096513 Resilient Base Specs.docx
DOCX document 29 KB Posted
- Solicitation number
- 36C25021B0029
About this file
This document provides specifications for a federal construction project to modernize finishes at a Veterans Affairs medical center in Columbus, Ohio. The project scope includes replacing flooring and resilient base in public areas of the first floor, and will take place at the Chalmers P. Wylie VA Ambulatory Care Center. The solicitation number is 36C25021B0029 and it is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses, who must be small under NAICS code 238330 with a size standard of $16.5 million. The SDVOSB is required to perform a minimum of 25% of the construction work. Bid, payment and performance bonds will be required. The estimated value is between $250,000 and $500,000. A pre-bid site visit will be scheduled and the solicitation will be posted on SAM.gov on or around March 22nd 2021 with bids due approximately 30 days later. Questions are due in writing to the contracting officer by the specified deadline.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25021B0029 0001.docx | DOCX document | |
| Drawings - Combined.pdf | ||
| 096800 Capreting Specs - UPDATED.docx | DOCX document | |
| 36C25021B0029_1.docx | DOCX document | |
| VAACC Health Requirements FINAL.docx | DOCX document | |
| VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf | ||
| 096519 Resilient Tile Flooring Specs.docx | DOCX document | |
| Franklin WD 02.26.2021.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
01-01-21
SECTION 09 65 13
RESILIENT BASE AND ACCESSORIES
GENERAL
SUMMARY
Section Includes:
Resilient base (RB) adhered to interior walls and partitions.
RELATED REQUIREMENTS
Sheet Flooring Integral Base: Section 09 65 16, RESILIENT SHEET FLOORING.
APPLICABLE PUBLICATIONS
Comply with references to extent specified in this section.
ASTM International (ASTM):
| F134415 | Rubber Floor Tile. |
| F185914e1 | Rubber Sheet Floor Covering without Backing. |
| F186014e1 | Rubber Sheet Floor Covering with Backing. |
| F186116 | Resilient Wall Base. |
| D425918 | Preparation of Concrete by Abrasion Prior to Coating Application. |
Federal Specifications (Fed. Spec.):
RRT650E (1994) Treads, Metallic and NonMetallic, SkidResistant.
International Concrete Repair Institute (ICRI):
310.2R2013 Selecting and Specifying Concrete Surface Preparation for Sealers, Coatings, Polymer Overlays, and Concrete Repair.
SUBMITTALS
Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
Manufacturer's Literature and Data:
Description of each product.
Adhesives and primers indicating manufacturer's recommendation for each application.
Installation instructions.
Samples:
Resilient Base: 150 mm (6 inches) long, each type and color.
Operation and Maintenance Data:
Care instructions for each exposed finish product.
DELIVERY
Deliver products in manufacturer's original sealed packaging.
Mark packaging, legibly. Indicate manufacturer's name or brand, type, color, production run number, and manufacture date.
Before installation, return or dispose of products within distorted, damaged, or opened packaging.
STORAGE AND HANDLING
Store products indoors in dry, weathertight facility.
Protect products from damage when handling and during construction operations.
FIELD CONDITIONS
Environment:
Product Temperature: Minimum 21 degrees C (70 degrees F) for minimum 48 hours before installation.
Work Area Ambient Temperature Range: 21 to 27 degrees C (70 to 80 degrees F) continuously, beginning 48 hours before installation.
Install products when building is permanently enclosed and when wet construction is completed, dried, and cured.
WARRANTY
Construction Warranty: FAR clause 52.24621, "Warranty of Construction."
PRODUCTS
PRODUCTS
Johnsonite/Tarkett Millwork Resilient Wall Base, Inflection Profile, 5.25”H, .375”D, Color: 11 Canvas Basis of Design: Section 09 06 00, SCHEDULE FOR FINISHES.
Provide each product from one manufacturer and from one production run.
Sustainable Construction Requirements:
Low PollutantEmitting Materials: Comply with VOC limits specified in Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS for the following products:
Flooring Adhesives and Sealants.
RESILIENT BASE
Resilient Base: .375” thick, 5.25” high.
Type: Rubber or vinyl; use one type throughout.
ASTM F1861, Type TP thermoplastic rubber or Type TV thermoplastic vinyl, Group 2 - layered.
PRIMER (FOR CONCRETE FLOORS)
Primer: Type recommended by adhesive manufacturer.
LEVELING COMPOUND (FOR CONCRETE FLOORS)
Leveling Compound: Provide products mixed with latex or polyvinyl acetate resins.
ADHESIVES
Adhesives: Low pollutantemitting, water based type recommended by adhered product manufacturer for each application.
EXECUTION
PREPARATION
Examine and verify substrate suitability for product installation.
Protect existing construction and completed work from damage.
Remove existing base to permit new installation.
Dispose of removed materials.
Correct substrate deficiencies.
Fill cracks, pits, and depressions with leveling compound.
Remove protrusions; grind high spots.
Apply leveling compound to achieve 3 mm (1/8 inch) in 3 m (10 feet) maximum surface variation.
Clean substrates. Remove contaminants capable of affecting subsequently installed product's performance.
Mechanically clean concrete floor substrate according to ASTM D4259.
Surface Profile: ICRI Guideline No. 310.2R.
Allow substrate to dry and cure.
Perform flooring manufacturer’s recommended bond, substrate moisture content, and pH tests.
INSTALLATION GENERAL
Install products according to manufacturer's instructions.
When instructions deviate from specifications, submit proposed resolution for Contracting Officer consideration.
RESILIENT BASE INSTALLATION
Applications:
Install resilient base in rooms scheduled on Drawings.
Install resilient base on casework and other curb supported fixed equipment.
Extend resilient base into closets, alcoves, and cabinet knee spaces, and around columns within scheduled room.
Lay out resilient base with minimum number of joints.
Length: 600 mm (24 inches) minimum, each piece.
Locate joints 150 mm (6 inches) minimum from corners and intersection of adjacent materials.
Installation:
Apply adhesive uniformly for full contact between resilient base and substrate.
Set resilient base with hairline butted joints aligned along top edge.
// Field // Factory // form corners and end stops.
Vgroove back of outside corner.
Vgroove face of inside corner and notch cove for miter joint.
Roll resilient base ensuring complete adhesion.
- E N D -