04-Architectural.pdf

PDF 32 MB Posted

Attached to
Y1DZ--620A4-18-204|Relocation of Audiology -
Solicitation number
36C24221B0045
Issued by

About this file

This document provides details of a federal contract opportunity for relocation of audiology services at the Castle Point VA Medical Center in New York. The contract requires relocation of the audiology department and has a performance period of 730 calendar days from the notice to proceed. The estimated value is between $1 million and $5 million. The solicitation will be released on or around June 18, 2021. The opportunity is open only to certified Service-Disabled Veteran-Owned Small Businesses, with a size standard of $39.5 million in average annual receipts. Interested firms must be registered in the System for Award Management and Vendor Information Pages databases. Questions are due by July 13, 2021 and bids are due in hard copy only on the date specified in the forthcoming solicitation. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 2.

View the file

Other files

File Type Posted
04-Architectural Draw.pdf PDF
36C24221B0045 0002.docx DOCX document
36C24221B0045 0001.docx DOCX document
620A4-18-204_Bid Specifications - Vol II.pdf PDF
02-Civil.pdf PDF
620A4-18-204_Bid Specifications Vol I 02.pdf PDF
00-General.pdf PDF
01-Hazardous Materials.pdf PDF
620A4-18-204_Bid Specifications Vol I.pdf PDF
08-Electrical.pdf PDF
09-Reference.pdf PDF
06-Plumbing.pdf PDF
P07 - Wage Determination 02.pdf PDF
36C24221B0045_1.docx DOCX document
07-Mechanical.pdf PDF
05-Fire Protection.pdf PDF
03-Structural.pdf PDF
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PARTITION TYPE LEGEND

METAL STUDS @ 16" O.C., x REFER TO SPEC'S FOR GA./MIL THICKNESSS

METAL STUDS @ 12" O.C./ FURRING CHANNELS / HAT CHANNELS/ Z-

FURRING CHANNELS x REFER TO SPECS FOR GA./MIL THICKNESS

F

MATERIAL DESIGNATION

SIZE SUFFIX

1 5/8" METAL STUDS1

2 1/2" METAL STUDS OR 2 1/2" C-H STUD(SEE REMARKS)2

3 5/8" METAL STUDS3

RATING SUFFIX

1 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)1

2 HR RATED CMU OR METAL STUD PARTITION (PER UL DESIGN NO.)2

ACCESSORIES SUFFIX

3-1/2" SOUND ATTENUATION BATT INSULATION TO UNDERSIDE OF DECKi

GENERAL PARTITION NOTES

ALL PARTITIONS EXTEND TO BOTTOM OF CONCRETE FLOOR TO METAL DECK ABOVE

UNLESS OTHERWISE INDICATED.

FILL FLUTES IN METAL DECK ABOVE PARTITION WITH FIRE SAFING INSULATION AND FIRE

STOP ENTIRE PERIMETER AT RATED PARTITIONS, AND EXTERIOR WALLS

WITH A UL LISTED JOINT SYSTEM FIRESTOP ASSEMBLY.

PROVIDE DEFLECTION TRACKS AT METAL STUD PARTITIONS THAT TERMINATE AT THE

UNDERSIDE OF STRUCTURE/ METAL DECK ABOVE.

ALL NON-BEARING PARTITIONS SHALL BE CONSTRUCTED TO LIMIT DEFLECTION TO

L/360 OF THE SPAN WITH UNIFORM 5 PSF HORIZONTAL LOADING.

ALL PENETRATIONS IN FIRE RATED PARTITIONS TO BE FIRE STOPPED AND SEALED.

ALL PARTITIONS SHALL BE SEALED TO PREVENT PASSAGE OF SMOKE.

CONTRACTOR TO REFER TO CODE/LIFE SAFETY DRAWINGS FOR RATED PARTITIONS.

PROVIDE MOISTURE RESISTANT GYPSUM BOARD AT ALL WET LOCATIONS AND AREAS

TO RECEIVE WALL TILE, REFER TO SPECIFICATION IN PROJECT MANUAL.

REFER TO STRUCTURAL DRAWINGS FOR MASONRY WALL REINFORCEMENT.

PROVIDE DOUBLE FRAMING AT ALL DOOR, WINDOW AND CASED OPENINGS JAMBS AND

HEAD CONDITIONS.

FOR ALL PARTITIONS, COORDINATE AND PROVIDE BLOCKING FOR ALL BUT NOT LIMITED

TO WALL MOUNTED ARCHITECTURAL WOODWORK, FINISH CARPENTRY, TOILET

PARTITIONS AND ACCESSORIES, EQUIPMENT, HANDRAILS, HARDWARE AND SIMILAR

MOUNTED ITEMS.

EXAMPLE: M 3 . 1 b

MATERIAL

DESIGNATION

SIZE SUFFIX

RATING SUFFIX

ACCESSORY SUFFIX

NON-RATED CMU OR METAL STUD PARTITION0

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

CS12.0b

DOUBLE LAYER OF GWBd

METAL C-H STUDS @ 24" O.C., REFER TO SPECS FOR GA./MIL THICKNESSSH

7/8" HAT CHANNELS0

1/2" RESILIENT CHANNEL (RC) AT 16" O.C.r

CLOSED CELL SPRAY FOAM INSULATIONc

BOTTOM OF STRUCTURE

3-1/2" SOUND ATTENUATION BATT INSULATION

(TO UNDERSIDE OF DECK) AT 'i' SUFFIX

CONT LATERAL BRACE

SLOTTED DEFLECTION TRACK

SECT. @ FLOOR

SECT. @ CLG.

PLAN VIEW

20 GAUGE - STEEL STUDS @ 16" O.C. (SEE

WALL TYPE MARK FOR STUD WIDTH)

5/8" TYPE "X" GWB EA. SIDE FULL

HEIGHT ON STEEL STUDS TO STRUCT.

ABOVE

(FOR 2 HR FIRE RATING PROVIDE 2

LAYERS 5/8" TYPE "X" GWB EA. SIDE

FULL HEIGHT) (FOR 3 HR FIRE RATING

PROVIDE 3 LAYERS 1/2" TYPE "X" GWB

EA. SIDE FULL HEIGHT)

SCHEDULED CEILING. SEE

REFLECTED CEILING PLAN FOR

HEIGHT.

ACOUSTICAL OR FIRE RESISTIVE JOINT

SEALANT (ALL SIDES)

SCHEDULED BASE MOLDING

ACOUSTICAL OR FIRE RESISTIVE JOINT SEALANT

(ALL SIDES)

STC

STUD SIZE

3 5/8"

FIRE TEST

DESIGN NO.

FIRE

RATING

-- NON-RATEDS3.0

GAUGE

PARTITIO

N WIDTH

20 GA 4 7/8"

--3 5/8" UL U419 1 HRS3.1 20 GA 4 7/8"

N O N R A

TE

D W

A

LL

S

G W B M

IN

A B O V E C

LG

--3 5/8" UL U419 2 HRS3.2 20 GA 6 1/8"

GYPSUM LAYERS

EACH SIDE

1x 5/8" + 1x 5/8"

1x 5/8" + 1x 5/8"

2x 5/8"+ 2x 5/8"

583 5/8" UL U465 NON-RATEDS3.0ri 20 GA 6" 2x 5/8" + 1x 5/8" w/ RC

WALL TYPE S (METAL STUD)

SECT. @ FLOOR

5/8" TYPE "X" GYPSUM WALL BOARD (ONE

SIDE)

BOTTOM OF DECK

EXTERIOR WALL, MASONRY

WALL OR INTERIOR PARTITION -

SEE FLOOR PLAN

SCHEDULED CEILING. SEE

REFLECTED CEILING PLAN FOR

HEIGHT.

F0.0

FURRING

CHANNEL SIZE

PARTITIO

N WIDTH

7/8" 1-1/2"

MARK

FURRING CHANNEL

SCHEDULED FLOOR FINISH AND BASE

SECT. @ FLOOR

SECT. @ CLG.

PLAN VIEW

GYPSUM WALL BOARD (ONE SIDE)

BOTTOM OF DECK

EXTERIOR WALL, MASONRY

WALL OR INTERIOR PARTITION -

SEE FLOOR PLAN

SCHEDULED CEILING. SEE

REFLECTED CEILING PLAN FOR

HEIGHT.

STEEL STUDS @ 16" O.C.

STUD SIZE

2 1/2"F2.0

GAUGE

PARTITIO

N WIDTH

18 GA 3 1/8"

SECT. @ CLG.

PLAN VIEW

MARKSTC

FIRE TEST

DESIGN NO.

FIRE

RATING

-- NON-RATED

STC

FIRE TEST

DESIGN NO.

FIRE

RATING

-- NON-RATED

---- NON-RATED

3/ 4" M

IN

7/ 8" M

IN

SCHEDULED FLOOR FINISH AND BASE

ACOUSTICAL SEALANT

2 1/2" 18 GA 3 1/8"

ACOUSTICAL SEALANT

SOUND ATTENUATION BATT INSULATION (TO

UNDERSIDE OF DECK) AT 'i' SUFFIX R-6.7

ACOUSTICAL SEALANT AT 'i' SUFFIX

CONTINUE GYPSUM BOARD TO

DECK AT 'i' SUFFIX

WALL TYPE F WALL TYPE F

1/2" RESILIENT CHANNEL (RC-1) @ 16" O.C.

(TO UNDERSIDE OF DECK) ON ONE SIDE

ONLY AT 'r' SUFFIX

--2 1/2" -- NON-RATEDS2.0 20 GA 3 3/4" 1x 5/8" + 1x 5/8"

--3 5/8" -- NON-RATEDS3.0d 20 GA 6 1/8" 2x 5/8" + 2x 5/8"

BOTTOM OF DECK

"J" SHAPED RUNNER

SECT. @ FLOOR

SECT. @ CLG.

PLAN VIEW

STEEL C-H STUDS @ 24" O.C.

SCHEDULED CEILING. SEE

REFLECTED CEILING PLAN FOR

HEIGHT.

STC

SH2.0

STUD SIZE

FIRE TEST

DESIGN NO.

FIRE

RATINGGAUGE

PARTITION

WIDTH

38+2 1/2" C-H UL-U415 NON-RATED25 GA 3-1/2"

1" SHAFT LINER PANEL

FIRE RESISTIVE JOINT SEALANT

FIRESTOP SEALANT

SCHEDULED BASE MOLDING

(2) LAYERS OF 1/2" TYPE "C"

GYPSUM WALL BOARD

J-SHAPED RUNNER

WALL TYPE SH (SHAFT ASSEMBLY, METAL C-H STUDS)

1" SOUND BATT IN CAVITY

1 5/8"F1.0 18 GA 2 1/4" ---- NON-RATED

F2.0c

---- NON-RATED3 5/8"F3.0 18 GA 4 1/4"

CLOSED CELL SPRAY FOAM INSULATION (TO

UNDERSIDE OF DECK) AT 'c' SUFFIX (R-X)

---- NON-RATED3 5/8" 18 GA 4 1/4"F3.0i

3 5/8" --S3.0i 20 GA 4 7/8" --NON-RATED 1x 5/8" + 1x 5/8"

MARK MARK

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A001

PARTITION TYPES

NO: DESCRIPTION: DATE:

R E

F

(E)S

(E )S

(E)S (E)S (E)S (E)S (E)S

(E )S

(E)S (E)S (E)S (E)S (E)S (E)S (E)S (E)S (E)S

(E )S

(E )S

(E )S

(E )S

(E )2

F B

(E )2

F B

(E )2

F B

(E )2

F B

(E )2

F B

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FB

(E)2FB

(E)2FB

(E )2

F B

(E )2

F B

(E)2FB

(E )2

F B

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FB

(E)2FB

(E)2FB

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FB (E)2FB (E)2FB (E)2FB (E)2FB (E)2FB

(E)S

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)2FB (E)2FB (E)2FB

(E)2FB (E)2FB (E)2FB (E)2FB (E)2FB (E)2FB

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FB (E)2FB

(E)2FB

MORGUE

COOLERS

BUILDING 16F

BUILDING 15H

BUILDING 16F

BUILDING 15H

1 2 3 4 5 6 7

A

B

ELEC. ROOM

E011

CORRIDOR

RECEPTION

E013

AUDIOMETRIC

ROOM 3

E023

AUDIOMETRIC

ROOM 4

E024

WAITING

E010

EXIT VESTIBULE

E022

OFFICE

E016

STAFF TOILET

E025

AUDIOMETRIC

ROOM 1

E019

AUDIOMETRIC

ROOM 2

E020

VESTIBULAR EXAM

E018

SPEECH THERAPY

E017

WORKROOM

E013A

CLEAN SUPPLY

E014

SOILED HOLD

E015

STORAGE

E021

CLINIC ROOM

E026

LAB

E028

PASSAGEWAY

E012

BREAKROOM /

CONFERENCE RM

E027

STOR.

E020A

STOR.

E023A

WALKWAY ABOVE

EXIST

CONFERENCE RM

042D

EXIST

ASSOCIATE PATH.

042B

EXIST

LAB. CHIEF

042C

EXIST

TOILET

EXIST

OFFICE

042A

EXIST

ADMIN. SUPPORT

EXIST

STAFF LOCKER

EXIST

HISTOLOGY

EXIST

STORAGE

EXIST

RECEIVING

EXIST

COLD RM

EXIST

LOADING BAY

EXIST

CORRIDOR

EXIST

CORRIDOR

E033C

EXIST

TRAVEL

E033C2

EXIST

H.A.S. CHECK-IN

E033

EXIST

STOR.

EXIST

DAV

E033C1

EXIST

STOR. 01

E033B

EXIST

HEMOTOLOGY

COAGUZATION

EXIST

CHEMISTRY

EXIST

BLOOD BANK

EXIST

OFFICE

EXIST

MICRO BIOLOGY

EXIST

FLOUR. CL.

032B

EXIST

ISOLATION

032A

EXIST

CORRIDOR

EXIST

CORRIDOR

EXIST

MECHANICAL

ROOM

EXIST

TOILET

EXIST

RECEPTION

016A

EXIST

OFFICE

016B

EXIST

PHLEBOTOMY

WAITING ROOM

EXIST

LABORATORY

016C

EXIST

TOILET

016D

EXIST

PHLEBOTOMY

EXIST

WAITING ROOM

E010

EXIST

OFFICE

E031

EXIST

OFFICE

E030

EXIST

SUPERVISOR

OFFICE

E033A

EXIST

OEF/OIF/OND

OFFICE

E032

EXIST

ELEGIBILITY

OFFICE

E034

EXIST

MECH. /

ELEC.

E036B

EXIST

HAC

E037

EXIST

MECH. /

ELEC. ROOM

E036B1

EXIST

URGENT CARE

WAITING ROOM

E036A1

EXIST

WOMEN'S

WAITING

ROOM

E036A

EXIST

URGENT CARE

LOBBY

E036

EXIST

VESTIBULE

E040

EXIST

CORRIDOR

EXIST

MEN'S

TOILET

E038

EXIST

WOMEN'S

TOILET

E039

EXIST

CONFERENCE

ROOM

H015

EXIST

STAFF TOILET

H016

EXIST

CORRIDOR

EXIST

EXAM

009E

EXIST

EXAM

009F

EXIST

EXAM

009G

EXIST

EXAM

009HEXIST

HALL

011A

EXIST

STAFF LOUNGE

EXIST

DATA

CLOSET

EXIST

ELEVATOR

E1

EXIST

CLOSET

011C

EXIST

DATA CLOSET

011B

EXIST

NURSE'S

STATION

EXIST

NURSE'S

STATION

EXIST

CORRIDOR

EXIST

ENTRY

EXIST

CORRIDOR

E035

EXIST

COMPRESSOR

ROOM

019A

EXIST

STORAGE

019B

EXIST

STAIR HALL

EXIST

ELEV.

MECH.

ROOM

H-053 EXIST

MECH. EQUIP. RM.

H-054

EXIST

MULTI-PURPOSE

STOR.

H003

EXIST

MULTI-PURPOSE RM

H008

EXIST

CLEAN

LIN.

H014

EXIST

OBSV. RM.

H012B

EXIST

PAT. TLT.

H012B1 EXIST

OBSV. RM.

H012C

EXIST

PAT. TLT.

H012D1

EXIST

FEMALE

EXAM / OBSV.

H012D

EXIST

NURSE

TRIAGE

H012E

EXIST

CLEAN

SUPPLY

STOR.

H012F

EXIST

STAIR

H017

FLOOR PLAN LEGEND

DOOR TAG

ROOM TAGROOM #

ROOM AREA

ROOM NAME

150 SF

NEW WALL CONSTRUCTION - SEE

PARTITION TYPES ON A001

EXISTING WALL CONSTRUCTION -

SEE PARTITION TYPES ON A001

NEW DOOR OPENING - SEE DOOR

AND FRAME TYPES, DOOR

ELEVATIONS AND DOOR SCHEDULE

ON SHEET A600

EXISTING DOOR OPENING - REFER

TO DOOR SCHEDULE SHEET A600

FOR MORE INFORMATION

ADJACENT BUILDINGS

OUT OF PROJECT SCOPE

DESIGNATES BUILDING

SEPARATION

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE

KEYPLAN

PLAN

NORTH

ACTUAL

NORTH

Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A100

OVERALL BASEMENT FLOOR PLAN

OF BUILDING 15E

SCALE: 1/8" = 1'-0"A100

1 OVERALL BASEMENT FLOOR PLAN OF BUILDING 15E

(E)S

(E )S

(E )2

F B

(E)2FB

(E)2FB

(E)2FB

(E )2

F B

(E )2

F B

(E)2FB

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)2FB

81 SF

ELEC. ROOM

E011

EXIST

CORRIDOR

112 SF

RECEPTION

E013

408 SF

AUDIOMETRIC

ROOM 3

E023

349 SF

AUDIOMETRIC

ROOM 4

E024

338 SF

WAITING

E010

EXIT VESTIBULE

E022

91 SF

OFFICE

E016

UP UP

WHEELCHAIR

SPACE

56 SF

STAFF TOILET

E025

349 SF

AUDIOMETRIC

ROOM 1

E019

415 SF

AUDIOMETRIC

ROOM 2

E020

246 SF

VESTIBULAR EXAM

E018

146 SF

SPEECH THERAPY

E017

68 SF

WORKROOM

E013A

6 SF

CLEAN SUPPLY

E0148 SF

SOILED HOLD

E015

STORAGE

E021

CLR

5' - 0"

125 SF

CLINIC ROOM

E026

207 SF

LAB

E028

246 SF

BREAKROOM /

CONFERENCE RM

E027

C

LE

A R

3'

937 SF

PASSAGEWAY

E012

21 SF

STOR.

E020A

21 SF

STOR.

E023A

E022-1

E021

E020

E019

E018

E017

E016

E013

E012

E014E015 E010

E011

E028E025

E027 E026

E024

E023

E023A

E022-2

A400

1 2 3 4 5 6 7

A

B

W1 W1 W1 W1 W1 W1 W1 W1

CONTROL

(STAFF)

EXAM

(PATIENT)

CONTROL

(STAFF)

EXAM

(PATIENT)

CONTROL

(STAFF)

EXAM

(PATIENT)

E020A

S3.0ri

F3.0

F3.0

F1.0 F3.0

S3.0ri

F3.0i

F3.0i

F3.0i S3.0d

F1.0 F1.0

F3.0

S3.0ri

S3.0ri

S3.0ri F1.0S3.0ri

F1.0

S3.0ri

S3.0ri

F3.0

F3.0

F3.0

F1.0 S3.0riF3.0 F3.0

F1.0

F3.0

F3.0 F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

F3.0

S3.0ri

F1.0

F1.0

F2.0c

F3.0

F1.0

F3.0

R2D

9'

9'

2' /2

C

LR

5'

9' - 5 1/2"

2' /2

F3.0

7' /2

2' /2

/2

2'

7' /2

0"

4'

2'

/2

4'

5' - 8" 17' - 8 1/2" 12' - 7 1/2" 5' - 5" 9' - 3 1/2" 7 1/2" 7' - 4 1/2" 3' - 1 1/2" 13' - 3 1/2"

7 1/2" EXIST. 5 1/2"

6" 5' - 4 1/2"

5' - 8" 17' - 8 1/2" 7' - 3" 5' - 5" 20' - 10" 1"

2' - 10" EXIST.

1' - 1 1/2"

2' - 10" EXIST.

1' - 2"

A210

A210 2

A210

A210 9

F3.0

A210

A400

A210

W2

2'

2' - 0"

2' - 1"

2'

2' - 0"

A210

A210

A210

A210

A210 A210

A500

1"

1' - 0"

4' - 8"

1' - 0"

A500

A400

CONTROL

(STAFF)

EXAM

(PATIENT)

6'

5'

3'

3' 0"

6'

5'

2' - 4" 5' - 10"

6" 3' - 0"

F1.0

EX1

EX1

EX1 EX1 EX1 EX1 EX1 EX1 EX1 EX1 EX1 EX1

WALKWAY ABOVE EXISTING WINDOW UNIT TO BE MODIFIED. LOWER GLASS UNIT

TO BE REMOVED. RELOCATE FAN UNIT AND INSULATED PANEL

TO LOWER PORTION OF WINDOW. PROVIDE NEW 12"X18"

LOUVER IN INSULATED PANEL AT UPPER PORTION.

AUTO

OPERATOR

BUTTON

AUTO

OPERATOR

BUTTON

SIM

SIM

2'

2'

E021

NEW RAILING AT

STAIR

F1.0

R A

IS

ED

C O U N

TE

R

4' /4

S3.0i

S3.0i

S3.0i S3.0i

S3.0i S3.0i

S3.0i

S3.0

S3.0

S3.0

S3.0S3.0

S3.0i

S3.0i

F2.0c

S3.0i

S3.0i

S3.0i

S3.0i

F2.0c F2.0c

F2.0cF2.0cF2.0c

F2.0c

F2.0c

F2.0c F2.0c

F2.0c

F2.0c

F2.0c

F2.0c

F2.0c

F2.0c

F2.0c

F2.0c F2.0c

F2.0c

F2.0c F2.0c

F2.0c

S3.0

S3.0

S3.0

S3.0

S3.0

GENERAL PLAN NOTES:

1. ALL NEW EXTERIOR WALL FURRING TO BE PARTITION TYPE F2.0c UNLESS

OTHERWISE NOTED, OFFSET 1/2" PARALLEL TO EXISTING WALL.

2. ALL DIMENSIONS TO BE TAKEN FROM CENTERLINE OF WALL UNLESS

INDICATED OTHERWISE. REFER TO SHEET A001 - PARTITION TYPES FOR

ACTUAL DIMENSIONS

3. JOINTS ABUTTING EXISTING WALLS ARE TO BE TAPED AND FINISHED

4. COORDINATE NEW DATA & POWER LOCATIONS WITH OWNER AND

ELECTRICAL DRAWINGS

5. CONTRACTOR SHALL PROVIDE BLOCKING AS REQUIRED FOR ALL

MILLWORK AND EQUIPMENT INSTALLATION

6. FURNITURE AND EQUIPMENT TO BE PROVIDED BY OWNER. VERIFY FINAL

LOCATION AND REQUIREMENTS OF ALL EQUIPMENT WITH OWNER

7. PATCH ALL EXISTING WALLS AS REQUIRED; PREPARE ALL WALLS FOR

PAINT

8. ALL NEW INTERIOR WALLS TO BE S3.0 UNLESS OTHERWISE NOTED,

REFER TO SHEET A001 - PARTITION TYPES FOR ADDITIONAL INFORMATION

FLOOR PLAN LEGEND

DOOR TAG

WINDOW TAG/LOUVER TAG

REFER TO SHEET A600 FOR WINDOW

TYPE AND SIZE INFORMATION.

EX- = EXISTING TO REMAIN

INTERIOR ELEVATIONS

DETAIL CALL OUTS

DETAIL NO

SHEET NO

X-XXX2

1 SIM

WALL TYPE; REFER TO PARTITION

TYPES ON SHEET A001

ROOM TAGROOM #

ROOM AREA

A101

SIM

CS12.0b

W-

ROOM NAME

150 SF

NEW WALL CONSTRUCTION - SEE

PARTITION TYPES ON A001

EXISTING WALL CONSTRUCTION -

SEE PARTITION TYPES ON A001

NEW DOOR OPENING - SEE DOOR

AND FRAME TYPES, DOOR

ELEVATIONS AND DOOR SCHEDULE

ON SHEET A600

EXISTING DOOR OPENING - REFER

TO DOOR SCHEDULE SHEET A600

FOR MORE INFORMATION

OUT OF PROJECT SCOPE

EXIST

COMPRESSOR

ROOM

019A

EXIST

STORAGE

019B

EXIST

STAIR HALL

EXIST

ELEVATOR

EXIST

MECHANICAL

ROOM

EXIST

DATA

CLOSET

EXIST

CLOSET

EXIST

DATA CLOSET

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE

KEYPLAN

PLAN

NORTH

ACTUAL

NORTH

Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR MG, REM

A110

ENLARGED BASEMENT FLOOR PLAN

SCALE: 1/4" = 1'-0"A110

1 BASEMENT ENLARGED FLOOR PLAN

FLOOR PLAN KEYNOTES

KEYNOTE NOTE DESCRIPTION

1 ALIGN FINISHED FACE OF NEW WALL CONSTRUCTION WITH EXISTING WALL

SUITE SQUARE FT AREA = 4,602 SF

PROJECT SQUARE FT AREA = 4,992 SF

R E

F

(E)S

(E )S

(E )2

F B

(E)2FB

(E)2FB

(E)2FB

(E )2

F B

(E )2

F B

(E)2FB

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)2FB

1 2 3 4 5 6 7

A

B

ELEC. ROOM

E011

CORRIDOR

RECEPTION

E013

AUDIOMETRIC

ROOM 3

E023

AUDIOMETRIC

ROOM 4

E024

WAITING

E010

EXIT VESTIBULE

E022

OFFICE

E016

STAFF TOILET

E025

AUDIOMETRIC

ROOM 1

E019

AUDIOMETRIC

ROOM 2

E020

VESTIBULAR EXAM

E018

SPEECH THERAPY

E017

WORKROOM

E013A

CLEAN SUPPLY

E014

SOILED HOLD

E015

CLINIC ROOM

E026

LAB

E028

PASSAGEWAY

E012

BREAKROOM /

CONFERENCE RM

E027

STOR.

E020A

STOR.

E023A

STORAGE

E021

12**

12**

12**

12**

COPIER

4 5

4 5

4 5

4 5

9 10 11

7 8

E Q

E

QE

Q

E Q

7 1/8" 7 1/8"

1' /8

1/ 2"

1' - 2 1/2"

1/ 4"

1/ 2"

CLEAR

2' - 6 3/4"

8 1/2"

1' /8 " 3 1/ 2"

7 1/8" 7 1/8"

1' - 8 5/8"

1' - 8 5/8"

13 14

1/ 4"

1/ 2"

10"

CLEAR

2' - 2 1/4"

EXIST

COMPRESSOR

ROOM

019A

EXIST

STORAGE

019B

EXIST

STAIR HALL

EXIST

MECHANICAL

ROOM

EXIST

DATA

CLOSET

EXIST

ELEVATOR

EXIST

DATA CLOSET

EXIST

CLOSET

EQUIPMENT PLAN LEGEND

ROOM TAGROOM #

ROOM AREA

ROOM NAME

150 SF

OUT OF PROJECT SCOPE

# EQUIPMENT KEYNOTE

FURNITURE; OWNER FURNISHED,

OWNER INSTALLED (OFOI)

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE

KEYPLAN

PLAN

NORTH

ACTUAL

NORTH

Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A120

BASEMENT EQUIPMENT PLAN

SCALE: 1/4" = 1'-0"A120

1 BASEMENT EQUIPMENT PLAN

EQUIPMENT KEYNOTES

KEYNOTE NOTE DESCRIPTION QUANTITY * FURNISHED BY

BLOCKING

REQ'D.

1 TELEVISION; WALL-MOUNTED 2 OFCI YES

2 FIRE EXTINGUISHER CABINET;

SEE 1/A500

3 CFCI YES

3 REFRIGERATOR 1 OFOI NO

4 SOAP DISPENSER 10 OFCI NO

5 PAPER TOWEL DISPENSER 10 OFCI NO

6 MIRROR (24 x 36) 1 CFCI YES

7 36" S.S. GRAB BAR (HORIZONTAL) 1 CFCI YES

8 42" S.S. GRAB BAR (HORIZONTAL) 1 CFCI YES

9 18" S.S. GRAB BAR (VERTICAL) 1 CFCI YES

10 TOILET PAPER DISPENSER 1 OFCI YES

11 SANITARY NAPKIN DISPOSAL 1 OFCI YES

12** AUDIOMETRIC EXAM BOOTH;

ACCUTONE 2 (Model #: 140act-2)

BASIS OF DESIGN

4 OFVI NO

13 PRINTER (RELOCATED) 1 OFOI NO

14 LATHE W/ SHIELD (RELOCATED) 1 OFOI NO

15 ULTRA VAC (RELOCATED) 1 OFOI NO

16 VESTIBULAR EXAM TABLE (3'-4" x 6'-0")

1 OFOI NO

17 COPIER 1 OFOI NO

18 HEARING AID TOOL (RELOCATED) 1 OFOI NO

19 COAT HOOK; REFER TO

ELEVATION

1 CFCI NO

* FURNISHED BY ABBREVIATIONS:

OFOI OWNER FURNISHED OWNER INSTALLED

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OFVI OWNER FURNISHED VENDOR INSTALLED

** - CONTRACTOR TO REFER TO AUDIOMETRIC BOOTH SHOP

DRAWING FROM VENDOR (INCLUDED IN DRAWING SET AS

REFERENCE DOCUMENT.)

(E)S

(E )S

(E )2

F B

(E)2FB

(E)2FB

(E)2FB

(E )2

F B

(E )2

F B

(E)2FB

(E )2

F B

(E )2

F B

(E )2

F B

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)S

(E)2FP

(E)2FB

1 2 3 4 5 6 7

A

B

ETR

ETR, REPAIR ANY

PORTION

DAMAGED DUE TO

CONSTRUCTION.

ETR

ETR

ETR

8' - 0"

8' - 0"

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

GWB

7' - 0" A.F.F.

GWB

7' - 0" A.F.F.

GWB

7' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

GWB

9' - 10" A.F.F.

7' - 10" 7' - 10" 7' - 10"

7' - 10"

7' - 10"

7' - 10"

7' - 10" 7' - 10" 7' - 10" 7' - 10" 7' - 10" 8' - 4"

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F. GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

GWB

9' - 10" A.F.F.

8' - 4"

AT-1

8' - 6" A.F.F.

AT-1

8' - 6" A.F.F.

AT-1

8' - 3" A.F.F.

AT-1

10' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

ACT-2

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

ACT-2

8' - 0" A.F.F.

1'

1'

1'

1'

1' - 7 1/4"

1'

1' - 0"

1'

1' - 7 1/4"

1'

1'

1'

1'

1'

1 1 1 1

ELEC. ROOM

E011

CORRIDOR

RECEPTION

E013

AUDIOMETRIC

ROOM 3

E023

AUDIOMETRIC

ROOM 4

E024

WAITING

E010

EXIT VESTIBULE

E022

OFFICE

E016

STAFF TOILET

E025

VESTIBULAR EXAM

E018

SPEECH THERAPY

E017

WORKROOM

E013A

CLEAN SUPPLY

E014

SOILED HOLD

E015

STORAGE

E021

CLINIC ROOM

E026

LAB

E028

PASSAGEWAY

E012

BREAKROOM /

CONFERENCE RM

E027

STOR.

E020A

STOR.

E023A

AT-1

8' - 0" A.F.F.

AUDIOMETRIC

ROOM 2

E020

AUDIOMETRIC

ROOM 1

E019

AT-1

8' - 0" A.F.F.

1 1

1 1

1 1 1

1 1

1 1

A130

A130

A130

A130

A130

A130

A130

A130

A130

A130

A130

A130

A130

A130

OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW

10'-0" ABOVE CORRIDOR

FLOOR; 7'-6" AT STAIR

LANDING

OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW

7' - 10"

7' - 10"

7' - 10"

OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW

OUTLINE OF AUDIOMETRIC EXAM BOOTH BELOW

7' - 10"

AT-1

8' - 0" A.F.F.

AT-1

8' - 0" A.F.F.

8' - 0"

ETR

ETR

2' - 2 1/2"

16A

A600

WALKWAY ABOVE

EX

A M B O O

TH

A

FT

E R

IN

S

TA

L L A

TI

O N

A

LI

G N

IN

F

IE

LD

, W

IT

H F R O N T O F

EX

A M B O O

TH

A

FT

E R

IN

S

TA

L L A

TI

O N

A

LI

G N

IN

F

IE

LD

, W

IT

H F R O N T O F

EX

A M B O O

TH

A

FT

E R

IN

S

TA

L L A

TI

O N

A

LI

G N

IN

F

IE

LD

, W

IT

H F R O N T O F

EX

A M B O O

TH

A

FT

E R

IN

S

TA

L L A

TI

O N

A

LI

G N

IN

F

IE

LD

, W

IT

H F R O N T O F

A130

A130

Sim

A130

Sim

A130

Sim

AT-1

8' - 3" A.F.F.

GWB

8' - 0" A.F.F.

OS

OS

OS OS

OS

OS

OS

OSOS

OS

OS OS

OS

OS

OS

OS

OS

OS

OS

A130

N.C.

N.C.

N.C.

N.C.

2'

A130 2' /8

2' /8

A130

A130

A130

A130

GENERAL CEILING NOTES

1. REFER TO INTERIORS, PLUMBING, MECHANICAL,

ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR ANY

ADDITIONAL CEILING AND WALL MOUNTED ITEMS NOT

SHOWN.

2. PROVIDE ACT-1 IN ALL LOCATIONS WHERE ACOUSTICAL

CEILING PANEL IS SHOWN UNLESS OTHERWISE NOTED.

3. ALL GYPSUM BOARD SOFFITS TO BE FRAMED WITH 3-5/8"

20GA METAL FRAMING, 16" O.C..

4. SOFFIT AND GWB CEILING PAINT COLORS ARE INDICATED

ON REFLECTED CEILING PLANS OR INTERIOR DRAWINGS.

PAINT ALL SIDES OF SOFFITS THE INDICATED COLOR.

5. ALL STAIR STEEL AND STAIR (UNDERSIDE) LANDINGS TO

RECEIVE PAINT.

6. ALL GYPSUM BOARD OR PLASTER CEILINGS TO BE

PAINTED PT1, UNLESS NOTED OTHERWISE.

7. ANY EXISTING TO REMAIN CEILING TO BE CLEANED AND

PAINTED AS NECESSARY

CEILING TYPE INDICATIONS

LEGEND

LIGHTING - RECESSED CEILING FIXTURE (REFER TO

ELECTRICAL DRAWINGS FOR TYPE)

LIGHTING - PENDENT FIXTURE (REFER TO

ELECTRICAL DRAWINGS FOR TYPE)

LIGHTING - SURFACE MOUNTED (REFER TO

ELECTRICAL)

LIGHTING - RECESSED CAN FIXTURE (LETTER

DESIGNATION TYPE)

HVAC SUPPLY (REFER TO MECHANICAL)

HVAC RETURN/EXHAUST (REFER TO MECHANICAL)

SINGLE FACE EXIT SIGN (REFER TO ELECTRICAL)

DOUBLE FACE EXIT SIGN (REFER TO ELECTRICAL)

CEILING FINISH TAG. REFER TO INTERIOR DWGS

FOR COLOR AND FINISH LEGEND

OCCUPANY SENSOR

SPRINKLER HEAD (REFER TO MECHANICAL)

2 x 2 ACOUSTICAL CEILING PANELS

GYPSUM BOARD - PAINTED REFER TO FINISH LEGEND

INDICATE OPENING THROUGH FLOOR -

REFER TO SECOND FLOOR RCP

N.C. NO CEILING

PT#

ETR EXISTING CEILING TO REMAIN

OS

3-5/8" METAL FRAMING

SECURED TO

STRUCTURE ABOVE

BOTTOM OF

SOFFIT/ CEILING

5/8" GWB, PAINTED

A S N O

TE

D

CEILING SYSTEM WHERE

OCCURS, REFER TO REFLECTED

CEILING PLANS

5"

8"

ANCHOR TRACK TO

STRUCTURE ABOVE &

BRACE AS REQUIRED

METAL STUD DIAGONAL BRACE

@ 48" O.C. MAX SECURED TO

STRUCTURE ABOVE

3-5/8" METAL FRAMING

SECURED TO

STRUCTURE ABOVE

METAL STUD DIAGONAL BRACE @

48" O.C. MAX SECURED TO

STRUCTURE ABOVE

BOTTOM OF

SOFFIT/ CEILING

5/8" GWB, PAINTED

A S N O

TE

D

AS NOTED

CEILING SYSTEM WHERE OCCURS,

REFER TO REFLECTED CEILING PLANS

LINE OF UPPER CABINET WHERE OCCURS

3"

3-5/8" METAL FRAMING SECURED

TO STRUCTURE ABOVE

METAL STUD DIAGONAL BRACE @

48" O.C. MAX SECURED TO

STRUCTURE ABOVE

5/8" GWB, PAINTED. TYPICAL FOR

ALL GWB IN DETAIL. REFER TO

FINISH SCHEDULE FOR COLOR

A S N O

TE

D

CEILING SYSTEM WHERE

OCCURS, REFER TO

REFLECTED CEILING PLANS

5"

A S N O

TE

D O N R C P

4"

EXISTING EXTERIOR WALL

EXISTING EXTERIOR WINDOW;

REFER TO WINDOW DETAILS

WHERE REPLACEMENT

OCCURS

CAULK GWB AT WINDOW ABUTMENT

ROLLER SHADE TO BE

PROVIDED AT ALL WINDOWS;

NEW AND EXISTING. REFER TO

FINISH SCHEDULE FOR

PRODUCT INFORMATION

LINE OF WALL BEYOND

SOFFIT BEYOND

(HEIGHT NOTED ON PLAN)

WINDOW SOFFET

(HEIGHT NOTED ON PLAN)

EXIST

COMPRESSOR

ROOM

019A

EXIST

STORAGE

019B

EXIST

STAIR HALL

EXIST

MECHANICAL

ROOM

EXIST

ELEVATOR

EXIST

DATA

CLOSET

EXIST

DATA CLOSET

EXIST

CLOSET

3-5/8" METAL FRAMING

SECURED TO

STRUCTURE ABOVE

CEILING SYSTEM WHERE

OCCURS, REFER TO REFLECTED

CEILING PLANS

4"

ANCHOR TRACK TO

STRUCTURE ABOVE &

BRACE AS REQUIRED

METAL STUD DIAGONAL BRACE

@ 48" O.C. MAX SECURED TO

STRUCTURE ABOVE

2"

AUDIOMETRIC EXAM BOOTH

HOLD BULKHEAD WALL FRAMING

ABOVE BOOTH CONSTRUCTION

1/2". INSERT COMPRESSIBLE FOAM

FILLER IN GAP; PROVIDE BACKER

ROD AND SEALANT AT JOINT.

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE

KEYPLAN

PLAN

NORTH

ACTUAL

NORTH

Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A130

BASEMENT REFLECTED CEILING

PLAN

SCALE: 1/4" = 1'-0"A130

1 BASEMENT REFLECTED CEILING PLAN

RCP KEYNOTES

VALUE Note Description

1 ALIGN BULKHEAD/SOFFIT WITH EDGE OF WALL/WALL OPENING.

2 EXISTING CEILING TILES THAT HAVE BEEN STORED AND

PROTECTED DURING CONSTRUCTION SHALL BE REINSTALLED

AFTER WORK IS COMPLETED FOR THE DAY. CEILING CANNOT

BE LEFT OPEN FOR MORE THAN A 24 HR PERIOD.

SCALE: 1 1/2" = 1'-0"A130

2 TYPICAL BULKHEAD DETAIL

SCALE: 1 1/2" = 1'-0"A130

3 SOFFIT @ WALL

SCALE: 1 1/2" = 1'-0"A130

4 SOFFIT @ WINDOW

SCALE: 1 1/2" = 1'-0"A130

5 BULKHEAD @ EXAM BOOTH

A500

A500

A500

A130

E017 E015 E014 E013E021

EX1

PROVIDE LOCK, TYP.

HPDL-2HPDL-2

SEE A600 FOR

WDW DETAILS

LINE OF SOFFIT BEYOND

A500

2' - 10 1/2" 2' - 6"

CLR

2' - 6"

2' 0"

1'

2'

6"

2' - 6" 2' - 6"

A500

A500

A500

FE

FE

FE

FE

FE

FE

P.LAM.

COUNTERTOP AND

BACKSPLASH

HPDL-2HPDL-2

HPDL-2

HPDL-2

HPDL-2

NEW LOCKERS

2'

4'

3' - 0" 3' - 0"

A500

FINISHED END

PROVIDE

LOCKSET, TYP.

HPDL-1 HPDL-1

A130

W1

A500

PROVIDE LOCK, TYP.

HPDL-1

7'

SEE A600 FOR

WDW DETAILS

E017

6"6"

2' 0"

1'

2'

6"

3' - 0" 3' - 0"

3' - 0"3' - 0"

1"

A500

�����������3

A500

A500

FE

FINISHED END

FINISHED END

PROVIDE LOCK,

TYP.

HPDL-1 HPDL-1

HPDL-1 HPDL-1

SSR-1

PTD

SD

2'

1'

2' 0"

3' - 3"3' - 3"3' - 3"1 1/2" FILLER PANEL 2" FILLER PANEL 2' - 6" 2' - 6" 2' - 6" 1 1/2" FILLER PANEL

1 1/2" FILLER PANEL

3' - 3" 3' - 3" 3' - 3" 2' - 0" 3' - 0" 2' - 0"

A500

A500

FINISHED P.LAM. PANEL W/ TOE KICK; MATCH ADJACENT

PROVIDE LOCK,

TYP.

HPDL-1HPDL-1HPDL-1HPDL-1HPDL-1HPDL-1

HPDL-1 HPDL-1 HPDL-1 HPDL-1 HPDL-1 HPDL-1

SSR-1

USER EQUIP -

SEE A120

USER EQUIP -

SEE A120

1 1/2" FILLER PANEL

2' - 6" 2' - 6" 2' - 6"

1 1/2" FILLER PANEL

A500

A500

PROVIDE LOCK,

TYP.

HPDL-1HPDL-1HPDL-1

HPDL-1HPDL-1

SSR-1

FILLER 4' - 0" 1' - 10" FILLER

1'

2' 0"

2'

4'

FLAT FILLER PANEL

(INACTIVE)

HPDL-1

HPDL-1

USE EQUIP - SEE

A120

USE EQUIP - SEE

A120

A500

A500

A500

2' - 9"2' - 9"2' - 9"

1 1/2" FILLER PANEL

2' - 0"

1" FILLER PANEL

2' - 6"3' - 0"2' - 6"

2' 0"

1'

2'

6"

2' - 9"2' - 9"2' - 9"2' - 2 1/2"2' - 6"3' - 0"3' - 0"

4" FILLER PANEL

FE

FINISHED

END

FINISHED

END

FE

PROVIDE LOCK, TYP.

SSR-1 SSR-1

HPDL-1

HPDL-1

HPDL-1 HPDL-1 HPDL-1 HPDL-1

HPDL-1HPDL-1

HPDL-1

HPDL-1HPDL-1

PTD

SD

E028

2' - 0" 3' - 1 1/2"

1" OVERHANG

2' 0"

A500

FINISHED

END

SOLID SURFACE

COUNTERTOP

AND

BACKSPLASH

SOLID SURFACE

COUNTERTOP

AND

BACKSPLASH

HPDL-1

2'

A500

A130

6'

FURNITURE, OFOI

GENERAL MILLWORK NOTES:

REFER TO EQUIPMENT SCHEDULE ON SHEET A120 FOR INFO REGARDING SCOPE RESPONSIBILITY

PROVIDE SHOP DRAWINGS FOR ALL MILLWORK TO BE APPROVED PRIOR TO FABRICATION.

DRILL 1-3/4" DIA. HOLE AT EACH PHONE, DATA OR ELECTRICAL OUTLET LOCATED BENEATH A

COUNTER AS DIRECTED BY OWNER. PROVIDE A PLASTIC TRIM GROMMET FOR EACH HOLE.

SEE SYMBOLS AND ABBREVIATIONS SHEET FOR TYPICAL ACCESSORY MOUNTING HEIGHTS IF NOT

INDICATED.

SEE EQUIPMENT SCHEDULE IN SPECIFICATIONS FOR OWNER FURNISHED ITEMS (OFCI) AND

CONTRACTOR FURNISHED ITEMS (CFCI).

ALL EXPOSED COUNTERTOP CORNERS SHALL BE RADIUSED. ALL EXPOSED SIDES TO BE FINISHED.

ALL CABINETS AND DRAWERS TO RECEIVE LOCKS. PROVIDE COMMON KEY FOR SUITE.

PROVIDE FIRE TREATED BLOCKING WHERE REQUIRED AT ALL MILLWORK & WALL MOUNTED

ACCESSORIES.

REFER TO FINISH DRAWINGS, SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

COORDINATE RACEWAY LOCATIONS WITH ELECTRICAL DRAWINGS.

ALL CASEWORK SHOWN FOR UPPER AND LOWER CABINETS, INCLUDING SHELVING & HARDWARE,

TO BE PROVIDED BY CONTRACTOR.

SEE DRAWING I-100 FOR ALL SIGNAGE MOUNTING TYPES AND LOCATIONS.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

IDENTIFIES FURNITURE THAT WILL BE PROVIDED AND INSTALLED BY THE VA.

WP-2

EQ EQ 4" RUBBER BASE

S.S. TRIM,

BOTH SIDES

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A210

INTERIOR ELEVATIONS

SCALE: 3/8" = 1'-0"A210

1 CORRIDOR - ELEVATION A

SCALE: 3/8" = 1'-0"A210

2 BREAKROOM / CONF. RM. - ELEVATION

SCALE: 3/8" = 1'-0"A210

9 WORKROOM - ELEVATION

SCALE: 3/8" = 1'-0"A210

3 CORRIDOR - ELEVATION B

SCALE: 3/8" = 1'-0"A210

4 SPEECH THERAPY - ELEVATION

SCALE: 3/8" = 1'-0"A210

5 LAB - ELEVATION A

SCALE: 3/8" = 1'-0"A210

6 LAB - ELEVATION B

SCALE: 3/8" = 1'-0"A210

7 LAB - ELEVATION C

SCALE: 3/8" = 1'-0"A210

8 LAB - ELEVATION D

SCALE: 3/8" = 1'-0"A210

10 WAITING - ELEVATION

SCALE: 3/8" = 1'-0"A210

11 TYP. SINK STATION

4" RUBBER BASE

EXISTING

WINDOW -

SEE A600

FOR INFO

FE

4" RUBBER BASE

TV

C.L.

PTD

SD

FESD

PTD

4" RUBBER BASE

4" RUBBER BASE

4" RUBBER BASE

NEW HANDRAIL -

SEE I100 FOR

ADDITIONAL INFO

NEW HANDRAIL -

SEE I100 FOR

ADDITIONAL INFO

NEW HANDRAIL -

SEE I100 FOR

ADDITIONAL INFO

A400

56 SF

STAFF TOILET

E025

E025

B

F1.0 F3.0

F3.0

F3.0

S3.0ri

F3.0

3' - 5" 3" 1' - 8" 1' - 10 1/2"

7' - 3"

7' /2

2'

1/ 2"

EQ EQ

EQ. EQ.

2' 0"

WRIST BLADE TYPE

HANDLES. SEE

PLUMBING

DRAWINGS FOR FIXTURE

AND HARDWARE

SPECIFICATIONS

BASE AS SCH'D.

WRAP DRAIN PIPE W/

INSULATED PIPE KIT

CEILING AS SCH'D.

PAPER TOWEL

DISPENSER; MOUNTING

HEIGHT SIMILAR TO

SOAP DISPENSER SOAP DISPENSER

MIRROR

O R A B O V E C O U N

TE

R

4'

TO

D

IS

P

EN

S

IN

G D

EV

IC

E

5'

6"

WALL TILE AS SCH'D.

16"-18"

3' - 0" 6"

2' - 0" 12" MIN.

*REFER TO OTHER ELEVATIONS FOR REMAINING MOUNTING HEIGHTS

1' 0"

4'

EQ EQ

BASE AS SCH'D.

WALL TILE AS SCH'D.

5'

6"

BASE AS SCH'D.

CEILING AS SCH'D.

1-1/2" DIA. S.S. GRAB

BARS W/ BLOCKING AT

MOUNTING

LOCATIONS, TYP.

7"-9"

1'

1'

12" MAX 3' - 6" MIN.

39"-41"

54" MIN.

TOILET PAPER

DISPENSER

WALL TILE AS SCH'D.

6" 5'

GENERAL MILLWORK NOTES:

REFER TO EQUIPMENT SCHEDULE ON SHEET A120 FOR INFO REGARDING SCOPE RESPONSIBILITY

PROVIDE SHOP DRAWINGS FOR ALL MILLWORK TO BE APPROVED PRIOR TO FABRICATION.

DRILL 1-3/4" DIA. HOLE AT EACH PHONE, DATA OR ELECTRICAL OUTLET LOCATED BENEATH A

COUNTER AS DIRECTED BY OWNER. PROVIDE A PLASTIC TRIM GROMMET FOR EACH HOLE.

SEE SYMBOLS AND ABBREVIATIONS SHEET FOR TYPICAL ACCESSORY MOUNTING HEIGHTS IF NOT

INDICATED.

SEE EQUIPMENT SCHEDULE IN SPECIFICATIONS FOR OWNER FURNISHED ITEMS (OFCI) AND

CONTRACTOR FURNISHED ITEMS (CFCI).

ALL EXPOSED COUNTERTOP CORNERS SHALL BE RADIUSED. ALL EXPOSED SIDES TO BE FINISHED.

ALL CABINETS AND DRAWERS TO RECEIVE LOCKS. PROVIDE COMMON KEY FOR SUITE.

PROVIDE FIRE TREATED BLOCKING WHERE REQUIRED AT ALL MILLWORK & WALL MOUNTED

ACCESSORIES.

REFER TO FINISH DRAWINGS, SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

COORDINATE RACEWAY LOCATIONS WITH ELECTRICAL DRAWINGS.

ALL CASEWORK SHOWN FOR UPPER AND LOWER CABINETS, INCLUDING SHELVING & HARDWARE,

TO BE PROVIDED BY CONTRACTOR.

SEE DRAWING I-100 FOR ALL SIGNAGE MOUNTING TYPES AND LOCATIONS.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

IDENTIFIES FURNITURE THAT WILL BE PROVIDED AND INSTALLED BY THE VA.

A

A4006

A400 7

A210 9

2' - 4"

CLR

1' - 11 3/4"

11"

11"

4'

6'

11" 1' - 4"

2' - 3"

/8

/8

C

LR

5'

3' /8

8' /8

W3

W3

A501

A501

AUTO OPERATOR BUTTON

SSR-1 DG-1

SSR-1

E0

/4

2' 0"

W3 W3

A501

A501

HPDL-1HPDL-1HPDL-1

SSR-1SSR-1SSR-1

DG-1

5'

2' - 1" 1' - 11" 7' - 0 1/2"4" RUBBER BASE

EQ EQ EQ EQ

A500

2'

2'

2'

2' - 0"

2' - 0"2' - 0"2' - 0"

2' - 0"

A500

A500

A501

PROVIDE LOCKSET, TYP.

PROVIDE GROMMETS IN

COUNTER; COORDINATE

LOCATIONS WITH

OWNER .

HPDL-1HPDL-1HPDL-1

HPDL-1HPDL-1

HPDL-2

W3 W3

4" RUBBER BASE.

1 2

B

BOOTH

16' - 0"

B O O

TH

9'

1/ 2"

A400

A400

CONTROL

(STAFF)

EXAM

(PATIENT)

A400

A400

A500

Sim

A600

0" 1/ 4"

6" P

IT

1/ 8" T O T O P O F S

IL

L

1/2" AT FRONT

0" 1/ 4"

6" P

IT

1/ 8" T O T O P O F S

IL

L

1/2" AT FRONT

BASEMENT FLOOR

-12' - 0"

1' - 2 1/2"

AUDIOMETRIC

BOOTH

CONCRETE SLAB ON

COMPACTED GRAVEL

REFER TO ENLARGED

FLOOR PLAN FOR WALL

TYPE

EXISTING COLUMN

EXISTING PIER ON TOP OF FOOTING

4"

5" 5"

6"

REFER TO STRUCT DWGS

FOR SLAB REINF.

BASEMENT FLOOR

-12' - 0"

11 5/8"

AUDIOMETRI

C BOOTH

4" 6" 5"

4"

CONCRETE SLAB ON

COMPACTED GRAVEL

EXISTING EXTERIOR WALL ON TOP OF FOOTING

REFER TO STRUCT

DWGS FOR SLAB REINF.

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A400

ENLARGED PLANS & INT.

ELEVATIONS

SCALE: 1/2" = 1'-0"A400

1 ENLARGED TOILET PLAN

SCALE: 1/2" = 1'-0"A400

2 STAFF TOILET - ELEVATION A

SCALE: 1/2" = 1'-0"A400

3 STAFF TOILET - ELEVATION B

SCALE: 1/2" = 1'-0"A400

4 STAFF TOILET - ELEVATION C

SCALE: 1/2" = 1'-0"A400

5 ENLARGED RECEPTION PLANSCALE: 1/2" = 1'-0"A400

6 RECEPTION - EXTERIOR ELEVATION

SCALE: 1/2" = 1'-0"A400

7 RECEPTION - INTERIOR ELEVATION

SCALE: 1/2" = 1'-0"A400

8 ENLARGED AUDIOMETRIC BOOTH

SCALE: 1/2" = 1'-0"A400

9 SINGLE WALL BOOTH PIT DETAIL

SCALE: 1/2" = 1'-0"A400

10 DOUBLE WALL BOOTH PIT DETAIL

SCALE: 1/2" = 1'-0"A400

11 SLAB CONDITION @ COLUMN

SCALE: 1/2" = 1'-0"A400

12 SLAB CONDITION @ EXTERIOR WALL

PARTITION AS NOTED

FIRE EXTINGUISHER

CABINET

REINFORCE PARTITION TOP

& BOTTOM AS REQUIRED

TO PROPERLY INSTALL

EXTINGUISHER CABINET

2'

M

A X.

4'

TO

O P

ER

A

TI

N G M

EC

H N A

IS

M

SCHEDULED BASE

FINISHED FLOOR

3/4" PARTICLE BOARD SHELF W/

MELAMINE FINISH TOP AND

BOTTOM (TYPICAL)

HEAVY DUTY ADJUSTABLE SHELF

BRACKET W/ SCREW DOWN ENDS

(TYPICAL)

SHELF STANDARDS @ 32" o.c.

(MAX.)

1X WOOD CLEATS @ SIDE WALLS

FOR ADDITIONAL SUPPORT

(TYPICAL)

HORIZONTAL WOOD BLOCKING

TOP AND BOTTOM AT 24" o.c.

(MAX.) - AS REQ'D. FOR PROPER

BRACKET PLACEMENT

PVC FACE TRIM

1' - 0"

6" 6'

PULLS PER SPEC (TYP.

FOR CABINET DOORS)

3/4" PARTICLE BD. SHELF

WRAPPED IN MELAMINE ON

ADJ. BRACKETS

SHELF STD.

3/4" THK. PLYWOOD BOTTOM

SCHEDULED BASE

FINISHED FLOOR

2X WOOD BLK'G @

24" O.C.

MELAMINE INTERIOR, TYP.

FIXED 3/4" PARTICLE BD.

SHELF WRAPPED IN

MELAMINE

PULLS PER SPEC (TYP.

FOR CABINET DOORS)

CLG. AS NOTED

ANCHOR TO STRUCTURE

ABOVE

5/8" GYP. BOARD ON 3 5/8"

METAL FRAMING

BRACE WITH 3 5/8" METAL STUDS

@4'-0" O.C. MAX.

PLASTIC LAMINATE TRIM

2X4 CONT. FURRING

ANCHORED TO WALL @

24" o.c.

PLASTIC LAMINATE ON

3/4" PARTICLE BOARD

21" TYP.

3" TYP.

4"

7'

2" TYP.

3" M

IN

SCRIBE TO WALL &

CAULK

FAUCET AS SPECIFIED

COUNTERTOP AS NOTED ON

ELEVATIONS; SEE 6/A500

TYPICAL CONSTRUCTION DETAILS

PLASTIC LAMINATE

ON 3/4" PLYWOOD

1/2" PARTICLE BOARD

ADHERED

SINK AS SPECIFIED

PLAM ON REMOVABLE

PLYWOOD PANEL &

PLAM ON ALL

EXPOSED EDGES

CONT. 1X WOOD

CLEAT

WHERE REQ'D, 3/4"

PLYWOOD END PANEL

W/ PLASTIC LAMINATE

FINISH & CONT. 1X

WOOD CLEAT

FACE OF WALL

BASE AS SPECIFIED FINISHED FLOOR

8"

11"

9" 1'

A S N

O

TE

D

1/

2" 2'

M

IN

H

EI

G H T

P

ER

IN

TE

R

IO

R E

LE

V A

TI

O N S

FACE OF WALL

COUNTERTOP AS NOTED ON

ELEVATIONS; SEE 6/A500 TYPICAL

CONSTRUCTION DETAILS

75 LB. DRAWER SLIDE

PER SPEC.

PULLS PER SPEC (TYP.

FOR CABINET DOORS &

DWRS)

1/4" THK. PANEL

DRAWER BOTTOM

PULLS PER SPEC (TYP.

FOR CABINET DOORS &

DWRS)

SHELF STD.

1/4" THK. PANEL PRODUCT

3/4" THK. PLYWOOD BOTTOM

SCHEDULED BASE

FINISHED FLOOR

CONTINUOUS 1X4 WOOD

FURRING ANCHOR AT WALL

STUDS

3/4" PLYWOOD SHELF

WRAPPED IN MELAMINE ON

ADJ. BRACKETS

2X WOOD BLK'G @ 24" O.C. (FIRE

TREATED)

H

EI

G H T

P

ER

IN

TE

R

IO

R E

LE

V A

TI

O N S

1' - 9" 3" TYP.

4"

6"

BASE AS SCHEDULED

2' - 1" OR AS NOTED ON PLAN

H

EI

G H T

P

ER

IN

TE

R

IO

R E

LE

V A

TI

O N

4"

2X4 WOOD BLOCKING IN WALL

PRE-FAB, PRE-FINISHED STEEL

BRACKET PER SPEC.

SEE TYP. COUNTERTOP DETAIL

6/A500 FOR ADD'L INFO

3/4"

PROVIDE 2" GROMMETS IN

COUNTER FOR ELEC/TELE

CABLES; COORDINATE WITH

ELEC. DEVICE LOCATIONS

PROVIDE 2" GROMMETS IN

COUNTER FOR ELEC/TELE

CABLES; COORDINATE WITH

ELEC. DEVICE LOCATIONS

CLG. AS NOTED

BOTTOM OF CABINET TO BE

FACED W/ PLASTIC LAMINATE

PULLS PER SPEC

3/4" PLYWOOD SHELF

WRAPPED IN PLASTIC

LAMINATE ON ADJUSTABLE

BRACKETS

EURO PIN SYSTEM W/ METAL

SHELF BRACKETS

ALL FACES OF DOORS & ALL

EXPOSED VERTICAL SURFACES

TO BE FACED WITH PLASTIC

LAMINATE

INTERIOR OF CABINET TO BE

FACED W/ MELAMINE (TYP.)

1/4" THICK PANEL PRODUCT

CONTINUOUS 1X4 WOOD

FURRING ANCHOR AT WALL

STUDS

1' - 3"

3" M

IN

CLR.

1' - 0" MIN.

O R A

S N

O

TE

D

2'

1/

4"

1/2" SOLID SURFACE COUNTERTOP

3/4" PARTICLEBOARD SUBSTRATE W/

WHITE LINER UNDERSIDE

REFER TO PLANS

BUILT- UP SOLID SURFACE EDGE,

LAPPED JOINERY

1/8" RADIUS EASED EDGES

B A C K S P

LA

S H H

T 4"

T

YP

1/2" SOLID SURFACE BACKSPLASH

CONTINUOUS SEALANT AT JUNCTURE OF BACK

AND SIDE SPLASHES WITH COUNTERTOP

1/2" SOLID SURFACE SIDE SPLASH WITH

EASED EDGES

WHITE LINER UNDERSIDE

3mm EDGE BANDING

B A C K S P

LA

S H H

T 4"

T

YP

1-1/8" PARTICLE BOARD

HIGH PRESSURE LAMINATE

3mm EDGE BANDING AT TOP AND 1mm EDGE

BANDING AT UNDERSIDE OF BACKSPLASH

AND SIDE SPLASH

3/4" PARTICLE BOARD WITH HIGH PRESSURE

LAMINATE BACKSPLASH AND SIDE SPLASH

SOLID SURFACE COUNTERTOP CONSTRUCTION

LAMINATE COUNTERTOP CONSTRUCTION

CONTINUOUS SEALANT AT JUNCTURE OF

BACK AND SIDE SPLASHES WITH

COUNTERTOP

REFER TO PLANS

3/4" THK. PLYWOOD BOTTOM

LOCK PER SPEC (TYP.

FOR LOCKER DOORS)

2x4 CONT. FURRING

ANCHORED TO WALL @

24" O.C.

PLASTIC LAMINATE ON

3/4" PARTICLE BOARD

9" 3"

4"

6'

5"

3/

4" 1'

/4

1'

/4

1'

/4

5" 5"

STAINLESS STEEL HOOK W/

CONCEALED FASTENERS

AND BLOCKING BEHIND

P.LAM BACKER

2x4 WOOD BLOCKING, TYP.

PLASTIC LAMINATE ON

3/4" PARTICLE BOARD

PLASTIC LAMINATE ON

3/4" PARTICLE BOARD

SCHEDULED BASE

FINISHED FLOOR

2X WOOD BLOCKING AT 24" O.C.

3/4" THK. PLYWOOD BOTTOM

4" 4"

6" 4"

6" 6"

12"

CLEAR

9"

STAINLESS STEEL CONCEALED

HINGES PER SPEC.

1/

2"

1/ 2"

BASEMENT FLOOR

-12' - 0"

1 1/2" TYP.

1 1/2" TYP.

3' -0

TY

P

AUDIOMETRIC BOOTH

REFER TO PARTITION TYPE

EXISTING STAIR

EXISTING CONCRETE SLAB EXISTING SLAB BEYOND

CONCRETE SLAB

6"

BLOCKING AS REQ'D

B

1/2" GYP. BD.; ADJUST TO

ALIGN W/ EXISTING WALL

2-1/2" METAL STUD W/

INSULATION

A600

Sim

3-5/8" METAL STUD W/

INSULATION AND (1)

LAYER OF 5/8" GYP. BD

ON EACH SIDE. REFER TO

PARTITION TYPE.

EXISTING WALLS

3/4" AIR GAP

REFER TO PARTITION

TYPE FOR WALL

CONSTRUCTION

CLG. AS NOTED

PULLS PER SPEC

3/4" PLYWOOD SHELF

WRAPPED IN PLASTIC

LAMINATE ON ADJUSTABLE

BRACKETS

EURO PIN SYSTEM W/ METAL

SHELF BRACKETS

ALL FACES OF DOORS & ALL

EXPOSED VERTICAL SURFACES

TO BE FACED WITH PLASTIC

LAMINATE

INTERIOR OF CABINET TO BE

FACED W/ MELAMINE (TYP.)

BOTTOM OF CABINET TO BE

FACED W/PLASTIC LAMINATE

TASK LIGHT

CONTINUOUS 1X4 WOOD

FURRING ANCHOR AT WALL

STUDS

1' - 3"

4" O R A

S N

O

TE

D

2'

CLR.

1' - 0" MIN.

3" M

IN

1/4" THICK PANEL PRODUCT

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A500

DETAILS

SCALE: 1 1/2" = 1'-0"A500

1 FIRE EXTINGUISHER CABINET

SCALE: 1 1/2" = 1'-0"A500

4 SHELVING DETAIL

SCALE: 1 1/2" = 1'-0"A500

5 TALL CABINET DETAIL

SCALE: 1 1/2" = 1'-0"A500

2 ADA SINK SHROUD

SCALE: 1 1/2" = 1'-0"A500

3 BASE CABINET DETAIL

SCALE: 1 1/2" = 1'-0"A500

7 COUNTERTOP SUPPORT DETAIL

SCALE: 1 1/2" = 1'-0"A500

8 UPPER CABINET DETAIL

SCALE: 3" = 1'-0"A500

6 TYPICAL COUNTERTOP CONSTRUCTION

SCALE: 1 1/2" = 1'-0"A500

11 P.LAM LOCKER DETAIL

SCALE: 3/4" = 1'-0"A500

9 HANDRAIL DETAIL

SCALE: 1 1/2" = 1'-0"A500

10 PLAN DETAIL -1

SCALE: 1 1/2" = 1'-0"A500

8A UPPER CABINET DETAIL W/ LIGHT

SEE A110

A600

A600

5/8" GWB, PAINTED.

TYPICAL FOR ALL GWB IN

DETAIL. REFER TO FINISH

SCHEDULE FOR COLOR

CEILING SYSTEM WHERE

OCCURS, REFER TO

REFLECTED CEILING PLANS

AS NOTED ON RCP

4"

4"

CEILING AS NOTED ON RCP

METAL STUD DIAGONAL

BRACE @ 48" O.C. MAX

SECURED TO STRUCTURE

ABOVE

1/2" SOLID SURFACE OVER 3/4" PLYWOOD

P.LAM OVER 3/4" PLYWOOD; ALL

EXPOSED EDGES TO BE

FINISHED

2x4 P.T. WOOD FRAMING, TYP.

11"

2' - 1"

2'

2"

9" 2'

2' 0"

2x4 WOOD BLOCK IN WALL; ANCHOR TO FRAMING

PRE-FAB., PRE-FINISHED STEEL BRACKET PER SPEC.

P.LAM OVER 3/4" PLYWOOD

1x4 WOOD BLOCK

BASE AS SCHEDULED

2x4 P.T. WOOD FRAMING, TYP.

SLIDING TRANSACTION

WINDOW

1' - 5" 2' - 0"

A600

W3 W3

A501

1/2" SOLID SURFACE

OVER 3/4" PLYWOOD

P.LAM OVER 3/4" PLYWOOD; ALL

EXPOSED EDGES TO BE

FINISHED

2x4 P.T. WOOD FRAMING, TYP.

2x6 P.T. WOOD FRAMING, TYP.

BASE AS SCHEDULED

A501

2' 0"

4"

1' - 10 3/4"

EQ EQ

DG-1 DECORATIVE

GLASS

DIVIDER/PRIVACY

PANEL - SEE SHEET

I100 FOR INFO

3/4" PLYWOOD WITH 1/2" SOLID SURFACE

COUNTER TOP WITH RADIUSED EDGES

ALUM. C TRACK PER SPEC; ROUTE

TRACK INTO COUNTER TOP

1/2" RESIN PANEL (RP-1) PER SPEC

ALUM. C TRACK PER SPEC;

PROVIDE BLOCKING IN CEILING

3/4" PLYWOOD WITH HIGH PRESSURE

LAMINATE TRANSACTION COUNTER;

PROVIDE 3MM EDGE BANDING - MATCH

LAMINATE COLOR

Engineering Architecture Environmental Planning

300 State Street Suite 201

Rochester, NY 14614 P: (585) 454-6110 www.labellapc.com

LaBella Powered by partnership.

Miller-RemickLLC

1010 KINGS HIGHWAY SOUTH

CHERRY HILL, NEW JERSEY 08034

PHONE: (856)429-4000

FAX: (856)429-5002

M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business

MR PROJECT NO: 0499-0119

A S e rv ic e

D i s a b l e d

Ve t e r an Owne d

S m a l l

B u s iness

SDVOSB

CVE Location

Issue Date o n e e ig h th i n c h o n e f o o t

B

A

C

D

E

F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

97 8654321

B

A

C

D

E

F

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT RELOCATION OF AUDIOLOGY

CASTLE POINT CAMPUS

WAPPINGERS FALLS, NY

620A4-18-204

15E

Project Director

C U s e rs

\R M o n ig le

\D o c u m e n ts \R e v it L o c a l F ile s \2

C a s tl e P o in t V

A M

C

A u d io lo g y C lin ic

R rm o n ig le

.r v t

BID DOCUMENTS

2021-05-17 JPR REM

A501

DETAILS

SCALE: 1 1/2" = 1'-0"A501

1 RECEPTION DESK @ WINDOW

SCALE: 1 1/2" = 1'-0"A501

2 RECEPTION DESK @ DIVIDER PANEL

SCALE: 1 1/2" = 1'-0"A501

3 RECEPTION DESK @ DIVIDER PANEL - Callout 1

AS SCHEDULED

A S S C H E D U

LE

D

AS SCHEDULED

A S S C H E D U

LE

D

A S S C H E D U

LE

D

2"

2" AS SCHEDULED

2"

FRAME TYPES

DOOR TYPES

AS SCHEDULED

A S S C H E D U

LE

D

3'

6"

5" 5"

2" AS SCHEDULED

2"

NL-1

FLUSH

WITH VISION PANEL

HG-1

HALF GLASS

HM-A

HOLLOW METAL FRAME

F-1

FLUSH

AL-A

ALUMINUM FRAME

A S S C H E D U

LE

D

4"

6" 6"

3'

6"

M A X

3'

M A X

3'

PER MFR

RAILING LENGHT

AL-B

SLIDING BAR DOOR

P

ER

M

FR

R A

IL

IN

G H

EI

G H T

SCHEDULED SEALANT -

PERIMETER BOTH

SIDES

GYPSUM

BOARD

SEE PARTITION TYPE

FOR WALL THICKNESS

VARIES2" 2"

2"

DBL. METAL STUD

BOX BEAM

HEADER

HOLLOW METAL

DOOR FRAME

S

EE

P A R

TI

TI

O N T

YP

E

FO

R W

A

LL

T H

IC

K N

ES

S

V A R

IE

S

2" 2"

2" 5/8"

SCHEDULED

SEALANT - PERIMETER

BOTH SIDES

1/ 2"

1/ 2"

GYPSUM

BOARD

DBL. METAL STUD

JAMB

HOLLOW METAL

DOOR FRAME

METAL STUD ANCHOR

(MIN. 3 PER JAMB)

SCHEDULED DOOR

SCHEDULED SEALANT -

PERIMETER BOTH

SIDES

GYPSUM

BOARD

SEE PARTITION TYPE

FOR WALL THICKNESS

DBL. METAL STUD

BOX BEAM

HEADER

VARIES

2" 2"

HOLLOW METAL

WINDOW FRAME

REMOVABLE

GLAZING

BEAD

METAL STUD

ANCHOR

(MIN. 3 PER JAMB)

1/4" CLEAR

TEMPERED GLASS

S

EE

P A R

TI

TI

O N T

YP

E

FO

R W

A

LL

T H

IC

K N

ES

S

V A R

IE

S

2" 2"

2"

5/8"

SCHEDULED

SEALANT - PERIMETER

BOTH SIDES

1/ 2"

1/ 2"

GYPSUM

BOARD

DBL. METAL STUD

JAMB

HOLLOW METAL

WINDOW FRAME

METAL STUD ANCHOR

(MIN. 3 PER JAMB)

REMOVABLE GLAZING BEAD

1/4" CLEAR TEMPERED

GLASS

SEE PARTITION TYPE

FOR WALL THICKNESS

VARIES

2"2"

6"

1/4" CLEAR TEMPERED GLASS

REMOVABLE GLAZING BEAD

HOLLOW METAL WINDOW FRAME

FIRE RETARDANT

TREATED BLOCKING AS

REQ'D

SEALANT AS REQ'D

(TYP. BOTH SIDES)

GRADE

STIFF CLIP

5/8" GYP. BD, EACH

SIDE, ON 3-5/8" STUDS

@ 16" O.C. (REFER TO

PARTITION TYPE)

V.I.F.

3' - 5" 2"

3' - 9"

V .I.

F.

5'

4' " 15

A600

A600

A600

2" 2' 2"

2' 2"

2"

14A/A600 TO BE

USED AT FIRST

FLOOR WALKWAY

2" 3'

2"

4'

3'

2" 2' - 9"

2" 2' - 9"

2"

6' - 0"

A600

A600

A600

A600

SCHEDULED SEALANT -

PERIMETER BOTH

SIDES

GYPSUM

BOARD

SEE PARTITION TYPE

FOR WALL THICKNESS

VARIES2" 2"

2"

HOLLOW METAL

DOOR FRAME

12 GA 3-5/8" HDS

HEADER ANCHORED

TO JAMB STUD W/

HEADER BRACKET

S

EE

P A R

TI

TI

O N T

YP

E

FO

R W

A

LL

T H

IC

K N

ES

S

V A R

IE

S

2" 2"

2" 5/8"

SCHEDULED

SEALANT - PERIMETER

BOTH SIDES

1/ 2"

1/ 2"

GYPSUM

BOARD

HOLLOW METAL

DOOR FRAME

METAL STUD ANCHOR

(MIN. 3 PER JAMB)

SCHEDULED DOOR

12 GA 3-5/8" HDS

METAL STUD EACH

SIDE EXTENDED AND

ANCHORED TO

STRUCTURE ABOVE

SCHEDULED DOOR

SEALANT AND BACKER

ROD, TYP. OF BOTH

SIDES

EXISTING EXTERIOR

WALL CONSTRUCTION

ALUMINUM DOOR

FRAME

SHIM FRAME,

DETERMINE

THICKNESS IN

FIELD

CHANNEL

RUNNER AT TOP

OF STUD

FRAMING

EXISTING

LINTEL(S) TO

REMAIN

LINE OF WALL BEYOND

REFER TO PARTITION TYPE

1/2" OFFSET

3"

SEALANT AND BACKER

ROD, TYP. OF BOTH

SIDES

EXISTING EXTERIOR

WALL CONSTRUCTION

ALUMINUM DOOR FRAME

SHIM WINDOW,

DETERMINE

THICKNESS IN

FIELD

5/8" TYPE "X"

GYP. BD.

REFER TO PARTITION TYPE

1/2" OFFSET

3"

SCHEDULED DOOR

1. ALL NEW HARDWARE TO CONFORM TO CABO-ANSI A117.1-2009

2. ALL NEW DOOR HANDLES SHALL BE LEVER TYPE.

3. HARDWARE FINISHES SHALL MATCH BUILDING STANDARD.

4. COORDINATE KEYING DIRECTLY WITH OWNER/TENANT.

5. H.C. TOILET ROOM PRIVACY LOCKS SHALL HAVE AN EMERGENCY

OVERRIDE KEY, TO BE MOUNTED CONSPICUOUSLY…

This is the start of the file's text. The full file is on GovTribe.