This is a set of 100% construction drawings for the South Dakota National Guard project to replace boilers at the Yankton Readiness Center located at 1204 W. 31st Street, Yankton, SD 57078 (Project No. 011152.001). The project involves the complete demolition and replacement of the existing boiler system, domestic hot water system, and associated mechanical and plumbing infrastructure. The drawings include architectural, plumbing, mechanical, and electrical plans with detailed specifications for new equipment installation, including two Aerco Benchmark 750 gas-fired hot water boilers, three Bradford White tankless gas water heaters (199 MBH each), domestic hot water recirculation pumps, expansion tanks, air separators, and related piping systems. The project incorporates building automation system (BAS) controls by Schneider Electric and requires coordination among multiple trades including mechanical, plumbing, and electrical contractors. The drawings are dated August 12, 2026, and were prepared by Schemmer architecture and engineering firm based in Sioux Falls, South Dakota.

The construction documents specify detailed demolition requirements, new equipment schedules, piping configurations using 30% propylene glycol, gas piping sizing for approximately 3,116 MBH total connected load at 2.0 PSI, and BAS integration for boiler sequencing and system control. The project requires contractors to field-verify existing conditions, coordinate with all trades, maintain hazardous material protocols, properly support and install all equipment per manufacturer specifications, and ensure proper commissioning and balancing of the heating system. The documents emphasize contractor responsibility for accurate measurements, field condition adjustments at no additional cost to the owner, protection of existing finishes, and restoration of all disturbed surfaces. All mechanical systems are configured for variable primary flow operation with pressure differential-based pump control, and the project includes provisions for glycol feeder systems, condensate neutralization, and emergency shutoff switches as required by code.

View the file

Other files

File Type Posted
Addendum 1 document.pdf PDF
011152001 - REPLACE BOILERS YANKTON READINESS CENTER - PROJECT MANUAL.pdf PDF
IFB Document.pdf PDF
Plan Holders List.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

PROJECT LOCATION MAP

NORTH

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

T H

IS

D

R A

W

IN

G I S

B E

IN

G

M

A D

E A

V A

IL

A

B L E

B Y

S

C H

E M

M E

R F

O R

U S

E O

N T

H

IS

P

R O

J E

C T

I N

A C

C O

R D

A N

E

W

IT

H

S C

H E

M M

E

'S

R E

E M

E N

T F

O

O

F E

S S

IO

N

A L S

E R

V

IC

E

H E

M M

E R

A S

S U

M E

S N

S P

O N

S

IB

IL

IT

Y O

R L

IA

B

IL

F

R A

N Y

U S

E O

F T

D

A

W

IN

G O

R A

N Y

P A

T

E

R E

O F

E X

C E

P T

I

C

O R

D A

N C

E W

IT

H

T

R M

S O

F T

H E

A B

O V

R E

E M

E N

T

D R

A W

N

C H

E C

K E

D

IS

S

U E

D A

T E

PROJECT NO.:

R E

V

IS

IO

N

S

N o

D

A T

E

B Y

D

E S

C R

IP

T

IO

N

D E

S

IG

N E

D a rc h it e c tu re e n g in e e ri n g

C

U se rs \r g u n n in k\

D o cu m en ts

\0

-A

R C

H _R

_r g u n n in k.

rv t

8/

/2

9:

:1

A

M

G001

S O

U T

H D

A K

O T

A N

A T

IO

N

A L

G U

A R

D

T

IT

L E

S H

E E

T

W . 3

1S T

S T

Y A

N K

T O

N , S

D

011152.001

A u th o r

D es ig n er A

U G

U S

T

2, R E

P L

A C

E B

O

IL

E R

S

Y A

N K

T O

N R

E A

D

IN

E S

S C

E N

T E

R

SOUTH DAKOTA NATIONAL GUARD

REPLACE BOILERS - YANKTON READINESS CENTER

1204 W. 31ST ST

YANKTON, SD 57078

100% CONSTRUCTION DRAWINGS

AUGUST 12, 2026

SOUTH DAKOTA

CFMO #466422

011152001-0-G001

W

7t h

S tr ee t, S ui te

2, S io ux

F al ls , S ou th

D ak ot a

| 6

.3

.7

S O

U T

H D

A K

O T

A

TITLE SHEET

ARCHITECTURAL

A 00 ARCHITECTURAL INFO SHEET

GENERAL

G001 TITLE SHEET

DRAWING INDEX

PLUMBING

P 00 PLUMBING INFO SHEET

P001 DEMOLITION FLOOR PLAN - PLUMBING

P101 FLOOR PLAN - PLUMBING

P401 DETAILS & SCHEDULES - PLUMBING

MECHANICAL

M 00 MECHANICAL INFO SHEET

M001 DEMOLITION FLOOR PLAN - MECHANICAL

M101 FLOOR PLAN - MECHANICAL

M301 ENLARGED PLAN & SECTION - MECHANICAL

M401 DETAILS - MECHANICAL

M501 GAS RISER & SCHEDULES - MECHANICAL

ELECTRICAL

E 00 ELECTRICAL INFO SHEET

E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS

E601 EQUIPMENT & PANEL SCHEDULES

08/12/2026

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

T H

IS

D

R A

W

IN

G I S

B E

D

E A

V A

IL

A

B L E

H

E M

M E

R F

O R

U S

E O

N T

O

J E

C T

I N

A C

C O

R D

A N

H

S C

H E

M M

E

R E

E M

E N

T F

O

F E

S S

IO

N

A L S

E R

V

IC

E

H E

M M

E R

A S

S U

M E

S

S P

O N

S

IB

IL

IT

Y O

R L

IA

B

IL

R A

N Y

U S

E O

F T

A

W

IN

G O

R A

N Y

P A

E

R E

O F

E X

C E

P T

C

O R

D A

N C

E W

IT

H

T

R M

S O

F T

H E

A B

O

R E

E M

E N

T

D R

A W

N

C H

E C

K E

D

IS

S

U E

D A

T E

PROJECT NO.:

R E

V

IS

IO

N

S

N o

D

A T

E

B Y

D

E S

C R

IP

T

IO

N

D E

S

IG

N E

D a rc h it e c tu re e n g in e e ri n g

C

U se rs \r g u n n in k\

D o cu m en ts

\0

-A

R C

H _R

_r g u n n in k.

rv t

8/

/2

9:

:1

A

M

A 00

S O

U T

H D

A K

O T

A N

A T

IO

N

A L

G U

A R

D

A R

C H

IT

E

C T

U R

A L

IN

F

O S

H E

E T

W . 3

1S T

S T

Y A

N K

T O

N , S

D

011152.001

R

JM

L A

S

R T

G A

U G

U S

T

2, R E

P L

A C

E B

O

IL

E R

S

Y A

N K

T O

N R

E A

D

IN

E S

S C

E N

T E

R

011152001-2-A 00_Rev 1

W

7t h

S tr ee t, S ui te

2, S io ux

F al ls , S ou th

D ak ot a

| 6

.3

.7

S O

U T

H D

A K

O T

A

ARCHITECTURAL INFO SHEET

NORTH

ARROW

NAME

ELEVATION

LEVEL

MATCHLINE

AREA A

AREA B

TITLE

MARKER

VIEW NAME

SCALE: 1/8" = 1'-0"

EXISTING

COLUMN

NEW

COLUMN

X

X

X

XX-XX

SIM

X

XX-XX

XXXX

DX

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE

NOTE

REFERENCE

DEMOLITION

NOTE

EQUIPMENT

NUMBER

ROOM NAME

150 SF

ROOM

NUMBER

LETTER INDICATES

NEW COLUMN LINE

LETTER INDICATES

EXISTING COLUMN LINE

SECTION/DETAIL

NUMBER

SHEET NUMBER

INDICATES DIRECTION

OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME

DESIGNATION

ROOM NUMBER

DESIGNATION

ROOM AREA

DESIGNATION

SYMBOL LEGEND

ROOM /

FRAMING

ELEVATION

EXTERIOR

ELEVATION

XX-XX

XX-XX

ELEVATION LETTER

DIRECTION OF VIEW

SHEET NUMBER

ELEVATION LETTER

DIRECTION OF VIEW

SHEET NUMBER

DOOR

NUMBER

DOOR NUMBER10

WINDOW

DESIGNATION

WINDOW DESIGNATION000

TA-X

TOILET

ACCESSORY

TOILET ACCESSORY

NUMBER

WALL

TYPE

LETTER

INDICATES

PARTITION OR

WALL TYPE

X

DETAIL NUMBER

LEVEL CALLOUT

DESIGNATION

ELEVATION

DESIGNATION

GRAPHIC AREA FOR

DRAWING

TITLE

SCALE OF THE

DRAWING

ABBREVIATIONS REF. DEMO NOTES ( )

REFERENCE LEGEND

PLAN VIEW

SECTION / ELEVATION VIEW

SHEAR WALL

MASONRY-CMU

MASONRY-VENEER

STUD WALL

CONCRETE

GRAVEL

EARTH / COMPACTED

EARTH /

NONCOMPACTED

RIGID INSULATION

JOINT FILLER

STEEL

GYPSUM

FLEXIBLE INSULATION

GROUT

PLYWOOD

WOOD (FINISH)

MASONRY-CMU FACE

MASONRY-CMU

MASONRY-VENEER

ARCHITECTURAL SHEET LIST

PROJECT ARCHITECTURAL REFERENCED DEMOLITION NOTES

GENERAL NOTES XDXGENERAL DEMO NOTES

PROJECT ARCHITECTURAL REFERENCED NOTES

REF. NOTES ( )

S SOUTH

SA SUPPLY AIR

SAN SANITARY

SB SECURITY BARS

SB SPLASH BLOCK

SCH SCHEDULE

SCHED SCHEDULE

SCR SCREW

SCT STRUCTURAL CLAY TILE

SCUT SCUTTLE

SCW SOFT COLD WATER

SD STORM DRAIN

SD SUBDRAIN

SDI STEEL DECK INSTITUTE

SECT SECTION

SECY SECRETARY

SEQ SEQUENCE

SF SQUARE FOOT (FEET)

SFU STRUCTURAL FACING

UNIT

SHLD SHOULDER

SHT SHEET

SHTG SHEATHING

SHW SOFT HOT WATER

SIM SIMILAR

SJI STEEL JOIST INSTITUTE

SL SNOW LOAD

SLBB SHORT LEG BACK TO

BACK

SM SPRINKLER MAIN

SOV SHUT OFF VALVE

SPA SPACE(ING)

SPEC SPECIFICATIONS

SPF SOUNDPROOF

SPH SPACE HEATER

SPKR SPEAKER

SPL SPECIAL

SQ SQUARE

SS SANITARY SEWER

SS STAINLESS STEEL

SSMR STANDING SEAM METAL

ROOFING

STA STATION

STAIR STAIRWAY

STC SOUND TRANSMISSION

COEFFICIENT

STD STANDARD

STGR STRINGER

STIFF STIFFENER

STIRR STIRRUPS

STL STEEL

STN STONE

STOR STORAGE

STR STRUCTURAL

SUB FL SUB FLOOR

SUCT SUCTION

SUSP SUSPENDED

SVF SHEET VINYL FLOORING

SW SWITCH

SWBD SWITCH BOARD

SYM SYMMETRICAL

T TREAD

T or TLT TOILET

TAN TANGENT

TBD TACK BOARD

TE TOP ELEVATION

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TERM TERMINAL

TGL TOGGLE

TH THRESHOLD

THK THICK

THRD THREAD

TO TOP OF

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOF TOP OF FOOTING

TOJ TOP OF JOIST

TOPO TOPOGRAPHIC

TOS TOP OF STEEL

TOW TOP OF WALL

TRANS TRANSVERSE

TSTAT THERMOSTAT

TV TELEVISION

TW TEMPERED WATER

TWR TEMPERED WATER

RETURN

TYP TYPICAL

UC UNIT COOLER

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS

LABORATORIES

UNEX UNEXCAVATED

UNFIN UNFINISHED

UNO UNLESS NOTED

OTHERWISE

UPS UNINTERRUPTIBLE

POWER SYSTEM

UR URINAL

UT UTILITY

UV UNIT VENTILATOR

V VOLT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VCP VITRIFIED CLAY PIPE

VCT VINYL COMPOSITION TILE

VD VAULT DOOR

VEL VELOCITY

VENT VENTILATOR(ION)

VERT VERTICAL

VEST VESTIBULE

VFD VARIABLE FREQUENCY

DRIVE

VOL VOLUME

VPC VERTICAL POINT OF

CURVATURE

VPI VERTICAL POINT OF

INTERSECTION

VPT VERTICAL POINT OF

TANGENCY

VS VENT STACK

VT VINYL-TILE

VTR VENT THRU ROOF

VWC VINYL WALL COVERING

W WEST

W WIDE (WIDTH)

W WIRE

W/ WITH

W/O WITHOUT

WB WET BULB

WC WATER CLOSET

WC WATER COLUMN

WD WASTE DRAIN

WD WOOD

WD BLKG WOOD BLOCKING

WD DR WOOD DOOR

WDW WINDOW

WF WIDE FLANGE

WG WIRE GLASS

WH WALL HYDRANT

WHT WHITE

WI WROUGHT IRON

WKSH WORK SHOP

WL WIND LOAD

WNSCT WAINSCOT

WP WEATHER PROOF

WP WORK POINT

WPF WATER PROOF

WPFG WATER PROOFING

WRB WARDROBE

WS WASTE STACK

WT WEIGHT

WWF WELDED WIRE FABRIC

WWM WOVEN WIRE MESH

XFMR TRANSFORMER

YD YARD or YARD DRAIN

LBS POUNDS

LD LOAD

LDG LOADING

LE LEFT END

LG LENGTH (LONG)

LIN LINEAR

LIS LAWN IRRIGATION

SYSTEM

LL LIVE LOAD

LLBB LONG LEG BACK TO BACK

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LNTL LINTEL

LP LOW POINT

LPG LIQUIFIED PETROLEUM

GAS

LPS LOW PRESSURE STEAM

LR LIVING ROOM

LS LAWN SPRINKLER

LT LIGHT

LT WT LIGHT WEIGHT

LTG LIGHTING

LVT LUXURY VINYL TILE

M MIDDLE

M THOUSAND

M & B MATCHED AND BEADED

MA MAKE-UP AIR

MACH MACHINE

MAS MASONRY

MAT or

MATL

MATERIAL

MAX MAXIMUM

MB MACHINE BOLT

MBH 1000 BTUH

MC MEDICINE CABINET

MC MISCELLANEOUS

CHANNELS

MECH MECHANICAL

MER MECHANICAL EQUIPMENT

ROOM

MET METAL

MFG MANUFACTURING

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

ML METAL LATH

MLDG MOULDING

MO MASONRY OPENING

MONO MONOLITHIC

MT METAL THRESHOLD

MTD MOUNTED

N NORTH

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE

PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO NUMBER

NR NOT REQUIRED

NS NEAR SIDE

NTS NOT TO SCALE

OA OUTSIDE AIR

OB WG OBSCURE WIRE GLASS

OBGL OBSCURE GLASS

OBSC OBSCURE

OC ON CENTER(S)

OCEW ON CENTER EACH WAY

OD OUTSIDE DIAMETER

OFF OFFICE

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

OPS OPERATIONS

OS & Y OUTSIDE SCREW & YOKE

OSF OUTSIDE FACE

OV OVERFLOW VALVE

OX OXYGEN

OZ OUNCE

P PAINT

PA PUBLIC ADDRESS

PBS PUSH BUTTON STATION

PC PIECE

PC POINT OF CURVATURE

PC PRECAST

PCC PORTLAND CEMENT

CONCRETE

PCT PORCELAIN CERAMIC TILE

PD PRESSURE DROP

PE POLYETHYLENE

PEN PENETRATION

PERF PERFORATED

PH PHASE

PHAR PHARMACY

PI POINT OF INTERSECTION

PIV POST INDICATING VALVE

PL or P PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLATF PLATFORM

PLBG PLUMBING

PLG PILING

PLWD PLYWOOD

PNL PANEL

POL POLISH(ED)

PORC PORCELAIN

PPM PARTS PER MILLION

PR PAIR

PREFAB PREFABRICATED

PREFIN PREFINISHED

PRESS PRESSURE

PROJ PROJECT

PRV PRESSURE REGULATING

VALVE

PS PRESSED STEEL

PSFT POUNDS PER SQUARE

FOOT

PSI POUNDS PER SQUARE

INCH

PT POINT

PT POINT OF TANGENCY

PTD PAINTED

PTN PARTITION

PVC POLYVINYL-CHLORIDE

PVMT PAVEMENT

PW PASS WINDOW

1/4 RD QUARTER ROUND

QT QUARRY TILE

QT QUART

QTRS QUARTERS

QTY QUANTITY

QTZ QUARTZ

R REGISTER

R RISER

RA RETURN AIR

RAD OR

R

RADIUS

RB RESILIENT BASE

RC REMOTE CONTROL

RCP REINFORCED CONCRETE

PIPE

RD ROOF DRAIN

RE RIGHT END

REC RECEIVER

RECP RECEPTACLE

RECR RECREATION

RECT RECTIFIER

REF REFERENCE

REFR REFRIGERANT

REFR REFRIGERATOR

REG REGISTER

REINF REINFORCEMENT

REM REMOVE(ABLE)

REQD REQUIRED

RESIL RESILIENT

REV REVISIONS

RFG ROOFING

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID

RM ROOM

RND ROUND

RO ROUGH OPENING

RPM REVOLUTIONS PER

MINUTE

RT RUBBER TILE

RTU ROOF TOP UNIT

RUB RUBBER

DIAG DIAGONAL

DIM DIMENSION

DIP DUCTILE IRON PIPE

DISC DISCONNECT

DIST DISTRIBUTION

DL DEAD LOAD

DMPR DAMPER

DN DOWN

DP DAMP PROOFING

DPT DEW POINT

DR DOOR

DRN DRAIN

DS DOWN SPOUT

DV DENTAL VACUUM

DWG DRAWING

DWLS DOWELS

DX DIRECT EXPANSION

E EAST

EA EACH

EA EXHAUST AIR

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY

RATIO

EJ EXPANSION JOINT

EL OR

ELEV

ELEVATION - GRADE OR

BUILDING

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

ENCL ENCLOSURE

ENT ENTERING

ENT ENTRANCE

EQ EQUAL

EQUIP EQUIPMENT

ES EACH SIDE

EST ESTIMATE

EVAP EVAPORATOR

EW EACH WAY

EWC ELECTRIC WATER

COOLER

EXC EXCAVATE

EXD EXIT DEVICE

EXH EXHAUST

EXIST EXISTING

EXP EXPOSED

EXPL EXPLOSION

EXPN EXPANSION

EXT EXTERIOR

F FAHRENHEIT

F

FIRE

FA FRESH AIR

FCG FACING

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEB FIRE EXTINGUISHER

BRACKET

FEC FIRE EXTINGUISHER

CABINET

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIG FIGURE

FIN FINISH

FIX FIXTURE

FL or FLR FLOOR

FLASH FLASHING

FLEX FLEXIBLE

FLG FLANGE

FLG FLOORING

FLUOR FLUORESCENT

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPRF FIRE PROOF

FR FRAME

FRG FURRING

FS FAR SIDE

FS FLOOR SINK

FS FULL SIZE

FT FEET (FOOT)

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALL COVERING

G GRILLE

G NATURAL GAS

GA GAGE OR GAUGE

GAL GALLON

GALV GALVANIZED

GEN GENERAL

GFE GOVERNMENT FURNISHED

EQUIPMENT

GFE/CI GOVERNMENT FURNISHED

EQUIPMENT/CONTRACTOR

INSTALLED

GFI GROUND FAULT

INTERRUPTER

GI GALVANIZED IRON

GL GLASS

GND GROUND

GOVT GOVERNMENT

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GR GRADE

GRS GALVANIZED RIGID STEEL

CONDUIT

GRTG GRATING

GSU GLAZED STRUCTURAL

UNITS

GWB GYPSUM WALLBOARD

GWT GLAZED WALL TILE

GYP GYPSUM

H or HT HEIGHT (HIGH)

HB HOSE BIBB

HBD HARDBOARD

HC HANDICAPPED

HD HEAD

HDPE HIGH DENSITY

POLYETHYLENE

HDR HEADER

HDW HARDWARE

HIP HIGH PRESSURE

HM HOLLOW METAL

HORIZ HORIZONTAL(LY)

HP HORSE POWER

HPS HIGH PRESURE STEAM

HPT HIGH POINT

HR HOUR

HS HIGH STRENGTH

HSGYP HIGH STRENGTH GYPSUM

PLASTER

HTG HEATING

HTR HEATER

HW HEAD WALL

HW HOT WATER

HWH HOT WATER HEATER

HWR HOT WATER RETURN

(HEATING)

HWS HOT WATER SUPPLY

(HEATING)

HYD HYDRAULIC

I or FE IRON

IC INTERCOM

ID INSIDE DIAMETER

IE INVERT ELEVATION

IES ILLUMINATING

ENGINEERING SOCIETY

IN INCH

INSUL INSULATION

INT INTERIOR

INV INVERT OR INVERTER

IP IRON PIPE

ISF INSIDE FACE

JB JUNCTION BOX

JBOX JUNCTION BOX

JC JANITOR CLOSET

JCT JUNCTION

JST JOIST

JT JOINT

K KEY

KCP KEENE'S CEMENT

PLASTER

KIP or K KILOPOUND (1000 LBS)

KIT KITCHEN

KL KEY LOCK

KP KICK PLATE

KV KILOVOLTS

KVA KILOVOLT AMPERES

KW KILOWATT

LAB LABORATORY

LAU LAUNDRY

LAV LAVATORY

LBR LUMBER

A COMPRESSED AIR

A/C AIR CONDITIONING

AB ANCHOR BOLT

ABS ACRYLONITRILE BUTAD

STYRENE

AC ALTERNATING CURRENT

ACI AMERICAN CONCRETE

INSTITUTE

ACSR ALUMINUM CONDUCTOR

STEEL REINFORCED

ACST ACOUSTIC

AD ACCESS DOOR

AD AREA DRAIN

ADMIN ADMIN ADMINISTRATION

(IVE)

AFF ABOVE FINISH FLOOR

AFFF AQUEOUS FILM FORMING

FOAM

AGG AGGREGATE

AHU AIR HANDLING UNIT

AI AREA INLET

AIC AMPS INTERRUPTING

CAPACITY (SYM RMS)

AISC AMERICAN INSTITUTE OF

STEEL CONSTRUCTION

AL ACTIVE LEAF

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL

STANDARDS INSTITUTE

AP ACCESS PANEL

APD AIR PRESSURE DROP

APPD APPROVED

APPROX APPROXIMATE

ARCH ARCHITECTURAL OR

ARCHITECT

ARI AMERICAN

REFRIGERATION

INSTITUTE

ASB ASBESTOS

ASPH ASPHALT

APC ACOUSTICAL PANEL

CEILING

AUTO AUTOMATIC

AV ACID VENT

AVG AVERAGE

AW ACID WASTE

AWC ACOUSTICAL WALL

COVERING

AWG AMERICAN WIRE GAUGE

L ANGLE

BATT BATT INSULATION

BB BULLETIN BOARD

BBO BOILER BLOW OFF

BC BOOKCASE

BD BOARD

BDY BOUNDARY

BEJ BRICK EXPANSION JOINT

BIT BITUMINOUS

BKR BREAKER

BL BUILDING LINE

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BM BENCH MARK

BO BOTTOM OF

BOT BOTTOM

BRCG BRACING

BRDG BRIDGING

BRG BEARING

BRK BRICK

BRKT BRACKET

BS BOTH SIDES

BTU BRITISH THERMAL UNIT

BTUH BTU PER HOUR

BUR BUILT-UP ROOFING

BW BOTH WAYS

C CENTER

C OR

CND

CONDUIT (ELECTRICAL

SHEETS)

C TO C CENTER TO CENTER

CAP CAPACITY

CB CATCH BASIN (OR CIRCUIT

BREAKER)

CC CENTER TO CENTER

CCT CIRCUIT

CD CONDENSATE DRAIN

CE COVER ELEVATION

CEM CEMENT

CF CUBIC FEET

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CHIM CHIMNEY

CI CAST IRON

CI CURB INLET

CIP CAST IN PLACE

CIR CIRCULAR

CJ CONTROL JOINT

CKT CIRCUIT

CL CENTER LINE

CL WG CLEAR WIRE GLASS

CLG CEILING

CLKG CAULKING

CMP CORRUGATED METAL PIPE

CMU CONCRETE MASONRY

UNIT

CNTR COUNTER

CO CLEAN OUT

CO2 CARBON DIOXIDE

COL COLUMN

COM COMMON

COMB COMBINATION

COMB COMBUSTION

COMP COMPRESSIBLE

COMPR COMPRESSOR

CONC CONCRETE

CONF CONFERENCE

CONN CONNECTION

CONSTR CONSTRUCTION

CONSTR

JT

CONSTRUCTION JOINT

CONT CONTINUOUS

(CONTINUATION)

CONTR CONTRACTOR

COR CORNER

CORR

COVEREDCOV

CORRIDOR

CPL CEMENT PLASTER

CPS CYCLES PER SECOND

(HERTZ)

CPT CARPET

CR CONDENSER WATER

RETURN

CRES CORROSIVE RESISTANT

STEEL

CRG CARRIAGE

CRSE COURSE

CS CONDENSER WATER

SUPPLY

CS COUNTER SINK

CSMT CASEMENT

CT CERAMIC TILE

CT CURRENT TRANSFORMER

CTL CARPET TILE

CU CONDENSING UNIT

CU YD CUBIC YARDS

CUH CABINET UNIT HEATER

CV CEILING VENT

CW COLD WATER

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

CYL CYLINDER

D DEPTH (DEEP)

D DIFFUSER

d PENNY (as in nail - 10d)

D&M DRESSED AND MATCHED

DA DOUBLE ACTING

DB DRY BULB

dB DECIBEL

DBL DOUBLE

DC DIRECT CURRENT

DCJ DOWELED CONTROL

JOINT

DCJT DUMMY CONTROL JOINT

DCL DOOR CLOSER

DCW DOMESTIC COLD WATER

DEG DEGREE

DEMO DEMOLITION

DEPR DEPRESSION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DH DOUBLE HUNG

DHW DOMESTIC HOT WATER

DI DEIONIZED WATER

DIA DIAMETER

CLO CLOSET

FR FIRE RATED

U/C UNDER CABINET

NORTH PLAN

NORTH

TRUE

NORTH

CBU CEMENTITIOUS BACKER

UNIT

F FLUSH or FRAME

FG FULL GLASS

G GLASS or GLASS TYPE

HG HALF GLASS

NV NARROW VISION

V VISION

SL SLIDING

BF(2) BIFOLD (DOUBLE)

IG INSULATED GLASS

SS SOLID SURFACE

G001 TITLE SHEET

A 00 ARCHITECTURAL INFO SHEET

A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL

DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.

DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR

SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED

TO BE REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS FULL-TONE

DASHED LINES AND ARE LISTED IN THE REFERENCED DEMOLITION NOTES.

ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN

HALF-TONE.

B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS BELOW OR

HERE-IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED

RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO

IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED

BELOW.

C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND

REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS,

EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD, ERECT,

INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER

HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.

D. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE

CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND

STORED OR REINSTALLED ON THE SITE AS DIRECTED. REMOVED AND

SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE OWNER.

E. WHERE EXISTING FLOOR MATERIALS AND/OR WALLS ARE TO BE REMOVED,

PREP REMAINING FLOOR AND/OR WALL SUBSTRATE AS REQUIRED PER

MANUFACTURERS RECOMMENDATIONS FOR THE NEW FLOOR/WALL FINISH

MATERIAL. REMOVE ALL FINISH FLOORING DOWN TO BASE SUBSTRATE

FLOORING AND PREP TO RECEIVE NEW FINISH.

F. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL

REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY

OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED

HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE

AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT

THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE

OWNER AND CONTRACTOR.

G. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE,

AND REMOVAL OF ALL CONSTRUCTION BARRIERS.

H. TEMPORARILY SHORE AND BRACE STRUCTURE AT ALL BEARING WALL

DEMOLITION LOCATIONS UNTIL NEW PERMANENT STRUCTURE IS

ESTABLISHED.

I. REMOVE EXISTING ELEMENTS/FINISHES NOT REQUIRED IN THE COMPLETED

PROJECT, BUT CONFLICTING WITH NEW FINISHES.

J. REMOVE EXISTING FLOOR FINISHES IN AREAS TO RECEIVE NEW FLOOR

FINISHES PER THE ROOM FINISH SCHEDULE. SEE MECHANICAL, AND

ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION, INCLUDING, BUT NOT

LIMITED TO, ALL CONCRETE SLAB REMOVAL AND REPLACEMENT.

K. REFER TO MECHANICAL DEMOLITION PLANS FOR ADDITIONAL DEMOLITION

REQUIRED TO ACCOMMODATE NEW MECHANICAL PIPING AND ASSOCIATED

EQUIPMENT.

L. THE OWNER HAS THE RIGHT TO SALVAGE ANY ITEMS DESIRED.

CONTRACTORS THAT WANT TO SALVAGE MATERIALS FOR THEIR OWN USE

SHALL MAKE A WRITTEN REQUEST.

M. ALL SURFACES OR FINISHES DAMAGED DURING CONSTRUCTION SHALL BE

REPAIRED OR REPLACED AND SHALL MATCH ADJACENT MATERIALS.

N. REMOVE ALL ABANDONED MECHANICAL EQUIPMENT, PIPING, AND/OR

CONDUIT.

O. CONTRACTOR SHALL PROTECT INTERIOR FINISHES IN OFFICE AREAS,

LOBBY, ETC. FROM DEMOLITION AND CONSTRUCTION ACTIVITIES.

CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OR REPLACEMENT OF

DAMAGED ITEMS.

A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER

AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY

ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE

ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM

THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO

ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF

DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR

SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE

SET OF DOCUMENTS.

C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE

RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD

CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.

D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO

REMAIN. FULL-TONE LINES INDICATE NEW OR RELOCATED CONSTRUCTION.

E. DIMENSIONS ARE TYPICALLY TO FINISH FACE OF MASONRY, CONCRETE,

GYPSUM WALL BOARD, AND METAL FRAMES; OR CENTER LINE OF COLUMN

OR BEAMS, UNLESS NOTED OTHERWISE.

F. CHANGES IN FLOOR MATERIALS SHALL OCCUR UNDER DOORS.

G. PROVIDE POSITIVE DRAINAGE TO ALL ROOMS WITH NEW FLOOR DRAINS.

H. ALL ANGLES ON THE FLOOR PLANS ARE 45 OR 90 DEGREES UNLESS

OTHERWISE INDICATED.

I. PROVIDE FIRE TREATED 2x6 OR LARGER WOOD BLOCKING IN WALLS AND

FURRING SPACES AS REQUIRED FOR MOUNTING OF ALL WALL SUPPORTED

ITEMS. WHETHER OR NOT DETAILED ON THE DRAWINGS, THE DRYWALL

CONTRACTOR SHALL COORDINATE AND INSTALL ALL STIFFENERS, BRACING,

BACK-UP PLATES, AND SUPPORTING BRACKETS AS REQUIRED FOR THE

INSTALLATION OF CASEWORK AND WALL MOUNTED OR SUSPENDED

MECHANICAL, ELECTRICAL, OR MISCELLANEOUS EQUIPMENT. THESE ITEMS

INCLUDE, BUT ARE NOT LIMITED TO, HANDRAIL BRACKETS, DOOR WALL

STOPS, FIRE EXTINGUISHER CABINETS, VANITY TOPS, BASE AND WALL

CABINETS, COUNTERTOPS, CONTROL PANELS, WATER COOLERS, WALL

HUNG SINKS, URINALS, TOILETS, MIRRORS, SOAP DISPENSERS, PAPER

TOWEL DISPENSERS, NAPKIN DISPOSAL, TOILET PARTITIONS, URINAL

SCREENS, TOILET PAPER DISPENSERS, SIGNAGE, GRAB BARS, FIRE ALARM

PANELS AND MASTER CLOCKS, ETC.

J. PATCH EXISTING WALLS, FLOORS, AND CEILING SURFACES DEMOLISHED,

CUT, CORED, OR ALTERED IN ANY WAY TO ACCOMMODATE NEW

CONSTRUCTION OR TO RECEIVE NEW FINISHES. PREP ALL EXISTING

FLOORS TO RECEIVE NEW FINISHES.

K. CONTRACTOR SHALL VERIFY CMU WALLS HAVE NO CHIPPED EDGES AND

THAT JOINTS HAVE BEEN TOOLED TO REMOVE ALL EXCESS MORTAR AND

ARE READY TO RECEIVE PAINT. CONTRACTOR SHALL APPROVE WALLS TO

RECEIVE PAINT PRIOR TO HAVING PAINTER INSPECT FOR APPROVAL.

L. PATCH ALL CONCRETE SLAB LOCATIONS DEMOLISHED TO INSTALL NEW

MECHANICAL, OR ELECTRICAL WORK.

M. REMOVE ALL ABANDONED MECHANICAL EQUIPMENT, PIPING, AND / OR

CONDUIT.

N. CONTRACTOR SHALL PROTECT INTERIOR FINISHES FROM DEMOLITION AND

CONSTRUCTION ACTIVITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR

REPAIR OR REPLACEMENT OF DAMAGED ITEMS.

O. CONTRACTOR SHALL REPAIR ALL SITE AREAS DAMAGED DURING

CONSTRUCTION TO MATCH EXISTING CONDITIONS.

P. IN THE AREA OF WORK THE CONTRACTOR SHALL REPAINT ALL NEW FLOOR

SURFACES AND FLOOR SURFACES DAMAGED DURING CONSTRUCTION.

REPAINT FLOOR WITH PAINT MATCHING THE EXISTING FLOOR FINISHES IN

THE ROOM (PAINT TYPE AND COLOR).

Q. IN THE AREA OF WORK THE CONTRACTOR SHALL REPAINT ALL WALL

SURFACES DAMAGED OR PATCHED DURING CONSTRUCTION. REPAINT

WALL SURFACES WITH PAINT MATCHING THE EXISTING WALL FINISHES IN

THE ROOM (PAINT TYPE AND COLOR).

08/12/2026

A.

B.

C.

D.

ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO

DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA

COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.

CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE FOR

SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL

EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER

TRADES AFFECTED.

ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT ANGLES AND PARALLEL

TO BUILDING WALLS UNLESS OTHERWISE INDICATED.

ALL PLUMBING INSTALLATION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE

LOCAL AUTHORITY HAVING JURISDICTION.

A.

B.

C.

D.

E.

F.

G.

H.

THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL DRAWINGS

PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION. DIMENSIONS AND EXISTING

CONDITIONS ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR SALVAGED

ARE SHOWN AS FULL-TONE LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE

AND ARE SHOWN AS HALF-TONE.

DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED BELOW OR HERE-

IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW

CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE

DEMOLITION REQUIRED AND AS LISTED BELOW.

THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING EQUIPMENT FROM FINISHED

AREAS AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL

PLANS AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING TO ENSURE

PROPER PATCHING AND REPAIR IS MADE TO THE BUILDING.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL

EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT,

INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST

RIGHT OF REFUSAL ON ALL ITEMS.

ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE CAREFULLY

REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND STORED OR REINSTALLED ON THE

SITE AS DIRECTED. REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE

OWNER.

COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND CONTROLS WITH

ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL REMOVALS.

IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL REASONABLY

BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL

WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY

STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE

RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND ARCHITECT.

ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION SHALL BE

COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

TH

IS

D R

AW

IN

G

IS

B

EI

AD

E

AV

AI

LA

BL

BY

SC

EM

M

ER

F O

R U

SE

O

N T

PR

JE

C T

IN

A

C C

O R

D

AN

C E

W

IT

H S

C H

EM

M

ER

AG

EE

M

EN

T

FO

FE

SS

IO

N

AL

S

ER

VI

C

ES

SC

H

EM

M

ER

A

SS

U M

ES

ES

PO

N

SI

BI

LI

TY

O R

L

IA

BI

LI

TY

A N

Y U

SE

O

F

TH

AW

IN

G O

R A

N Y

PA

R

T

TH

ER

EO

F

EX

C

EP

AC

O

R D

AN

C

E W

IT

H

T H

E

TE

R M

S O

F

TH

E

AB

VE

EE

M

EN

T.

DR

AW

N:

CH

EC

KE

D:

IS

SU

E

DA

TE

PROJECT NO.:

RE

VI

SI

ON

S:

No

DA

TE

BY

DE

SC

RI

PT

IO

N:

DE

SI

GN

ED

ar ch ite ct ur e

| e ng in ee rin g

C:

\U se rs

\aa ris te o\

Do cu m en ts \R ev it_ te m p\

1-

ME

CH

_R

_a ar ist eo

XZ

HQ

L.

rv t 8/9

/20

8:

:4 1 A

M

P 00

SO

UT

H

DA

KO

TA

N

AT

IO

NA

L

GU

AR

D

PL

UM

BI

NG

IN

FO

S

HE

ET

W . 3

1S T

ST

YA

NK

TO

N, S

D

011152.001

JE

K

AM

A

AM

A

AU

GU

ST

, 2

RE

PL

AC

E

BO

IL

ER

S

- Y

AN

KT

ON

R

EA

DI

NE

SS

C

EN

TE

R

011152001-5-P 00

W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota

8 |

5.3

.78

SO

UT

H

DA

KO

TA

PLUMBING INFO SHEET

NORTH

ARROW

SYMBOL LEGEND ABBREVIATIONS

MATCHLINE AREA A

AREA B

EXISTING

COLUMN

NEW COLUMN

X

X

X

XXXX

SIM/OPP

X

XXXX

XX-1

X

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE NOTE

REFERENCE

DEMOLITION NOTE

EQUIPMENT

NUMBER

ROOM NAME

ROOM / SPACE

NUMBER

LETTER/NUMBER INDICATES NEW

COLUMN LINE

LETTER/NUMBER INDICATES

EXISTING COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER 1

VIEW NAME

SCALE: 1/8" = 1'-0"

DRAWING/DETAIL NUMBER

LEVEL CALLOUT DESIGNATION

ELEVATION DESIGNATION

GRAPHIC AREA FOR DRAWING

TITLE

SCALE OF THE DRAWING

VOLUME DAMPER

DEMO TO EXISTING CONNECTION

SPRINKLER DRAIN

FIRE SUPPRESSION PIPING

ISOLATION VALVE

TAMPER SWITCH

MANUAL BALANCING VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

CONTROL VALVE (3 WAY)

CONTROL VALVE (2 WAY)

HOSE END DRAIN VALVE

PRESSURE REDUCING VALVE

AUTO FLOW CONTROL VALVE

CHECK VALVE

HVAC DUCTWORK AND SPECIALTIES (CONT.)

MISCELLANEOUS SYMBOLS

RETURN DUCT DOWN

AIR TERMINAL (VERTICAL MOUNTING)

ROUND DUCT UP / DOUBLE LINE PIPE

ROUND DUCT DOWN / DOUBLE LINE

PIPE

RETURN DUCT UP

TURNING VANES

SUPPLY AND FRESH AIR DUCT DOWN

SUPPLY AND FRESH AIR DUCT UP

SIZE/TYPE

SIZE/TYPE

FLOW

FLOW

SIZE/TYPE

FLOW

SMOKE DAMPER

FIRE DAMPER-HORIZ FIRE SEPARATION

MOTORIZED DAMPER-OPPOSED BLADE

MOTORIZED DAMPER-PARALLEL BLADE

ROUND AIR TERMINAL

(HORIZONTAL MOUNTING)

GRAVITY DAMPER

(OR) SAFETY VALVE-STEAM

TEMP & PRESS RELIEF

FLOOR SINK

FLOOR DRAIN

GRADE CLEANOUT

PLUMBING VENT THRU ROOF

CLEANOUT / WALL CLEANOUT

THERMOSTATIC MIXING VALVE

M

M

MANHOLE

TRENCH DRAIN

OVERFLOW ROOF DRAIN

OXYGEN OUTLET

PIPE CAP

ELBOW UP

AIR OUTLET

TEE

ELBOW DOWN

VACUUM OUTLET

ROOF DRAIN

SIZE/TYPE

FLOW

HUMIDISTAT

THERMOSTAT

FLEXIBLE DUCT

S

H

T

TEMPERATURE SENSOR

UNION

TEE DOWN

STRAINER

EXPANSION JOINT

FLEXIBLE PIPE CONNECTION

AIR VENT

TEE UP

FIRE/SMOKE DAMPER

RECTANGULAR RETURN AIR TERMINAL

(HORIZONTAL MOUNTING)

RECTANGULAR SUPPLY AIR TERMINAL

(HORIZONTAL MOUNTING)

SOLENOID VALVE

F D

TS

VALVES

FS

M

M

S

LPR

HPS

MPR

MPS

LPS

HVAC PIPING

GHWR

GHWS

HWR

HWS

PC

HPR

ES

BBD BOILER BLOW DOWN

EXHAUST STEAM

PUMPED CONDENSATE

HIGH PRESSURE RETURN

HIGH PRESSURE STEAM

MEDIUM PRESSURE RETURN

MEDIUM PRESSURE STEAM

LOW PRESSURE RETURN

LOW PRESSURE STEAM

GLYCOL HOT WATER RETURN

GLYCOL HOT WATER SUPPLY

HOT WATER RETURN

HOT WATER SUPPLY

FS-_

FD-_

CO

VTR

GCO

ORD-_

MH

X

A

V

RD-_

PIPING SPECIALTIES AND FITTINGS

WCO

FIRE PROTECTION

XXX-1

PLUMBING FIXTURES

PLUMBING FIXTURE DESIGNATION

X"PIPE

SIZE PIPE SIZE (DIAMETER)

X"xX"

DUCT SIZE

WIDTH x HEIGHT

SIZE/TYPE

FLOW

RECTANGULAR EXHAUST AIR TERMINAL

(HORIZONTAL MOUNTING)

REF. DEMO NOTES ( )GENERAL NOTES XXGENERAL DEMOLITION NOTES

CWS

GCWS

CWR

CR

CS

RL

RDL

RS

GCWR GLYCOL CHILLED WATER RETURN

GLYCOL CHILLED WATER SUPPLY

REFRIGERANT LIQUID LINE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION LINE

HCWS

HCWR

HOT/CHILLED WATER SUPPLY

HOT/CHILLED WATER RETURN

REF. NOTES ( )

DOMESTIC HOT WATER

RECIRCULATING (DHWR)

DOMESTIC COLD WATER (DCW)

DOMESTIC HOT WATER (DHW)

ST/OST

PLUMBING PIPING

ACID VENT

TW

AV

AW

W

DS

DSCW

TWR

DSHW

SANITARY VENT

BURIED EXTERIOR WATER

TEPID WATER RECIRCULATING

TEPID WATER

DISTILLED WATER

SOFTENED HOT WATER

SOFTENED COLD WATER

ACID WASTE

STORM DRAIN

SANITARY DRAIN (BELOW FLOOR)

SANITARY DRAIN (ABOVE FLOOR)

OXYGEN

VACUUM

OX

VAC

RO

A

REVERSE OSMOSIS WATER

COMPRESSED AIR

DEIONIZED WATERDI

AIR FLOW STATIONAFS

SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.

HPWR

HPWS

HEAT PUMP WATER RETURN

HEAT PUMP WATER SUPPLY

F

S

FS

NEW TO EXISTING CONNECTION

G NATURAL GAS

FOF

FOG

LPG

FOV

FOR

FOS

FUEL OIL RETURN

FUEL OIL SUPPLY

FUEL OIL GAGE

FUEL OIL FILL

FUEL OIL VENT

LIQUEFIED PETROLEUM GAS

CD CONDENSATE DRAIN

EXHAUST DUCT DOWN

EXHAUST DUCT UP

CO CARBON MONOXIDE SENSOR

CO2 CARBON DIOXIDE SENSOR

NO2 NITROGEN DIOXIDE SENSOR

SENSOR WITH GUARD'X'

DOUBLE - GRADE CLEANOUTDGCO

ST/OST STORM DRAIN (BELOW FLOOR)

WASTE AND ANESTHETIC GAS

DISPOSAL

NITROGEN

WAGD

N

MEDICAL AIRMA

PIPE GUIDE

HOSE BIBB

THERMOMETER

PIPE ANCHOR

HB

STEAM TRAP

RHY

WH

ROOF HYDRANT

WALL HYDRANT

PRESSURE GAUGE

EXISTINGDEMO

EXISTINGNEW

18 Ø

18x10

18/10

ROUND DUCT

FLAT OVAL DUCT-1ST FIG IS SIDE

SHOWN

RECT DUCT-1ST FIG IS SIDE SHOWN

ACOUSTICAL DUCT LINER

HVAC DUCTWORK AND SPECIALTIES

HIGH EFFICIENCY TAKEOFF

HIGH EFFICIENCY TAKOFF

WITH VOLUME DAMPER

NITROGEN OUTLET

MEDICAL AIR OUTLET

WASTE AND ANESTHETIC GAS

DISPOSAL OUTLET

N

MA

V

FLEXIBLE DUCTWORK CONNECTION

X"/X" WIDTH / HEIGHT

X" DIAMETER

NORTH

GW SANITARY GREASE WASTE

PLUMBING SHEET LIST

PROJECT PLUMBING REFERENCED DEMOLITION NOTES PROJECT PLUMBING REFERENCED NOTES

MAU MAKE-UP AIR UNIT

MAX MAXIMUM

MBH 1000 BTUH

MCA MINIMUM CIRCUIT AMPS

MD MOTORIZED DAMPER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT

PROTECTION

MPR MEDIUM PRESSURE

RETURN

MPS MEDIUM PRESSURE STEAM

MS MOP SINK

N NITROGEN

NC NORMALLY CLOSED

NO NORMALLY OPEN

NPCW NONPOTABLE COLD WATER

NPHW NONPOTABLE HOT WATER

NPHWR NONPOTABLE HOT WATER

RECIRCULATING

OA OUTSIDE AIR

ORD OVERFLOW ROOF DRAIN

OX OXYGEN

P PUMP

PHC PREHEAT COIL

PIV POST INDICATING VALVE

PRV PRESSURE REGULATING VALVE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PSIG POUNDS PER SQUARE INCH,

GAUGE

PTAC PACKAGED TERMINAL AIR

CONDITIONER

RA RETURN AIR

RCP RADIANT CEILING PANEL

RD ROOF AREA DRAINS

RF RETURN FAN

RH RELIEF HOOD

RHC REHEAT COIL

RL REFRIGERANT LIQUID LINE

RLA RELIEF AIR

RLF RELIEF FAN

RO REVERSE OSMOSIS WATER

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION LINE

RTU ROOF TOP UNIT

RV RELIEF VALVE

S SINK

SA SUPPLY AIR

SAN SANITARY SEWER

SD SMOKE DAMPER

SF SUPPLY FAN

SFU SANITARY FIXTURE UNIT

SH SHOWER

SP STATIC PRESSURE

SSS SURGICAL SCRUB SINK

ST STORM WATER

TD TRENCH DRAIN

TMV THERMOSTATIC MIXING VALVE

TONS TONS OF REFRIGERATION

TSP TOTAL STATIC PRESSURE

T THERMOSTAT

UH UNIT HEATER

UR URINAL

V VENT

VAC VACUUM

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THRU ROOF

WB WET BULB

WC WATER CLOSETS

WCO WALL CLEANOUT

WF WASH FOUNTAINS

WFU WATER FIXTURE UNITS

WH WALL HYDRANT

WPD WATER PRESSURE DROP

WS WATER SOFTENER

WSHP WATER SOURCE HEAT PUMP

WWHP WATER TO WATER HEAT PUMP

YH YARD HYDRANT

A COMPRESSED AIR

AC AIR COMPRESSOR

AD AIR DOOR

AFCV AUTO FLOW CONTROL VALVE

AHU AIR HANDLING UNIT

AMP AMPERE

APD AIR PRESSURE DROP

AS AIR SEPARATOR

AV ACID VENT

AW ACID WASTE

B BOILER

BC BLOWER COIL

BD BIDET

BFP BACKFLOW PREVENTER

BFV BUTTERFLY VALVE

BHP BRAKE HORSEPOWER

BLKG BLOCKING

BS BRANCH SELECTOR BOX

BT BATHTUB

BV BALL VALVE

BW BEDPAN WASHER

CH CHILLER

CC COOLING COIL

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CUH CABINET UNIT HEATER

CI CAST IRON

CMU CONCRETE MASONRY UNITS

CR CONDENSER WATER RETURN

CRAC COMPUTER ROOM AIR

CONDITIONER

CS CONDENSER WATER SUPPLY

CSS CLINICAL SERVICE SINKS

CT COOLING TOWER

CU CONDENSING UNIT - SPLIT SYSTEM

CWR CHILLED WATER RETURN

CWS CHILLED WATER SUPPLY

ACC AIR COOLED CONDENSER

ACCU AIR COOLED CONDENSING UNIT

ASHP AIR SOURCE HEAT PUMP

ARU AIR ROTATION UNIT

OI OIL INTERCEPTOR

SOI SAND OIL INTERCEPTOR

SP SUMP PUMP

OST OVERFLOW STORM WATER

WMB WASHING MACHINE BOX

OB OUTLET BOX

RH ROOF HYDRANT

CWP CHILLED WATER PUMP

DB DRY-BULB TEMPERATURE

DCW DOMESTIC COLD WATER

DEG DEGREE

DF DRINKING FOUNTAIN

DGCO DOUBLE GRADE CLEANOUT

DH EMERGENCY DRENCH HOSES

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RECIRCULATING

DI DEIONIZED WATER

DOAS DEDICATED OUTDOOR AIR SYSTEM

DS DISTILLED WATER

DSA DUCT SOUND ATTENUATORS

DSCW DOMESTIC SOFT COLD WATER

DSHW DOMESTIC SOFT HOT WATER

DSHWR DOMESTIC SOFT HOT WATER

RECIRCULATING

DST DOMESTIC STORAGE TANK

DTW DOMESTIC TEPID WATER

DTWR DOMESTIC TEPID WATER

RECIRCULATING

EA. EACH

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EDH ELECTRIC DUCT HEATER

EEW EMERGENCY EYE WASH

EEWS EMERGENCY EYE

WASH/SHOWER

EF EXHAUST FAN

EFF EFFICIENCY

EFW EMERGENCY FACE WASH

EH EXHAUST HOOD

ERV ENERGY RECOVERY

VENTILATOR

ES EMERGENCY SHOWER

ESP EXTERNAL STATIC PRESSURE

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWT ENTERING WATER

TEMPERATURE

ET EXPANSION TANK

F FIRE SUPPRESSION PIPING

F-_ FURNACE

FCO FLOOR CLEANOUT

FC FLUID COOLER

FCU FAN COIL UNIT

FD FIRE DAMPER

FLA FULL LOAD AMPS

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FPM FEET PER MINUTE

FPS FEET PER SECOND

FS FLOOR SINK

FSD FIRE/SMOKE DAMPER

FT FINNED TUBE

G GAS

GCWR GLYCOL CHILLED

WATER RETURN

GCWS GLYCOL CHILLED

WATER SUPPLY

GD GARBAGE DISPOSAL

GDH GAS DUCT HEATER

GHCR GLYCOL HOT/CHILLED

WATER RETURN

GHCS GLYCOL HOT/CHILLED

WATER SUPPLY

GHWR GLYCOL HOT WATER RETURN

GHWS GLYCOL HOT WATER SUPPLY

GI GREASE INTERCEPTOR

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GV GAS VENT

GWH GAS WATER HEATER

HB HOSE BIBB

HC HEATING COIL

HCR HOT/CHILLED WATER RETURN

HCS HOT/CHILLED WATER SUPPLY

DSS DUCTLESS SPLIT SYSTEM

H HUMIDIFIER

DHWP DOMESTIC HOT WATER RECIRCULATING PUMP

DWET DOMESTIC WATER EXPANSION

TANK

HP HORSEPOWER

HPR HIGH PRESSURE RETURN

HPS HIGH PRESURE STEAM

HRC HEAT RECOVERY COIL

HWR HOT WATER RETURN (HEATING)

HWS HOT WATER SUPPLY (HEATING)

HP-_ HEAT PUMP

HVLS HIGH VOLUME LOW SPEED

EUH ELECTRIC UNIT HEATER

HX HEAT EXCHANGER

HY HYDRANTS

IH INTAKE HOOD

IRH INFRARED RADIANT HEATER

KH KITCHEN HOOD

KW KILOWATT

KWH KILOWATT HOURS

L LAVATORY

LAT LEAVING AIR TEMPERATURE

LPR LOW PRESSURE RETURN

LPG LIQUIFIED PETROLEUM GAS

LPS LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LS LAUNDRY SINK

LV LOUVER

LWT LEAVING WATER TEMPERATURE

HWP HOT WATER PUMP

BLV BALANCING VALVE

VRF VARIABLE REFRIGERANT FLOW

P 00 PLUMBING INFO SHEET

P001 DEMOLITION FLOOR PLAN - PLUMBING

P101 FLOOR PLAN - PLUMBING

P401 DETAILS & SCHEDULES - PLUMBING

8/12/26

P001

STORAGE /

LOCKERS

ASSEMBLY

ROOM / DRILL

FLOOR

MECHANICAL

ROOM

STORAGE /

OFFICE

STORAGE

116B

LOCKER / PT

MENS

WOMENS

ENTRY HALL

OFFICE

OFFICE

OFFICE

VEST.

OFFICE

LOBRARY /

CLASSROOM

IT

HALL

CLASSROOM

ARMS VAULT

UNIT STORAGE

/ SUPPLY

ROOM

KITCHEN

STORAGE

112B

KITCHEN

NBC NCO

OFFICE

SUPPLY

OFFICE

STORAGE

VAULT

110SUPPLY ENTRY

108A

MECHANICAL

ROOM

FD (E)

LS (E)MS (E)

WS (E)

WH (E) WH (E)

DWET(E)DWET(E)

SHELVING (E)

ELECTRICAL

HOUSEKEEPING PAD (E)

WATER/FIRE

SERVICE

2 2 3

BRANCH TO HEATING

WATER MAKEUP

7 (TYP.)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

TH

IS

D R

AW

IN

G

IS

B

EI

E

AV

AI

LA

BL

EM

M

ER

F O

R U

SE

O

N T

JE

C T

IN

A

C C

O R

D

AN

C E

W

IT

H S

C H

EM

M

EE

M

EN

T

FE

SS

IO

N

AL

S

ER

VI

C

ES

SC

H

EM

M

ER

A

SS

U M

ES

PO

N

SI

BI

LI

TY

O R

L

IA

BI

A N

Y U

SE

O

F

AW

IN

G O

R A

N Y

PA

R

T

TH

ER

EO

F

EX

C

EP

O

R D

AN

C

E W

IT

H

T H

E

TE

R M

S O

F

TH

E

AB

EE

M

EN

T.

DR

AW

N:

CH

EC

KE

D:

IS

SU

E

DA

TE

PROJECT NO.:

RE

VI

SI

ON

S:

No

DA

TE

BY

DE

SC

RI

PT

IO

N:

DE

SI

GN

ED

ar ch ite ct ur e

| e ng in ee rin g

C:

\U se rs

\aa ris te o\

Do cu m en ts \R ev it_ te m p\

1-

ME

CH

_R

_a ar ist eo

XZ

HQ

L.

rv t 8/9

/20

8:

:4 3 A

M

P001

SO

UT

H

DA

KO

TA

N

AT

IO

NA

L

GU

AR

D

DE

MO

LI

TI

ON

F

LO

OR

P

LA

N

- P

LU

MB

IN

G

W . 3

1S T

ST

YA

NK

TO

N, S

D

011152.001

JE

K

AM

A

AM

A

AU

GU

ST

, 2

RE

PL

AC

E

BO

IL

ER

S

- Y

AN

KT

ON

R

EA

DI

NE

SS

C

EN

TE

R

011152001-5-P001

W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota

8 |

5.3

.78

SO

UT

H

DA

KO

TA

DEMOLITION FLOOR PLAN - PLUMBING

REF. DEMO NOTES ( ):X

1 OWNER TO REMOVE SHELVING.

2 DEMO TANK TYPE WATER HEATER, EXPANSION TANK, AND ASSOCIATED PIPING AS

SHOWN.

3 DEMO HOT WATER RECIRC PUMP AND ASSOCIATED PIPING AS SHOWN.

4 DEMO FLOOR DRAIN, CUT FLOOR AS NEEDED TO FACILITATE THE REMOVAL OF

CORRODED FLOOR DRAIN. PREPARE BELOW GRADE SANITARY PIPE TO RECEIVE NEW

FLOOR DRAIN.

5 EXISTING HOUSEKEEPING PAD WILL NEED TO BE REMOVED. SAWCUT, REMOVE, AND

REPLACE FLOOR AS NEEDED. COORDINATE WITH ARCH.

6 DEMO DCW PIPE AS SHOWN. DEMO TUBING FROM PIPE TO BOILER CONDENSATE TRAP.

7 DEMOLISHED GAS PIPING AND PVC VENTING SHOWN ON MECHANICAL DEMO PLANS.

SCALE: 1/8" = 1'-0"

1 FIRST FLOOR PLAN - DEMO PLUMBING

SCALE: 1/4" = 1'-0"

2 FIRST FLOOR PLAN - DEMO PLUMBING - ENLARGED MECH ROOM

NORTH

P101

STORAGE /

LOCKERS

ASSEMBLY

ROOM / DRILL

FLOOR

MECHANICAL

ROOM

STORAGE /

OFFICE

STORAGE

116B

LOCKER / PT

MENS

WOMENS

ENTRY HALL

OFFICE

OFFICE

VEST.

OFFICE

LOBRARY /

CLASSROOM

IT

HALL

CLASSROOM

ARMS VAULT

UNIT STORAGE

/ SUPPLY

ROOM

KITCHEN

STORAGE

112B

KITCHEN

NBC NCO

OFFICE

SUPPLY

OFFICE

STORAGE

VAULT

110SUPPLY ENTRY

108A

OFFICE

MECHANICAL

ROOM

GW

H-

GW

H-

GW

H-

DW

ET

-1

DH

W P-

WS (E)

LS (E)MS (E)

FD-1

ELECTRICAL

WATER/FIRE

SERVICE

HB-1

1 (TYP.)

P101

(REF.)

7'-3"

1/2 " D

CW

1 1 /4"

D

HW

1 1 /4"

D

CW

1 1 /4"

D

HW

1/2 " D

HW

R

WATER SOFTENER

SEE ISOMETIC VIEWS ON SHEET

M401 FOR MORE INFORMATION.

4 4

FIRST FLOOR

100' - 0"

LOWER ROOF

111' - 8 7/8"

F

F F

F

WATER SERVICE

AND METER

WATER

SOFTENER

GW

H-

GW

H-

GW

H-

DW

ET

-1

DHWP-1

G

1 1/4" DHW

1 1/4" DCW

1 1/4" DHW

1/2" DHWR

SEE WATER HEATER PIPING

DETAIL ON SHEET P401 FOR

MORE INFORMATION

3/4" DCW

3/4" DHW

G

(T

YP

2 Ø COMB. AIR

2 Ø FLUE GAS (T

YP

DC

WG

DH

W

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

TH

IS

D R

AW

IN

G

IS

B

EI

E

AV

AI

LA

BL

EM

M

ER

F O

R U

SE

O

N T

JE

C T

IN

A

C C

O R

D

AN

C E

W

IT

H S

C H

EM

M

EE

M

EN

T

FE

SS

IO

N

AL

S

ER

VI

C

ES

SC

H

EM

M

ER

A

SS

U M

ES

PO

N

SI

BI

LI

TY

O R

L

IA

BI

A N

Y U

SE

O

F

AW

IN

G O

R A

N Y

PA

R

T

TH

ER

EO

F

EX

C

EP

O

R D

AN

C

E W

IT

H

T H

E

TE

R M

S O

F

TH

E

AB

EE

M

EN

T.

DR

AW

N:

CH

EC

KE

D:

IS

SU

E

DA

TE

PROJECT NO.:

RE

VI

SI

ON

S:

No

DA

TE

BY

DE

SC

RI

PT

IO

N:

DE

SI

GN

ED

ar ch ite ct ur e

| e ng in ee rin g

C:

\U se rs

\aa ris te o\

Do cu m en ts \R ev it_ te m p\

1-

ME

CH

_R

_a ar ist eo

XZ

HQ

L.

rv t 8/9

/20

8:

:4 5 A

M

P101

SO

UT

H

DA

KO

TA

N

AT

IO

NA

L

GU

AR

D

FL

OO

R

PL

AN

PL

UM

BI

NG

W . 3

1S T

ST

YA

NK

TO

N, S

D

011152.001

JE

K

AM

A

AM

A

AU

GU

ST

, 2

RE

PL

AC

E

BO

IL

ER

S

- Y

AN

KT

ON

R

EA

DI

NE

SS

C

EN

TE

R

011152001-5-P101

W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota

8 |

5.3

.78

SO

UT

H

DA

KO

TA

FLOOR PLAN - PLUMBING

REF. NOTES ( ):X

1 GAS PIPING AND PVC VENTING SHOWN ON MECHANICAL PLANS.

2 CONNECT NEW FLOOR DRAIN TO EXISTING BELOW GRADE SANITARY PIPE. PATCH

CONCRETE FLOORING AROUND DRAIN. SLOPE AS REQUIRED.

3 SURFACE MOUNT PIPING TO NEW HOSE BIB. BIB TO BE 4' 6" AFF.

4 THIS SPACE IS RESERVED FOR ELECTRICAL EQUIPMENT. NO PIPING OR DUCTWORK

SHALL PASS BELOW, ABOVE, OR AROUND ELECTRICAL EQUIPMENT. PROVIDE CODE

REQUIRED MINIMUM CLEARANCE ABOVE ELECTRICAL EQUIPMENT ACCESS SPACE.

5 DOMESTIC HOT WATER RECIRCULATION PUMP SHALL BE ENABLED BASED ON THE

BUILDING AUTOMATION SYSTEM (BAS) OCCUPANCY SCHEDULE. THE DOMESTIC HOT

WATER RECIRCULATION LOOP TEMPERATURE SHALL BE MONITORED BY THE BAS. THE

BAS SHALL START THE RECIRCULATION PUMP WHENEVER THE LOOP TEMPERATURE

FALLS BELOW THE ADJUSTABLE LOOP TEMPERATURE SETPOINT AND STOP THE PUMP

WHEN THE LOOP TEMPERATURE RISES ABOVE THE SETPOINT (ADJUSTABLE DEADBAND

TO BE PROVIDED). ALL CONTROLS BY SCHNEIDER ELECTRIC.

SCALE: 1/8" = 1'-0"

1 FIRST FLOOR PLAN - PLUMBING

SCALE: 1/4" = 1'-0"

2 FIRST FLOOR PLAN - PLUMBING - ENLARGED MECH ROOM

NORTH

SCALE: 1/4" = 1'-0"

3 SECTION VIEW AT WATER HEATERS

INSULATION

THREADED ROD

INSULATION

THREADED ROD

HANGER NOT

SWALLOWED BY

INSULATION

PIPE, 1"Ø MAX

BAND

THREADED

ROD

HANGER

INSULATION

PIPE

SHIELD TO COVER 180°

OF PIPE, SEE CHART FOR

LENGTH

SEE CHART

SHIELD LENGTH

SEE CHART

SHIELD LENGTH,

SWIVEL

a.

b.

c.

d.

e.

SHIELD LENGTH FOR PIPE - NOT LESS THAN THE FOLLOWING:

NPS 1/4" TO 3-1/2" 12" LONG AND .048" THICK

NPS 4" 12" LONG AND .06" THICK

NPS 5" TO 6" 18" LONG AND .06" THICK

NPS 8" TO 14" 24" LONG AND .075" THICK

NPS 16" TO 24" 24" LONG AND .105" THICK

1.

2.

NOTE:

PIPES NPS 8" AND LARGER: INCLUDE WOOD OR REINFORCED CALCIUM-SILICATE-INSULATION INSERTS OF LENGTH AT LEAST AS LONG

AS PROTECTIVE SHIELD.

THERMAL-HANGER SHIELDS: INSTALL WITH INSULATION SAME THICKNESS AS PIPING INSULATION.

SHIELD TO COVER 180°

OF PIPE, SEE CHART FOR

LENGTH

SHIELD TO COVER 180°

OF PIPE, SEE CHART FOR

LENGTH

THREADED ROD

U-BOLT

UNISTRUT OR STEEL ANGLE

WITH LONG LEG DOWN

PIPE

ISOLATION

VALVE (TYP.)

PRESSURE

GAUGE

PUMP

SUPPORT PUMP

SEPARATE FROM

PIPING

CHECK

VALVE

STRAINER

UNION

(TYP.)

STRUCTURAL SLAB

FLOOR DRAIN

FLOOR DRAIN

STRUCTURAL SLAB

3'x3' WATERPROOF

MEMBRANE

2" FINISH SLAB BY

OTHERS

CHLORALOY MEMBRANE

SLAB ON-GRADE

APPLICATIONS

SLAB ABOVE GRADE

APPLICATIONS

DOMESTIC COLD

WATER IN

NATURAL GAS IN

DOMESTIC HOT WATER OUT

GWH-1GWH-2GWH-3

EXHAUST AND INTAKE

CONNECTION SIZES AND

LOCATIONS MAY VARY

BETWEEN MANUFACTURERS.

EXHAUST VENT

COMBUSTION AIR INTAKE

EXHAUST NON-RETURN VALVE WITH

MANUFACTURER RECOMMENDED

CONDENSATE TRAP (TYPICAL)

0.25":12"

CONNECTION SIZES AND

LOCATIONS MAY VARY

BETWEEN MANUFACTURERS.

RELIEF VALVE

(TYPICAL)

PIPE TO DRAIN

(TYPICAL)

DRAIN VALVE (TYPICAL)

CONDENSATE OUT

(TO FLOOR DRAIN)

SHUTOFF VALVE (TYPICAL)

CONDENSATE DRAIN

WITH MANUFACTURER

RECOMMENDED TRAP.

1.

2.

NOTE:

INSTALLATION SHALL COMPLY WITH ALL LOCAL CODES AND WITH MANUFACTURER RECOMMENDATIONS AND SPECIFICATIONS.

COLD AND HOT WATER PIPING TO BE ROUTED IN A "FIRST IN, LAST OUT" CONFIGURATION.

VENTING SIZES AND MATERIAL AS PER

MANUFACTURER RECOMMENDATIONS

1-1/4"

1-1/4"

1-1/4"

INLET TEE

WALL

CONDENSATE NEUTRALIZER,

CONFIGURE PER MANUFACTURER

RECOMMENDATIONS (TYPICAL)

EXPANSION

TANK

DW

ET

-1

DOMESTIC HOT WATER

RECIRCULATION

1/2

DHWP-1

CHECK VALVE

(TYPICAL)

1" 0.125":12"

1-1/4"

1-1/4"

1-1/4"

PROVIDE SEPARATION PER

CODE AND MANUFACTURER

REQUIREMENTS

TEMP GAUGE

TEMP GAUGE

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

1-1/4" 1-1/4"1-1/4"

3/4

3/4

3/4

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

TH

IS

D R

AW

IN

G

IS

B

EI

E

AV

AI

LA

BL

EM

M

ER

F O

R U

SE

O

N T

JE

C T

IN

A

C C

O R

D

AN

C E

W

IT

H S

C H

EM

M

EE

M

EN

T

FE

SS

IO

N

AL

S

ER

VI

C

ES

SC

H

EM

M

ER

A

SS

U M

ES

PO

N

SI

BI

LI

TY

O R

L

IA

BI

A N

Y U

SE

O

F

AW

IN

G O

R A

N Y

PA

R

T

TH

ER

EO

F

EX

C

EP

O

R D

AN

C

E W

IT

H

T H

E

TE

R M

S O

F

TH

E

AB

EE

M

EN

T.

DR

AW

N:

CH

EC

KE

D:

IS

SU

E

DA

TE

PROJECT NO.:

RE

VI

SI

ON

S:

No

DA

TE

BY

DE

SC

RI

PT

IO

N:

DE

SI

GN

ED

ar ch ite ct ur e

| e ng in ee rin g

C:

\U se rs

\aa ris te o\

Do cu m en ts \R ev it_ te m p\

1-

ME

CH

_R

_a ar ist eo

XZ

HQ

L.

rv t 8/9

/20

8:

:4 6 A

M

P401

SO

UT

H

DA

KO

TA

N

AT

IO

NA

L

GU

AR

D

DE

TA

IL

S

SC

HE

DU

LE

S

- P

LU

MB

IN

G

W . 3

1S T

ST

YA

NK

TO

N, S

D

011152.001

JE

K

AM

A

AM

A

AU

GU

ST

, 2

RE

PL

AC

E

BO

IL

ER

S

- Y

AN

KT

ON

R

EA

DI

NE

SS

C

EN

TE

R

011152001-5-P401

W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota

8 |

5.3

.78

SO

UT

H

DA

KO

TA

DETAILS & SCHEDULES - PLUMBING

2. PROVIDE WITH MPT (CP STYLE) INLET.

NOTES: 1. PROVIDE NICKEL BRONZE ROUND STRAINER, PROVIDE 3" OUTLET SIZE TO MATCH EXISTING - CONFIRM IN FIELD PRIOR TO ORDERING.

HB-1 HOSE BIBB -- 1/2" -- -- -- ~54" A.F.F. -- WOODFORD 24 -- -- -- 2

FD-1 FLOOR DRAIN -- -- 3" -- -- FLOOR -- ZURN Z415B -- -- -- 1

HOT

WATER

COLD

WATER WASTE VENT OTHER FIXTURE FAUCET/FLUSH VALVE ACCESSORY #1 ACCESSORY #2 REMARKSMARK DESCRIPTION

FIXTURE CONNECTIONS

MOUNTING

HEIGHT

FLOW

RATE

MANUFACTURER AND MODEL NUMBER

PLUMBING FIXTURE SCHEDULE

2. PROVIDE WITH 3/4" CONNECTION SIZE.

NOTES: 1. PUMP TO BE CONTROLLED BROM BAS BASED ON OCCUPANCY SCHEDULE AND LOOP TEMPERATURE.

DHWP-1 MECHANICAL 115 DHW INLINE HOT WATER 2.5 30 3250 1/8 115 1 60 BAS TACO 009-SF5 1, 2

TYPE RPM HP VOLTS PH HZ TYPEMARK LOCATION SERVES TYPE

FLUID FLOW

GPM

HEAD FT

WG

ELECTRICAL DATA CONTROL MANUFACTURER AND

MODEL NUMBER REMARKS

PUMP SCHEDULE

4. MANIFOLD AND LINK UNITS TOGTHER USING CASCADE MODE.

3. PROVIDE WITH WATER HEATER SERVICE VALVE KIT- WEBSTONE 4444 SERIES OR EQUIVALENT, 150 PSI RATED PRESSURE RELIEF VALVE.

2. PROVIDE UNIT WITH CONDENSATE NEUTRALIZATION KIT. PIPE CONDENSATE TO NEAREST FLOOR DRAIN.

NOTES: 1. PROVIDE COMMON VENT PER MANUFACTURER RECOMMENDATIONS. PROVIDE NON-RETURN VALVES ON VENTING AS REQUIRED.

GWH-3 MECH 115 NG 199 4.9 10 40 120 TANKLESS 120 1 2 BRADFORD WHITE RTGS199N1 1, 2, 3, 4 GWH-2 MECH 115 NG 199 4.9 10 40 120 TANKLESS 120 1 2 BRADFORD WHITE RTGS199N1 1, 2, 3, 4 GWH-1 MECH 115 NG 199 4.9 10 40 120 TANKLESS 120 1 2 BRADFORD WHITE RTGS199N1 1, 2, 3, 4

VOLT PHASE FLAMARK LOCATION

GAS

TYPE

INPUT

RATING

(MBH)

DESIGN

FLOW RATE

AT TEMP

RISE (GPM)

PRESSURE

DROP AT

DESIGN FLOW

RATE (PSI)

EWT

(°F)

LWT

(°F)

STORAGE

CAPACITY

(GALLONS)

ELECTRICAL DATA

BASIS OF DESIGN REMARKS

INSTANTANEOUS GAS-FIRED WATER HEATER SCHEDULE

2. SUPPORT INDEPENDENTLY FROM PIPING.

NOTES: 1. INSTALL AT COLD WATER INLET HEADER TO TANKLESS WATER HEATERS.

DWET-1 GWH-1 / 2 / 3 MECH 115 DIAPHRAGM 16 40 - 120 MATCH SYSTEM PRESSURE (~48 PSI) 150 2.0 AMTROL ST-5 1, 2

MARK SERVES LOCATION TYPE

TOTAL

SYSTEM

VOLUME

(GAL)

TEMP

RANGE (°F) FILL PRESSURE (PSIG)

MAX OPER.

PRESSURE

(PSIG)

TANK

VOLUME

(GAL) BASIS OF DESIGN REMARKS

EXPANSION TANK SCHEDULE

SCALE: NOT TO SCALE

2 PIPE HANGER DETAIL

SCALE: NOT TO SCALE

1 IN-LINE PUMP DETAIL

SCALE: NOT TO SCALE

3 FLOOR DRAIN DETAIL

SCALE: NOT TO SCALE

4 INSTANTANEOUS HOT WATER HEATER DETAIL

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND LIMITED

FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS

AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR

VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST

TO ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.

ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO

DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA

COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.

CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE FOR

SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL

EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER

TRADES AFFECTED.

SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN. FULL-TONE

LINES INDICATED NEW OR RELOCATED CONSTRUCTION.

CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH STRUCTURE,

CEILING, LIGHTING, AND PIPING.

MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL EQUIPMENT TO ALLOW

FOR MAINTENANCE ACCESS.

ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT ANGLES AND PARALLEL

TO BUILDING WALLS UNLESS OTHERWISE INDICATED.

DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS. MAINTAIN ALL CODE

REQUIRED CLEARANCES.

IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL REASONABLY

BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL

WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY

STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE

RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND CONTRACTOR.

ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING CONSTRUCTION SHALL BE

COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.

A.

B.

C.

D.

E.

F.

G.

H.

THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL DRAWINGS

PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION. DIMENSIONS AND EXISTING

CONDITIONS ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING

CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR SALVAGED

ARE SHOWN AS FULL-TONE LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE

AND ARE SHOWN AS HALF-TONE.

DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED BELOW OR HERE-

IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW

CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE

DEMOLITION REQUIRED AND AS LISTED BELOW.

THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING EQUIPMENT FROM FINISHED

AREAS AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL

PLANS AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING TO ENSURE

PROPER PATCHING AND REPAIR IS MADE TO THE BUILDING.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL

EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT,

INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST

RIGHT OF REFUSAL ON ALL ITEMS.

ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE CAREFULLY

REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND STORED OR REINSTALLED ON THE

SITE AS DIRECTED. REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE

OWNER.

COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND CONTROLS WITH

ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL REMOVALS.

IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL REASONABLY

BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL

WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY

STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND

ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE

RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND ARCHITECT.

ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION SHALL BE

COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

A

B

C

D

E

F

G

H

J

K

L

M

N

P

A

B

C

D

E

F

G

H

J

K

L

M

N

P

TH

IS

D R

AW

IN

G

IS

B

EI

E

AV

AI

LA

BL

EM

M

ER

F O

R U

SE

O

N T

JE

C T

IN

A

C C

O R

D

AN

C E

W

IT

H S

C H

EM

M

EE

M

EN

T

FE

SS

IO

N

AL

S

ER

VI

C

ES

SC

H

EM

M

ER

A

SS

U M

ES

PO

N

SI

BI

LI

TY

O R

L

IA

BI

A N

Y U

SE

O

F

AW

IN

G O

R A

N Y

PA

R

T

TH

ER

EO

F

EX

C

EP

O

R D

AN

C

E W

IT

H

T H

E

TE

R M

S O

F

TH

E

AB

EE

M

EN

T.

DR

AW

N:

CH

EC

KE

D:

IS

SU

E

DA

TE

PROJECT NO.:

RE

VI

SI

ON

S:

No

DA

TE

BY

DE

SC

RI

PT

IO

N:

DE

SI

GN

ED

ar ch ite ct ur e

| e ng in ee rin g

C:

\U se rs

\aa ris te o\

Do cu m en ts \R ev it_ te m p\

1-

ME

CH

_R

_a ar ist eo

XZ

HQ

L.

rv t 8/9

/20

8:

:4 7 A

M

M 00

SO

UT

H

DA

KO

TA

N

AT

IO

NA

L

GU

AR

D

ME

CH

AN

IC

AL

IN

FO

S

HE

ET

W . 3

1S T

ST

YA

NK

TO

N, S

D

011152.001

JE

K

AM

A

AM

A

AU

GU

ST

, 2

RE

PL

AC

E

BO

IL

ER

S

- Y

AN

KT

ON

R

EA

DI

NE

SS

C

EN

TE

R

011152001-6-M 00

W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota

8 |

5.3

.78

SO

UT

H

DA

KO

TA

MECHANICAL INFO SHEET

NORTH

ARROW

SYMBOL LEGEND ABBREVIATIONS

MATCHLINE AREA A

AREA B

EXISTING

COLUMN

NEW COLUMN

X

X

X

XXXX

SIM/OPP

X

XXXX

XX-1

X

X

SECTION/

DETAIL

PLAN

DETAIL

REFERENCE NOTE

REFERENCE

DEMOLITION NOTE

EQUIPMENT

NUMBER

ROOM NAME

ROOM / SPACE

NUMBER

LETTER/NUMBER INDICATES NEW

COLUMN LINE

LETTER/NUMBER INDICATES

EXISTING COLUMN LINE

SECTION/DETAIL NUMBER

SHEET NUMBER

INDICATES DIRECTION OF VIEW

DETAIL NUMBER

SHEET NUMBER

REFERENCE

DESIGNATION

DEMOLITION

DESIGNATION

EQUIPMENT

NUMBER

ROOM NAME DESIGNATION

ROOM NUMBER DESIGNATION

REFERENCE LEGEND

NAME

ELEVATION

LEVEL

TITLE

MARKER 1

VIEW NAME

SCALE: 1/8" = 1'-0"

DRAWING/DETAIL NUMBER

LEVEL CALLOUT DESIGNATION

ELEVATION DESIGNATION

GRAPHIC AREA FOR DRAWING

TITLE

SCALE OF THE DRAWING

VOLUME DAMPER

DEMO TO EXISTING CONNECTION

SPRINKLER DRAIN

FIRE SUPPRESSION PIPING

ISOLATION VALVE

TAMPER SWITCH

MANUAL BALANCING VALVE

FLOW SWITCH

FIRE DEPARTMENT CONNECTION

CONTROL VALVE (3 WAY)

CONTROL VALVE (2 WAY)

HOSE END DRAIN VALVE

PRESSURE REDUCING VALVE

AUTO FLOW CONTROL VALVE

CHECK VALVE

HVAC DUCTWORK AND SPECIALTIES (CONT.)

MISCELLANEOUS SYMBOLS

RETURN DUCT DOWN

AIR TERMINAL (VERTICAL MOUNTING)

ROUND DUCT UP / DOUBLE LINE PIPE

ROUND DUCT DOWN / DOUBLE LINE

PIPE

RETURN DUCT UP

TURNING VANES

SUPPLY AND FRESH AIR DUCT DOWN

SUPPLY AND FRESH AIR DUCT UP

SIZE/TYPE

SIZE/TYPE

FLOW

FLOW

SIZE/TYPE

FLOW

SMOKE DAMPER

FIRE DAMPER-HORIZ FIRE SEPARATION

MOTORIZED DAMPER-OPPOSED BLADE

MOTORIZED DAMPER-PARALLEL BLADE

ROUND AIR TERMINAL

(HORIZONTAL MOUNTING)

GRAVITY DAMPER

(OR) SAFETY VALVE-STEAM

TEMP & PRESS RELIEF

FLOOR SINK

FLOOR DRAIN

GRADE CLEANOUT

PLUMBING VENT THRU ROOF

CLEANOUT / WALL CLEANOUT

THERMOSTATIC MIXING VALVE

M

M

MANHOLE

TRENCH DRAIN

OVERFLOW ROOF DRAIN

OXYGEN OUTLET

PIPE CAP

ELBOW UP

AIR OUTLET

TEE

ELBOW DOWN

VACUUM OUTLET

ROOF DRAIN

SIZE/TYPE

FLOW

HUMIDISTAT

THERMOSTAT

FLEXIBLE DUCT

S

H

T

TEMPERATURE SENSOR

UNION

TEE DOWN

STRAINER

EXPANSION JOINT

FLEXIBLE PIPE CONNECTION

AIR VENT

TEE UP

FIRE/SMOKE DAMPER

RECTANGULAR RETURN AIR TERMINAL

(HORIZONTAL MOUNTING)

RECTANGULAR SUPPLY AIR TERMINAL

(HORIZONTAL MOUNTING)

SOLENOID VALVE

F D

TS

VALVES

FS

M

M

S

LPR

HPS

MPR

MPS

LPS

HVAC PIPING

GHWR

GHWS

HWR

HWS

PC

HPR

ES

BBD BOILER BLOW DOWN

EXHAUST STEAM

PUMPED CONDENSATE

HIGH PRESSURE RETURN

HIGH PRESSURE…