITH 3/4” PLYWOOD PAINTED WHITE
INSULATION: ENVELO-SEAL 2.0 SPRAY FOAM; FLOOR, WALLS, AND CEILING - R18
FRONT WALL: 2X4'S ON 16” CENTER, 3/8” AC PLYWOOD, AND R13 FIBERGLASS INSULATION
EXTERIOR DOOR: 36” WOOD FRAMED INSULATED METAL DOOR WITH SCHLAGE KEYED ENTRY [QTY 1/MODULE KEYED ALIKE]
36”X36” DOUBLE PANE SINGLE SLIDER WINDOW WITH BUG SCREEN
DAMPERS: 36”X36” EXTREME TEMPERATURE THERMALLY EFFICIENT BLADE DAMPER [QTY 2]
ACTUATOR: ON/OFF WITH SPRING RETURN, 120V ACTUATOR WITH 22 IN-LB MOTOR [QTY 2]
DAMPER RAIN HOOD: 36” X 36” WITH SOUND ATTENUATION MATERIAL [QTY 1]
DUCTWORK FOR GENERATOR EXHAUST CONNECTION [QTY 1]
LOUVERED DAMPER FOR
GENERATOR MODULE ONLY
GENERAL VIEW OF DOORS
AND WINDOW/DAMPER
PV POWER CABLE ROUTING AND CROSS BRACING DETAILS1
E103 NO SCALE
CHAMFER EDGES
OF FOUNDATION 1"
PV CABLES &
CONNECTORS
SPLICE BOX FOR TRANSITION
OF PV CABLES TO MC-HL CABLE
MC-HL CABLE
MC-HL CABLE TO EQUIPMENT MODULE
(1 CABLE PER SET OF PV PANELS)
RACKING CROSS BRACING
SIDE ELEVATION OF RACK & FOUNDATION FRONT ELEVATION OF RACK & FOUNDATION
TOP PLAN OF FOUNDATION PLAN OF SETS (3) OF ARRAY FOUNDATIONS
CONFIGURE PV ARRAYS AND
RACKING TO PROVIDE MINIMUM OF
12" BETWEEN PV PANELS TO ALLOW
FOR MOVEMENT OF PADS
PANEL 'A'
CKT P TRIP LOAD SERVED LOAD
TYPE
LOAD
(VA) BUS
LOAD
(VA)
LOAD
TYPE LOAD SERVED TRIP P CKT
NO.NO.
1 1 20 LTS - ELEC MODULE L 97 A 180 R REC - ELEC RM EXT 20 1 2
3 1 20 CLEAN AGENT CTL - ELEC L 97 B 720 R REC - ELEC RM 20 1 4
5 1 20 EXHAUST FAN 1/4 HP/DAMPERS E 3 C 0 S SPARE 20 1 6
7 1 20 SPARE E 100 A 0 S " " 20 1 8
9 1 20 " " E 50 B 0 S " " 20 1 10
11 -- -- PREPARED SPACE E 50 C 0 S PREPARED SPACE -- -- 12
13 -- -- " " S 0 A 0 S " " -- -- 14 15 -- -- " " S 0 B 0 S " " -- -- 16 17 -- -- " " S 0 C 0 S " " -- -- 18
19 -- -- " " S 0 A 3,000 E TRANSFORMER TO FEED NPS FACILITIES 125 3 20
21 -- -- " " S 0 B 3,000 E " " 22 23 -- -- " " S 0 C 3,000 E " " 24
25 3 30 FEEDER TO PANEL G F 457 A 0 S PREPARED SPACE -- -- 26
27 " " F 183 B 0 S OR -- -- 28
29 " " F 150 C 0 S DOUBLE LUG BREAKER -- -- 30
MAIN: 200 AMPS MCB PHASE A: 3,734 VA 31.1 A CONNECTED: 11,167 VA NOTES
TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 3,953 VA 32.9 A AMPS: 31.0 A
AIC: 10,000 RMS SYMM. AMPS PHASE C: 3,480 VA 29.0 A VOLTAGE: 208 V
N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:
LIGHTING 0 VA 0.0 A L = LIGHTING (LOAD X 125%)
RECEPTACLES 1,440 VA 4.0 A R = RECEPTACLES (NEC 220.44)
EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%
EQUIPMENT (NON-CONTINUOUS) 9,533 VA 26.5 A E = EQUIPMENT (NON-CONTINUOUS) X 100%
MOTORS 0 VA 0.0 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)
TOTAL DEMAND LOAD 10,973 VA 30.5 A F = FEEDERS
MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION
SURFACE RM ELEC
PANEL 'G'
CKT P TRIP LOAD SERVED LOAD
TYPE
LOAD
(VA)
BU
S
LOAD
(VA)
LOAD
TYPE LOAD SERVED TRIP P CKT
NO.NO.
1 1 20 REC - GEN RM R 360 A 97 L LTS - GEN MODULE 20 1 2
3 1 20 REC - GEN RM EXT R 180 B 3 E VENT DAMPERS 20 1 4
5 1 20 CLEAN AGENT CTL - GEN E 50 C 100 E GEN SET BATT CHARGER 20 1 6
7 1 20 SPARE S 0 A 0 S PREPARED SPACE -- -- 8
9 1 20 " " S 0 B 0 S " " -- -- 10
11 -- -- PREPARED SPACE S 0 C 0 S " " -- -- 12
13 -- -- " " S 0 A 0 S " " -- -- 14 15 -- -- " " S 0 B 0 S " " -- -- 16 17 -- -- " " S 0 C 0 S " " -- -- 18
MAIN: 100 AMPS MCB PHASE A: 457 VA 3.8 A CONNECTED: 790 VA NOTES
TYPE: 208Y/120 V 3 PH, 4 W. PHASE B: 183 VA 1.5 A AMPS: 2.2 A
AIC: 10,000 RMS SYMM. AMPS PHASE C: 150 VA 1.2 A VOLTAGE: 208 V
N.E.C. FEEDER CALCULATIONS: (VA) (A) LOAD TYPE:
LIGHTING 0 VA 0.0 A L = LIGHTING (LOAD X 125%)
RECEPTACLES 540 VA 1.5 A R = RECEPTACLES (NEC 220.44)
EQUIPMENT (CONTINUOUS) 0 VA 0.0 A C = EQUIPMENT (CONTINUOUS) X 125%
EQUIPMENT (NON-CONTINUOUS) 153 VA 0.4 A E = EQUIPMENT (NON-CONTINUOUS) X 100%
MOTORS 0 VA 0.0 A M = MOTORS (LOAD + 25% OF LARGEST MOTOR)
TOTAL DEMAND LOAD 693 VA 1.9 A F = FEEDERS
MOUNTING SPECIAL REQUIREMENTS: S = SPARE OR SPACE LOCATION
SURFACE RM GEN
File details come from the government source that posted it. Updated .