03. SALIENT CHARACTERISTICS BLD.759.pdf
PDF 13 KB Posted
- Attached to
- Replace Chiller, 759, 1368 & 559
- Solicitation number
- FA252126QB098
About this file
This is a Form 9 equipment specification document for Patrick Space Force Base, FL's 45 Civil Engineer Squadron, Operations Flight. The document specifies procurement of one Trane air-cooled scroll packaged chiller, model CGAM026A2, for the Operations Flight facility.
The chiller must include the following salient characteristics: air-cooled scroll packaged design with startup and commissioning performed by Trane Service (required for warranty validation), R-454B refrigerant charge, factory-installed freeze protection, refrigerant isolation discharge valve, factory-installed flow switch set to 60 cm/sec, standard cooling configuration with grooved pipe connections, 1.25-inch factory insulation rated for high humidity and low evaporator temperature conditions, complete coat lanced aluminum fins with BLYGOLD coating for corrosion protection, across-the-line direct online starter, high fault-rated circuit breaker control panel, BACnet MS/TP interface capability, high short-circuit rating, elastomeric isolators, factory-installed water strainer, and architectural louvered panels. The equipment includes a comprehensive ten-year warranty covering parts, labor, and refrigerant. The specification emphasizes extra efficiency and performance capabilities suitable for wide ambient operating conditions typical of Florida coastal military installations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PATRICK SPACE FORCE BASE, FL
45 CES / OPERATIONS FLIGHT
26_16342068 Form 9
1 TRANE CHILLER Operations Flight
Air-Cooled Scroll Packaged Chiller/CGAM026A2
Salient Characteristics
Air-Cooled Scroll Packaged Chiller
Startup Included - Trane Service must start equipment for warranty to be honored
Extra efficiency/performance
Refrigerant Charge R-454B
With factory installed freeze protection
Refrigerant isolation valves (discharge valve)
Factory installed flow switch - set point 60 cm/sec
Standard Cooling
Grooved pipe connection
Factory insulation 1.25" - high humidity/low evaporator temperature
Wide Ambient complete Coat lanced aluminum fins
BLYGOLD coating for cabinet & casing
Across the line starter/direct online
Single point connection main line unit power-ancillary items require other power
Circuit breaker-high fault rated control panel
BACnet MS/TP Interface
High A short circuit rating
Elastomeric isolators
With water strainer factory installed
Architectural louvered panels
Ten (10) year parts, labor & refrigerant warranty
File details come from the government source that posted it. Updated .