FLANDREAU SUBSTATION
STAGE 09
SOUTH DAKOTA
SECTION C
DESCRIPTION/SPECIFICATIONS
Solicitation No. 89503421BWA000022 Spec. No. 21WC138924-1011
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION DRAWINGS: Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale. Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: Where details shown on standard drawings included herein differ from construction or project drawings or text, the details of construction or project drawings or text shall govern. A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise Western of any errors or omissions.
B. LIST OF DRAWINGS:
LOCATION MAP:
1. FL 0016 Rev. B – Location and Vicinity Map
ELECTRICAL:
2. FL 0001 Rev. M EI – Switching Diagram (Existing Installation)
3. FL 0001 Rev. N – Switching Diagram
4. FL 1010 Rev. E EI – Arrangement Plan (Existing Installation)
5. FL 1010 Rev. F – Arrangement Plan
6. FL 1012 Rev. D EI – Transformer KY1A 115, 69 and 12.47kV Areas Plan (Existing Installation)
7. FL 1012 Rev. E – Transformer KY1A 115, 69 and 12.47kV Areas Plan
8. FL 1100 Rev. C – Equipment and Material Index
9. FL 1101 – Substation Signs
10. FL 1114 Rev C EI – Transformer KY1A 115 and 69kV Areas Sections (Existing Installation)
11. FL 1114 Rev D – Transformer KY1A 115 and 69kV Areas Sections
12. FL 1115 Rev. E EI – Transformer KY1A 12.47kV Area Sections (Existing Installation)
13. FL 1115 Rev. F – Transformer KY1A 12.47kV Area Sections
14. FL 1117 – 69kV Area Sections
15. FL 1500 Rev. C EI – Key Grounding Plan (Existing Installation)
16. FL 1500 Rev. D – Key Grounding Plan
17. FL 1511 Rev. D EI – Transformer KY1A 115, 69 and 12.47kV Areas Grounding Plan (Existing Installation)
18. FL 1511 Rev. E – Transformer KY1A 115, 69 and 12.47kV Areas Grounding Plan
19. FL 1610 Rev. C EI – 240/120V Power and Lighting Wiring Diagram (Existing Installation)
20. FL 1610 Rev. D – 240/120V Power and Lighting Wiring Diagram
21. FL 1611 Rev. C EI – Distribution Panel DW1C, DW1D, Transformers KW1C, KW1D and KZ1A Wiring Diagram (Existing Installation)
22. FL 1611 Rev. D – Distribution Panel DW1C, DW1D, Transformers KW1C, KW1D and KZ1A Wiring Diagram
23. FL 1711 – Transformer KY1A 115, 69 and 12.47kV Areas Conduit and Buried Cable Plan
CIVIL & SITE DRAWINGS:
24. 2004 Rev. E FIO – Grading and Plot Plan (For Information Only)
FOUNDATION AND STRUCTURAL DRAWING INDEX:
25. FL 2008 Rev. O EI – Foundation/Structural Data and Drawing Index (Existing Installation)
26. FL 2008 Rev. P – Foundation/Structural Data and Drawing Index
CONCRETE:
27. FL 2005 Rev. N EI – Foundation General Plan (Existing Installation)
28. FL 2005-1 – Foundation General Plan (Sheet 1 of 3)
29. FL 2005-2 Rev. A – XFMR KY1A 115, 69 & 12.47kV Areas Foundation Plan (Sheet 2 of 3)
30. FL 2005-3 FIO – 115kV Area Foundation Plan (Sheet 3 of 3) (For Information Only)
31. FL 2006 Rev. D EI – Concrete Structures Foundations (Existing Installation)
32. FL 2006 Rev. E – Concrete Structures Foundations
33. FL 2016 Rev. C EI – Foundations Outline and Reinforcement (Existing Installation)
34. FL 2016 Rev. D – Foundations Outline and Reinforcement
35. FL 2017 Rev. B EI – Foundations Outline and Reinforcement (Existing Installation)
36. FL 2017 Rev. C – Foundations Outline and Reinforcement
37. FL 2301 – Foundations Outline and Reinforcement https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx
PROJECT DRAWINGS
38. FL 2302 – Foundations Outline and Reinforcement
39. FL 2303 Rev. A – Foundations Outline and Reinforcement
ANCHORAGE TO CONCRETE:
40. FL 2550 – Anchor Bolts & Embeds
STEEL STRUCTURES:
41. FL 2600 – Bus Frames Steel Design and Details
42. FL 2601 – Bus Frames Steel Design and Details
43. FL 2602 Rev. A – 69kV Take-Off Structure and Equipment Support Elevations
44. FL 2603 Rev. A – 69kV Take-Off Structure and Equipment Support Assemblies and Connections
45. FL 2925 – Equipment Cabinet Platforms Steel Design and Details
46. FL 2926 – Switch Operating Platforms Steel Design and Details
STRINGING REQUIREMENTS:
47. FL 2027 EI – Stringing Requirements (Existing Installation)
48. FL 2027 Rev. A – Stringing Requirements
CONTROL:
49. FL T600 – 69Kv Bay Addition Control Cable List
GEOLOGY:
50. FL 8000 – Geology Log PR-A
51. FL 8001 – Geology Log PR-B
52. FL 8002 – Geology Log PR87-1
53. FL 8003 – Geology Log PR87-2
54. FL 8004 – Geology Log PR87-3
55. FL 8005 – Geology Log PR87-4
56. FL 8006 – Geology Log PR87-5
57. FL 8007 – Geology Log PR87-6
58. FL 8008 – Geology Log PR87-7
STANDARD DRAWINGS:
59. 31 1085 Rev I – Terminal and Fuse Boxes
STATION SERVICE XFMR
KZ1A
100 KVA 67KV-120/240V
STATION SERVICE
FL 2051
FUSE FZ1A 69KV
EAST RIVER COOP #2
FL 2252
PCB JZ2A 69KV
EAST RIVER COOP #2
FL 2253
DISC SW WZ2A 69KV
EAST RIVER COOP #2
FL 2251
DISC SW YZ2A 69KV
EAST RIVER COOP #2
QZ22A1
CURRENT XFMR 69KV
EAST RIVER COOP #2
QZ22A2
CURRENT XFMR 69KV
EAST RIVER COOP #2
QZ22A3
CURRENT XFMR 69KV
EAST RIVER COOP #2
VZ22A1
CCVT 69KV
EAST RIVER COOP #2
EZ22A1
VZ22A1 SECONDARY FUSES
EAST RIVER COOP #2
EZ22A
QZ22A SHORTING BLOCKS
EAST RIVER COOP #1
VZ21A1
CCVT 69KV
EAST RIVER COOP #1
QZ21A1
CURRENT XFMR 69KV
EAST RIVER COOP #1
QZ21A2
CURRENT XFMR 69KV
EAST RIVER COOP #1
QZ21A3
CURRENT XFMR 69KV
EAST RIVER COOP #1
EZ21A1
VZ21A1 SECONDARY FUSES
EAST RIVER COOP #1
EZ21A
QZ21A SHORTING BLOCKS
Denton For Information Only
N
C
1;
C C w
C w w
E L 0.-□
"' C "' 0
NL,_ ��
I C
D W
NL
D-□ N C
�s; 00 0 C c� .8 � C � W(I) .. 00 "'�
CD �
� E
PHASE SPACING
INSULATOR MOUNTING BRACKET
1/2"" VENT HOLE,
NS & FS 1 1/2"
FROM END OF TUBE
H w I wc:: ::::, COLUMN SPACING
PLAN
PHASE SPACING
BEAf.1
COLUMN SPACING
9"
1/4 cc
B
A
B
HOLE MAY BE FLAME
CUT WITH 1 1/2"
RADIUS AT CORNERS
DETAIL T
HOLES FOR 1/2"" BOLTS D"" ANCHOR BOLTS
DRILL & TAP (x2) di I L: C"" HOLES FOR
GROUNDING CONNECTION -�----1'------�--
I
I CSEE TABLE BELOW)
1" l --i 1"
SECTION 8-8
BASE PLATE ASSEMBLY
BASE DETAIL DIMENSIONS
COLUMN SIZE PLATE
I I C THICKNESS A B I
HSS 8x8x1/4 1 1/2" 5 3/4" I a" I 1 7/16" I
3/4" BENT PL
D 1 1/4"
� j 1 1/2" · _1 +--+---+�
1 1/2"
� r:LUMN
BEAM
I
�1" PLATE (TYP)
SECTION C-C
W10x50x5'-0" W10x50x5'-0"
COLUMN CTYPJ
TOP OF
---'---==+=_!� CTYP)
CONCRETE
1/4 1/4
1/4" COVER PLATE M�1
----1----1-
EAOi SIDE, TYPI l 5/8"" HOLE FOR
1/2"" THROUGH BOLT
COLUMN SPACING
ELEVATION
STRUCTURE VOLTAGE STRUCTURE COLUMN
1YPE CKVl HEIGHT
COLUMN SIZE
SPACING
VII 69 22'-0" HSS 8x8x1/4 6 1 -611
BEAM SIZE
HSS 8x8x1/4
PHASE STRUCTURE
SPACING WEIGHT C I bsl
5 1 -011 2488
HSS8x8 COLUMN
8"
HSS8x8
STIFFENER PLATES
PL 1/2"x4 1/2"x8 7/8" Cx3l EACH SIDE OF
WEB, SPACED @28"0.C.
(SIX TOTAL PER W10l
PL 1x10x10
DETAIL 8
18"±
10"± W10x50
SECTION W-W
TOP OF W10x49 IS LOCATED
6" BELOW BOTTOM OF BEAM
1/2x16 GAUGE EXPANDED METAL
GRATING, SPOT WELDED IN TUBE
SEE NOTE ,fl,8 _ _.__,_-+-Ci_
W10x49x5'-0"
10"
CAP PL
3/4" BENT PL
DETAIL T
1/2" l(x4l-11/16"" HOLES ON
5" BC FOR 5/8"" BOLTS
BEAM
CAP PLATE
PL 1 "x10"x10"
NOTES
1. ADDITIONAL NOTES AND REFERENCE DRAWINGS ARE
SHOWN ON FL 2008.
2.STRUCTURAL STEEL: ASTM A572 GR 50.
3.STRUCTURAL STEEL TUBING: ASTM A500, GRADE B.
4.GALVANIZE MATERIAL AFTER FABRICATION.
5.WELDS ARE TYPICAL FOR SIMILAR CONDITIONS.
6.START AND STOP WELDS AT CENTER OF TUBING.
7.BOLTS ARE 1"<1>, ASTM A325N (WITH 1 1/16" HOLES),
UNLESS NOTED OTHERWISE CUNOJ.
8.ELECTRICAL MOUNTING DIMENSIONS ARE UNKNOWN.
HOLES SHALL BE DRILLED IN FIELD TO MOUNT
ELECTRICAL EQUIPMENT.
UNITED STATES DEPARTMENT OF ENERGY
WESTERN AREA POWER ADMINISTRATION
HEADQUARTERS - LAKEWOOD. COLORADO
FLANDREAU SUBSTATION
SOUTH DAKOTA
BUS FRAMES
STEEL DESIGN AND DETAILS
DESIGNED �R..!5._ �S�G�_ _ _ _ _ APPROVED GINA CRAWFORD ______ _
CIVIL ENGINEERING MANAGER
0 / A DECEMBER 22. 2020 FL 2601 ��LXR_EF_I-SI-,--------------------------------------------------------------------------------------....... "--------....... --....... =---....... -==---------'
C
.0 w
D
C
C
L u a C
.8 i f;; �
Cl �
"O •• • W(/) 0
-wL
11" 11" 8" 8"
3" --=-------- I+-
HSS 12x12x1/4
'- II
N '.._ IN-,
ii:, I I I a, I
I I
I I N
I I � ii:, a, IN
II ;::
1/2" STIFFENER I 10 1/2" 10 1/2" I
PLATES, 1YPICAL
SECTION D-D
(BEAM-TO-COLUMN CONNECTION)
l 1 1/16''- DRILLED
HOLES, ROUND EDGES
1/16", 1 1/4" EDGE
DISTANCE
11" 11"
5/16
HSS 12x12x1/4
HSS
3/8
HSS 8x8x1/4 t 1/2"- VENT HOLE, BF ii:, ii:, 1 1/2" FROM END OF PLATE
C1YPICAL FOR BEAM SPLICE)
SECTION A-A c2602i
COGW ATTACHMENT)
10" 8"-
II
I I I
I
,J �1 + L
T '\.
I f �I '\.
ii
10" 8"
I
I
I
I
1 1
1/
,..... r7
/114P
1"---- HOLE MAY BE
CUT WITH 1 1
FLAME
/2"
RADIUS AT CORNERS
SECTION F-F
(GROUND MAST-BEAM CONNECTION)
5/16
I I PL 3/8x3x1
:J 2"
SECTION K-K c 2502i
(OPERATING ARM MOUNT)
t COLUMN
1 1 -0" 1/4"
PL 1 "x20"x22"
ASTM A572,
GRADE 50
HSS 12x12x1/4
_j PL 1 "x22"x23"
C I ASTM A572,
..J GRADE 50
DETAIL A c2602i E
(COLUMN, HIGH BEAM AND GROUND MAST
CONNECTION)
I I l COLUMN� 21 -011
STIFFENER
PLATES
DETAIL B c2602i
CCOLUM TO LOWER-BEAM CONNECTION)
11" 11" 1"
8" 8"
3"
3"
HSS 12x12x1/4
GROUND MAST
HSS 12x12x1/4
HIGH BEAM
1/4
1/4 t COLUMN
SECTION E-E
(COLUMN, BEAM AND GROUND MAST CONNECTION)
17"
SECTION L-L
HOLE MAY BE
FLAME CUT WITH
1 1/2" RADIUS
AT EACH CORNER
PL 1"
(SPLICE PLATE FOR LOW BEAM)
1 '-6"
811 511
PL 1x15x21 HSS 12x12x1/4
1 1 -011
3/16" COVER PLATE
HOLE MAY BE
FLAME CUT WITH
1 1/2" RADIUS
AT EACH CORNER
PL 1"
HSS 12x12x1/4
SECTION M-M
(SPLICE PLATE FOR HIGH BEAM)
611 611 t 1 .. _ DRILLED HOLES, --HI>------- ---10-+-�--+ ROUND EDGES 1/ 16", 1 1/2" EDGE DISTANCE
HSS 8x8x1/4
-------- t 11/16"
HOLES FOR
5/8"- BOLTS
t t FOR MOUNTING
SWITCHES
DETAIL C c2602i (SWITCH MOUNTl it Cx4l-1"- HOLES PL 1"x17"x17"
HSS 8x8x1/4
� 11.42" 1 .2.79" �r
SECTION J-J c2602 & 2603l (EQUIPMENT MOUNTING PLATEl t. 5/8"- HOLE FOR
1/2"-x22"LONG HSS 12x12x1/4
1 '-3"
HOLE MAY BE FLAME CUT WITH
1 1/2" RADIUS AT CORNERS
SECTION C-C
CHIGH BEAM-COLUMN CONNECTION)
PL 3/8x3x7 (COLUMN B ONLYl
I ;;-;,PL 3/Bx3x7 3"
THROUGH BOLTS
DETAIL V
BIRD NEST PLATES
AT EACH BENT ELECTRICAL
EQUIPMENT ATTACHMENT PL
PROVIDE 2 BIRD NEST PLATES
AND 2 THROUGH BOLTS
AND 2 NUTS AND WASHERS
AS SHOWN IN DETAIL V
SECTION 2-Z SECTION H-H c2602i
(OPERATING ARM MOUNT) (ELECTRICAL EQUIPMENT ATTACHMENT PLATE)
PL 1x15x21 t
DETAIL G c2602i
CONDUCTOR ATTACHMENT
HSS12x12x1/4
BENT & GALVANIZED,
EQUIP.-MOUNT PLATES:
18"WIDE
1/4
PL 1x15x21
1/2"x6" II 6" BENT PLATES
DETAIL T c2602i
(ELECTRICAL EQUIPMENT ATTACHMENT PLATE)
1/4 NOTES
1. ELEVATIONS ARE SHOWN ON FL 2602.
2. BOLTS ARE 1 1/8"- ASTM A325 C 1 3/16"- HOLESl
UNLESS OTHERWISE NOTED.
3. STEEL IS ASTM A36 UNLESS OTHERWISE NOTED.
4. 3/16" COVER PLATE REQUIRED FOR EXPOSED ENDS.
5. "X" DIMSENSION SHALL BE DETERMINED BY CONTRACTOR
AND SHALL FIELD-DRILLED TO MATCH MATCH THE
ELECTRICAL EQUIPMENT AT NO ADDITIONAL COST TO
WESTERN. THIS FIELD-DRILLING IS MENTIONED
IN DIVISON 4 OF THE SPECIFICATION.
EXPLANATION
Q INDICATES MINOR REVISION
MINOR REVISIONS.
UNITED STATES DEPARTMENT OF ENERGY
WESTERN AREA POWER ADMINISTRATION
HEADQUARTERS - LAKEWOOD. COLORADO
FLANDREAU SUBSTATION
SOUTH DAKOTA
69KV TAKE-OFF STRUCTURE
AND EQUIPMENT SUPPORT
ASSEMBLIES AND CONNECTIONS
DESIGNED �� �.Ql�R_ _ _ _ _ APPROVED GINA CRAWFORD _____ _
CIVIL ENGINEERING MANAGER
:§�-:, A DECEMBER 22, 2020 FL 2603
�H(/)�---------------------------------------------------------------------------------------��-------�--��--����
AutoCAD SHX Text
WESTERN AREA POWER ADMINISTRATION
AutoCAD SHX Text
UNITED STATES DEPARTMENT OF ENERGY1
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text E
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text
DESIGNED
AutoCAD SHX Text
FLANDREAU SUBSTATION
AutoCAD SHX Text
SOUTH DAKOTA
AutoCAD SHX Text
CONTROL CABLE LIST
AutoCAD SHX Text
ELIJAH MASKA
AutoCAD SHX Text
FL
AutoCAD SHX Text T600
AutoCAD SHX Text C:\Users\maska\Desktop\PROJECT\FL BAY ADD & NEW 69KV BKR\fl_t600a.dwg Last Saved By: Maska, Elijah on 12/10/2020 1:40 PM Last Saved By: Maska, Elijah on 12/10/2020 1:40 PMMaska, Elijah on 12/10/2020 1:40 PM on 12/10/2020 1:40 PM12/10/2020 1:40 PM
AutoCAD SHX Text
BREAKER CONTROL CABLE SCHEDULE
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
DESIGNATION
AutoCAD SHX Text #C
AutoCAD SHX Text
C SIZE
AutoCAD SHX Text
PCB
AutoCAD SHX Text
AutoCAD SHX Text
JZ2A
AutoCAD SHX Text 1JZ2A-CHA5R 2JZ2A-CHA5R 3JZ2A-CHA3R 4JZ2A-CHA3R119DW1C-JZ2A111CHA3R-JZ2A 2CHA3R-JZ2A 5CHA4R-JZ2A
AutoCAD SHX Text 5 5 5 5 3 12 12 12
AutoCAD SHX Text 10 10 10 10 8 10 10 10
AutoCAD SHX Text
INSTRUMENT XFMR CTRL CABLE SCHEDULE
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
DESIGNATION
AutoCAD SHX Text #C
AutoCAD SHX Text
C SIZE
AutoCAD SHX Text
CCVT
AutoCAD SHX Text
VZ22A1
AutoCAD SHX Text
EZ22A-CHA3F
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CT
AutoCAD SHX Text
QZ22A
AutoCAD SHX Text
EZ22C-CHA3R
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOTES
AutoCAD SHX Text 1.
AutoCAD SHX Text
CHA END POINT DESIGNATIONS INDICATE THE CABLE
AutoCAD SHX Text
WILL TERMINATE IN ONE OF THE SWITCHBOARD SECTIONS.
AutoCAD SHX Text
THE CONTRACTOR SHALL PROVIDE SUFFICIENT CABLE
AutoCAD SHX Text
TO ALLOW TERMINATION ON THE HIGHEST TERMINAL
AutoCAD SHX Text
BLOCK IN THE SWITCHBOARD SECTION THAT IS
AutoCAD SHX Text
FARTHEST FROM THE OTHER END POINT OF THE CABLE.
AutoCAD SHX Text
ALL CABLE SHOWN IS MULTICONDUCTOR SHIELDED CABLE
AutoCAD SHX Text
PER CONSTRUCTION CONTRACT SPECIFICATIONS.
AutoCAD SHX Text
ONE CONDUCTOR IN EACH CABLE SHALL BE AN INACTIVE
AutoCAD SHX Text
CONDUCTOR WHICH IS TO BE GROUNDED AT BOTH ENDS OF
AutoCAD SHX Text
THE CABLE. ALL SPARE CONDUCTORS AND THE SHIELD ARE
AutoCAD SHX Text
TO BE GROUNDED AT BOTH ENDS OF THE CABLE. REFER TO
AutoCAD SHX Text
INSTALLATION SPECIFICATIONS.
AutoCAD SHX Text 2.
AutoCAD SHX Text 3.
AutoCAD SHX Text
DECEMBER 10, 2020
AutoCAD SHX Text
SOUTH DAKOTA MAINTENANCE - HURON, SOUTH DAKOTA
AutoCAD SHX Text
69KV BAY ADDTION
Message from the Administrator At Western Area Power Administration (WAPA), we show our commitment to safety every day through the actions we take, the training we offer and the work conditions we provide. We expect the same commitment to safety from each of our contractors who provide products or services to WAPA. In performing work for WAPA, all contractors must make the right decisions to ensure that the work environment is as safe as possible.
Our safety program is based on four points:
Safety procedures or common sense must be applied by each Federal and contract employee. Safety should not be set aside to meet a project schedule or for personal convenience.
Employees and contractors must believe that they have the right and the responsibility to identify and take action to reduce, if not eliminate, hazardous work environments and hazardous work practices.
Managers and supervisors must lead by example and execute their responsibility to ensure each job is accomplished in a safe and healthy way.
Safety is a personal responsibility. Each individual makes the decision on what action to take to accomplish a task.
By integrating these principles into every task we take, together we can ensure WAPA is a safe place to work.
Mark A. Gabriel Administrator and CEO
Mark A Gabriel
| Cover Page |
| Drawing List |
| fl_0016b |
| fl_0001m_ei |
| fl_0001n |
| fl_1010e_ei |
| fl_1010f |
| fl_1012d_ei |
| fl_1012e |
| fl_1100c |
| fl_1101 |
| fl_1114c_ei |
| fl_1114d |
| fl_1115e_ei |
| fl_1115f |
| fl_1117 |
| fl_1500c_ei |
| fl_1500d |
| fl_1511d_ei |
| fl_1511e |
| fl_1610c_ei |
| fl_1610d |
| fl_1611c_ei |
| fl_1611d |
| fl_1711 |
| fl_2004e_fio |
| fl_2008o_ei |
| fl_2008p |
| fl_2005n_ei |
| fl_2005_1 |
| fl_2005_2a |
| fl_2005_3_fio |
| fl_2006d_ei |
| fl_2006e |
| fl_2016c_ei |
| fl_2016d |
| fl_2017b_ei |
| fl_2017c |
| fl_2301 |
| fl_2302 |
| fl_2303a |
| fl_2550 |
| fl_2600 |
| fl_2601 |
| fl_2602a |
| fl_2603a |
| fl_2925 |
| fl_2926 |
| fl_2027_ei |
| fl_2027a |
| fl_t600 |
| fl_8000 |
| fl_8001 |
| fl_8002 |
| fl_8003 |
| fl_8004 |
| fl_8005 |
| fl_8006 |
| fl_8007 |
| fl_8008 |
| 31_1085i |
File details come from the government source that posted it. Updated .