02_23_24 Construction Documents.pdf
PDF 1 MB Posted
- Attached to
- Replace Switchgear at Central Plant
- Solicitation number
- PE-56300-RFQ-2024-000000004
- Issued by
- Dooly County, Georgia
About this file
The provided document is a set of 100% Construction Documents for the Central Energy Plant Electrical Gear Replacement project at the College of Coastal Georgia's main campus in Brunswick, Georgia. The project involves replacing the existing 3000A, 480V, 3-phase switchgear, motor control centers, and associated electrical infrastructure. Key details include replacing the existing switchboard, installing a new 3000A main switchboard, a new 225A panel, and reconnecting existing loads such as chillers, air compressors, and boiler pumps. The project appears to be managed by NBP Engineers, Inc. on behalf of the College of Coastal Georgia.
The documents do not provide pricing terms, set asides, or funding details. However, they indicate that the project is a state and local contract opportunity for the College of Coastal Georgia, involving the jurisdictions of Glynn County and the City of Brunswick, Georgia.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT CONSULTANTS
INDEX OF
DRAWINGS
TITLESHEET NO.
316 CORPORATE PARKWAY MACON, GEORGIA
NBP ENGINEERS, INC.
CONSULTANTS
CCGA PROJECT No. 2412
E00
E01
E02
COLLEGE OF COASTAL GEORGIA
Brunswick, Georgia
LEGEND - ELECTRICAL
LARGE SCALE PLAN - NEW WORK - ELECTRICAL
MAIN CAMPUS - CENTRAL ENERGY PLANT
ELECTRICAL GEAR REPLACEMENT
02.23.24 CONSTRUCTION DOCUMENTS
CENTRAL ENERGY PLANT - RISER & PANEL SCHEDULES
P:\23083\23083e00.dgn
DATE PLOTTED
DGN FILE
22-FEB-2024
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23083\23083e00.dgn
AS SHOWN
23083
C o ll e g e o f C o a s ta l G e o rg ia
B ru n s w ic k
G e o rg ia
TWT
BCO
TWT
02.23.24
P ro je c t
N o
C
C G
A
M a in C a m p u s C e n tr a l E n e rg y P la n t E le c tr ic a l G e a r
R e p la c e m e n t
C O
N S T
R U
C T
IO
N
D
C U
M E
N T S
E00
CT
TRACK LIGHTS: QUANTITY OF HEADS AS SHOWN EMERGENCY BATTERY PACK-CEILING
EMERGENCY BATTERY PACK-WALL
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
PANELBOARD-OVER 250 VAC
SURFACE MOUNTED
PANELBOARD-OVER 250 VAC
RECESSED
CABLE TRAY
BACKBOARD
CONNECTION TO EQUIPMENT
CAP
CONDUIT DOWN
CONDUIT UP
J
F
BT
C
C
BR
SLAB OR BELOW GRADE
GROUNDING CONDUCTOR- UNDER
U
SP
DP
PE
M
ICM
S
V
S
IC
MM
MC
GG
G
LIGHTING FIXTURES (SYMBOLS VARY BASED ON FIXTURES TYPE)
LIGHTING CONTROL
RECEPTACLES
CIRCUITS
GENERAL EQUIPMENT
FIRE PROTECTION EQUIPMENT
COMMUNICATIONS
LIGHTNING PROTECTION AND GROUNDING
T
JJ
I
UI
I
ELECTRICAL LEGEND
TV
C
G
B
K
LED ON "NORMAL" POWER
CEILING MOUNTED FIXTURE
WALL MOUNTED FIXTURE
EXIT LIGHT (ARROWS AS SHOWN)
LIFE SAFETY EGRESS FIXTURE
CEILING MOUNTED ULTRASONIC OCCUPANCY
SENSOR AND RELAY
CEILING/WALL MOUNTED INFRARED OCCUPANCY
SENSOR AND RELAY
CEILING MOUNTED COMBINATION INFRARED/
ULTRASONIC OCCUPANCY SENSOR AND RELAY -
SWITCHING PHOTOCELL (INTERIOR TYPE) F.C. NOTED
DIMMING PHOTOCELL (INTERIOR TYPE)
EXTERIOR TYPE PHOTO SWITCH
LOW VOLTAGE OVERRIDE SWITCH
INFRARED OCCUPANCY SENSOR
WALL MOUNTED SWITCH
"P" INDICATES PILOT LIGHT
KEYED SWITCH
DIMMER SWITCH
FOUR WAY SWITCH
THREE WAY SWITCH
SINGLE POLE SWITCH
DUPLEX RECEPTACLE - NORMAL
QUAD - NORMAL
GFCI DUPLEX RECEPTACLE - NORMAL
GFCI QUAD - NORMAL
FLOOR DUPLEX RECEPTACLE - NORMAL
FLOOR QUAD - NORMAL
CEILING DUPLEX RECEPTACLE - NORMAL CLOCK OUTLET
WALL/CEILING RACEWAY
CEILING SPECIAL - TYPE NOTED OR SHOWN
SPECIAL - TYPE NOTED OR SHOWN
HORIZONTALLY MOUNTED DUPLEX RECEPTACLE
WEATHER PROOF RECEPTACLE (GFCI)
ELECTRIC WATER COOLER RECEPTACLE(GFCI)
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT IN GROUND, SLAB, OR UNDER FLOOR
FLEXIBLE RACEWAY
RACEWAY EXPOSED
TRANSFORMER
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
ENCLOSED BREAKER-RECESSED IN WALL
ENCLOSED CIRCUIT BREAKER
EMERGENCY PUSHBUTTON
COMBINATION STARTER AND DISCONNECT
EXHAUST FAN
MANUAL STARTER AND MOTOR RATED SWITCH
MOTOR
JUNCTION BOX - WALL/CEILING/FLOOR
SURGE SUPPRESSOR
VOICE OUTLET, QUANTITY OF JACKS AS NOTED
DATA OUTLET, QUANTITY OF JACKS AS NOTED
COMBINATION VOICE/DATA OUTLET, QUANTITY OF
VOICE/DATA JACKS AS NOTED
FLOOR VOICE OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR DATA OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR COMBINATION VOICE/DATA OUTLET,
QUANTITY OF JACKS AS NOTED
MASTER CLOCK
INTERCOM MASTER STATION
INTERCOM CALL-IN STATION
WALL MOUNTED VOLUME CONTROL
BOX, STUB-UP, AND MODULAR PLATE W/ BLANKS
TELEVISION OUTLET
SPEAKER: CEILING/WALL
MICROPHONE: FLOOR/WALL
FIBER OUTLET
GROUND ROD - C IF CHEMICAL
GROUND CONNECTION (SCHEMATIC)
CONCEALED IN ROOF OR WALLS
GROUNDING CONDUCTOR-
GROUNDING CONDUCTOR- EXPOSED
AIR TERMINAL
GROUNDING PLATE
FACP
FAA
WF
VS
DH
SMOKE DETECTOR/SENSOR - BEAM RECEIVER
SMOKE DETECTOR/SENSOR - BEAM TRANSMITTER
SPEAKER/VISUAL ALARM: CEILING/WALL
VISUAL ALARM: CEILING/WALL
AUDIO/VISUAL ALARM: CEILING/WALL
MANUAL PULL STATION
FIRE ALARM ANNUNCIATOR
FIRE ALARM PANEL
DUCT MOUNTED SMOKE DETECTOR
SMOKE DETECTOR: CEILING / WALL
HEAT DETECTOR: CEILING / WALL
WATER FLOW SWITCH
WATER TAMPER SWITCH
DOOR HOLDER
FIREMAN'S PHONE OUTLET
EWC
WP
H
D
P
I
L
TWO ZONE LOW VOLTAGE SWITCHL2
VACANCY AUTO SHUT OFF
FOUR ZONE LOW VOLTAGE SWITCHL4
DUPLEX RECEPTACLE WITH INTEGRAL USBUSB
TV DUPLEX RECEPTACLETV
AC
ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE
HEIGHT WITH ARCHITECT)
J-HOOK
SECURITY
C CARD READER
P DOOR POSITION SENSOR
SECURITY CAMERA: CEILING/WALL MOUNTED
ES ELECTRIC STRIKE
C
CABLE TRAY
DUPLEX RECEPTACLE MOUNTED IN RACEWAYR
R DATA OUTLET MOUNTED IN RACEWAY
DUPLEX RECEPTACLE - TAMPER PROOFT
DUPLEX RECEPTACLE - GENERATOR CIRCUIT, RED IN COLOR
QUAD - GENERATOR CIRCUIT, RED IN COLOR
SINGLE ZONE LOW VOLTAGE SWITCHL1
HOMERUN - ONE ARROW PER CIRCUIT
DISCONNECT SWITCH: "F" IF FUSED
F
ELECTRICAL
LEGEND -
HSBLE
F A
P
E L
E C
MCC #3
T E
L
M C
C
MSG
S
POWER PANEL
EXISTING PULSED
M C
C
AIR COMPRESSOR
CHILLER#2
EXISTING
CP-1
EXISTING
CHILLER#1
EXISTING
CHILLER#3
EXISTING
FINAL CONNECTIONS.
FEED BACK TO NEW CIRCUIT BREAKER IN NEW PANEL HCEP. MAKE ALL
WHICH IS BEING REMOVED AS PART OF THIS SCOPE. RECONNECT THIS
IS FED FROM A CIRCUIT BREAKER IN MOTOR CONTROL CENTER MCC-1
EXISTING 480 VOLT POWER TO BOILER FEED PUMPS IN THIS AREA
IN NEW PANEL HCEP. MAKE ALL FINAL CONNECTIONS.
25 HP FAN. RECONNECT EXISTING VFD FROM NEW CIRCUIT BREAKER
THIS IS THE EXISTING VFD FOR COOLING TOWER FAN CT-1. THIS IS A
PANEL HCEP. MAKE ALL FINAL CONNECTIONS.
SCOPE. RECONNECT THIS FEED BACK TO NEW CIRCUIT BREAKER IN
CONTROL CENTER MCC-1 WHICH IS BEING REMOVED AS PART OF THIS
AIR COMPRESSOR IS SERVED FROM A CIRCUIT BREAKER IN MOTOR
EXISTING 480 VOLT AIR COMPRESSOR IS A DUPLEX 5 HP UNIT. THIS
LIGHTING CIRCUITS AND EXTEND AS REQUIRED.
EQUALLY SPACE LIGHTS AS REQUIRED FOR FULL COVERAGE. REUSE EXISTING
FOR THESE TO BE INDIVIDUALLY MOUNTED SO COVER SERVICE AREAS.
SUPPORTS FOR THE NEW LIGHTS. THE INTENT FOR THE NEW LIGHTS ARE
ALL OF THE EXISTING LIGHT FIXTURE SUPPORTS AND INSTALL ALL NEW
BASIS OF DESIGN IS ACUITY CLX-L48-7000LM-SEF-WDL-MVOLT-40K. REMOVE
AND PROVIDE A QUANTITY OF 40 TOTAL 4 FOOT LED STRIP LIGHT FIXTURES.
CONTRACTOR SHALL DEMO ALL OF THE EXISTING FLUORESCENT LIGHTING
PROVIDE ALL NEW LED LIGHT FIXTURES FOR THE CENTRAL ENERGY PLANT.
SCHEDULE OF NEW CIRCUIT BREAKER. MAKE ALL FINAL CONNECTIONS.
ADJACENT TO PUMP CP-1 ON A UNISTRUT FRAME. SEE PANEL HCEP
AS PART OF THIS SCOPE. PROVIDE A NEW COMBINATION STARTER
LOCATED IN MOTOR CONTROL CENTER MCC-1 WHICH IS BEING REMOVED
EXISTING 480 VOLT, 20 HP PUMP CP-1 IS SERVED FROM A STARTER
P:\23083\23083e01.dgn
DATE PLOTTED
DGN FILE
22-FEB-2024
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23083\23083e01.dgn
AS SHOWN
23083
C o ll e g e o f C o a s ta l G e o rg ia
B ru n s w ic k
G e o rg ia
TWT
BCO
TWT
02.23.24
P ro je c t
N o
C
C G
A
M a in C a m p u s C e n tr a l E n e rg y P la n t E le c tr ic a l G e a r
R e p la c e m e n t
N S T
R U
C T
C U
M E
N T S
SECURITY OFFICE
CHILLER ROOM
BOILER ROOM
TLT
TLT
CONTROL ROOM
LINK FENCE
EXISTING CHAIN
LINK FENCE
EXISTING CHAIN
LINK FENCE
EXISTING CHAIN
SCALE:
= 1'-0
4 0 2 4 8
E01
N
ELECTRICAL
NEW WORK -
LARGE SCALE PLAN - LARGE SCALE PLAN - NEW WORK - ELECTRICAL
T-1
SB
NOTES:(THIS SHEET ONLY)
VFD
CT-2
3 PHASE, 4 WIRE.
VOLTAGE IS 12,470 VOLTS. SECONDARY IS 480Y/277 VOLTS,
EXISTING 2000 KVA PADMOUNT TRANSFORMER. PRIMARY
REPLACED IN PLACE.
EXISTING 3000 AMP BUSS DUCT TAP BOX SHALL BE
2 OF 2.
REMAIN IN PLACE. MAIN SHALL BE LABELED AS SERVICE
TRANSFORMER TO EXISTING SERVICE PANEL SB SHALL
EXISTING SERVICE ENTRANCE FROM THE PADMOUNT
AND RECONNECT, EXTENDING AS REQUIRED.
CIRCUIT CONDUCTORS SERVING THE BOILER. DISCONNECT
ORDER TO BE ABLE TO REUSE THE EXISTING BRANCH
BOILER TO BE ON THIS END OF THE GEAR LINEUP IN
INTENT IS FOR THE NEW GEAR SECTION SERVING THE
AND BREAKER TO BE PROVIDED FOR THE BOILER. THE
WHICH SHOWS NEW REQUIRED SWITCHBOARD SECTION
ELECTRIC BOILER SHALL BE REMOVED. SEE NEW RISER
SWITCHBOARD SECTION THAT CURRENTLY SERVES THE
EXISTING 2000 AMP, 480 VOLT, 3 PHASE SQUARE D QED 6
CIRCUIT BREAKERS ARE SPARES AND NOT IN USE.
SERVING CHILLER #1. THE REMAINDER OF THE EXISTING
CENTER MCC-2, 400A/3P SERVING PANEL HCEP, AND 700A/3P
CONTROL CENTER MCC-1, 225A/3P SERVING MOTOR CONTROL
A TWO SPEED EXHAUST FAN, 400A/3P SERVING MOTOR
ARE AS FOLLOWS: 3000A MAIN BREAKER, 20A/3P SERVING
THE ONLY ACTIVE CIRCUIT BREAKERS IN THIS GEAR LINEUP
GEAR SERVE LOADS THAT ARE NO LONGER IN SERVICE.
SEVERAL OF THE EXISTING CIRCUIT BREAKERS IN THIS
PLACE. SEE NEW PROPOSED SWITCHBOARD LAYOUT.
SQUARE D SWITCHBOARD SA SHALL BE REPLACED IN
EXISTING 3000 AMP, 480 VOLT, 3 PHASE, TWO SECTION 7
8 EXISTING MOTOR CONTROL CENTER MCC-2 TO REMAIN IN PLACE.
ENTRANCE CONDUCTORS TO NEW TAP BOX.
RISER CONDUITS MAY BE REUSED. CONNECT NEW SERVICE
TO THE NEW TAP BOX. EXISTING UNDERGROUND AND EXPOSED
SHALL BE REPLACED WITH NEW FROM THE TRANSFORMER
COPPER) FROM THE EXISTING PADMOUNT TRANSFORMER
EXISTING SERVICE CONDUCTORS (8 SETS OF 4#500 KCMIL
SAME SIZE AND RATING.
BE REPLACED IN PLACE WITH A NEW BUSS DUCT OF THE
EXISTING 3000 AMP, 480 VOLT, 3 PHASE BUSS DUCT SHALL
225 AMP PANELBOARD HCEP.
CENTER MCC-1 SHALL BE REMOVED. PROVIDE NEW 480Y/277 VOLT,
EXISTING 480 VOLT, 3 PHASE, 400 AMP RATED MOTOR CONTROL
CT-2
CT-1
NEW
SF-3
B L
R 1B
E X
IS
T
IN
G
BLR-1A
EXISTING
BLR-1C
EXISTING
B L
R 1D
E X
IS
T
IN
G
ELECTRIC
BOILER
P:\23083\23083e02.dgn
DATE PLOTTED
DGN FILE
22-FEB-2024
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\23083\23083e02.dgn
AS SHOWN
23083
C o ll e g e o f C o a s ta l G e o rg ia
B ru n s w ic k
G e o rg ia
TWT
BCO
TWT
02.23.24
P ro je c t
N o
C
C G
A
M a in C a m p u s C e n tr a l E n e rg y P la n t E le c tr ic a l G e a r
R e p la c e m e n t
N S T
R U
C T
C U
M E
N T S
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
P O
L E
CKT
SWITCHBOARD SA
THIS EXISTING GEAR IS IN TWO SECTIONS. THERE IS ALSO A BUS TAP ON THE LINE SIDE OF THE MAIN TO SERVE THE ELECTRIC BOILER BREAKER AT 2000 AMPS.
NOTES
Minimum KAIC:
CKT
TRIP
WIRE
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
SPARE
SPARE
SPARE
SERVES
WIRE
PH,
AMPS
VOLT-
EXISTING
A
PHASE LOAD V.A.
B
FED BY
C
SERVICE ENTRANCE BUSS DUCT
LOCATION:
AMPS
VOLT-
CENTRAL PLANT
CHILLER
PANEL HCEP
MCC-2
MCC-1
SPARE
2 SPEED EX FAN
SERVES CD.
FLOOR
MAIN
WIRE
TRIP
MOUNTED
AMPS
GEAR SECTION 3 - DISTRIBUTION
GEAR SECTION 2 - 3000A/3P MAIN BREAKER
GEAR SECTION 1 - 2000A/3P BREAKER FOR BOILER
NOTES
Minimum KAIC:
CKT
TRIP
WIRE
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
SPACE
SPACE
SPACE
SPACE
SPARE
SPARE
ELEC BOILER
SERVES
WIRE
PH,
AMPS
VOLT-
NEW
LOCATION:
23620
23620
23620
AMPS
VOLT-
CENTRAL PLANT
NEW SPD
CHILLER
PANEL HCEP
MCC-2
NEW PANEL HCEP2
SPARE
2 SPEED EX FAN
SERVES
2-1/2"
CD.
FLOOR
MAIN
1#4G
4#4/0
WIRE
TRIP
MOUNTED
AMPS
CKT
SWITCHBOARD SA
ALL EXISTING TO REMAIN LOADS SHALL BE REFED FROM NEW PANEL HCEP2. THESE INCLUDE CT-1, AIR COMPRESSOR, CP-1, AND BOILER #1 PUMPS.
PROVIDE STAND ALONE COMBINATION STARTERS FOR PUMPS CP-1 AND BOILER #1. CONTRACTOR VERIFY STARTER SIZE REQUIRED PRIOR TO BIDDING.
THIS EXISTING MOTOR CONTROL CENTER SHALL BE DEMOLISHED AS PART OF THIS PROJECT.
NOTES
MCC MIN. 50 KAIC
BUS MIN. 50 KAIC
XXX
1F
1E
1D
1C
1B
1A
CKT SIZE
NEMA
X
WIRE
XX
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
XXX
SPARE
CP-1
AIR COMPRESSOR
SPARE
SPARE
CT-1 VFD
SERVES
WIRE
PH,
AMPS
VOLT-
EXISTING
A
PHASE LOAD V.A.
B
FED BY
C
EXISTING SWITCHBOARD SA
AMPS
VOLT-
XXX
SPACE
SPARE
SPARE
SPARE
BOILER #1 PUMPS
SPARE
SERVES
MLO
XX
CD.
FREESTANDING
XX
WIRE
XX
SIZE
NEMA
AMPS
X
X
X
X
2F
2E
2D
2C
2B
2A
CKT
MCC-1
X
X
X
TRIP
AMPS
VOLT-
NEW
AMPS
VOLT-
CENTRAL PLANT
SPACE
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
SERVES CD.
SURFACE
MLO
WIRE
TRIP
MOUNTED
AMPS
CKT
PANEL HCEP2
23620
23620
23620
A
PHASE LOAD V.A.
23620
23620
23620
B
FED BY
23620
23620
23620
C
SERVICE ENTRANCE BUSS DUCT
INTENT IS TO PROVIDE CIRCUIT BREAKER SIZES TO MATCH THE SIZE OF THE EXISTING BREAKER OR FUSES.
CONTRACTOR SHALL VERIFY REQUIRED BREAKER SIZES FOR THE AIR COMPRESSOR, PUMP CP-1, AND BOILER #1 PUMPS PRIOR TO BIDDING.
NOTES
Minimum KAIC:
CKT
4#10
1#8G
3#4
4#10
1#8G
3#4
WIRE
3/4"
1-1/4"
3/4"
1-1/4"
CD.
MULTISECTION CONN AMPS
MULTISECTION CONN V A
PANEL SECTION CONN AMPS
PANEL SECTION CONN V A
SPACE
SPACE
SPACE
4 X 1 HP
BOILER #1 PUMPS
20 HP
CP-1
2 X 5 HP
AIR COMPRESSOR
CT-1 VFD
SERVES
WIRE
PH,
23620
23620
A
PHASE LOAD V.A.
23620
23620
B
FED BY
23620
23620
C
SWITCHBOARD SA
E02
SWITCHBOARD SA
INTERIOREXTERIOR
SWITCHBOARD SA
MCC-1
400A, 480V, 3 PHASE
REMOVE EXISTING
TO REMAIN
MCC-2
EXISTING
OF MAIN
AHEAD
BUS TAP
480Y/277V
PADMOUNT TRANSFORMER
EXISTING
PARTIAL POWER RISER DIAGRAM - EXISTING
NOT TO SCALE
SWITCHBOARD SA
INTERIOREXTERIOR
SWITCHBOARD SA
TO REMAIN
MCC-2
EXISTING
PANEL SB
1200A
EXISTING
480Y/277V
PADMOUNT TRANSFORMER
EXISTING
NOT TO SCALE
PARTIAL POWER RISER DIAGRAM - NEW
MAIN
3000A
MAIN
3000A
BOILER
FOR ELEC
BREAKER
2000A
SECTION
DIST.
SWITCHBOARD SA
SERVICE ENTRANCE
480Y/277V, 3 PHASE
NEW 3000 AMP,
REQUIRED
BOILER - EXTEND AS
TO EXISTING ELECTRIC
FEEDER CONDUCTORS
RECONNECT EXISTING
EXTEND AS REQUIRED.
NEW FEEDER BREAKERS.
FEEDER CONDUCTORS TO
RECONNECT ALL EXISTING SWITCHBOARD SA.
BREAKER IN NEW
1#4G TO NEW 225A/3P
NEW 4#4/0 AWG COPPER,
BE REUSED. PROVIDE
EXISTING CONDUIT CAN
225A
PANEL HCEP2
480Y/277V
NEW
TO REMAIN
PANEL SB
1200A
EXISTING
BOILER BREAKER
2000A ELEC
REMOVE EXISTING
SWITCHBOARD SA
EXISTING 3000A 480V
REMOVE
REMOVE EXISTING 3000A, 480V, 3 PHASE, 4 WIRE BUSS DUCT
TAP BOX
BUSS SVC.
EXISTING
REMOVE
TO BUSS DUCT
ENTRANCE CONDUCTORS
TRANSITION SERVICE
RATED TAP BOX TO
PROVIDE NEW EXTERIOR
CONDUITS
COPPER IN EXISTING
8 SETS OF 4#500 KCMIL
ENTRANCE CONDUCTORS -
PROVIDE NEW SERVICE
GROUNDED NEUTRAL
DUCT WITH FULL SIZE
480 VOLT, 3 PHASE BUSS
PROVIDE NEW 3000 AMP,
PANEL SCHEDULES
PLANT - RISER &
CENTRAL ENERGY
| 23083aCov |
| 23083e00 |
| References |
| tb, 23083tb.dgn |
| 23083e01 |
| References |
| tb, 23083tb.dgn |
| afp, 23083a1.dgn |
| 23083e02 |
| References |
| tb, 23083tb.dgn |
| panels, panel1-Excel.dgn |
File details come from the government source that posted it. Updated .