03. Salient Characteristics Bld.559.pdf

PDF 82 KB Posted

Attached to
Replace Chiller, 759, 1368 & 559
Solicitation number
FA252126QB098
Issued by

About this file

This is a Form 9 equipment specification document for Patrick Space Force Base, FL, dated 12 June 2026 (Revision 0), reference number 26_17164692, detailing requirements for one Trane air-cooled scroll packaged chiller (Model CGAM052A2) for the 45 Civil Engineer Squadron Operations Flight.

The chiller specification requires a 52 nominal ton capacity unit operating at 208 volts, 3 phases with extra efficiency/performance rating. Key operational features include R-454B refrigerant charge, factory-installed freeze protection, refrigerant isolation valves with discharge valve, factory-installed flow switch set at 60 cm/sec, grooved pipe connections, 1.25-inch factory insulation rated for high humidity/low evaporator temperature conditions, and wide ambient performance capability. The unit must feature complete coated lanced aluminum fins with BLYGOLD coating on cabinet and casings, elastomeric isolators, factory-installed water strainer, architectural louvered panels, and super-quiet operation. Control systems include across-the-line/direct online starter, single-point connection for main line unit power with ancillary items requiring separate power, circuit breaker with high fault-rated control panel, and BACnet MS/TP interface capability. Startup must be performed by Trane Service to honor the ten-year parts, labor, and refrigerant warranty. The electrical parts specification includes detailed requirements for a 400-amp, 3-phase, 600-volt, Nema 4x, 316 stainless steel disconnect; 40 feet of 2-inch schedule-40 PVC conduit; rigid conduit clamps; 10 feet of Unistrut framing; liquid-tight connectors and fittings; and 60 feet of 3 AWG green copper wire and 180 feet of 250 MCM black copper wire for electrical connections.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PATRICK SPACE FORCE BASE, FL

45 CES / OPERATIONS FLIGHT

Date: 12 June 2026

REV: 0

26_17164692 Form 9

1 TRANE CHILLER Operations Flight

Air-Cooled Scroll Packaged Chiller/CGAM052A2

Salient Characteristics

Air-Cooled Scroll Packaged Chiller

Startup Included - Trane Service must start equipment for warranty to be honored 52 nominal tons 208 volt 3 phases Extra efficiency/performance

Refrigerant Charge R-454B

With factory installed freeze protection Refrigerant isolation valves (discharge valve)

Factory installed flow switch - set point 60 cm/sec

Standard Cooling

Grooved pipe connection

Factory insulation 1.25" - high humidity/low evaporator temperature

Performance based on water

Wide Ambient

Complete Coat lanced aluminum fins

BLYGOLD Coating cabinet & casings

Across the line starter/direct online

Single point connection main line unit power-ancillary items require other power

Circuit breaker-high fault rated control panel BACnet MS/TP Interface

Elastomeric isolators

With water strainer factory installed

Super quiet

Architectural louvered panels

Ten (10) year parts, labor & refrigerant warranty

ELECTRICAL PARTS

Disconnect, 400a, 3p, 600v, Nema 4x, 316SS Mfr. Model H365NDS

40feet 2-inch sch-40 PVC conduit Mfr. Model A52CA12

2Inch Rigid Conduit Clamp 304SS Mfr. Model V111 2EG

10feet Unistrut 1-5/8-inch 304SS Mfr. Model FS-500SS ST4 120.00

6feet 2inch Liquid-Tite Mfr. Model 6107-30-00

2inch Liquid-Tite Connector Mfr. Model P200NGY

2inch 90-Deg Sch40 PVC Cond Elbow Mfr. Model 5133828 2inch

PVC Cond Female Adapter Mfr. Model 5140048

2inch PVC Cond Coupling Mfr. Model 6141628

2inch PVC Cond Threaded Male Adapter Mfr. Model 5140108

2inch Conduit Lock Nut Mfr. Model 1008

2inch Sealing Ring Mfr. Model GR-N70033

60feet THHN Str Green 3AWG Copper Wire Mfr. Model 60197101

180feet THHN Str Blk 250MCM Copper Wire Mfr. Model 20509602

File details come from the government source that posted it. Updated .