03 OP1141681_Combined Drawings.pdf

PDF 1 MB Posted

Attached to
REPLACE TRANSFORMER Federal contract opportunity
Solicitation number
FA441724B0001
Issued by
Department of the Air Force Special Operations Command

About this file

This solicitation is for a construction project to replace a transformer at Hurlburt Field in Florida. The project involves installing a new 2000A NEMA 3R switchboard and 1500KVA pad mounted transformer in the same locations as the equipment being removed. A new primary junction cabinet will also be installed. The requirement is set aside for small businesses under NAICS code 237130, with an estimated value between $250,000 and $500,000. The pre-bid site visit information can be found in section L. Bids are due by the date and time specified in the solicitation, which will be awarded following FAR part 14 for sealed bidding. Primary and alternate points of contact for company representatives are requested. The Department of the Air Force Special Operations Command is the issuing agency.

View the file

Other files for this federal contract opportunity

Other files attached to REPLACE TRANSFORMER, newest first.
File Type Posted
Site Visit Sign in roster.pdf PDF
Solicitation - FA441724B0001 - 1.pdf PDF
Amendment FA441724B00010001 - Replace Transformer.pdf PDF
Question 4 and 7.jpg JPG image
06 OP1141681_Working Time Analysis v2.pdf PDF
Replace Transformer - Question Responses.docx DOCX document
PJC J672 Exterior.jpg JPG image
PJC J672 Interior.jpg JPG image
AMRS Hurlburt Field ION8650 details.pdf PDF
Solicitation - FA441724B0001 - Released.pdf PDF
Wage Determination.pdf PDF
06 OP1141681_Working Time Analysis.pdf PDF
02 OP1141681_Specifications.pdf PDF
Solicitation - FA441724B0001.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SP

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

C E

T

R A

N S

F O

R M

E R

B U

I L

D I N

G

OF 7

OP1141681

8 DEC 2023

91029

C. MARTEL

C. MARTEL

G-001

REPLACE TRANSFORMER, BUILDING

91029

AutoCAD SHX Text 91158

AutoCAD SHX Text 91131

AutoCAD SHX Text 91129

AutoCAD SHX Text 91362

AutoCAD SHX Text 91157

AutoCAD SHX Text 91107

AutoCAD SHX Text 91041

AutoCAD SHX Text 91261

AutoCAD SHX Text 91263

AutoCAD SHX Text 91264

AutoCAD SHX Text 29077

AutoCAD SHX Text 29077

AutoCAD SHX Text 91043

AutoCAD SHX Text 91038

AutoCAD SHX Text 91124

AutoCAD SHX Text 91149

AutoCAD SHX Text 91101

AutoCAD SHX Text 91141

AutoCAD SHX Text 99005

AutoCAD SHX Text 91262

AutoCAD SHX Text 91259

AutoCAD SHX Text 91113

AutoCAD SHX Text 91258

AutoCAD SHX Text 91042

AutoCAD SHX Text 91136

AutoCAD SHX Text 91126

AutoCAD SHX Text 91153

AutoCAD SHX Text 91041

AutoCAD SHX Text 91250

AutoCAD SHX Text 91257

AutoCAD SHX Text 91144

AutoCAD SHX Text 91028

AutoCAD SHX Text 91260

AutoCAD SHX Text 91036

AutoCAD SHX Text 91268

AutoCAD SHX Text 91114

AutoCAD SHX Text 91119

AutoCAD SHX Text 91033

AutoCAD SHX Text 91147

AutoCAD SHX Text 91027

AutoCAD SHX Text 91361

AutoCAD SHX Text 91370

AutoCAD SHX Text 91351

AutoCAD SHX Text 99019

AutoCAD SHX Text 91365

AutoCAD SHX Text 91603

AutoCAD SHX Text 91601

AutoCAD SHX Text 91120

AutoCAD SHX Text 91035

AutoCAD SHX Text 91266

AutoCAD SHX Text 91310

AutoCAD SHX Text 91135

AutoCAD SHX Text 91106

AutoCAD SHX Text 91325

AutoCAD SHX Text 91360

AutoCAD SHX Text 91156

AutoCAD SHX Text 91099

AutoCAD SHX Text 91145

AutoCAD SHX Text 91152

AutoCAD SHX Text 91030

AutoCAD SHX Text 91132

AutoCAD SHX Text 91034

AutoCAD SHX Text 99018

AutoCAD SHX Text 99004

AutoCAD SHX Text 91112

AutoCAD SHX Text 91133

AutoCAD SHX Text 99017

AutoCAD SHX Text 99016

AutoCAD SHX Text 99014

AutoCAD SHX Text 99013

AutoCAD SHX Text 99020

AutoCAD SHX Text 91154

AutoCAD SHX Text 91032

AutoCAD SHX Text 99015

AutoCAD SHX Text 91122

AutoCAD SHX Text 91330

AutoCAD SHX Text 91105

AutoCAD SHX Text 91103

AutoCAD SHX Text 91104

AutoCAD SHX Text 91146

AutoCAD SHX Text 91155

AutoCAD SHX Text 91252

AutoCAD SHX Text 91037

AutoCAD SHX Text 91140

AutoCAD SHX Text 91151

AutoCAD SHX Text 91031

AutoCAD SHX Text 91039

AutoCAD SHX Text 91130

AutoCAD SHX Text 91363

AutoCAD SHX Text 91350

AutoCAD SHX Text 99001

AutoCAD SHX Text 99105

AutoCAD SHX Text 99007

AutoCAD SHX Text 99083

AutoCAD SHX Text 99055

AutoCAD SHX Text 99126

AutoCAD SHX Text 99145

AutoCAD SHX Text 91300

AutoCAD SHX Text 91142

AutoCAD SHX Text 91137

AutoCAD SHX Text 91255

AutoCAD SHX Text 91254

AutoCAD SHX Text 91364

AutoCAD SHX Text 91303

AutoCAD SHX Text 91148

AutoCAD SHX Text 91265

AutoCAD SHX Text 91400

AutoCAD SHX Text 91159

AutoCAD SHX Text 91307

AutoCAD SHX Text 99045

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

VICINITY OF WORK - B91029

AutoCAD SHX Text

COMMERCIAL ENTRY BASE ACCESS GATE

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text 91028

AutoCAD SHX Text 91027

AutoCAD SHX Text 91035

AutoCAD SHX Text 91030

AutoCAD SHX Text 91039

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text 91029

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

TITLE, VICINITY MAP, AND LOCATION MAP

AutoCAD SHX Text N

AutoCAD SHX Text

%%UHURLBURT FIELD BASE MAP - VICINITY OF WORK

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text N

AutoCAD SHX Text

%%UBUILDING 91029 - AREA OF WORK

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

INDEX OF DRAWINGS

AutoCAD SHX Text 1 2 3 4 5 6 7

AutoCAD SHX Text

INDEX #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text G-001 TITLE, INDEX, AND PROJECT LOCATION TITLE, INDEX, AND PROJECT LOCATION G-002 GENERAL PROJECT NOTES GENERAL PROJECT NOTES E-001 ELECTRICAL LEGEND, NOTES ELECTRICAL LEGEND, NOTES E-002 DEMOLITION POWER RISER DIAGRAM DEMOLITION POWER RISER DIAGRAM E-003 NEW WORK POWER RISER DIAGRAM NEW WORK POWER RISER DIAGRAM E-301 PANEL SCHEDULE PANEL SCHEDULE E-400 ELECTRICAL SITE PLANELECTRICAL SITE PLAN

AutoCAD SHX Text

SHEET #

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

A

N S

F O

R M

E R

B U

I L

D I N

G

OF 7

OP1141681

8 DEC 2023

91029

C. MARTEL

C. MARTEL

G-002

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

GENERAL PROJECT NOTES

AutoCAD SHX Text

GENERAL PROJECT NOTES

AutoCAD SHX Text THIS PROJECT CONSISTS OF ELECTRICAL WORK AS OUTLINED IN THE CONTRACT DRAWINGS AND SPECIFICATIONS. BUILDING 91029 CONSISTS OF FOUR SECTIONS AS SHOWN IN THE KEY PLAN AS A, B, C, AND D. THE CONTRACTOR SHALL COORDINATE WITH THE USERS AND CONTRACTING OFFICER'S REPRESENTATIVE ON EXACT PHASING PLAN FOR ALL AREAS OF THE FACILITY AT THE TIME OF CONSTRUCTION. THE CONTRACTOR SHALL COORDINATE WITH THE CONTRACTING OFFICER'S REPRESENTATIVE (COR), THE FACILITY MANAGER, AND USERS TO DEVELOP A DETAILED WRITTEN PLAN AND SCHEDULE. THE WRITTEN PLAN SHALL FOLLOW THE GENERAL PHASING PLANS OUTLINED ON THIS DRAWING AND INDIVIDUAL DISCIPLINE DRAWINGS. THE FOLLOWING ARE GENERAL PHASING NOTES THAT APPLY TO THE OVERALL PROJECT. 1. THE FACILITY OPERATES 24 HOURS A DAY 7 DAYS PER WEEK. THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION. CONTRACTOR SHALL THE FACILITY OPERATES 24 HOURS A DAY 7 DAYS PER WEEK. THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION. CONTRACTOR SHALL SEQUENCE WORK TO MINIMIZE DISRUPTION TO OCCUPANTS. 2. ALL WORK REQUIRING UTILITY, ELECTRICAL, OR HVAC OUTAGES SHALL BE SCHEDULED AND PERFORMED ON WEEKENDS. ALL OUTAGES SHALL BE ALL WORK REQUIRING UTILITY, ELECTRICAL, OR HVAC OUTAGES SHALL BE SCHEDULED AND PERFORMED ON WEEKENDS. ALL OUTAGES SHALL BE SCHEDULED A MINIMUM OF 2 WEEKS IN ADVANCE WITH THE USER AND CONTRACTING OFFICER'S REPRESENTATIVE.. THE SWITCHGEAR REPLACEMENT SHALL BE SCHEDULED 4 WEEKS IN ADVANCE. OUTAGES SHALL BE APPROVED BY THE CONTRACTING OFFICER'S REPRESENTATIVE. 3. BUILDING 91029 IS A SECURE FACILITY. WORK RESTRICTIONS AND ACCESS WILL NEED TO BE COORDINATED. TO GAIN ACCESS TO CONTROLLED BUILDING 91029 IS A SECURE FACILITY. WORK RESTRICTIONS AND ACCESS WILL NEED TO BE COORDINATED. TO GAIN ACCESS TO CONTROLLED TO GAIN ACCESS TO CONTROLLED ROOMS, COORDINATE WITH THE BUILDING MANAGERS AND CONTRACTING OFFICER'S REPRESENTATIVE. AN ESCORT WILL BE REQUIRED DURING THE TIME OF WORK IN CONTROLLED ROOMS. THE GOVERNMENT SHALL PROVIDE A MAXIMUM OF TWO (2) ESCORTS. 4. SEE ELECTRICAL PLANS FOR ADDITIONAL PHASING DETAILS. SEE ELECTRICAL PLANS FOR ADDITIONAL PHASING DETAILS.

AutoCAD SHX Text N

AutoCAD SHX Text

%%UBUILDING 91029 KEY PLAN

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text

NO WORK THIS AREA

AutoCAD SHX Text

(2 FLOORS)

AutoCAD SHX Text

(2 FLOORS)

AutoCAD SHX Text

(3 FLOORS)

AutoCAD SHX Text

(3 FLOORS)

AutoCAD SHX Text

(CHILLER/BOILER PLANT BLDG)

AutoCAD SHX Text

NO WORK THIS AREA

AutoCAD SHX Text

NO WORK THIS AREA

AutoCAD SHX Text

WORK AREA

OUTSIDE BLDG A

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

A

N S

F O

R M

E R

B U

I L

D I N

G

OF

OP1141681

8 DEC 2023

91029

C. MARTEL

C. MARTEL

ELECTRICAL GENERAL NOTES

ELECTRICAL LEGEND

E-001

E L

E C

T R

I C

A L

G

E N

D

N

O T

E S

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

1. ALL CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. ALL CONDUCTORS ARE COPPER UNLESS OTHERWISE NOTED. 2. ALL ELECTRICAL CONDUITS SHALL BE MARKED WITH COLORS, SOLID COLOR CONDUIT OR ELECTRICAL TAPE. ALL ELECTRICAL CONDUITS SHALL BE MARKED WITH COLORS, SOLID COLOR CONDUIT OR ELECTRICAL TAPE. O UNCOLORED - ELECTRICAL 120-208V AC UNCOLORED - ELECTRICAL 120-208V AC O YELLOW - ELECTRICAL 277-480V AC O YELLOW - ELECTRICAL 277-480V AC YELLOW - ELECTRICAL 277-480V AC O BLACK - LOW VOLTAGE FACILITY (DDC, BLDG AUTOMATION, ETC.) BLACK - LOW VOLTAGE FACILITY (DDC, BLDG AUTOMATION, ETC.) 3. ALL JUNCTION BOX COVERS, EXCEPT THOSE REQUIRED TO BE PAINTED, SHALL BE MARKED WITH THE CIRCUIT NUMBER OF THE CIRCUITS CONTAINED IN THE BOX ALL JUNCTION BOX COVERS, EXCEPT THOSE REQUIRED TO BE PAINTED, SHALL BE MARKED WITH THE CIRCUIT NUMBER OF THE CIRCUITS CONTAINED IN THE BOX WITH LABELS OR PERMANENT MARKER. 4. INSTALL LABEL INDICATING SOURCE OF SUPPLY FOR ALL PANELS IN ACCORDANCE WITH NATIONAL ELECTRIC CODE SECTION 408.4(B) INSTALL LABEL INDICATING SOURCE OF SUPPLY FOR ALL PANELS IN ACCORDANCE WITH NATIONAL ELECTRIC CODE SECTION 408.4(B) 5. PANEL SCHEDULE, SHOWN IN DESIGN DRAWING, SHALL BE UPDATED WITH AS-BUILT CONDITIONS FOR FINAL RECORD DRAWING SUBMITTAL. PANEL SCHEDULE, SHOWN IN DESIGN DRAWING, SHALL BE UPDATED WITH AS-BUILT CONDITIONS FOR FINAL RECORD DRAWING SUBMITTAL. 6. DEMOLITION OF ELECTRICAL COMPONENTS SHALL INCLUDE REMOVAL OF CONDUIT AND WIRE BACK TO PANEL, UNLESS OTHERWISE SPECIFIED ON DRAWINGS. DEMOLITION OF ELECTRICAL COMPONENTS SHALL INCLUDE REMOVAL OF CONDUIT AND WIRE BACK TO PANEL, UNLESS OTHERWISE SPECIFIED ON DRAWINGS. EXISTING PANEL SCHEDULES MUST BE UPDATED. 7. ALL ELECTRICAL CONNECTIONS MUST BE TIGHTENED TO MANUFACTURER RECOMMENDATIONS WITH A CALIBRATED TOOL. ALL ELECTRICAL CONNECTIONS MUST BE TIGHTENED TO MANUFACTURER RECOMMENDATIONS WITH A CALIBRATED TOOL. 8. UTILIZE NON-REVERSIBLE COMPRESSION CONNECTIONS FOR GROUND CONNECTIONS. EXOTHERMIC IS NOT ALLOWED UNLESS SPECIFICALLY APPROVED BY THE UTILIZE NON-REVERSIBLE COMPRESSION CONNECTIONS FOR GROUND CONNECTIONS. EXOTHERMIC IS NOT ALLOWED UNLESS SPECIFICALLY APPROVED BY THE CONTRACTING OFFICER.

AutoCAD SHX Text

GROUND FAULT CIRCUIT INTERRUPTER

AutoCAD SHX Text G

AutoCAD SHX Text

UNIVERSAL

AutoCAD SHX Text

UNV

AutoCAD SHX Text

CENTERLINE

AutoCAD SHX Text C/L

AutoCAD SHX Text

CONDUIT

AutoCAD SHX Text C

AutoCAD SHX Text

AMPS

AutoCAD SHX Text A

AutoCAD SHX Text

WIRE

AutoCAD SHX Text W

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

GND

AutoCAD SHX Text

MAIN BREAKER

AutoCAD SHX Text

MB

AutoCAD SHX Text

POLE

AutoCAD SHX Text P

AutoCAD SHX Text

%%UPANELS AND POWER

AutoCAD SHX Text

ELECTRICAL PANELBOARD

AutoCAD SHX Text

%%UMISCELLANEOUS

AutoCAD SHX Text

WEATHERPROOF

AutoCAD SHX Text

UNLESS NOTED OTHERWISE

AutoCAD SHX Text

ABOVE FINISH FLOOR

AutoCAD SHX Text

WP

AutoCAD SHX Text U.N.O.

AutoCAD SHX Text A.F.F.

AutoCAD SHX Text

Y INDICATES # OF POLES, AND Z INDICATES NEMA RATING

NON-FUSIBLE DISCONNECT SWITCH; XX/YY/ZZ WHERE X INDICATES AMPERAGE,

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

A

N S

F O

R M

E R

B U

I L

D I N

G

OF

OP1141681

6 DEC 2023

91029

C. MARTEL

C. MARTEL

E-002

D E

M O

L I T

I O

N

P

O W

I S

D

A

G R

A M

MDP

DEMOLITION POWER RISER DIAGRAM

T

PJC

T

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text

KEYNOTES:

AutoCAD SHX Text

AutoCAD SHX Text EXISTING HIGH VOLTAGE PRIMARY JUNCTION CABINET TO BE REMOVED AND REPLACED. EXISTING UNDERGROUND PRIMARY TO BE REMOVED BACK TO EXISTING PRIMARY JUNCTION CABINET. REFER TO SHEET E-400 FOR EXISTING PJC LOCATION. EXISTING UNDERGROUND CONDUIT MAY BE ABANDONED IN PLACE FAR ENOUGH FOR NEW PRIMARY TO BE RUN TO NEW PAD MOUNTED TRANSFORMER. EXISTING 12470V/7200V - 480V/277V 3 PH, PAD-MOUNTED TRANSFORMER TO BE REMOVED. EXISTING BUS DUCT TO BE REMOVED. EXISTING SWITCHBOARD TO BE REMOVED. REMOVE EXISTING PRIMARY 12470V/7200V CABLE FROM 480V/277V TRANSFORMER (672-1) TO 208V/120V TRANSFORMER (672-2) EXISTING 12470V/7200V - 208V/120V 3 PH, PAD-MOUNTED TRANSFORMER (672-2) TO REMAIN. EXISTING UNDERGROUND 480V/277V FEEDER CONDUITS AND WIRES TO REMAIN FOR RECONNECTION TO NEW SWITCHBOARD VIA SPLICES WITHIN JUNCTION BOX PLACED IN FOOTPRINT OF EXISTING SWITCHBOARD. CONTRACTOR SHALL TRACE ALL FEEDERS AND VERIFY BREAKER SIZES PRIOR TO ORDERING NEW GEAR. SEE NEW WORK POWER RISER DIAGRAM SHEET E-003. EXISTING UNDERGROUND 208V/120V FEEDER CONDUITS AND WIRES TO REMAIN.

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING SWITCHBOARD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 91029

AutoCAD SHX Text CONTRACTOR SHALL COORDINATE ALL OUTAGES WITH GOVERNMENT AT LEAST ONE MONTH PRIOR TO OUTAGES. OUTAGES MUST TAKE PLACE OVER A WEEKEND.

AutoCAD SHX Text

COORDINATION NOTE:

AutoCAD SHX Text X

AutoCAD SHX Text THE EXISTING PAD MOUNTED TRANSFORMER MAY NOT BE DE-ENERGIZED/REMOVED UNTIL THE NEW PAD MOUNT TRANSFORMER AND ASSOCIATED NEW PRIMARY HAS BEEN INSTALLED. ALL WORK SHALL BE PERFORMED IN ORDER TO MINIMIZE REQUIRED DOWNTIME.

AutoCAD SHX Text

PHASING NOTE:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text X

AutoCAD SHX Text X

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

A

N S

F O

R M

E R

B U

I L

D I N

G

OF

OP1141681

6 DEC 2023

91029

C. MARTEL

C. MARTEL

E-003

N E

W

W

O R

K

P

O W

S

D

A

G R

A M

NOTE: ALL GROUND CONNECTIONS SHALL BE BRAZED OR EXOTHERMIC WELDED

GROUND ROD TYPICAL FOR 3/4"x10'

COPPER CLAD (TYPICAL)

PVC CONDUIT

SEE PLANS & RISER

#4/0 BARE COPPER GROUND

CABLE, 24" BELOW GRADE

PROVIDE MOUNTING BOLTS

AS REQUIRED

SLOT IN PAD, LOCATION AND

SIZE AS REQUIRED FOR EQUIPMENT

FURNISHED PER MANUFACTURER

RECOMMENDATIONS

12"

H.V. L.V.

SCH. 40 PVC CONDUIT

SEE PLANS AND RISERS

FOR NUMBER AND SIZE

THERMAL WELD

CONNECTION (TYPICAL)

BOND EQUIPMENT CASE

TO GROUND LOOP AT

TWO POINTS

FOR NUMBER & SIZE

PAD MOUNTED TRANSFORMER DETAILS

FILL PAD MOUNTED TRANSFORMER

OPENINGS WITH PEA GRAVEL

MDP

NEW WORK POWER RISER DIAGRAM

T

12"

WARNING TAPE

FINISHED GRADE

(1-ACTIVE, 1-SPARE)

2-5" SCHEDULE 40 PVC

48"

UNDERGROUND PRIMARY DETAIL

NOT TO SCALE

CONCRETE ENCASED 3000 PSI

T

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text 3%%C, 4W

AutoCAD SHX Text 277/480V

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text

KEYNOTES:

AutoCAD SHX Text

AutoCAD SHX Text NEW PRIMARY JUNCTION CABINET WITH TWO NEW 12470V/7200V FEEDS. NEW 1,500KVA 12470/7200V - 480V/277V 3 PH, 4W, 60HZ, 5.75%Z PAD-MOUNTED TRANSFORMER. CONTRACTOR TO POUR NEW CONCRETE PAD FOR NEW TRANSFORMER NEW 12470/7200V CABLE PROVIDING PRIMARY POWER TO EXISTING 12470V/7200V - 208V/120V 3 PH, PAD-MOUNTED TRANSFORMER (672-2) DIRECTLY FROM PJC. NEW SWITCHBOARD MDP, 2000A MB GFI 277V/480V, 3 PH, 4W. CONTRACTOR TO POUR NEW CONCRETE PAD FOR NEW SWITCHBOARD MDP. INCLUDE 2 EMPTY CONDUIT STUB-UPS THROUGH NEW CONCRETE PAD TO ENABLE INSTALLATION OF ADDITIONAL 480V/277V CIRCUITS IN THE FUTURE. NEW SURGE SUPPRESSOR PER SPECIFICATIONS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. NEW JUNCTION BOX PLACED ON EXISTING CONCRETE PAD IN FOOTPRINT OF REMOVED SWITCHBOARD. NEW 480V/277V UNDERGROUND CONDUIT AND CONDUCTORS FROM NEW SWITCHBOARD TO TERMINATE IN THIS JUNCTION BOX AND BE CONNECTED TO EXISTING 480V/277V CONDUCTORS ENTERING BUILDING. EXISTING 12470V/7200V - 208V/120V 3 PH, PAD-MOUNTED TRANSFORMER. EXISTING UNDERGROUND CONDUITS AND WIRES SERVING EXISTING PANELS INSIDE 91029 TO REMAIN. CONTRACTOR SHALL TRACE, PROVIDE NECESSARY MATERIALS, AND PERFORM ALL WORK REQUIRED TO CONNECT TO NEW BREAKERS IN NEW SWITCHBOARD MDP.

AutoCAD SHX Text

AutoCAD SHX Text

NEW SWITCHBOARD

AutoCAD SHX Text

AutoCAD SHX Text

5 PARALLEL RUNS OF

AutoCAD SHX Text

1#3/0 GND IN 1"C

AutoCAD SHX Text

AutoCAD SHX Text

2000A MB GFI

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text NEW PRIMARY 3#2(CU) 15KV, 1/3RD CONCENTRIC NEUTRAL WITH 133% INSULATION IN TWO 5" CONCRETE ENCASED SCH 40 PVC CONDUITS. ONE 5" CONDUIT SHALL CONTAIN WIRE AND THE OTHER 5" CONDUIT PROVIDED AS A 'SPARE'.

AutoCAD SHX Text CONTRACTOR SHALL COORDINATE ALL OUTAGES WITH GOVERNMENT AT LEAST ONE MONTH PRIOR TO OUTAGES. OUTAGES MUST TAKE PLACE OVER A WEEKEND.

AutoCAD SHX Text

COORDINATION NOTE:

AutoCAD SHX Text CONTRACTOR SHALL PROVIDE ARC FLASH/COORDINATION STUDY FOR NEW SWITCHBOARD AND PANELS.

AutoCAD SHX Text

ARC FLASH NOTE:

AutoCAD SHX Text

AutoCAD SHX Text

BUILDING 91029

AutoCAD SHX Text

4#600MCM, IN 4"C

AutoCAD SHX Text

PER NEC 250

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

A

N S

F O

R M

E R

B U

I L

D I N

G

OF

OP1141681

8 DEC 2023

91029

C. MARTEL

C. MARTEL

E-301

P A

N E

L

S

C H

E D

U L

E S

AutoCAD SHX Text

CKT

AutoCAD SHX Text

LOAD DESCRIPTION

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

AMP

AutoCAD SHX Text

POLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KVA/PHASE

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

2000 AMP MAIN GFCI BREAKER

AutoCAD SHX Text

277/480 VOLT 3%%C 4W

AutoCAD SHX Text

CIRCUIT BREAKER PANEL SCHEDULE

AutoCAD SHX Text

NEW SWITCHBOARD MDP

AutoCAD SHX Text

MINIMUM INTERRUPTING CAPACITY:

AutoCAD SHX Text

65,000 AMPS SYMMETRICAL

AutoCAD SHX Text

CKT

AutoCAD SHX Text

LOAD DESCRIPTION

AutoCAD SHX Text

BREAKER

AutoCAD SHX Text

AMP

AutoCAD SHX Text

POLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KVA/PHASE

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

NEMA 3R ENCLOSURE

AutoCAD SHX Text

PAD MOUNTED

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

LIBRARY HIGHBAY MOTION SYSTEMS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

TWST UPS MOTION SYSTEMS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING PANEL LP

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING SUB MAIN

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EWST/TWST HPU MOTION SYSTEMS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING PANEL MDPH

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXISTING PANEL P-1

AutoCAD SHX Text

AutoCAD SHX Text RE-CONNECT EXISTING CONDUIT AND WIRE TO NEW SWITCHBOARD. CONFIRM BREAKER SIZE WITH EXISTING BREAKER IN EXISTING SWITCHBOARD.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SURGE SUPPRESSOR

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SPACE ONLY

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

DATE:

NEW WORK ELECTRICAL SITE PLAN

SP

EC

IA

L O

PE

RA

TI

O

NS

C

IV

IL

E

NG

IN

EE

R

SQ

UA

DR

O N

HU

RL

BU

RT

F

IE

LD

, F

LO

RI

DA

O

PE

RA

TI

O

NS

C O

M M

AN

D

AI

R

FO

RC

E

SP

EC

IA

L R

E P

L A

A

N S

F O

R M

E R

B U

I L

D I N

G

OF

OP1141681

6 DEC 2023

91029

C. MARTEL

C. MARTEL

E-400

C O

O L

I N

G

T

O W

B

U I L

D I N

G

P

O W

P

A

N

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NUP

AutoCAD SHX Text

NEW PRIMARY

AutoCAD SHX Text

JUNCTION CABINET

AutoCAD SHX Text

KEYNOTES:

AutoCAD SHX Text

AutoCAD SHX Text NEW PAD MOUNTED TRANSFORMER. LOCATION IS APPROXIMATE. SEE NEW WORK POWER RISER DIAGRAM SHEET E-003. NEW NEMA 3R 2000A SWITCHBOARD. LOCATION IS APPROXIMATE. SEE NEW WORK POWER RISER DIAGRAM SHEET E-003. NEW JUNCTION BOX PLACED ON EXISTING PAD IN FOOTPRINT OF REMOVED SWITCHBOARD. SEE NEW WORK POWER RISER DIAGRAM SHEET E-003. EXISTING PAD MOUNTED TRANSFORMER TO REMAIN. EXISTING 208V/120V CONDUIT WITH WIRE RUNNING INTO FACILITY TO REMAIN EXISTING 480V/277V CONDUIT WITH WIRE RUNNING INTO FACILITY TO REMAIN NEW UNDERGROUND PRIMARY CONCRETE ENCASED CONDUITS WITH WIRE RUNNING TO TRANSFORMERS 672-1 AND 672-2. REFER TO POWER RISER AND PRIMARY DETAIL FOR ADDITIONAL INFORMATION. ROUTE SHOWN IS APPROXIMATE. CONTRACTOR SHALL INSTALL TO AVOID CONFLICT WITH EXISTING UTILITIES.

AutoCAD SHX Text

SCALE: 1/16" = 1'-0"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text N

AutoCAD SHX Text

LOCATE ALL EXISTING UTILITIES PRIOR TO PERFORMING ANY UNDERGROUND WORK.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

SHEET NUMBER:

AutoCAD SHX Text

SHEET REFERENCE:

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text O

AutoCAD SHX Text F

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text N

AutoCAD SHX Text N

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text L

AutoCAD SHX Text O

AutoCAD SHX Text A

AutoCAD SHX Text T

AutoCAD SHX Text I

AutoCAD SHX Text O

AutoCAD SHX Text M

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text C

AutoCAD SHX Text O

AutoCAD SHX Text D

AutoCAD SHX Text

REV #

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

DATE

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

BUILDING NUMBER:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DESIGNED BY:

DATE:

E-001
Sheets and Views
E-001
E-002
Sheets and Views
E-002
E-003
Sheets and Views
E-003
E-301
Sheets and Views
E-301
E-400
Sheets and Views
E-400
G-001
Sheets and Views
-
G-002
Sheets and Views
-
OLE1