04-Architectural.pdf
PDF 32 MB Posted
- Attached to
- Y1DZ--620A4-18-204|Relocation of Audiology -
- Solicitation number
- 36C24221B0045
About this file
This document provides details of a federal contract opportunity for relocation of audiology services at the Castle Point VA Medical Center in New York. The contract requires relocation of the audiology department and has a performance period of 730 calendar days from the notice to proceed. The estimated value is between $1 million and $5 million. The solicitation will be released on or around June 18, 2021. The opportunity is open only to certified Service-Disabled Veteran-Owned Small Businesses, with a size standard of $39.5 million in average annual receipts. Interested firms must be registered in the System for Award Management and Vendor Information Pages databases. Questions are due by July 13, 2021 and bids are due in hard copy only on the date specified in the forthcoming solicitation. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 2.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 04-Architectural Draw.pdf | ||
| 36C24221B0045 0002.docx | DOCX document | |
| 36C24221B0045 0001.docx | DOCX document | |
| 620A4-18-204_Bid Specifications - Vol II.pdf | ||
| 02-Civil.pdf | ||
| 620A4-18-204_Bid Specifications Vol I 02.pdf | ||
| 00-General.pdf | ||
| 01-Hazardous Materials.pdf | ||
| 620A4-18-204_Bid Specifications Vol I.pdf | ||
| 08-Electrical.pdf | ||
| 09-Reference.pdf | ||
| 06-Plumbing.pdf | ||
| P07 - Wage Determination 02.pdf | ||
| 36C24221B0045_1.docx | DOCX document | |
| 07-Mechanical.pdf | ||
| 05-Fire Protection.pdf | ||
| 03-Structural.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARTITION TYPE LEGEND
METAL STUDS @ 16" O.C., x REFER TO SPEC'S FOR GA./MIL THICKNESSS
METAL STUDS @ 12" O.C./ FURRING CHANNELS / HAT CHANNELS/ Z-
FURRING CHANNELS x REFER TO SPECS FOR GA./MIL THICKNESS
F
MATERIAL DESIGNATION
SIZE SUFFIX
1 5/8" METAL STUDS1
2 1/2" METAL STUDS OR 2 1/2" C-H STUD(SEE REMARKS)2
3 5/8" METAL STUDS3
RATING SUFFIX
1 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)1
2 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)2
ACCESSORIES SUFFIX
3-1/2" SOUND ATTENUATION BATT INSULATION TO UNDERSIDE OF DECKi
GENERAL PARTITION NOTES
ALL PARTITIONS EXTEND TO BOTTOM OF CONCRETE FLOOR TO METAL DECK ABOVE
UNLESS OTHERWISE INDICATED.
FILL FLUTES IN METAL DECK ABOVE PARTITION WITH FIRE SAFING INSULATION AND FIRE
STOP ENTIRE PERIMETER AT RATED PARTITIONS, AND EXTERIOR WALLS
WITH A UL LISTED JOINT SYSTEM FIRESTOP ASSEMBLY.
PROVIDE DEFLECTION TRACKS AT METAL STUD PARTITIONS THAT TERMINATE AT THE
UNDERSIDE OF STRUCTURE/ METAL DECK ABOVE.
ALL NON-BEARING PARTITIONS SHALL BE CONSTRUCTED TO LIMIT DEFLECTION TO
L/360 OF THE SPAN WITH UNIFORM 5 PSF HORIZONTAL LOADING.
ALL PENETRATIONS IN FIRE RATED PARTITIONS TO BE FIRE STOPPED AND SEALED.
ALL PARTITIONS SHALL BE SEALED TO PREVENT PASSAGE OF SMOKE.
CONTRACTOR TO REFER TO CODE/LIFE SAFETY DRAWINGS FOR RATED PARTITIONS.
PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT ALL WET LOCATIONS AND AREAS
TO RECEIVE WALL TILE, REFER TO SPECIFICATION IN PROJECT MANUAL.
REFER TO STRUCTURAL DRAWINGS FOR MASONRY WALL REINFORCEMENT.
PROVIDE DOUBLE FRAMING AT ALL DOOR, WINDOW AND CASED OPENINGS JAMBS AND
HEAD CONDITIONS.
FOR ALL PARTITIONS, COORDINATE AND PROVIDE BLOCKING FOR ALL BUT NOT LIMITED
TO WALL MOUNTED ARCHITECTURAL WOODWORK, FINISH CARPENTRY, TOILET
PARTITIONS AND ACCESSORIES, EQUIPMENT, HANDRAILS, HARDWARE AND SIMILAR
MOUNTED ITEMS.
EXAMPLE: M 3 . 1 b
MATERIAL
DESIGNATION
SIZE SUFFIX
RATING SUFFIX
ACCESSORY SUFFIX
NON-RATED CMU OR METAL STUD PARTITION0
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
CS12.0b
DOUBLE LAYER OF GWBd
METAL C-H STUDS @ 24" O.C., REFER TO SPECS FOR GA./MIL THICKNESSSH
7/8" HAT CHANNELS0
1/2" RESILIENT CHANNEL (RC) AT 16" O.C.r
CLOSED CELL SPRAY FOAM INSULATIONc
BOTTOM OF STRUCTURE
3-1/2" SOUND ATTENUATION BATT INSULATION
(TO UNDERSIDE OF DECK) AT 'i' SUFFIX
CONT LATERAL BRACE
SLOTTED DEFLECTION TRACK
SECT. @ FLOOR
SECT. @ CLG.
PLAN VIEW
20 GAUGE - STEEL STUDS @ 16" O.C. (SEE
WALL TYPE MARK FOR STUD WIDTH)
5/8" TYPE "X" GWB EA. SIDE FULL
HEIGHT ON STEEL STUDS TO STRUCT.
ABOVE
(FOR 2 HR FIRE RATING PROVIDE 2
LAYERS 5/8" TYPE "X" GWB EA. SIDE
FULL HEIGHT) (FOR 3 HR FIRE RATING
PROVIDE 3 LAYERS 1/2" TYPE "X" GWB
EA. SIDE FULL HEIGHT)
SCHEDULED CEILING. SEE
REFLECTED CEILING PLAN FOR
HEIGHT.
ACOUSTICAL OR FIRE RESISTIVE JOINT
SEALANT (ALL SIDES)
SCHEDULED BASE MOLDING
ACOUSTICAL OR FIRE RESISTIVE JOINT SEALANT
(ALL SIDES)
STC
STUD SIZE
3 5/8"
FIRE TEST
DESIGN NO.
FIRE
RATING
-- NON-RATEDS3.0
GAUGE
PARTITIO
N WIDTH
20 GA 4 7/8"
--3 5/8" UL U419 1 HRS3.1 20 GA 4 7/8"
N O N R A
TE
D W
A
LL
S
G W B M
IN
A B O V E C
LG
--3 5/8" UL U419 2 HRS3.2 20 GA 6 1/8"
GYPSUM LAYERS
EACH SIDE
1x 5/8" + 1x 5/8"
1x 5/8" + 1x 5/8"
2x 5/8"+ 2x 5/8"
583 5/8" UL U465 NON-RATEDS3.0ri 20 GA 6" 2x 5/8" + 1x 5/8" w/ RC
WALL TYPE S (METAL STUD)
SECT. @ FLOOR
5/8" TYPE "X" GYPSUM WALL BOARD (ONE
SIDE)
BOTTOM OF DECK
EXTERIOR WALL, MASONRY
WALL OR INTERIOR PARTITION -
SEE FLOOR PLAN
SCHEDULED CEILING. SEE
REFLECTED CEILING PLAN FOR
HEIGHT.
F0.0
FURRING
CHANNEL SIZE
PARTITIO
N WIDTH
7/8" 1-1/2"
MARK
FURRING CHANNEL
SCHEDULED FLOOR FINISH AND BASE
SECT. @ FLOOR
SECT. @ CLG.
PLAN VIEW
GYPSUM WALL BOARD (ONE SIDE)
BOTTOM OF DECK
EXTERIOR WALL, MASONRY
WALL OR INTERIOR PARTITION -
SEE FLOOR PLAN
SCHEDULED CEILING. SEE
REFLECTED CEILING PLAN FOR
HEIGHT.
STEEL STUDS @ 16" O.C.
STUD SIZE
2 1/2"F2.0
GAUGE
PARTITIO
N WIDTH
18 GA 3 1/8"
SECT. @ CLG.
PLAN VIEW
MARKSTC
FIRE TEST
DESIGN NO.
FIRE
RATING
-- NON-RATED
STC
FIRE TEST
DESIGN NO.
FIRE
RATING
-- NON-RATED
---- NON-RATED
3/ 4" M
IN
7/ 8" M
IN
SCHEDULED FLOOR FINISH AND BASE
ACOUSTICAL SEALANT
2 1/2" 18 GA 3 1/8"
ACOUSTICAL SEALANT
SOUND ATTENUATION BATT INSULATION (TO
UNDERSIDE OF DECK) AT 'i' SUFFIX R-6.7
ACOUSTICAL SEALANT AT 'i' SUFFIX
CONTINUE GYPSUM BOARD TO
DECK AT 'i' SUFFIX
WALL TYPE F WALL TYPE F
1/2" RESILIENT CHANNEL (RC-1) @ 16" O.C.
(TO UNDERSIDE OF DECK) ON ONE SIDE
ONLY AT 'r' SUFFIX
--2 1/2" -- NON-RATEDS2.0 20 GA 3 3/4" 1x 5/8" + 1x 5/8"
--3 5/8" -- NON-RATEDS3.0d 20 GA 6 1/8" 2x 5/8" + 2x 5/8"
BOTTOM OF DECK
"J" SHAPED RUNNER
SECT. @ FLOOR
SECT. @ CLG.
PLAN VIEW
STEEL C-H STUDS @ 24" O.C.
SCHEDULED CEILING. SEE
REFLECTED CEILING PLAN FOR
HEIGHT.
STC
SH2.0
STUD SIZE
FIRE TEST
DESIGN NO.
FIRE
RATINGGAUGE
PARTITION
WIDTH
38+2 1/2" C-H UL-U415 NON-RATED25 GA 3-1/2"
1" SHAFT LINER PANEL
FIRE RESISTIVE JOINT SEALANT
FIRESTOP SEALANT
SCHEDULED BASE MOLDING
(2) LAYERS OF 1/2" TYPE "C"
GYPSUM WALL BOARD
J-SHAPED RUNNER
WALL TYPE SH (SHAFT ASSEMBLY, METAL C-H STUDS)
1" SOUND BATT IN CAVITY
1 5/8"F1.0 18 GA 2 1/4" ---- NON-RATED
F2.0c
---- NON-RATED3 5/8"F3.0 18 GA 4 1/4"
CLOSED CELL SPRAY FOAM INSULATION (TO
UNDERSIDE OF DECK) AT 'c' SUFFIX (R-X)
---- NON-RATED3 5/8" 18 GA 4 1/4"F3.0i
3 5/8" --S3.0i 20 GA 4 7/8" --NON-RATED 1x 5/8" + 1x 5/8"
MARK MARK
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A001
PARTITION TYPES
NO: DESCRIPTION: DATE:
R E
F
(E)S
(E )S
(E)S (E)S (E)S (E)S (E)S
(E )S
(E)S (E)S (E)S (E)S (E)S (E)S (E)S (E)S (E)S
(E )S
(E )S
(E )S
(E )S
(E )2
F B
(E )2
F B
(E )2
F B
(E )2
F B
(E )2
F B
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FB
(E)2FB
(E)2FB
(E )2
F B
(E )2
F B
(E)2FB
(E )2
F B
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FB
(E)2FB
(E)2FB
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FB (E)2FB (E)2FB (E)2FB (E)2FB (E)2FB
(E)S
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)2FB (E)2FB (E)2FB
(E)2FB (E)2FB (E)2FB (E)2FB (E)2FB (E)2FB
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FB (E)2FB
(E)2FB
MORGUE
COOLERS
BUILDING 16F
BUILDING 15H
BUILDING 16F
BUILDING 15H
1 2 3 4 5 6 7
A
B
ELEC. ROOM
E011
CORRIDOR
RECEPTION
E013
AUDIOMETRIC
ROOM 3
E023
AUDIOMETRIC
ROOM 4
E024
WAITING
E010
EXIT VESTIBULE
E022
OFFICE
E016
STAFF TOILET
E025
AUDIOMETRIC
ROOM 1
E019
AUDIOMETRIC
ROOM 2
E020
VESTIBULAR EXAM
E018
SPEECH THERAPY
E017
WORKROOM
E013A
CLEAN SUPPLY
E014
SOILED HOLD
E015
STORAGE
E021
CLINIC ROOM
E026
LAB
E028
PASSAGEWAY
E012
BREAKROOM /
CONFERENCE RM
E027
STOR.
E020A
STOR.
E023A
WALKWAY ABOVE
EXIST
CONFERENCE RM
042D
EXIST
ASSOCIATE PATH.
042B
EXIST
LAB. CHIEF
042C
EXIST
TOILET
EXIST
OFFICE
042A
EXIST
ADMIN. SUPPORT
EXIST
STAFF LOCKER
EXIST
HISTOLOGY
EXIST
STORAGE
EXIST
RECEIVING
EXIST
COLD RM
EXIST
LOADING BAY
EXIST
CORRIDOR
EXIST
CORRIDOR
E033C
EXIST
TRAVEL
E033C2
EXIST
H.A.S. CHECK-IN
E033
EXIST
STOR.
EXIST
DAV
E033C1
EXIST
STOR. 01
E033B
EXIST
HEMOTOLOGY
COAGUZATION
EXIST
CHEMISTRY
EXIST
BLOOD BANK
EXIST
OFFICE
EXIST
MICRO BIOLOGY
EXIST
FLOUR. CL.
032B
EXIST
ISOLATION
032A
EXIST
CORRIDOR
EXIST
CORRIDOR
EXIST
MECHANICAL
ROOM
EXIST
TOILET
EXIST
RECEPTION
016A
EXIST
OFFICE
016B
EXIST
PHLEBOTOMY
WAITING ROOM
EXIST
LABORATORY
016C
EXIST
TOILET
016D
EXIST
PHLEBOTOMY
EXIST
WAITING ROOM
E010
EXIST
OFFICE
E031
EXIST
OFFICE
E030
EXIST
SUPERVISOR
OFFICE
E033A
EXIST
OEF/OIF/OND
OFFICE
E032
EXIST
ELEGIBILITY
OFFICE
E034
EXIST
MECH. /
ELEC.
E036B
EXIST
HAC
E037
EXIST
MECH. /
ELEC. ROOM
E036B1
EXIST
URGENT CARE
WAITING ROOM
E036A1
EXIST
WOMEN'S
WAITING
ROOM
E036A
EXIST
URGENT CARE
LOBBY
E036
EXIST
VESTIBULE
E040
EXIST
CORRIDOR
EXIST
MEN'S
TOILET
E038
EXIST
WOMEN'S
TOILET
E039
EXIST
CONFERENCE
ROOM
H015
EXIST
STAFF TOILET
H016
EXIST
CORRIDOR
EXIST
EXAM
009E
EXIST
EXAM
009F
EXIST
EXAM
009G
EXIST
EXAM
009HEXIST
HALL
011A
EXIST
STAFF LOUNGE
EXIST
DATA
CLOSET
EXIST
ELEVATOR
E1
EXIST
CLOSET
011C
EXIST
DATA CLOSET
011B
EXIST
NURSE'S
STATION
EXIST
NURSE'S
STATION
EXIST
CORRIDOR
EXIST
ENTRY
EXIST
CORRIDOR
E035
EXIST
COMPRESSOR
ROOM
019A
EXIST
STORAGE
019B
EXIST
STAIR HALL
EXIST
ELEV.
MECH.
ROOM
H-053 EXIST
MECH. EQUIP. RM.
H-054
EXIST
MULTI-PURPOSE
STOR.
H003
EXIST
MULTI-PURPOSE RM
H008
EXIST
CLEAN
LIN.
H014
EXIST
OBSV. RM.
H012B
EXIST
PAT. TLT.
H012B1 EXIST
OBSV. RM.
H012C
EXIST
PAT. TLT.
H012D1
EXIST
FEMALE
EXAM / OBSV.
H012D
EXIST
NURSE
TRIAGE
H012E
EXIST
CLEAN
SUPPLY
STOR.
H012F
EXIST
STAIR
H017
FLOOR PLAN LEGEND
DOOR TAG
ROOM TAGROOM #
ROOM AREA
ROOM NAME
150 SF
NEW WALL CONSTRUCTION - SEE
PARTITION TYPES ON A001
EXISTING WALL CONSTRUCTION -
SEE PARTITION TYPES ON A001
NEW DOOR OPENING - SEE DOOR
AND FRAME TYPES, DOOR
ELEVATIONS AND DOOR SCHEDULE
ON SHEET A600
EXISTING DOOR OPENING - REFER
TO DOOR SCHEDULE SHEET A600
FOR MORE INFORMATION
ADJACENT BUILDINGS
OUT OF PROJECT SCOPE
DESIGNATES BUILDING
SEPARATION
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE
KEYPLAN
PLAN
NORTH
ACTUAL
NORTH
Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A100
OVERALL BASEMENT FLOOR PLAN
OF BUILDING 15E
SCALE: 1/8" = 1'-0"A100
1 OVERALL BASEMENT FLOOR PLAN OF BUILDING 15E
(E)S
(E )S
(E )2
F B
(E)2FB
(E)2FB
(E)2FB
(E )2
F B
(E )2
F B
(E)2FB
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)2FB
81 SF
ELEC. ROOM
E011
EXIST
CORRIDOR
112 SF
RECEPTION
E013
408 SF
AUDIOMETRIC
ROOM 3
E023
349 SF
AUDIOMETRIC
ROOM 4
E024
338 SF
WAITING
E010
EXIT VESTIBULE
E022
91 SF
OFFICE
E016
UP UP
WHEELCHAIR
SPACE
56 SF
STAFF TOILET
E025
349 SF
AUDIOMETRIC
ROOM 1
E019
415 SF
AUDIOMETRIC
ROOM 2
E020
246 SF
VESTIBULAR EXAM
E018
146 SF
SPEECH THERAPY
E017
68 SF
WORKROOM
E013A
6 SF
CLEAN SUPPLY
E0148 SF
SOILED HOLD
E015
STORAGE
E021
CLR
5' - 0"
125 SF
CLINIC ROOM
E026
207 SF
LAB
E028
246 SF
BREAKROOM /
CONFERENCE RM
E027
C
LE
A R
3'
937 SF
PASSAGEWAY
E012
21 SF
STOR.
E020A
21 SF
STOR.
E023A
E022-1
E021
E020
E019
E018
E017
E016
E013
E012
E014E015 E010
E011
E028E025
E027 E026
E024
E023
E023A
E022-2
A400
1 2 3 4 5 6 7
A
B
W1 W1 W1 W1 W1 W1 W1 W1
CONTROL
(STAFF)
EXAM
(PATIENT)
CONTROL
(STAFF)
EXAM
(PATIENT)
CONTROL
(STAFF)
EXAM
(PATIENT)
E020A
S3.0ri
F3.0
F3.0
F1.0 F3.0
S3.0ri
F3.0i
F3.0i
F3.0i S3.0d
F1.0 F1.0
F3.0
S3.0ri
S3.0ri
S3.0ri F1.0S3.0ri
F1.0
S3.0ri
S3.0ri
F3.0
F3.0
F3.0
F1.0 S3.0riF3.0 F3.0
F1.0
F3.0
F3.0 F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
F3.0
S3.0ri
F1.0
F1.0
F2.0c
F3.0
F1.0
F3.0
R2D
9'
9'
2' /2
C
LR
5'
9' - 5 1/2"
2' /2
F3.0
7' /2
2' /2
/2
2'
7' /2
0"
4'
2'
/2
4'
5' - 8" 17' - 8 1/2" 12' - 7 1/2" 5' - 5" 9' - 3 1/2" 7 1/2" 7' - 4 1/2" 3' - 1 1/2" 13' - 3 1/2"
7 1/2" EXIST. 5 1/2"
6" 5' - 4 1/2"
5' - 8" 17' - 8 1/2" 7' - 3" 5' - 5" 20' - 10" 1"
2' - 10" EXIST.
1' - 1 1/2"
2' - 10" EXIST.
1' - 2"
A210
A210 2
A210
A210 9
F3.0
A210
A400
A210
W2
2'
2' - 0"
2' - 1"
2'
2' - 0"
A210
A210
A210
A210
A210 A210
A500
1"
1' - 0"
4' - 8"
1' - 0"
A500
A400
CONTROL
(STAFF)
EXAM
(PATIENT)
6'
5'
3'
3' 0"
6'
5'
2' - 4" 5' - 10"
6" 3' - 0"
F1.0
EX1
EX1
EX1 EX1 EX1 EX1 EX1 EX1 EX1 EX1 EX1 EX1
WALKWAY ABOVE EXISTING WINDOW UNIT TO BE MODIFIED. LOWER GLASS UNIT
TO BE REMOVED. RELOCATE FAN UNIT AND INSULATED PANEL
TO LOWER PORTION OF WINDOW. PROVIDE NEW 12"X18"
LOUVER IN INSULATED PANEL AT UPPER PORTION.
AUTO
OPERATOR
BUTTON
AUTO
OPERATOR
BUTTON
SIM
SIM
2'
2'
E021
NEW RAILING AT
STAIR
F1.0
R A
IS
ED
C O U N
TE
R
4' /4
S3.0i
S3.0i
S3.0i S3.0i
S3.0i S3.0i
S3.0i
S3.0
S3.0
S3.0
S3.0S3.0
S3.0i
S3.0i
F2.0c
S3.0i
S3.0i
S3.0i
S3.0i
F2.0c F2.0c
F2.0cF2.0cF2.0c
F2.0c
F2.0c
F2.0c F2.0c
F2.0c
F2.0c
F2.0c
F2.0c
F2.0c
F2.0c
F2.0c
F2.0c F2.0c
F2.0c
F2.0c F2.0c
F2.0c
S3.0
S3.0
S3.0
S3.0
S3.0
GENERAL PLAN NOTES:
1. ALL NEW EXTERIOR WALL FURRING TO BE PARTITION TYPE F2.0c UNLESS
OTHERWISE NOTED, OFFSET 1/2" PARALLEL TO EXISTING WALL.
2. ALL DIMENSIONS TO BE TAKEN FROM CENTERLINE OF WALL UNLESS
INDICATED OTHERWISE. REFER TO SHEET A001 - PARTITION TYPES FOR
ACTUAL DIMENSIONS
3. JOINTS ABUTTING EXISTING WALLS ARE TO BE TAPED AND FINISHED
4. COORDINATE NEW DATA & POWER LOCATIONS WITH OWNER AND
ELECTRICAL DRAWINGS
5. CONTRACTOR SHALL PROVIDE BLOCKING AS REQUIRED FOR ALL
MILLWORK AND EQUIPMENT INSTALLATION
6. FURNITURE AND EQUIPMENT TO BE PROVIDED BY OWNER. VERIFY FINAL
LOCATION AND REQUIREMENTS OF ALL EQUIPMENT WITH OWNER
7. PATCH ALL EXISTING WALLS AS REQUIRED; PREPARE ALL WALLS FOR
PAINT
8. ALL NEW INTERIOR WALLS TO BE S3.0 UNLESS OTHERWISE NOTED,
REFER TO SHEET A001 - PARTITION TYPES FOR ADDITIONAL INFORMATION
FLOOR PLAN LEGEND
DOOR TAG
WINDOW TAG/LOUVER TAG
REFER TO SHEET A600 FOR WINDOW
TYPE AND SIZE INFORMATION.
EX- = EXISTING TO REMAIN
INTERIOR ELEVATIONS
DETAIL CALL OUTS
DETAIL NO
SHEET NO
X-XXX2
1 SIM
WALL TYPE; REFER TO PARTITION
TYPES ON SHEET A001
ROOM TAGROOM #
ROOM AREA
A101
SIM
CS12.0b
W-
ROOM NAME
150 SF
NEW WALL CONSTRUCTION - SEE
PARTITION TYPES ON A001
EXISTING WALL CONSTRUCTION -
SEE PARTITION TYPES ON A001
NEW DOOR OPENING - SEE DOOR
AND FRAME TYPES, DOOR
ELEVATIONS AND DOOR SCHEDULE
ON SHEET A600
EXISTING DOOR OPENING - REFER
TO DOOR SCHEDULE SHEET A600
FOR MORE INFORMATION
OUT OF PROJECT SCOPE
EXIST
COMPRESSOR
ROOM
019A
EXIST
STORAGE
019B
EXIST
STAIR HALL
EXIST
ELEVATOR
EXIST
MECHANICAL
ROOM
EXIST
DATA
CLOSET
EXIST
CLOSET
EXIST
DATA CLOSET
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE
KEYPLAN
PLAN
NORTH
ACTUAL
NORTH
Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR MG, REM
A110
ENLARGED BASEMENT FLOOR PLAN
SCALE: 1/4" = 1'-0"A110
1 BASEMENT ENLARGED FLOOR PLAN
FLOOR PLAN KEYNOTES
KEYNOTE NOTE DESCRIPTION
1 ALIGN FINISHED FACE OF NEW WALL CONSTRUCTION WITH EXISTING WALL
SUITE SQUARE FT AREA = 4,602 SF
PROJECT SQUARE FT AREA = 4,992 SF
R E
F
(E)S
(E )S
(E )2
F B
(E)2FB
(E)2FB
(E)2FB
(E )2
F B
(E )2
F B
(E)2FB
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)2FB
1 2 3 4 5 6 7
A
B
ELEC. ROOM
E011
CORRIDOR
RECEPTION
E013
AUDIOMETRIC
ROOM 3
E023
AUDIOMETRIC
ROOM 4
E024
WAITING
E010
EXIT VESTIBULE
E022
OFFICE
E016
STAFF TOILET
E025
AUDIOMETRIC
ROOM 1
E019
AUDIOMETRIC
ROOM 2
E020
VESTIBULAR EXAM
E018
SPEECH THERAPY
E017
WORKROOM
E013A
CLEAN SUPPLY
E014
SOILED HOLD
E015
CLINIC ROOM
E026
LAB
E028
PASSAGEWAY
E012
BREAKROOM /
CONFERENCE RM
E027
STOR.
E020A
STOR.
E023A
STORAGE
E021
12**
12**
12**
12**
COPIER
4 5
4 5
4 5
4 5
9 10 11
7 8
E Q
E
QE
Q
E Q
7 1/8" 7 1/8"
1' /8
1/ 2"
1' - 2 1/2"
1/ 4"
1/ 2"
CLEAR
2' - 6 3/4"
8 1/2"
1' /8 " 3 1/ 2"
7 1/8" 7 1/8"
1' - 8 5/8"
1' - 8 5/8"
13 14
1/ 4"
1/ 2"
10"
CLEAR
2' - 2 1/4"
EXIST
COMPRESSOR
ROOM
019A
EXIST
STORAGE
019B
EXIST
STAIR HALL
EXIST
MECHANICAL
ROOM
EXIST
DATA
CLOSET
EXIST
ELEVATOR
EXIST
DATA CLOSET
EXIST
CLOSET
EQUIPMENT PLAN LEGEND
ROOM TAGROOM #
ROOM AREA
ROOM NAME
150 SF
OUT OF PROJECT SCOPE
# EQUIPMENT KEYNOTE
FURNITURE; OWNER FURNISHED,
OWNER INSTALLED (OFOI)
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE
KEYPLAN
PLAN
NORTH
ACTUAL
NORTH
Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A120
BASEMENT EQUIPMENT PLAN
SCALE: 1/4" = 1'-0"A120
1 BASEMENT EQUIPMENT PLAN
EQUIPMENT KEYNOTES
KEYNOTE NOTE DESCRIPTION QUANTITY * FURNISHED BY
BLOCKING
REQ'D.
1 TELEVISION; WALL-MOUNTED 2 OFCI YES
2 FIRE EXTINGUISHER CABINET;
SEE 1/A500
3 CFCI YES
3 REFRIGERATOR 1 OFOI NO
4 SOAP DISPENSER 10 OFCI NO
5 PAPER TOWEL DISPENSER 10 OFCI NO
6 MIRROR (24 x 36) 1 CFCI YES
7 36" S.S. GRAB BAR (HORIZONTAL) 1 CFCI YES
8 42" S.S. GRAB BAR (HORIZONTAL) 1 CFCI YES
9 18" S.S. GRAB BAR (VERTICAL) 1 CFCI YES
10 TOILET PAPER DISPENSER 1 OFCI YES
11 SANITARY NAPKIN DISPOSAL 1 OFCI YES
12** AUDIOMETRIC EXAM BOOTH;
ACCUTONE 2 (Model #: 140act-2)
BASIS OF DESIGN
4 OFVI NO
13 PRINTER (RELOCATED) 1 OFOI NO
14 LATHE W/ SHIELD (RELOCATED) 1 OFOI NO
15 ULTRA VAC (RELOCATED) 1 OFOI NO
16 VESTIBULAR EXAM TABLE (3'-4" x 6'-0")
1 OFOI NO
17 COPIER 1 OFOI NO
18 HEARING AID TOOL (RELOCATED) 1 OFOI NO
19 COAT HOOK; REFER TO
ELEVATION
1 CFCI NO
* FURNISHED BY ABBREVIATIONS:
OFOI OWNER FURNISHED OWNER INSTALLED
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED
OFVI OWNER FURNISHED VENDOR INSTALLED
** - CONTRACTOR TO REFER TO AUDIOMETRIC BOOTH SHOP
DRAWING FROM VENDOR (INCLUDED IN DRAWING SET AS
REFERENCE DOCUMENT.)
(E)S
(E )S
(E )2
F B
(E)2FB
(E)2FB
(E)2FB
(E )2
F B
(E )2
F B
(E)2FB
(E )2
F B
(E )2
F B
(E )2
F B
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)S
(E)2FP
(E)2FB
1 2 3 4 5 6 7
A
B
ETR
ETR, REPAIR ANY
PORTION
DAMAGED DUE TO
CONSTRUCTION.
ETR
ETR
ETR
8' - 0"
8' - 0"
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
GWB
7' - 0" A.F.F.
GWB
7' - 0" A.F.F.
GWB
7' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
GWB
9' - 10" A.F.F.
7' - 10" 7' - 10" 7' - 10"
7' - 10"
7' - 10"
7' - 10"
7' - 10" 7' - 10" 7' - 10" 7' - 10" 7' - 10" 8' - 4"
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F. GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
GWB
9' - 10" A.F.F.
8' - 4"
AT-1
8' - 6" A.F.F.
AT-1
8' - 6" A.F.F.
AT-1
8' - 3" A.F.F.
AT-1
10' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
ACT-2
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
ACT-2
8' - 0" A.F.F.
1'
1'
1'
1'
1' - 7 1/4"
1'
1' - 0"
1'
1' - 7 1/4"
1'
1'
1'
1'
1'
1 1 1 1
ELEC. ROOM
E011
CORRIDOR
RECEPTION
E013
AUDIOMETRIC
ROOM 3
E023
AUDIOMETRIC
ROOM 4
E024
WAITING
E010
EXIT VESTIBULE
E022
OFFICE
E016
STAFF TOILET
E025
VESTIBULAR EXAM
E018
SPEECH THERAPY
E017
WORKROOM
E013A
CLEAN SUPPLY
E014
SOILED HOLD
E015
STORAGE
E021
CLINIC ROOM
E026
LAB
E028
PASSAGEWAY
E012
BREAKROOM /
CONFERENCE RM
E027
STOR.
E020A
STOR.
E023A
AT-1
8' - 0" A.F.F.
AUDIOMETRIC
ROOM 2
E020
AUDIOMETRIC
ROOM 1
E019
AT-1
8' - 0" A.F.F.
1 1
1 1
1 1 1
1 1
1 1
A130
A130
A130
A130
A130
A130
A130
A130
A130
A130
A130
A130
A130
A130
OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW
10'-0" ABOVE CORRIDOR
FLOOR; 7'-6" AT STAIR
LANDING
OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW
7' - 10"
7' - 10"
7' - 10"
OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW
OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW
7' - 10"
AT-1
8' - 0" A.F.F.
AT-1
8' - 0" A.F.F.
8' - 0"
ETR
ETR
2' - 2 1/2"
16A
A600
WALKWAY ABOVE
EX
A M B O O
TH
A
FT
E R
IN
S
TA
L L A
TI
O N
A
LI
G N
IN
F
IE
LD
, W
IT
H F R O N T O F
EX
A M B O O
TH
A
FT
E R
IN
S
TA
L L A
TI
O N
A
LI
G N
IN
F
IE
LD
, W
IT
H F R O N T O F
EX
A M B O O
TH
A
FT
E R
IN
S
TA
L L A
TI
O N
A
LI
G N
IN
F
IE
LD
, W
IT
H F R O N T O F
EX
A M B O O
TH
A
FT
E R
IN
S
TA
L L A
TI
O N
A
LI
G N
IN
F
IE
LD
, W
IT
H F R O N T O F
A130
A130
Sim
A130
Sim
A130
Sim
AT-1
8' - 3" A.F.F.
GWB
8' - 0" A.F.F.
OS
OS
OS OS
OS
OS
OS
OSOS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
A130
N.C.
N.C.
N.C.
N.C.
2'
A130 2' /8
2' /8
A130
A130
A130
A130
GENERAL CEILING NOTES
1. REFER TO INTERIORS, PLUMBING, MECHANICAL,
ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR ANY
ADDITIONAL CEILING AND WALL MOUNTED ITEMS NOT
SHOWN.
2. PROVIDE ACT-1 IN ALL LOCATIONS WHERE ACOUSTICAL
CEILING PANEL IS SHOWN UNLESS OTHERWISE NOTED.
3. ALL GYPSUM BOARD SOFFITS TO BE FRAMED WITH 3-5/8"
20GA METAL FRAMING, 16" O.C..
4. SOFFIT AND GWB CEILING PAINT COLORS ARE INDICATED
ON REFLECTED CEILING PLANS OR INTERIOR DRAWINGS.
PAINT ALL SIDES OF SOFFITS THE INDICATED COLOR.
5. ALL STAIR STEEL AND STAIR (UNDERSIDE) LANDINGS TO
RECEIVE PAINT.
6. ALL GYPSUM BOARD OR PLASTER CEILINGS TO BE
PAINTED PT1, UNLESS NOTED OTHERWISE.
7. ANY EXISTING TO REMAIN CEILING TO BE CLEANED AND
PAINTED AS NECESSARY
CEILING TYPE INDICATIONS
LEGEND
LIGHTING - RECESSED CEILING FIXTURE (REFER TO
ELECTRICAL DRAWINGS FOR TYPE)
LIGHTING - PENDENT FIXTURE (REFER TO
ELECTRICAL DRAWINGS FOR TYPE)
LIGHTING - SURFACE MOUNTED (REFER TO
ELECTRICAL)
LIGHTING - RECESSED CAN FIXTURE (LETTER
DESIGNATION TYPE)
HVAC SUPPLY (REFER TO MECHANICAL)
HVAC RETURN/EXHAUST (REFER TO MECHANICAL)
SINGLE FACE EXIT SIGN (REFER TO ELECTRICAL)
DOUBLE FACE EXIT SIGN (REFER TO ELECTRICAL)
CEILING FINISH TAG. REFER TO INTERIOR DWGS
FOR COLOR AND FINISH LEGEND
OCCUPANY SENSOR
SPRINKLER HEAD (REFER TO MECHANICAL)
2 x 2 ACOUSTICAL CEILING PANELS
GYPSUM BOARD - PAINTED REFER TO FINISH LEGEND
INDICATE OPENING THROUGH FLOOR -
REFER TO SECOND FLOOR RCP
N.C. NO CEILING
PT#
ETR EXISTING CEILING TO REMAIN
OS
3-5/8" METAL FRAMING
SECURED TO
STRUCTURE ABOVE
BOTTOM OF
SOFFIT/ CEILING
5/8" GWB, PAINTED
A S N O
TE
D
CEILING SYSTEM WHERE
OCCURS, REFER TO REFLECTED
CEILING PLANS
5"
8"
ANCHOR TRACK TO
STRUCTURE ABOVE &
BRACE AS REQUIRED
METAL STUD DIAGONAL BRACE
@ 48" O.C. MAX SECURED TO
STRUCTURE ABOVE
3-5/8" METAL FRAMING
SECURED TO
STRUCTURE ABOVE
METAL STUD DIAGONAL BRACE @
48" O.C. MAX SECURED TO
STRUCTURE ABOVE
BOTTOM OF
SOFFIT/ CEILING
5/8" GWB, PAINTED
A S N O
TE
D
AS NOTED
CEILING SYSTEM WHERE OCCURS,
REFER TO REFLECTED CEILING PLANS
LINE OF UPPER CABINET WHERE OCCURS
3"
3-5/8" METAL FRAMING SECURED
TO STRUCTURE ABOVE
METAL STUD DIAGONAL BRACE @
48" O.C. MAX SECURED TO
STRUCTURE ABOVE
5/8" GWB, PAINTED. TYPICAL FOR
ALL GWB IN DETAIL. REFER TO
FINISH SCHEDULE FOR COLOR
A S N O
TE
D
CEILING SYSTEM WHERE
OCCURS, REFER TO
REFLECTED CEILING PLANS
5"
A S N O
TE
D O N R C P
4"
EXISTING EXTERIOR WALL
EXISTING EXTERIOR WINDOW;
REFER TO WINDOW DETAILS
WHERE REPLACEMENT
OCCURS
CAULK GWB AT WINDOW ABUTMENT
ROLLER SHADE TO BE
PROVIDED AT ALL WINDOWS;
NEW AND EXISTING. REFER TO
FINISH SCHEDULE FOR
PRODUCT INFORMATION
LINE OF WALL BEYOND
SOFFIT BEYOND
(HEIGHT NOTED ON PLAN)
WINDOW SOFFET
(HEIGHT NOTED ON PLAN)
EXIST
COMPRESSOR
ROOM
019A
EXIST
STORAGE
019B
EXIST
STAIR HALL
EXIST
MECHANICAL
ROOM
EXIST
ELEVATOR
EXIST
DATA
CLOSET
EXIST
DATA CLOSET
EXIST
CLOSET
3-5/8" METAL FRAMING
SECURED TO
STRUCTURE ABOVE
CEILING SYSTEM WHERE
OCCURS, REFER TO REFLECTED
CEILING PLANS
4"
ANCHOR TRACK TO
STRUCTURE ABOVE &
BRACE AS REQUIRED
METAL STUD DIAGONAL BRACE
@ 48" O.C. MAX SECURED TO
STRUCTURE ABOVE
2"
AUDIOMETRIC EXAM BOOTH
HOLD BULKHEAD WALL FRAMING
ABOVE BOOTH CONSTRUCTION
1/2". INSERT COMPRESSIBLE FOAM
FILLER IN GAP; PROVIDE BACKER
ROD AND SEALANT AT JOINT.
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE
KEYPLAN
PLAN
NORTH
ACTUAL
NORTH
Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A130
BASEMENT REFLECTED CEILING
PLAN
SCALE: 1/4" = 1'-0"A130
1 BASEMENT REFLECTED CEILING PLAN
RCP KEYNOTES
VALUE Note Description
1 ALIGN BULKHEAD/SOFFIT WITH EDGE OF WALL/WALL OPENING.
2 EXISTING CEILING TILES THAT HAVE BEEN STORED AND
PROTECTED DURING CONSTRUCTION SHALL BE REINSTALLED
AFTER WORK IS COMPLETED FOR THE DAY. CEILING CANNOT
BE LEFT OPEN FOR MORE THAN A 24 HR PERIOD.
SCALE: 1 1/2" = 1'-0"A130
2 TYPICAL BULKHEAD DETAIL
SCALE: 1 1/2" = 1'-0"A130
3 SOFFIT @ WALL
SCALE: 1 1/2" = 1'-0"A130
4 SOFFIT @ WINDOW
SCALE: 1 1/2" = 1'-0"A130
5 BULKHEAD @ EXAM BOOTH
A500
A500
A500
A130
E017 E015 E014 E013E021
EX1
PROVIDE LOCK, TYP.
HPDL-2HPDL-2
SEE A600 FOR
WDW DETAILS
LINE OF SOFFIT BEYOND
A500
2' - 10 1/2" 2' - 6"
CLR
2' - 6"
2' 0"
1'
2'
6"
2' - 6" 2' - 6"
A500
A500
A500
FE
FE
FE
FE
FE
FE
P.LAM.
COUNTERTOP AND
BACKSPLASH
HPDL-2HPDL-2
HPDL-2
HPDL-2
HPDL-2
NEW LOCKERS
2'
4'
3' - 0" 3' - 0"
A500
FINISHED END
PROVIDE
LOCKSET, TYP.
HPDL-1 HPDL-1
A130
W1
A500
PROVIDE LOCK, TYP.
HPDL-1
7'
SEE A600 FOR
WDW DETAILS
E017
6"6"
2' 0"
1'
2'
6"
3' - 0" 3' - 0"
3' - 0"3' - 0"
1"
A500
�����������3
A500
A500
FE
FINISHED END
FINISHED END
PROVIDE LOCK,
TYP.
HPDL-1 HPDL-1
HPDL-1 HPDL-1
SSR-1
PTD
SD
2'
1'
2' 0"
3' - 3"3' - 3"3' - 3"1 1/2" FILLER PANEL 2" FILLER PANEL 2' - 6" 2' - 6" 2' - 6" 1 1/2" FILLER PANEL
1 1/2" FILLER PANEL
3' - 3" 3' - 3" 3' - 3" 2' - 0" 3' - 0" 2' - 0"
A500
A500
FINISHED P.LAM. PANEL W/ TOE KICK; MATCH ADJACENT
PROVIDE LOCK,
TYP.
HPDL-1HPDL-1HPDL-1HPDL-1HPDL-1HPDL-1
HPDL-1 HPDL-1 HPDL-1 HPDL-1 HPDL-1 HPDL-1
SSR-1
USER EQUIP -
SEE A120
USER EQUIP -
SEE A120
1 1/2" FILLER PANEL
2' - 6" 2' - 6" 2' - 6"
1 1/2" FILLER PANEL
A500
A500
PROVIDE LOCK,
TYP.
HPDL-1HPDL-1HPDL-1
HPDL-1HPDL-1
SSR-1
FILLER 4' - 0" 1' - 10" FILLER
1'
2' 0"
2'
4'
FLAT FILLER PANEL
(INACTIVE)
HPDL-1
HPDL-1
USE EQUIP - SEE
A120
USE EQUIP - SEE
A120
A500
A500
A500
2' - 9"2' - 9"2' - 9"
1 1/2" FILLER PANEL
2' - 0"
1" FILLER PANEL
2' - 6"3' - 0"2' - 6"
2' 0"
1'
2'
6"
2' - 9"2' - 9"2' - 9"2' - 2 1/2"2' - 6"3' - 0"3' - 0"
4" FILLER PANEL
FE
FINISHED
END
FINISHED
END
FE
PROVIDE LOCK, TYP.
SSR-1 SSR-1
HPDL-1
HPDL-1
HPDL-1 HPDL-1 HPDL-1 HPDL-1
HPDL-1HPDL-1
HPDL-1
HPDL-1HPDL-1
PTD
SD
E028
2' - 0" 3' - 1 1/2"
1" OVERHANG
2' 0"
A500
FINISHED
END
SOLID SURFACE
COUNTERTOP
AND
BACKSPLASH
SOLID SURFACE
COUNTERTOP
AND
BACKSPLASH
HPDL-1
2'
A500
A130
6'
FURNITURE, OFOI
GENERAL MILLWORK NOTES:
REFER TO EQUIPMENT SCHEDULE ON SHEET A120 FOR INFO REGARDING SCOPE RESPONSIBILITY
PROVIDE SHOP DRAWINGS FOR ALL MILLWORK TO BE APPROVED PRIOR TO FABRICATION.
DRILL 1-3/4" DIA. HOLE AT EACH PHONE, DATA OR ELECTRICAL OUTLET LOCATED BENEATH A
COUNTER AS DIRECTED BY OWNER. PROVIDE A PLASTIC TRIM GROMMET FOR EACH HOLE.
SEE SYMBOLS AND ABBREVIATIONS SHEET FOR TYPICAL ACCESSORY MOUNTING HEIGHTS IF NOT
INDICATED.
SEE EQUIPMENT SCHEDULE IN SPECIFICATIONS FOR OWNER FURNISHED ITEMS (OFCI) AND
CONTRACTOR FURNISHED ITEMS (CFCI).
ALL EXPOSED COUNTERTOP CORNERS SHALL BE RADIUSED. ALL EXPOSED SIDES TO BE FINISHED.
ALL CABINETS AND DRAWERS TO RECEIVE LOCKS. PROVIDE COMMON KEY FOR SUITE.
PROVIDE FIRE TREATED BLOCKING WHERE REQUIRED AT ALL MILLWORK & WALL MOUNTED
ACCESSORIES.
REFER TO FINISH DRAWINGS, SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
COORDINATE RACEWAY LOCATIONS WITH ELECTRICAL DRAWINGS.
ALL CASEWORK SHOWN FOR UPPER AND LOWER CABINETS, INCLUDING SHELVING & HARDWARE,
TO BE PROVIDED BY CONTRACTOR.
SEE DRAWING I-100 FOR ALL SIGNAGE MOUNTING TYPES AND LOCATIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
IDENTIFIES FURNITURE THAT WILL BE PROVIDED AND INSTALLED BY THE VA.
WP-2
EQ EQ 4" RUBBER BASE
S.S. TRIM,
BOTH SIDES
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A210
INTERIOR ELEVATIONS
SCALE: 3/8" = 1'-0"A210
1 CORRIDOR - ELEVATION A
SCALE: 3/8" = 1'-0"A210
2 BREAKROOM / CONF. RM. - ELEVATION
SCALE: 3/8" = 1'-0"A210
9 WORKROOM - ELEVATION
SCALE: 3/8" = 1'-0"A210
3 CORRIDOR - ELEVATION B
SCALE: 3/8" = 1'-0"A210
4 SPEECH THERAPY - ELEVATION
SCALE: 3/8" = 1'-0"A210
5 LAB - ELEVATION A
SCALE: 3/8" = 1'-0"A210
6 LAB - ELEVATION B
SCALE: 3/8" = 1'-0"A210
7 LAB - ELEVATION C
SCALE: 3/8" = 1'-0"A210
8 LAB - ELEVATION D
SCALE: 3/8" = 1'-0"A210
10 WAITING - ELEVATION
SCALE: 3/8" = 1'-0"A210
11 TYP. SINK STATION
4" RUBBER BASE
EXISTING
WINDOW -
SEE A600
FOR INFO
FE
4" RUBBER BASE
TV
C.L.
PTD
SD
FESD
PTD
4" RUBBER BASE
4" RUBBER BASE
4" RUBBER BASE
NEW HANDRAIL -
SEE I100 FOR
ADDITIONAL INFO
NEW HANDRAIL -
SEE I100 FOR
ADDITIONAL INFO
NEW HANDRAIL -
SEE I100 FOR
ADDITIONAL INFO
A400
56 SF
STAFF TOILET
E025
E025
B
F1.0 F3.0
F3.0
F3.0
S3.0ri
F3.0
3' - 5" 3" 1' - 8" 1' - 10 1/2"
7' - 3"
7' /2
2'
1/ 2"
EQ EQ
EQ. EQ.
2' 0"
WRIST BLADE TYPE
HANDLES. SEE
PLUMBING
DRAWINGS FOR FIXTURE
AND HARDWARE
SPECIFICATIONS
BASE AS SCH'D.
WRAP DRAIN PIPE W/
INSULATED PIPE KIT
CEILING AS SCH'D.
PAPER TOWEL
DISPENSER; MOUNTING
HEIGHT SIMILAR TO
SOAP DISPENSER SOAP DISPENSER
MIRROR
O R A B O V E C O U N
TE
R
4'
TO
D
IS
P
EN
S
IN
G D
EV
IC
E
5'
6"
WALL TILE AS SCH'D.
16"-18"
3' - 0" 6"
2' - 0" 12" MIN.
*REFER TO OTHER ELEVATIONS FOR REMAINING MOUNTING HEIGHTS
1' 0"
4'
EQ EQ
BASE AS SCH'D.
WALL TILE AS SCH'D.
5'
6"
BASE AS SCH'D.
CEILING AS SCH'D.
1-1/2" DIA. S.S. GRAB
BARS W/ BLOCKING AT
MOUNTING
LOCATIONS, TYP.
7"-9"
1'
1'
12" MAX 3' - 6" MIN.
39"-41"
54" MIN.
TOILET PAPER
DISPENSER
WALL TILE AS SCH'D.
6" 5'
GENERAL MILLWORK NOTES:
REFER TO EQUIPMENT SCHEDULE ON SHEET A120 FOR INFO REGARDING SCOPE RESPONSIBILITY
PROVIDE SHOP DRAWINGS FOR ALL MILLWORK TO BE APPROVED PRIOR TO FABRICATION.
DRILL 1-3/4" DIA. HOLE AT EACH PHONE, DATA OR ELECTRICAL OUTLET LOCATED BENEATH A
COUNTER AS DIRECTED BY OWNER. PROVIDE A PLASTIC TRIM GROMMET FOR EACH HOLE.
SEE SYMBOLS AND ABBREVIATIONS SHEET FOR TYPICAL ACCESSORY MOUNTING HEIGHTS IF NOT
INDICATED.
SEE EQUIPMENT SCHEDULE IN SPECIFICATIONS FOR OWNER FURNISHED ITEMS (OFCI) AND
CONTRACTOR FURNISHED ITEMS (CFCI).
ALL EXPOSED COUNTERTOP CORNERS SHALL BE RADIUSED. ALL EXPOSED SIDES TO BE FINISHED.
ALL CABINETS AND DRAWERS TO RECEIVE LOCKS. PROVIDE COMMON KEY FOR SUITE.
PROVIDE FIRE TREATED BLOCKING WHERE REQUIRED AT ALL MILLWORK & WALL MOUNTED
ACCESSORIES.
REFER TO FINISH DRAWINGS, SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
COORDINATE RACEWAY LOCATIONS WITH ELECTRICAL DRAWINGS.
ALL CASEWORK SHOWN FOR UPPER AND LOWER CABINETS, INCLUDING SHELVING & HARDWARE,
TO BE PROVIDED BY CONTRACTOR.
SEE DRAWING I-100 FOR ALL SIGNAGE MOUNTING TYPES AND LOCATIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
IDENTIFIES FURNITURE THAT WILL BE PROVIDED AND INSTALLED BY THE VA.
A
A4006
A400 7
A210 9
2' - 4"
CLR
1' - 11 3/4"
11"
11"
4'
6'
11" 1' - 4"
2' - 3"
/8
/8
C
LR
5'
3' /8
8' /8
W3
W3
A501
A501
AUTO OPERATOR BUTTON
SSR-1 DG-1
SSR-1
E0
/4
2' 0"
W3 W3
A501
A501
HPDL-1HPDL-1HPDL-1
SSR-1SSR-1SSR-1
DG-1
5'
2' - 1" 1' - 11" 7' - 0 1/2"4" RUBBER BASE
EQ EQ EQ EQ
A500
2'
2'
2'
2' - 0"
2' - 0"2' - 0"2' - 0"
2' - 0"
A500
A500
A501
PROVIDE LOCKSET, TYP.
PROVIDE GROMMETS IN
COUNTER; COORDINATE
LOCATIONS WITH
OWNER .
HPDL-1HPDL-1HPDL-1
HPDL-1HPDL-1
HPDL-2
W3 W3
4" RUBBER BASE.
1 2
B
BOOTH
16' - 0"
B O O
TH
9'
1/ 2"
A400
A400
CONTROL
(STAFF)
EXAM
(PATIENT)
A400
A400
A500
Sim
A600
0" 1/ 4"
6" P
IT
1/ 8" T O T O P O F S
IL
L
1/2" AT FRONT
0" 1/ 4"
6" P
IT
1/ 8" T O T O P O F S
IL
L
1/2" AT FRONT
BASEMENT FLOOR
-12' - 0"
1' - 2 1/2"
AUDIOMETRIC
BOOTH
CONCRETE SLAB ON
COMPACTED GRAVEL
REFER TO ENLARGED
FLOOR PLAN FOR WALL
TYPE
EXISTING COLUMN
EXISTING PIER ON TOP OF FOOTING
4"
5" 5"
6"
REFER TO STRUCT DWGS
FOR SLAB REINF.
BASEMENT FLOOR
-12' - 0"
11 5/8"
AUDIOMETRI
C BOOTH
4" 6" 5"
4"
CONCRETE SLAB ON
COMPACTED GRAVEL
EXISTING EXTERIOR WALL ON TOP OF FOOTING
REFER TO STRUCT
DWGS FOR SLAB REINF.
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A400
ENLARGED PLANS & INT.
ELEVATIONS
SCALE: 1/2" = 1'-0"A400
1 ENLARGED TOILET PLAN
SCALE: 1/2" = 1'-0"A400
2 STAFF TOILET - ELEVATION A
SCALE: 1/2" = 1'-0"A400
3 STAFF TOILET - ELEVATION B
SCALE: 1/2" = 1'-0"A400
4 STAFF TOILET - ELEVATION C
SCALE: 1/2" = 1'-0"A400
5 ENLARGED RECEPTION PLANSCALE: 1/2" = 1'-0"A400
6 RECEPTION - EXTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A400
7 RECEPTION - INTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A400
8 ENLARGED AUDIOMETRIC BOOTH
SCALE: 1/2" = 1'-0"A400
9 SINGLE WALL BOOTH PIT DETAIL
SCALE: 1/2" = 1'-0"A400
10 DOUBLE WALL BOOTH PIT DETAIL
SCALE: 1/2" = 1'-0"A400
11 SLAB CONDITION @ COLUMN
SCALE: 1/2" = 1'-0"A400
12 SLAB CONDITION @ EXTERIOR WALL
PARTITION AS NOTED
FIRE EXTINGUISHER
CABINET
REINFORCE PARTITION TOP
& BOTTOM AS REQUIRED
TO PROPERLY INSTALL
EXTINGUISHER CABINET
2'
M
A X.
4'
TO
O P
ER
A
TI
N G M
EC
H N A
IS
M
SCHEDULED BASE
FINISHED FLOOR
3/4" PARTICLE BOARD SHELF W/
MELAMINE FINISH TOP AND
BOTTOM (TYPICAL)
HEAVY DUTY ADJUSTABLE SHELF
BRACKET W/ SCREW DOWN ENDS
(TYPICAL)
SHELF STANDARDS @ 32" o.c.
(MAX.)
1X WOOD CLEATS @ SIDE WALLS
FOR ADDITIONAL SUPPORT
(TYPICAL)
HORIZONTAL WOOD BLOCKING
TOP AND BOTTOM AT 24" o.c.
(MAX.) - AS REQ'D. FOR PROPER
BRACKET PLACEMENT
PVC FACE TRIM
1' - 0"
6" 6'
PULLS PER SPEC (TYP.
FOR CABINET DOORS)
3/4" PARTICLE BD. SHELF
WRAPPED IN MELAMINE ON
ADJ. BRACKETS
SHELF STD.
3/4" THK. PLYWOOD BOTTOM
SCHEDULED BASE
FINISHED FLOOR
2X WOOD BLK'G @
24" O.C.
MELAMINE INTERIOR, TYP.
FIXED 3/4" PARTICLE BD.
SHELF WRAPPED IN
MELAMINE
PULLS PER SPEC (TYP.
FOR CABINET DOORS)
CLG. AS NOTED
ANCHOR TO STRUCTURE
ABOVE
5/8" GYP. BOARD ON 3 5/8"
METAL FRAMING
BRACE WITH 3 5/8" METAL STUDS
@4'-0" O.C. MAX.
PLASTIC LAMINATE TRIM
2X4 CONT. FURRING
ANCHORED TO WALL @
24" o.c.
PLASTIC LAMINATE ON
3/4" PARTICLE BOARD
21" TYP.
3" TYP.
4"
7'
2" TYP.
3" M
IN
SCRIBE TO WALL &
CAULK
FAUCET AS SPECIFIED
COUNTERTOP AS NOTED ON
ELEVATIONS; SEE 6/A500
TYPICAL CONSTRUCTION DETAILS
PLASTIC LAMINATE
ON 3/4" PLYWOOD
1/2" PARTICLE BOARD
ADHERED
SINK AS SPECIFIED
PLAM ON REMOVABLE
PLYWOOD PANEL &
PLAM ON ALL
EXPOSED EDGES
CONT. 1X WOOD
CLEAT
WHERE REQ'D, 3/4"
PLYWOOD END PANEL
W/ PLASTIC LAMINATE
FINISH & CONT. 1X
WOOD CLEAT
FACE OF WALL
BASE AS SPECIFIED FINISHED FLOOR
8"
11"
9" 1'
A S N
O
TE
D
1/
2" 2'
M
IN
H
EI
G H T
P
ER
IN
TE
R
IO
R E
LE
V A
TI
O N S
FACE OF WALL
COUNTERTOP AS NOTED ON
ELEVATIONS; SEE 6/A500 TYPICAL
CONSTRUCTION DETAILS
75 LB. DRAWER SLIDE
PER SPEC.
PULLS PER SPEC (TYP.
FOR CABINET DOORS &
DWRS)
1/4" THK. PANEL
DRAWER BOTTOM
PULLS PER SPEC (TYP.
FOR CABINET DOORS &
DWRS)
SHELF STD.
1/4" THK. PANEL PRODUCT
3/4" THK. PLYWOOD BOTTOM
SCHEDULED BASE
FINISHED FLOOR
CONTINUOUS 1X4 WOOD
FURRING ANCHOR AT WALL
STUDS
3/4" PLYWOOD SHELF
WRAPPED IN MELAMINE ON
ADJ. BRACKETS
2X WOOD BLK'G @ 24" O.C. (FIRE
TREATED)
H
EI
G H T
P
ER
IN
TE
R
IO
R E
LE
V A
TI
O N S
1' - 9" 3" TYP.
4"
6"
BASE AS SCHEDULED
2' - 1" OR AS NOTED ON PLAN
H
EI
G H T
P
ER
IN
TE
R
IO
R E
LE
V A
TI
O N
4"
2X4 WOOD BLOCKING IN WALL
PRE-FAB, PRE-FINISHED STEEL
BRACKET PER SPEC.
SEE TYP. COUNTERTOP DETAIL
6/A500 FOR ADD'L INFO
3/4"
PROVIDE 2" GROMMETS IN
COUNTER FOR ELEC/TELE
CABLES; COORDINATE WITH
ELEC. DEVICE LOCATIONS
PROVIDE 2" GROMMETS IN
COUNTER FOR ELEC/TELE
CABLES; COORDINATE WITH
ELEC. DEVICE LOCATIONS
CLG. AS NOTED
BOTTOM OF CABINET TO BE
FACED W/ PLASTIC LAMINATE
PULLS PER SPEC
3/4" PLYWOOD SHELF
WRAPPED IN PLASTIC
LAMINATE ON ADJUSTABLE
BRACKETS
EURO PIN SYSTEM W/ METAL
SHELF BRACKETS
ALL FACES OF DOORS & ALL
EXPOSED VERTICAL SURFACES
TO BE FACED WITH PLASTIC
LAMINATE
INTERIOR OF CABINET TO BE
FACED W/ MELAMINE (TYP.)
1/4" THICK PANEL PRODUCT
CONTINUOUS 1X4 WOOD
FURRING ANCHOR AT WALL
STUDS
1' - 3"
3" M
IN
CLR.
1' - 0" MIN.
O R A
S N
O
TE
D
2'
1/
4"
1/2" SOLID SURFACE COUNTERTOP
3/4" PARTICLEBOARD SUBSTRATE W/
WHITE LINER UNDERSIDE
REFER TO PLANS
BUILT- UP SOLID SURFACE EDGE,
LAPPED JOINERY
1/8" RADIUS EASED EDGES
B A C K S P
LA
S H H
T 4"
T
YP
1/2" SOLID SURFACE BACKSPLASH
CONTINUOUS SEALANT AT JUNCTURE OF BACK
AND SIDE SPLASHES WITH COUNTERTOP
1/2" SOLID SURFACE SIDE SPLASH WITH
EASED EDGES
WHITE LINER UNDERSIDE
3mm EDGE BANDING
B A C K S P
LA
S H H
T 4"
T
YP
1-1/8" PARTICLE BOARD
HIGH PRESSURE LAMINATE
3mm EDGE BANDING AT TOP AND 1mm EDGE
BANDING AT UNDERSIDE OF BACKSPLASH
AND SIDE SPLASH
3/4" PARTICLE BOARD WITH HIGH PRESSURE
LAMINATE BACKSPLASH AND SIDE SPLASH
SOLID SURFACE COUNTERTOP CONSTRUCTION
LAMINATE COUNTERTOP CONSTRUCTION
CONTINUOUS SEALANT AT JUNCTURE OF
BACK AND SIDE SPLASHES WITH
COUNTERTOP
REFER TO PLANS
3/4" THK. PLYWOOD BOTTOM
LOCK PER SPEC (TYP.
FOR LOCKER DOORS)
2x4 CONT. FURRING
ANCHORED TO WALL @
24" O.C.
PLASTIC LAMINATE ON
3/4" PARTICLE BOARD
9" 3"
4"
6'
5"
3/
4" 1'
/4
1'
/4
1'
/4
5" 5"
STAINLESS STEEL HOOK W/
CONCEALED FASTENERS
AND BLOCKING BEHIND
P.LAM BACKER
2x4 WOOD BLOCKING, TYP.
PLASTIC LAMINATE ON
3/4" PARTICLE BOARD
PLASTIC LAMINATE ON
3/4" PARTICLE BOARD
SCHEDULED BASE
FINISHED FLOOR
2X WOOD BLOCKING AT 24" O.C.
3/4" THK. PLYWOOD BOTTOM
4" 4"
6" 4"
6" 6"
12"
CLEAR
9"
STAINLESS STEEL CONCEALED
HINGES PER SPEC.
1/
2"
1/ 2"
BASEMENT FLOOR
-12' - 0"
1 1/2" TYP.
1 1/2" TYP.
3' -0
TY
P
AUDIOMETRIC BOOTH
REFER TO PARTITION TYPE
EXISTING STAIR
EXISTING CONCRETE SLAB EXISTING SLAB BEYOND
CONCRETE SLAB
6"
BLOCKING AS REQ'D
B
1/2" GYP. BD.; ADJUST TO
ALIGN W/ EXISTING WALL
2-1/2" METAL STUD W/
INSULATION
A600
Sim
3-5/8" METAL STUD W/
INSULATION AND (1)
LAYER OF 5/8" GYP. BD
ON EACH SIDE. REFER TO
PARTITION TYPE.
EXISTING WALLS
3/4" AIR GAP
REFER TO PARTITION
TYPE FOR WALL
CONSTRUCTION
CLG. AS NOTED
PULLS PER SPEC
3/4" PLYWOOD SHELF
WRAPPED IN PLASTIC
LAMINATE ON ADJUSTABLE
BRACKETS
EURO PIN SYSTEM W/ METAL
SHELF BRACKETS
ALL FACES OF DOORS & ALL
EXPOSED VERTICAL SURFACES
TO BE FACED WITH PLASTIC
LAMINATE
INTERIOR OF CABINET TO BE
FACED W/ MELAMINE (TYP.)
BOTTOM OF CABINET TO BE
FACED W/PLASTIC LAMINATE
TASK LIGHT
CONTINUOUS 1X4 WOOD
FURRING ANCHOR AT WALL
STUDS
1' - 3"
4" O R A
S N
O
TE
D
2'
CLR.
1' - 0" MIN.
3" M
IN
1/4" THICK PANEL PRODUCT
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A500
DETAILS
SCALE: 1 1/2" = 1'-0"A500
1 FIRE EXTINGUISHER CABINET
SCALE: 1 1/2" = 1'-0"A500
4 SHELVING DETAIL
SCALE: 1 1/2" = 1'-0"A500
5 TALL CABINET DETAIL
SCALE: 1 1/2" = 1'-0"A500
2 ADA SINK SHROUD
SCALE: 1 1/2" = 1'-0"A500
3 BASE CABINET DETAIL
SCALE: 1 1/2" = 1'-0"A500
7 COUNTERTOP SUPPORT DETAIL
SCALE: 1 1/2" = 1'-0"A500
8 UPPER CABINET DETAIL
SCALE: 3" = 1'-0"A500
6 TYPICAL COUNTERTOP CONSTRUCTION
SCALE: 1 1/2" = 1'-0"A500
11 P.LAM LOCKER DETAIL
SCALE: 3/4" = 1'-0"A500
9 HANDRAIL DETAIL
SCALE: 1 1/2" = 1'-0"A500
10 PLAN DETAIL -1
SCALE: 1 1/2" = 1'-0"A500
8A UPPER CABINET DETAIL W/ LIGHT
SEE A110
A600
A600
5/8" GWB, PAINTED.
TYPICAL FOR ALL GWB IN
DETAIL. REFER TO FINISH
SCHEDULE FOR COLOR
CEILING SYSTEM WHERE
OCCURS, REFER TO
REFLECTED CEILING PLANS
AS NOTED ON RCP
4"
4"
CEILING AS NOTED ON RCP
METAL STUD DIAGONAL
BRACE @ 48" O.C. MAX
SECURED TO STRUCTURE
ABOVE
1/2" SOLID SURFACE OVER 3/4" PLYWOOD
P.LAM OVER 3/4" PLYWOOD; ALL
EXPOSED EDGES TO BE
FINISHED
2x4 P.T. WOOD FRAMING, TYP.
11"
2' - 1"
2'
2"
9" 2'
2' 0"
2x4 WOOD BLOCK IN WALL; ANCHOR TO FRAMING
PRE-FAB., PRE-FINISHED STEEL BRACKET PER SPEC.
P.LAM OVER 3/4" PLYWOOD
1x4 WOOD BLOCK
BASE AS SCHEDULED
2x4 P.T. WOOD FRAMING, TYP.
SLIDING TRANSACTION
WINDOW
1' - 5" 2' - 0"
A600
W3 W3
A501
1/2" SOLID SURFACE
OVER 3/4" PLYWOOD
P.LAM OVER 3/4" PLYWOOD; ALL
EXPOSED EDGES TO BE
FINISHED
2x4 P.T. WOOD FRAMING, TYP.
2x6 P.T. WOOD FRAMING, TYP.
BASE AS SCHEDULED
A501
2' 0"
4"
1' - 10 3/4"
EQ EQ
DG-1 DECORATIVE
GLASS
DIVIDER/PRIVACY
PANEL - SEE SHEET
I100 FOR INFO
3/4" PLYWOOD WITH 1/2" SOLID SURFACE
COUNTER TOP WITH RADIUSED EDGES
ALUM. C TRACK PER SPEC; ROUTE
TRACK INTO COUNTER TOP
1/2" RESIN PANEL (RP-1) PER SPEC
ALUM. C TRACK PER SPEC;
PROVIDE BLOCKING IN CEILING
3/4" PLYWOOD WITH HIGH PRESSURE
LAMINATE TRANSACTION COUNTER;
PROVIDE 3MM EDGE BANDING - MATCH
LAMINATE COLOR
Engineering Architecture Environmental Planning
300 State Street Suite 201
Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com
LaBella Powered by partnership.
Miller-RemickLLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0119
A S e rv ic e
D i s a b l e d
Ve t e r an Owne d
S m a l l
B u s iness
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY
CASTLE POINT CAMPUS
WAPPINGERS FALLS, NY
620A4-18-204
15E
Project Director
C U s e rs
\R M o n ig le
\D o c u m e n ts \R e v it L o c a l F ile s \2
C a s tl e P o in t V
A M
C
A u d io lo g y C lin ic
R rm o n ig le
.r v t
BID DOCUMENTS
2021-05-17 JPR REM
A501
DETAILS
SCALE: 1 1/2" = 1'-0"A501
1 RECEPTION DESK @ WINDOW
SCALE: 1 1/2" = 1'-0"A501
2 RECEPTION DESK @ DIVIDER PANEL
SCALE: 1 1/2" = 1'-0"A501
3 RECEPTION DESK @ DIVIDER PANEL - Callout 1
AS SCHEDULED
A S S C H E D U
LE
D
AS SCHEDULED
A S S C H E D U
LE
D
A S S C H E D U
LE
D
2"
2" AS SCHEDULED
2"
FRAME TYPES
DOOR TYPES
AS SCHEDULED
A S S C H E D U
LE
D
3'
6"
5" 5"
2" AS SCHEDULED
2"
NL-1
FLUSH
WITH VISION PANEL
HG-1
HALF GLASS
HM-A
HOLLOW METAL FRAME
F-1
FLUSH
AL-A
ALUMINUM FRAME
A S S C H E D U
LE
D
4"
6" 6"
3'
6"
M A X
3'
M A X
3'
PER MFR
RAILING LENGHT
AL-B
SLIDING BAR DOOR
P
ER
M
FR
R A
IL
IN
G H
EI
G H T
SCHEDULED SEALANT -
PERIMETER BOTH
SIDES
GYPSUM
BOARD
SEE PARTITION TYPE
FOR WALL THICKNESS
VARIES2" 2"
2"
DBL. METAL STUD
BOX BEAM
HEADER
HOLLOW METAL
DOOR FRAME
S
EE
P A R
TI
TI
O N T
YP
E
FO
R W
A
LL
T H
IC
K N
ES
S
V A R
IE
S
2" 2"
2" 5/8"
SCHEDULED
SEALANT - PERIMETER
BOTH SIDES
1/ 2"
1/ 2"
GYPSUM
BOARD
DBL. METAL STUD
JAMB
HOLLOW METAL
DOOR FRAME
METAL STUD ANCHOR
(MIN. 3 PER JAMB)
SCHEDULED DOOR
SCHEDULED SEALANT -
PERIMETER BOTH
SIDES
GYPSUM
BOARD
SEE PARTITION TYPE
FOR WALL THICKNESS
DBL. METAL STUD
BOX BEAM
HEADER
VARIES
2" 2"
HOLLOW METAL
WINDOW FRAME
REMOVABLE
GLAZING
BEAD
METAL STUD
ANCHOR
(MIN. 3 PER JAMB)
1/4" CLEAR
TEMPERED GLASS
S
EE
P A R
TI
TI
O N T
YP
E
FO
R W
A
LL
T H
IC
K N
ES
S
V A R
IE
S
2" 2"
2"
5/8"
SCHEDULED
SEALANT - PERIMETER
BOTH SIDES
1/ 2"
1/ 2"
GYPSUM
BOARD
DBL. METAL STUD
JAMB
HOLLOW METAL
WINDOW FRAME
METAL STUD ANCHOR
(MIN. 3 PER JAMB)
REMOVABLE GLAZING BEAD
1/4" CLEAR TEMPERED
GLASS
SEE PARTITION TYPE
FOR WALL THICKNESS
VARIES
2"2"
6"
1/4" CLEAR TEMPERED GLASS
REMOVABLE GLAZING BEAD
HOLLOW METAL WINDOW FRAME
FIRE RETARDANT
TREATED BLOCKING AS
REQ'D
SEALANT AS REQ'D
(TYP. BOTH SIDES)
GRADE
STIFF CLIP
5/8" GYP. BD, EACH
SIDE, ON 3-5/8" STUDS
@ 16" O.C. (REFER TO
PARTITION TYPE)
V.I.F.
3' - 5" 2"
3' - 9"
V .I.
F.
5'
4' " 15
A600
A600
A600
2" 2' 2"
2' 2"
2"
14A/A600 TO BE
USED AT FIRST
FLOOR WALKWAY
2" 3'
2"
4'
3'
2" 2' - 9"
2" 2' - 9"
2"
6' - 0"
A600
A600
A600
A600
SCHEDULED SEALANT -
PERIMETER BOTH
SIDES
GYPSUM
BOARD
SEE PARTITION TYPE
FOR WALL THICKNESS
VARIES2" 2"
2"
HOLLOW METAL
DOOR FRAME
12 GA 3-5/8" HDS
HEADER ANCHORED
TO JAMB STUD W/
HEADER BRACKET
S
EE
P A R
TI
TI
O N T
YP
E
FO
R W
A
LL
T H
IC
K N
ES
S
V A R
IE
S
2" 2"
2" 5/8"
SCHEDULED
SEALANT - PERIMETER
BOTH SIDES
1/ 2"
1/ 2"
GYPSUM
BOARD
HOLLOW METAL
DOOR FRAME
METAL STUD ANCHOR
(MIN. 3 PER JAMB)
SCHEDULED DOOR
12 GA 3-5/8" HDS
METAL STUD EACH
SIDE EXTENDED AND
ANCHORED TO
STRUCTURE ABOVE
SCHEDULED DOOR
SEALANT AND BACKER
ROD, TYP. OF BOTH
SIDES
EXISTING EXTERIOR
WALL CONSTRUCTION
ALUMINUM DOOR
FRAME
SHIM FRAME,
DETERMINE
THICKNESS IN
FIELD
CHANNEL
RUNNER AT TOP
OF STUD
FRAMING
EXISTING
LINTEL(S) TO
REMAIN
LINE OF WALL BEYOND
REFER TO PARTITION TYPE
1/2" OFFSET
3"
SEALANT AND BACKER
ROD, TYP. OF BOTH
SIDES
EXISTING EXTERIOR
WALL CONSTRUCTION
ALUMINUM DOOR FRAME
SHIM WINDOW,
DETERMINE
THICKNESS IN
FIELD
5/8" TYPE "X"
GYP. BD.
REFER TO PARTITION TYPE
1/2" OFFSET
3"
SCHEDULED DOOR
1. ALL NEW HARDWARE TO CONFORM TO CABO-ANSI A117.1-2009
2. ALL NEW DOOR HANDLES SHALL BE LEVER TYPE.
3. HARDWARE FINISHES SHALL MATCH BUILDING STANDARD.
4. COORDINATE KEYING DIRECTLY WITH OWNER/TENANT.
5. H.C. TOILET ROOM PRIVACY LOCKS SHALL HAVE AN EMERGENCY
OVERRIDE KEY, TO BE MOUNTED CONSPICUOUSLY…