About this file
This is a set of 100% construction drawings for the South Dakota National Guard project to replace boilers at the Yankton Readiness Center located at 1204 W. 31st Street, Yankton, SD 57078 (Project No. 011152.001). The project involves the complete demolition and replacement of the existing boiler system, domestic hot water system, and associated mechanical and plumbing infrastructure. The drawings include architectural, plumbing, mechanical, and electrical plans with detailed specifications for new equipment installation, including two Aerco Benchmark 750 gas-fired hot water boilers, three Bradford White tankless gas water heaters (199 MBH each), domestic hot water recirculation pumps, expansion tanks, air separators, and related piping systems. The project incorporates building automation system (BAS) controls by Schneider Electric and requires coordination among multiple trades including mechanical, plumbing, and electrical contractors. The drawings are dated August 12, 2026, and were prepared by Schemmer architecture and engineering firm based in Sioux Falls, South Dakota.
The construction documents specify detailed demolition requirements, new equipment schedules, piping configurations using 30% propylene glycol, gas piping sizing for approximately 3,116 MBH total connected load at 2.0 PSI, and BAS integration for boiler sequencing and system control. The project requires contractors to field-verify existing conditions, coordinate with all trades, maintain hazardous material protocols, properly support and install all equipment per manufacturer specifications, and ensure proper commissioning and balancing of the heating system. The documents emphasize contractor responsibility for accurate measurements, field condition adjustments at no additional cost to the owner, protection of existing finishes, and restoration of all disturbed surfaces. All mechanical systems are configured for variable primary flow operation with pressure differential-based pump control, and the project includes provisions for glycol feeder systems, condensate neutralization, and emergency shutoff switches as required by code.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Addendum 1 document.pdf | ||
| 011152001 - REPLACE BOILERS YANKTON READINESS CENTER - PROJECT MANUAL.pdf | ||
| IFB Document.pdf | ||
| Plan Holders List.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
PROJECT LOCATION MAP
NORTH
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
T H
IS
D
R A
W
IN
G I S
B E
IN
G
M
A D
E A
V A
IL
A
B L E
B Y
S
C H
E M
M E
R F
O R
U S
E O
N T
H
IS
P
R O
J E
C T
I N
A C
C O
R D
A N
E
W
IT
H
S C
H E
M M
E
'S
R E
E M
E N
T F
O
O
F E
S S
IO
N
A L S
E R
V
IC
E
H E
M M
E R
A S
S U
M E
S N
S P
O N
S
IB
IL
IT
Y O
R L
IA
B
IL
F
R A
N Y
U S
E O
F T
D
A
W
IN
G O
R A
N Y
P A
T
E
R E
O F
E X
C E
P T
I
C
O R
D A
N C
E W
IT
H
T
R M
S O
F T
H E
A B
O V
R E
E M
E N
T
D R
A W
N
C H
E C
K E
D
IS
S
U E
D A
T E
PROJECT NO.:
R E
V
IS
IO
N
S
N o
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
D E
S
IG
N E
D a rc h it e c tu re e n g in e e ri n g
C
U se rs \r g u n n in k\
D o cu m en ts
\0
-A
R C
H _R
_r g u n n in k.
rv t
8/
/2
9:
:1
A
M
G001
S O
U T
H D
A K
O T
A N
A T
IO
N
A L
G U
A R
D
T
IT
L E
S H
E E
T
W . 3
1S T
S T
Y A
N K
T O
N , S
D
011152.001
A u th o r
D es ig n er A
U G
U S
T
2, R E
P L
A C
E B
O
IL
E R
S
Y A
N K
T O
N R
E A
D
IN
E S
S C
E N
T E
R
SOUTH DAKOTA NATIONAL GUARD
REPLACE BOILERS - YANKTON READINESS CENTER
1204 W. 31ST ST
YANKTON, SD 57078
100% CONSTRUCTION DRAWINGS
AUGUST 12, 2026
SOUTH DAKOTA
CFMO #466422
011152001-0-G001
W
7t h
S tr ee t, S ui te
2, S io ux
F al ls , S ou th
D ak ot a
| 6
.3
.7
S O
U T
H D
A K
O T
A
TITLE SHEET
ARCHITECTURAL
A 00 ARCHITECTURAL INFO SHEET
GENERAL
G001 TITLE SHEET
DRAWING INDEX
PLUMBING
P 00 PLUMBING INFO SHEET
P001 DEMOLITION FLOOR PLAN - PLUMBING
P101 FLOOR PLAN - PLUMBING
P401 DETAILS & SCHEDULES - PLUMBING
MECHANICAL
M 00 MECHANICAL INFO SHEET
M001 DEMOLITION FLOOR PLAN - MECHANICAL
M101 FLOOR PLAN - MECHANICAL
M301 ENLARGED PLAN & SECTION - MECHANICAL
M401 DETAILS - MECHANICAL
M501 GAS RISER & SCHEDULES - MECHANICAL
ELECTRICAL
E 00 ELECTRICAL INFO SHEET
E201 FLOOR PLAN - POWER & AUXILIARY SYSTEMS
E601 EQUIPMENT & PANEL SCHEDULES
08/12/2026
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
T H
IS
D
R A
W
IN
G I S
B E
D
E A
V A
IL
A
B L E
H
E M
M E
R F
O R
U S
E O
N T
O
J E
C T
I N
A C
C O
R D
A N
H
S C
H E
M M
E
R E
E M
E N
T F
O
F E
S S
IO
N
A L S
E R
V
IC
E
H E
M M
E R
A S
S U
M E
S
S P
O N
S
IB
IL
IT
Y O
R L
IA
B
IL
R A
N Y
U S
E O
F T
A
W
IN
G O
R A
N Y
P A
E
R E
O F
E X
C E
P T
C
O R
D A
N C
E W
IT
H
T
R M
S O
F T
H E
A B
O
R E
E M
E N
T
D R
A W
N
C H
E C
K E
D
IS
S
U E
D A
T E
PROJECT NO.:
R E
V
IS
IO
N
S
N o
D
A T
E
B Y
D
E S
C R
IP
T
IO
N
D E
S
IG
N E
D a rc h it e c tu re e n g in e e ri n g
C
U se rs \r g u n n in k\
D o cu m en ts
\0
-A
R C
H _R
_r g u n n in k.
rv t
8/
/2
9:
:1
A
M
A 00
S O
U T
H D
A K
O T
A N
A T
IO
N
A L
G U
A R
D
A R
C H
IT
E
C T
U R
A L
IN
F
O S
H E
E T
W . 3
1S T
S T
Y A
N K
T O
N , S
D
011152.001
R
JM
L A
S
R T
G A
U G
U S
T
2, R E
P L
A C
E B
O
IL
E R
S
Y A
N K
T O
N R
E A
D
IN
E S
S C
E N
T E
R
011152001-2-A 00_Rev 1
W
7t h
S tr ee t, S ui te
2, S io ux
F al ls , S ou th
D ak ot a
| 6
.3
.7
S O
U T
H D
A K
O T
A
ARCHITECTURAL INFO SHEET
NORTH
ARROW
NAME
ELEVATION
LEVEL
MATCHLINE
AREA A
AREA B
TITLE
MARKER
VIEW NAME
SCALE: 1/8" = 1'-0"
EXISTING
COLUMN
NEW
COLUMN
X
X
X
XX-XX
SIM
X
XX-XX
XXXX
DX
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE
NOTE
REFERENCE
DEMOLITION
NOTE
EQUIPMENT
NUMBER
ROOM NAME
150 SF
ROOM
NUMBER
LETTER INDICATES
NEW COLUMN LINE
LETTER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL
NUMBER
SHEET NUMBER
INDICATES DIRECTION
OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME
DESIGNATION
ROOM NUMBER
DESIGNATION
ROOM AREA
DESIGNATION
SYMBOL LEGEND
ROOM /
FRAMING
ELEVATION
EXTERIOR
ELEVATION
XX-XX
XX-XX
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
ELEVATION LETTER
DIRECTION OF VIEW
SHEET NUMBER
DOOR
NUMBER
DOOR NUMBER10
WINDOW
DESIGNATION
WINDOW DESIGNATION000
TA-X
TOILET
ACCESSORY
TOILET ACCESSORY
NUMBER
WALL
TYPE
LETTER
INDICATES
PARTITION OR
WALL TYPE
X
DETAIL NUMBER
LEVEL CALLOUT
DESIGNATION
ELEVATION
DESIGNATION
GRAPHIC AREA FOR
DRAWING
TITLE
SCALE OF THE
DRAWING
ABBREVIATIONS REF. DEMO NOTES ( )
REFERENCE LEGEND
PLAN VIEW
SECTION / ELEVATION VIEW
SHEAR WALL
MASONRY-CMU
MASONRY-VENEER
STUD WALL
CONCRETE
GRAVEL
EARTH / COMPACTED
EARTH /
NONCOMPACTED
RIGID INSULATION
JOINT FILLER
STEEL
GYPSUM
FLEXIBLE INSULATION
GROUT
PLYWOOD
WOOD (FINISH)
MASONRY-CMU FACE
MASONRY-CMU
MASONRY-VENEER
ARCHITECTURAL SHEET LIST
PROJECT ARCHITECTURAL REFERENCED DEMOLITION NOTES
GENERAL NOTES XDXGENERAL DEMO NOTES
PROJECT ARCHITECTURAL REFERENCED NOTES
REF. NOTES ( )
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SB SECURITY BARS
SB SPLASH BLOCK
SCH SCHEDULE
SCHED SCHEDULE
SCR SCREW
SCT STRUCTURAL CLAY TILE
SCUT SCUTTLE
SCW SOFT COLD WATER
SD STORM DRAIN
SD SUBDRAIN
SDI STEEL DECK INSTITUTE
SECT SECTION
SECY SECRETARY
SEQ SEQUENCE
SF SQUARE FOOT (FEET)
SFU STRUCTURAL FACING
UNIT
SHLD SHOULDER
SHT SHEET
SHTG SHEATHING
SHW SOFT HOT WATER
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SL SNOW LOAD
SLBB SHORT LEG BACK TO
BACK
SM SPRINKLER MAIN
SOV SHUT OFF VALVE
SPA SPACE(ING)
SPEC SPECIFICATIONS
SPF SOUNDPROOF
SPH SPACE HEATER
SPKR SPEAKER
SPL SPECIAL
SQ SQUARE
SS SANITARY SEWER
SS STAINLESS STEEL
SSMR STANDING SEAM METAL
ROOFING
STA STATION
STAIR STAIRWAY
STC SOUND TRANSMISSION
COEFFICIENT
STD STANDARD
STGR STRINGER
STIFF STIFFENER
STIRR STIRRUPS
STL STEEL
STN STONE
STOR STORAGE
STR STRUCTURAL
SUB FL SUB FLOOR
SUCT SUCTION
SUSP SUSPENDED
SVF SHEET VINYL FLOORING
SW SWITCH
SWBD SWITCH BOARD
SYM SYMMETRICAL
T TREAD
T or TLT TOILET
TAN TANGENT
TBD TACK BOARD
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TERM TERMINAL
TGL TOGGLE
TH THRESHOLD
THK THICK
THRD THREAD
TO TOP OF
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOPO TOPOGRAPHIC
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSVERSE
TSTAT THERMOSTAT
TV TELEVISION
TW TEMPERED WATER
TWR TEMPERED WATER
RETURN
TYP TYPICAL
UC UNIT COOLER
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UPS UNINTERRUPTIBLE
POWER SYSTEM
UR URINAL
UT UTILITY
UV UNIT VENTILATOR
V VOLT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VD VAULT DOOR
VEL VELOCITY
VENT VENTILATOR(ION)
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY
DRIVE
VOL VOLUME
VPC VERTICAL POINT OF
CURVATURE
VPI VERTICAL POINT OF
INTERSECTION
VPT VERTICAL POINT OF
TANGENCY
VS VENT STACK
VT VINYL-TILE
VTR VENT THRU ROOF
VWC VINYL WALL COVERING
W WEST
W WIDE (WIDTH)
W WIRE
W/ WITH
W/O WITHOUT
WB WET BULB
WC WATER CLOSET
WC WATER COLUMN
WD WASTE DRAIN
WD WOOD
WD BLKG WOOD BLOCKING
WD DR WOOD DOOR
WDW WINDOW
WF WIDE FLANGE
WG WIRE GLASS
WH WALL HYDRANT
WHT WHITE
WI WROUGHT IRON
WKSH WORK SHOP
WL WIND LOAD
WNSCT WAINSCOT
WP WEATHER PROOF
WP WORK POINT
WPF WATER PROOF
WPFG WATER PROOFING
WRB WARDROBE
WS WASTE STACK
WT WEIGHT
WWF WELDED WIRE FABRIC
WWM WOVEN WIRE MESH
XFMR TRANSFORMER
YD YARD or YARD DRAIN
LBS POUNDS
LD LOAD
LDG LOADING
LE LEFT END
LG LENGTH (LONG)
LIN LINEAR
LIS LAWN IRRIGATION
SYSTEM
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LNTL LINTEL
LP LOW POINT
LPG LIQUIFIED PETROLEUM
GAS
LPS LOW PRESSURE STEAM
LR LIVING ROOM
LS LAWN SPRINKLER
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LVT LUXURY VINYL TILE
M MIDDLE
M THOUSAND
M & B MATCHED AND BEADED
MA MAKE-UP AIR
MACH MACHINE
MAS MASONRY
MAT or
MATL
MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBH 1000 BTUH
MC MEDICINE CABINET
MC MISCELLANEOUS
CHANNELS
MECH MECHANICAL
MER MECHANICAL EQUIPMENT
ROOM
MET METAL
MFG MANUFACTURING
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
ML METAL LATH
MLDG MOULDING
MO MASONRY OPENING
MONO MONOLITHIC
MT METAL THRESHOLD
MTD MOUNTED
N NORTH
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFPA NATIONAL FIRE
PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NR NOT REQUIRED
NS NEAR SIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OB WG OBSCURE WIRE GLASS
OBGL OBSCURE GLASS
OBSC OBSCURE
OC ON CENTER(S)
OCEW ON CENTER EACH WAY
OD OUTSIDE DIAMETER
OFF OFFICE
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPS OPERATIONS
OS & Y OUTSIDE SCREW & YOKE
OSF OUTSIDE FACE
OV OVERFLOW VALVE
OX OXYGEN
OZ OUNCE
P PAINT
PA PUBLIC ADDRESS
PBS PUSH BUTTON STATION
PC PIECE
PC POINT OF CURVATURE
PC PRECAST
PCC PORTLAND CEMENT
CONCRETE
PCT PORCELAIN CERAMIC TILE
PD PRESSURE DROP
PE POLYETHYLENE
PEN PENETRATION
PERF PERFORATED
PH PHASE
PHAR PHARMACY
PI POINT OF INTERSECTION
PIV POST INDICATING VALVE
PL or P PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLATF PLATFORM
PLBG PLUMBING
PLG PILING
PLWD PLYWOOD
PNL PANEL
POL POLISH(ED)
PORC PORCELAIN
PPM PARTS PER MILLION
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PRESS PRESSURE
PROJ PROJECT
PRV PRESSURE REGULATING
VALVE
PS PRESSED STEEL
PSFT POUNDS PER SQUARE
FOOT
PSI POUNDS PER SQUARE
INCH
PT POINT
PT POINT OF TANGENCY
PTD PAINTED
PTN PARTITION
PVC POLYVINYL-CHLORIDE
PVMT PAVEMENT
PW PASS WINDOW
1/4 RD QUARTER ROUND
QT QUARRY TILE
QT QUART
QTRS QUARTERS
QTY QUANTITY
QTZ QUARTZ
R REGISTER
R RISER
RA RETURN AIR
RAD OR
R
RADIUS
RB RESILIENT BASE
RC REMOTE CONTROL
RCP REINFORCED CONCRETE
PIPE
RD ROOF DRAIN
RE RIGHT END
REC RECEIVER
RECP RECEPTACLE
RECR RECREATION
RECT RECTIFIER
REF REFERENCE
REFR REFRIGERANT
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCEMENT
REM REMOVE(ABLE)
REQD REQUIRED
RESIL RESILIENT
REV REVISIONS
RFG ROOFING
RH RELATIVE HUMIDITY
RL REFRIGERANT LIQUID
RM ROOM
RND ROUND
RO ROUGH OPENING
RPM REVOLUTIONS PER
MINUTE
RT RUBBER TILE
RTU ROOF TOP UNIT
RUB RUBBER
DIAG DIAGONAL
DIM DIMENSION
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DIST DISTRIBUTION
DL DEAD LOAD
DMPR DAMPER
DN DOWN
DP DAMP PROOFING
DPT DEW POINT
DR DOOR
DRN DRAIN
DS DOWN SPOUT
DV DENTAL VACUUM
DWG DRAWING
DWLS DOWELS
DX DIRECT EXPANSION
E EAST
EA EACH
EA EXHAUST AIR
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY
RATIO
EJ EXPANSION JOINT
EL OR
ELEV
ELEVATION - GRADE OR
BUILDING
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
ENCL ENCLOSURE
ENT ENTERING
ENT ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EST ESTIMATE
EVAP EVAPORATOR
EW EACH WAY
EWC ELECTRIC WATER
COOLER
EXC EXCAVATE
EXD EXIT DEVICE
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPL EXPLOSION
EXPN EXPANSION
EXT EXTERIOR
F FAHRENHEIT
F
FIRE
FA FRESH AIR
FCG FACING
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER
BRACKET
FEC FIRE EXTINGUISHER
CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIG FIGURE
FIN FINISH
FIX FIXTURE
FL or FLR FLOOR
FLASH FLASHING
FLEX FLEXIBLE
FLG FLANGE
FLG FLOORING
FLUOR FLUORESCENT
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPRF FIRE PROOF
FR FRAME
FRG FURRING
FS FAR SIDE
FS FLOOR SINK
FS FULL SIZE
FT FEET (FOOT)
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALL COVERING
G GRILLE
G NATURAL GAS
GA GAGE OR GAUGE
GAL GALLON
GALV GALVANIZED
GEN GENERAL
GFE GOVERNMENT FURNISHED
EQUIPMENT
GFE/CI GOVERNMENT FURNISHED
EQUIPMENT/CONTRACTOR
INSTALLED
GFI GROUND FAULT
INTERRUPTER
GI GALVANIZED IRON
GL GLASS
GND GROUND
GOVT GOVERNMENT
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRADE
GRS GALVANIZED RIGID STEEL
CONDUIT
GRTG GRATING
GSU GLAZED STRUCTURAL
UNITS
GWB GYPSUM WALLBOARD
GWT GLAZED WALL TILE
GYP GYPSUM
H or HT HEIGHT (HIGH)
HB HOSE BIBB
HBD HARDBOARD
HC HANDICAPPED
HD HEAD
HDPE HIGH DENSITY
POLYETHYLENE
HDR HEADER
HDW HARDWARE
HIP HIGH PRESSURE
HM HOLLOW METAL
HORIZ HORIZONTAL(LY)
HP HORSE POWER
HPS HIGH PRESURE STEAM
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HSGYP HIGH STRENGTH GYPSUM
PLASTER
HTG HEATING
HTR HEATER
HW HEAD WALL
HW HOT WATER
HWH HOT WATER HEATER
HWR HOT WATER RETURN
(HEATING)
HWS HOT WATER SUPPLY
(HEATING)
HYD HYDRAULIC
I or FE IRON
IC INTERCOM
ID INSIDE DIAMETER
IE INVERT ELEVATION
IES ILLUMINATING
ENGINEERING SOCIETY
IN INCH
INSUL INSULATION
INT INTERIOR
INV INVERT OR INVERTER
IP IRON PIPE
ISF INSIDE FACE
JB JUNCTION BOX
JBOX JUNCTION BOX
JC JANITOR CLOSET
JCT JUNCTION
JST JOIST
JT JOINT
K KEY
KCP KEENE'S CEMENT
PLASTER
KIP or K KILOPOUND (1000 LBS)
KIT KITCHEN
KL KEY LOCK
KP KICK PLATE
KV KILOVOLTS
KVA KILOVOLT AMPERES
KW KILOWATT
LAB LABORATORY
LAU LAUNDRY
LAV LAVATORY
LBR LUMBER
A COMPRESSED AIR
A/C AIR CONDITIONING
AB ANCHOR BOLT
ABS ACRYLONITRILE BUTAD
STYRENE
AC ALTERNATING CURRENT
ACI AMERICAN CONCRETE
INSTITUTE
ACSR ALUMINUM CONDUCTOR
STEEL REINFORCED
ACST ACOUSTIC
AD ACCESS DOOR
AD AREA DRAIN
ADMIN ADMIN ADMINISTRATION
(IVE)
AFF ABOVE FINISH FLOOR
AFFF AQUEOUS FILM FORMING
FOAM
AGG AGGREGATE
AHU AIR HANDLING UNIT
AI AREA INLET
AIC AMPS INTERRUPTING
CAPACITY (SYM RMS)
AISC AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AL ACTIVE LEAF
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL
STANDARDS INSTITUTE
AP ACCESS PANEL
APD AIR PRESSURE DROP
APPD APPROVED
APPROX APPROXIMATE
ARCH ARCHITECTURAL OR
ARCHITECT
ARI AMERICAN
REFRIGERATION
INSTITUTE
ASB ASBESTOS
ASPH ASPHALT
APC ACOUSTICAL PANEL
CEILING
AUTO AUTOMATIC
AV ACID VENT
AVG AVERAGE
AW ACID WASTE
AWC ACOUSTICAL WALL
COVERING
AWG AMERICAN WIRE GAUGE
L ANGLE
BATT BATT INSULATION
BB BULLETIN BOARD
BBO BOILER BLOW OFF
BC BOOKCASE
BD BOARD
BDY BOUNDARY
BEJ BRICK EXPANSION JOINT
BIT BITUMINOUS
BKR BREAKER
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BM BENCH MARK
BO BOTTOM OF
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BTU BRITISH THERMAL UNIT
BTUH BTU PER HOUR
BUR BUILT-UP ROOFING
BW BOTH WAYS
C CENTER
C OR
CND
CONDUIT (ELECTRICAL
SHEETS)
C TO C CENTER TO CENTER
CAP CAPACITY
CB CATCH BASIN (OR CIRCUIT
BREAKER)
CC CENTER TO CENTER
CCT CIRCUIT
CD CONDENSATE DRAIN
CE COVER ELEVATION
CEM CEMENT
CF CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CHIM CHIMNEY
CI CAST IRON
CI CURB INLET
CIP CAST IN PLACE
CIR CIRCULAR
CJ CONTROL JOINT
CKT CIRCUIT
CL CENTER LINE
CL WG CLEAR WIRE GLASS
CLG CEILING
CLKG CAULKING
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY
UNIT
CNTR COUNTER
CO CLEAN OUT
CO2 CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINATION
COMB COMBUSTION
COMP COMPRESSIBLE
COMPR COMPRESSOR
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION
CONSTR CONSTRUCTION
CONSTR
JT
CONSTRUCTION JOINT
CONT CONTINUOUS
(CONTINUATION)
CONTR CONTRACTOR
COR CORNER
CORR
COVEREDCOV
CORRIDOR
CPL CEMENT PLASTER
CPS CYCLES PER SECOND
(HERTZ)
CPT CARPET
CR CONDENSER WATER
RETURN
CRES CORROSIVE RESISTANT
STEEL
CRG CARRIAGE
CRSE COURSE
CS CONDENSER WATER
SUPPLY
CS COUNTER SINK
CSMT CASEMENT
CT CERAMIC TILE
CT CURRENT TRANSFORMER
CTL CARPET TILE
CU CONDENSING UNIT
CU YD CUBIC YARDS
CUH CABINET UNIT HEATER
CV CEILING VENT
CW COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
CYL CYLINDER
D DEPTH (DEEP)
D DIFFUSER
d PENNY (as in nail - 10d)
D&M DRESSED AND MATCHED
DA DOUBLE ACTING
DB DRY BULB
dB DECIBEL
DBL DOUBLE
DC DIRECT CURRENT
DCJ DOWELED CONTROL
JOINT
DCJT DUMMY CONTROL JOINT
DCL DOOR CLOSER
DCW DOMESTIC COLD WATER
DEG DEGREE
DEMO DEMOLITION
DEPR DEPRESSION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DH DOUBLE HUNG
DHW DOMESTIC HOT WATER
DI DEIONIZED WATER
DIA DIAMETER
CLO CLOSET
FR FIRE RATED
U/C UNDER CABINET
NORTH PLAN
NORTH
TRUE
NORTH
CBU CEMENTITIOUS BACKER
UNIT
F FLUSH or FRAME
FG FULL GLASS
G GLASS or GLASS TYPE
HG HALF GLASS
NV NARROW VISION
V VISION
SL SLIDING
BF(2) BIFOLD (DOUBLE)
IG INSULATED GLASS
SS SOLID SURFACE
G001 TITLE SHEET
A 00 ARCHITECTURAL INFO SHEET
A. THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL
DRAWINGS PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION.
DIMENSIONS AND EXISTING CONDITIONS ARE APPROXIMATE. CONTRACTOR
SHALL FIELD VERIFY EXISTING CONDITIONS. ITEMS WHICH ARE INTENDED
TO BE REMOVED, RELOCATED, OR SALVAGED ARE SHOWN AS FULL-TONE
DASHED LINES AND ARE LISTED IN THE REFERENCED DEMOLITION NOTES.
ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE AND ARE SHOWN
HALF-TONE.
B. DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS BELOW OR
HERE-IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED
RENOVATION AND NEW CONSTRUCTION WITH THE EXISTING BUILDING TO
IDENTIFY THE TOTAL EXTENT OF THE DEMOLITION REQUIRED AND AS LISTED
BELOW.
C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND
REMOVAL OF ALL EXISTING BUILDING COMPONENTS, MATERIALS,
EQUIPMENT, AND APPURTENANCES AS REQUIRED TO BUILD, ERECT,
INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER
HAVING FIRST RIGHT OF REFUSAL ON ALL ITEMS.
D. ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE
CAREFULLY REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND
STORED OR REINSTALLED ON THE SITE AS DIRECTED. REMOVED AND
SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE OWNER.
E. WHERE EXISTING FLOOR MATERIALS AND/OR WALLS ARE TO BE REMOVED,
PREP REMAINING FLOOR AND/OR WALL SUBSTRATE AS REQUIRED PER
MANUFACTURERS RECOMMENDATIONS FOR THE NEW FLOOR/WALL FINISH
MATERIAL. REMOVE ALL FINISH FLOORING DOWN TO BASE SUBSTRATE
FLOORING AND PREP TO RECEIVE NEW FINISH.
F. IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL
REASONABLY BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY
OTHER HAZARDOUS MATERIAL WHICH HAS NOT BEEN RENDERED
HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY STOP WORK IN THE
AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND
ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT
THEREAFTER BE RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE
OWNER AND CONTRACTOR.
G. THE CONTRACTOR IS RESPONSIBLE FOR THE ERECTION, MAINTENANCE,
AND REMOVAL OF ALL CONSTRUCTION BARRIERS.
H. TEMPORARILY SHORE AND BRACE STRUCTURE AT ALL BEARING WALL
DEMOLITION LOCATIONS UNTIL NEW PERMANENT STRUCTURE IS
ESTABLISHED.
I. REMOVE EXISTING ELEMENTS/FINISHES NOT REQUIRED IN THE COMPLETED
PROJECT, BUT CONFLICTING WITH NEW FINISHES.
J. REMOVE EXISTING FLOOR FINISHES IN AREAS TO RECEIVE NEW FLOOR
FINISHES PER THE ROOM FINISH SCHEDULE. SEE MECHANICAL, AND
ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION, INCLUDING, BUT NOT
LIMITED TO, ALL CONCRETE SLAB REMOVAL AND REPLACEMENT.
K. REFER TO MECHANICAL DEMOLITION PLANS FOR ADDITIONAL DEMOLITION
REQUIRED TO ACCOMMODATE NEW MECHANICAL PIPING AND ASSOCIATED
EQUIPMENT.
L. THE OWNER HAS THE RIGHT TO SALVAGE ANY ITEMS DESIRED.
CONTRACTORS THAT WANT TO SALVAGE MATERIALS FOR THEIR OWN USE
SHALL MAKE A WRITTEN REQUEST.
M. ALL SURFACES OR FINISHES DAMAGED DURING CONSTRUCTION SHALL BE
REPAIRED OR REPLACED AND SHALL MATCH ADJACENT MATERIALS.
N. REMOVE ALL ABANDONED MECHANICAL EQUIPMENT, PIPING, AND/OR
CONDUIT.
O. CONTRACTOR SHALL PROTECT INTERIOR FINISHES IN OFFICE AREAS,
LOBBY, ETC. FROM DEMOLITION AND CONSTRUCTION ACTIVITIES.
CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIR OR REPLACEMENT OF
DAMAGED ITEMS.
A. EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER
AND LIMITED FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY
ALL EXISTING CONDITIONS AND DIMENSIONS AND NOTIFY THE
ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR VARIATIONS FROM
THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST TO
ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.
B. ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF
DOCUMENTS TO DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR
SHALL NOT BE ALLOWED EXTRA COSTS DUE TO FAILURE TO REVIEW ENTIRE
SET OF DOCUMENTS.
C. CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE
RESPONSIBLE FOR SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD
CONDITIONS AT NO ADDITIONAL EXPENSE TO OWNER. COORDINATE THE
WORK AND SHOP DRAWINGS WITH ALL OTHER TRADES AFFECTED.
D. SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO
REMAIN. FULL-TONE LINES INDICATE NEW OR RELOCATED CONSTRUCTION.
E. DIMENSIONS ARE TYPICALLY TO FINISH FACE OF MASONRY, CONCRETE,
GYPSUM WALL BOARD, AND METAL FRAMES; OR CENTER LINE OF COLUMN
OR BEAMS, UNLESS NOTED OTHERWISE.
F. CHANGES IN FLOOR MATERIALS SHALL OCCUR UNDER DOORS.
G. PROVIDE POSITIVE DRAINAGE TO ALL ROOMS WITH NEW FLOOR DRAINS.
H. ALL ANGLES ON THE FLOOR PLANS ARE 45 OR 90 DEGREES UNLESS
OTHERWISE INDICATED.
I. PROVIDE FIRE TREATED 2x6 OR LARGER WOOD BLOCKING IN WALLS AND
FURRING SPACES AS REQUIRED FOR MOUNTING OF ALL WALL SUPPORTED
ITEMS. WHETHER OR NOT DETAILED ON THE DRAWINGS, THE DRYWALL
CONTRACTOR SHALL COORDINATE AND INSTALL ALL STIFFENERS, BRACING,
BACK-UP PLATES, AND SUPPORTING BRACKETS AS REQUIRED FOR THE
INSTALLATION OF CASEWORK AND WALL MOUNTED OR SUSPENDED
MECHANICAL, ELECTRICAL, OR MISCELLANEOUS EQUIPMENT. THESE ITEMS
INCLUDE, BUT ARE NOT LIMITED TO, HANDRAIL BRACKETS, DOOR WALL
STOPS, FIRE EXTINGUISHER CABINETS, VANITY TOPS, BASE AND WALL
CABINETS, COUNTERTOPS, CONTROL PANELS, WATER COOLERS, WALL
HUNG SINKS, URINALS, TOILETS, MIRRORS, SOAP DISPENSERS, PAPER
TOWEL DISPENSERS, NAPKIN DISPOSAL, TOILET PARTITIONS, URINAL
SCREENS, TOILET PAPER DISPENSERS, SIGNAGE, GRAB BARS, FIRE ALARM
PANELS AND MASTER CLOCKS, ETC.
J. PATCH EXISTING WALLS, FLOORS, AND CEILING SURFACES DEMOLISHED,
CUT, CORED, OR ALTERED IN ANY WAY TO ACCOMMODATE NEW
CONSTRUCTION OR TO RECEIVE NEW FINISHES. PREP ALL EXISTING
FLOORS TO RECEIVE NEW FINISHES.
K. CONTRACTOR SHALL VERIFY CMU WALLS HAVE NO CHIPPED EDGES AND
THAT JOINTS HAVE BEEN TOOLED TO REMOVE ALL EXCESS MORTAR AND
ARE READY TO RECEIVE PAINT. CONTRACTOR SHALL APPROVE WALLS TO
RECEIVE PAINT PRIOR TO HAVING PAINTER INSPECT FOR APPROVAL.
L. PATCH ALL CONCRETE SLAB LOCATIONS DEMOLISHED TO INSTALL NEW
MECHANICAL, OR ELECTRICAL WORK.
M. REMOVE ALL ABANDONED MECHANICAL EQUIPMENT, PIPING, AND / OR
CONDUIT.
N. CONTRACTOR SHALL PROTECT INTERIOR FINISHES FROM DEMOLITION AND
CONSTRUCTION ACTIVITIES. CONTRACTOR SHALL BE RESPONSIBLE FOR
REPAIR OR REPLACEMENT OF DAMAGED ITEMS.
O. CONTRACTOR SHALL REPAIR ALL SITE AREAS DAMAGED DURING
CONSTRUCTION TO MATCH EXISTING CONDITIONS.
P. IN THE AREA OF WORK THE CONTRACTOR SHALL REPAINT ALL NEW FLOOR
SURFACES AND FLOOR SURFACES DAMAGED DURING CONSTRUCTION.
REPAINT FLOOR WITH PAINT MATCHING THE EXISTING FLOOR FINISHES IN
THE ROOM (PAINT TYPE AND COLOR).
Q. IN THE AREA OF WORK THE CONTRACTOR SHALL REPAINT ALL WALL
SURFACES DAMAGED OR PATCHED DURING CONSTRUCTION. REPAINT
WALL SURFACES WITH PAINT MATCHING THE EXISTING WALL FINISHES IN
THE ROOM (PAINT TYPE AND COLOR).
08/12/2026
A.
B.
C.
D.
ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO
DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA
COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE FOR
SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL
EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER
TRADES AFFECTED.
ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT ANGLES AND PARALLEL
TO BUILDING WALLS UNLESS OTHERWISE INDICATED.
ALL PLUMBING INSTALLATION SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
LOCAL AUTHORITY HAVING JURISDICTION.
A.
B.
C.
D.
E.
F.
G.
H.
THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL DRAWINGS
PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION. DIMENSIONS AND EXISTING
CONDITIONS ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR SALVAGED
ARE SHOWN AS FULL-TONE LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
AND ARE SHOWN AS HALF-TONE.
DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED BELOW OR HERE-
IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW
CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE
DEMOLITION REQUIRED AND AS LISTED BELOW.
THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING EQUIPMENT FROM FINISHED
AREAS AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL
PLANS AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING TO ENSURE
PROPER PATCHING AND REPAIR IS MADE TO THE BUILDING.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL
EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT,
INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST
RIGHT OF REFUSAL ON ALL ITEMS.
ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE CAREFULLY
REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND STORED OR REINSTALLED ON THE
SITE AS DIRECTED. REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE
OWNER.
COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND CONTROLS WITH
ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL REMOVALS.
IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL REASONABLY
BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL
WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY
STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND
ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND ARCHITECT.
ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION SHALL BE
COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
TH
IS
D R
AW
IN
G
IS
B
EI
AD
E
AV
AI
LA
BL
BY
SC
EM
M
ER
F O
R U
SE
O
N T
PR
JE
C T
IN
A
C C
O R
D
AN
C E
W
IT
H S
C H
EM
M
ER
AG
EE
M
EN
T
FO
FE
SS
IO
N
AL
S
ER
VI
C
ES
SC
H
EM
M
ER
A
SS
U M
ES
ES
PO
N
SI
BI
LI
TY
O R
L
IA
BI
LI
TY
A N
Y U
SE
O
F
TH
AW
IN
G O
R A
N Y
PA
R
T
TH
ER
EO
F
EX
C
EP
AC
O
R D
AN
C
E W
IT
H
T H
E
TE
R M
S O
F
TH
E
AB
VE
EE
M
EN
T.
DR
AW
N:
CH
EC
KE
D:
IS
SU
E
DA
TE
PROJECT NO.:
RE
VI
SI
ON
S:
No
DA
TE
BY
DE
SC
RI
PT
IO
N:
DE
SI
GN
ED
ar ch ite ct ur e
| e ng in ee rin g
C:
\U se rs
\aa ris te o\
Do cu m en ts \R ev it_ te m p\
1-
ME
CH
_R
_a ar ist eo
XZ
HQ
L.
rv t 8/9
/20
8:
:4 1 A
M
P 00
SO
UT
H
DA
KO
TA
N
AT
IO
NA
L
GU
AR
D
PL
UM
BI
NG
IN
FO
S
HE
ET
W . 3
1S T
ST
YA
NK
TO
N, S
D
011152.001
JE
K
AM
A
AM
A
AU
GU
ST
, 2
RE
PL
AC
E
BO
IL
ER
S
- Y
AN
KT
ON
R
EA
DI
NE
SS
C
EN
TE
R
011152001-5-P 00
W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota
8 |
5.3
.78
SO
UT
H
DA
KO
TA
PLUMBING INFO SHEET
NORTH
ARROW
SYMBOL LEGEND ABBREVIATIONS
MATCHLINE AREA A
AREA B
EXISTING
COLUMN
NEW COLUMN
X
X
X
XXXX
SIM/OPP
X
XXXX
XX-1
X
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE NOTE
REFERENCE
DEMOLITION NOTE
EQUIPMENT
NUMBER
ROOM NAME
ROOM / SPACE
NUMBER
LETTER/NUMBER INDICATES NEW
COLUMN LINE
LETTER/NUMBER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER 1
VIEW NAME
SCALE: 1/8" = 1'-0"
DRAWING/DETAIL NUMBER
LEVEL CALLOUT DESIGNATION
ELEVATION DESIGNATION
GRAPHIC AREA FOR DRAWING
TITLE
SCALE OF THE DRAWING
VOLUME DAMPER
DEMO TO EXISTING CONNECTION
SPRINKLER DRAIN
FIRE SUPPRESSION PIPING
ISOLATION VALVE
TAMPER SWITCH
MANUAL BALANCING VALVE
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
CONTROL VALVE (3 WAY)
CONTROL VALVE (2 WAY)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
HVAC DUCTWORK AND SPECIALTIES (CONT.)
MISCELLANEOUS SYMBOLS
RETURN DUCT DOWN
AIR TERMINAL (VERTICAL MOUNTING)
ROUND DUCT UP / DOUBLE LINE PIPE
ROUND DUCT DOWN / DOUBLE LINE
PIPE
RETURN DUCT UP
TURNING VANES
SUPPLY AND FRESH AIR DUCT DOWN
SUPPLY AND FRESH AIR DUCT UP
SIZE/TYPE
SIZE/TYPE
FLOW
FLOW
SIZE/TYPE
FLOW
SMOKE DAMPER
FIRE DAMPER-HORIZ FIRE SEPARATION
MOTORIZED DAMPER-OPPOSED BLADE
MOTORIZED DAMPER-PARALLEL BLADE
ROUND AIR TERMINAL
(HORIZONTAL MOUNTING)
GRAVITY DAMPER
(OR) SAFETY VALVE-STEAM
TEMP & PRESS RELIEF
FLOOR SINK
FLOOR DRAIN
GRADE CLEANOUT
PLUMBING VENT THRU ROOF
CLEANOUT / WALL CLEANOUT
THERMOSTATIC MIXING VALVE
M
M
MANHOLE
TRENCH DRAIN
OVERFLOW ROOF DRAIN
OXYGEN OUTLET
PIPE CAP
ELBOW UP
AIR OUTLET
TEE
ELBOW DOWN
VACUUM OUTLET
ROOF DRAIN
SIZE/TYPE
FLOW
HUMIDISTAT
THERMOSTAT
FLEXIBLE DUCT
S
H
T
TEMPERATURE SENSOR
UNION
TEE DOWN
STRAINER
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
AIR VENT
TEE UP
FIRE/SMOKE DAMPER
RECTANGULAR RETURN AIR TERMINAL
(HORIZONTAL MOUNTING)
RECTANGULAR SUPPLY AIR TERMINAL
(HORIZONTAL MOUNTING)
SOLENOID VALVE
F D
TS
VALVES
FS
M
M
S
LPR
HPS
MPR
MPS
LPS
HVAC PIPING
GHWR
GHWS
HWR
HWS
PC
HPR
ES
BBD BOILER BLOW DOWN
EXHAUST STEAM
PUMPED CONDENSATE
HIGH PRESSURE RETURN
HIGH PRESSURE STEAM
MEDIUM PRESSURE RETURN
MEDIUM PRESSURE STEAM
LOW PRESSURE RETURN
LOW PRESSURE STEAM
GLYCOL HOT WATER RETURN
GLYCOL HOT WATER SUPPLY
HOT WATER RETURN
HOT WATER SUPPLY
FS-_
FD-_
CO
VTR
GCO
ORD-_
MH
X
A
V
RD-_
PIPING SPECIALTIES AND FITTINGS
WCO
FIRE PROTECTION
XXX-1
PLUMBING FIXTURES
PLUMBING FIXTURE DESIGNATION
X"PIPE
SIZE PIPE SIZE (DIAMETER)
X"xX"
DUCT SIZE
WIDTH x HEIGHT
SIZE/TYPE
FLOW
RECTANGULAR EXHAUST AIR TERMINAL
(HORIZONTAL MOUNTING)
REF. DEMO NOTES ( )GENERAL NOTES XXGENERAL DEMOLITION NOTES
CWS
GCWS
CWR
CR
CS
RL
RDL
RS
GCWR GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
REFRIGERANT LIQUID LINE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION LINE
HCWS
HCWR
HOT/CHILLED WATER SUPPLY
HOT/CHILLED WATER RETURN
REF. NOTES ( )
DOMESTIC HOT WATER
RECIRCULATING (DHWR)
DOMESTIC COLD WATER (DCW)
DOMESTIC HOT WATER (DHW)
ST/OST
PLUMBING PIPING
ACID VENT
TW
AV
AW
W
DS
DSCW
TWR
DSHW
SANITARY VENT
BURIED EXTERIOR WATER
TEPID WATER RECIRCULATING
TEPID WATER
DISTILLED WATER
SOFTENED HOT WATER
SOFTENED COLD WATER
ACID WASTE
STORM DRAIN
SANITARY DRAIN (BELOW FLOOR)
SANITARY DRAIN (ABOVE FLOOR)
OXYGEN
VACUUM
OX
VAC
RO
A
REVERSE OSMOSIS WATER
COMPRESSED AIR
DEIONIZED WATERDI
AIR FLOW STATIONAFS
SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES. SEE INDIVIDUAL SHEETS FOR REFERENCE NOTES.
HPWR
HPWS
HEAT PUMP WATER RETURN
HEAT PUMP WATER SUPPLY
F
S
FS
NEW TO EXISTING CONNECTION
G NATURAL GAS
FOF
FOG
LPG
FOV
FOR
FOS
FUEL OIL RETURN
FUEL OIL SUPPLY
FUEL OIL GAGE
FUEL OIL FILL
FUEL OIL VENT
LIQUEFIED PETROLEUM GAS
CD CONDENSATE DRAIN
EXHAUST DUCT DOWN
EXHAUST DUCT UP
CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR
NO2 NITROGEN DIOXIDE SENSOR
SENSOR WITH GUARD'X'
DOUBLE - GRADE CLEANOUTDGCO
ST/OST STORM DRAIN (BELOW FLOOR)
WASTE AND ANESTHETIC GAS
DISPOSAL
NITROGEN
WAGD
N
MEDICAL AIRMA
PIPE GUIDE
HOSE BIBB
THERMOMETER
PIPE ANCHOR
HB
STEAM TRAP
RHY
WH
ROOF HYDRANT
WALL HYDRANT
PRESSURE GAUGE
EXISTINGDEMO
EXISTINGNEW
18 Ø
18x10
18/10
ROUND DUCT
FLAT OVAL DUCT-1ST FIG IS SIDE
SHOWN
RECT DUCT-1ST FIG IS SIDE SHOWN
ACOUSTICAL DUCT LINER
HVAC DUCTWORK AND SPECIALTIES
HIGH EFFICIENCY TAKEOFF
HIGH EFFICIENCY TAKOFF
WITH VOLUME DAMPER
NITROGEN OUTLET
MEDICAL AIR OUTLET
WASTE AND ANESTHETIC GAS
DISPOSAL OUTLET
N
MA
V
FLEXIBLE DUCTWORK CONNECTION
X"/X" WIDTH / HEIGHT
X" DIAMETER
NORTH
GW SANITARY GREASE WASTE
PLUMBING SHEET LIST
PROJECT PLUMBING REFERENCED DEMOLITION NOTES PROJECT PLUMBING REFERENCED NOTES
MAU MAKE-UP AIR UNIT
MAX MAXIMUM
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPS
MD MOTORIZED DAMPER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
MPR MEDIUM PRESSURE
RETURN
MPS MEDIUM PRESSURE STEAM
MS MOP SINK
N NITROGEN
NC NORMALLY CLOSED
NO NORMALLY OPEN
NPCW NONPOTABLE COLD WATER
NPHW NONPOTABLE HOT WATER
NPHWR NONPOTABLE HOT WATER
RECIRCULATING
OA OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
OX OXYGEN
P PUMP
PHC PREHEAT COIL
PIV POST INDICATING VALVE
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH,
GAUGE
PTAC PACKAGED TERMINAL AIR
CONDITIONER
RA RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF AREA DRAINS
RF RETURN FAN
RH RELIEF HOOD
RHC REHEAT COIL
RL REFRIGERANT LIQUID LINE
RLA RELIEF AIR
RLF RELIEF FAN
RO REVERSE OSMOSIS WATER
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION LINE
RTU ROOF TOP UNIT
RV RELIEF VALVE
S SINK
SA SUPPLY AIR
SAN SANITARY SEWER
SD SMOKE DAMPER
SF SUPPLY FAN
SFU SANITARY FIXTURE UNIT
SH SHOWER
SP STATIC PRESSURE
SSS SURGICAL SCRUB SINK
ST STORM WATER
TD TRENCH DRAIN
TMV THERMOSTATIC MIXING VALVE
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T THERMOSTAT
UH UNIT HEATER
UR URINAL
V VENT
VAC VACUUM
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THRU ROOF
WB WET BULB
WC WATER CLOSETS
WCO WALL CLEANOUT
WF WASH FOUNTAINS
WFU WATER FIXTURE UNITS
WH WALL HYDRANT
WPD WATER PRESSURE DROP
WS WATER SOFTENER
WSHP WATER SOURCE HEAT PUMP
WWHP WATER TO WATER HEAT PUMP
YH YARD HYDRANT
A COMPRESSED AIR
AC AIR COMPRESSOR
AD AIR DOOR
AFCV AUTO FLOW CONTROL VALVE
AHU AIR HANDLING UNIT
AMP AMPERE
APD AIR PRESSURE DROP
AS AIR SEPARATOR
AV ACID VENT
AW ACID WASTE
B BOILER
BC BLOWER COIL
BD BIDET
BFP BACKFLOW PREVENTER
BFV BUTTERFLY VALVE
BHP BRAKE HORSEPOWER
BLKG BLOCKING
BS BRANCH SELECTOR BOX
BT BATHTUB
BV BALL VALVE
BW BEDPAN WASHER
CH CHILLER
CC COOLING COIL
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CUH CABINET UNIT HEATER
CI CAST IRON
CMU CONCRETE MASONRY UNITS
CR CONDENSER WATER RETURN
CRAC COMPUTER ROOM AIR
CONDITIONER
CS CONDENSER WATER SUPPLY
CSS CLINICAL SERVICE SINKS
CT COOLING TOWER
CU CONDENSING UNIT - SPLIT SYSTEM
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
ACC AIR COOLED CONDENSER
ACCU AIR COOLED CONDENSING UNIT
ASHP AIR SOURCE HEAT PUMP
ARU AIR ROTATION UNIT
OI OIL INTERCEPTOR
SOI SAND OIL INTERCEPTOR
SP SUMP PUMP
OST OVERFLOW STORM WATER
WMB WASHING MACHINE BOX
OB OUTLET BOX
RH ROOF HYDRANT
CWP CHILLED WATER PUMP
DB DRY-BULB TEMPERATURE
DCW DOMESTIC COLD WATER
DEG DEGREE
DF DRINKING FOUNTAIN
DGCO DOUBLE GRADE CLEANOUT
DH EMERGENCY DRENCH HOSES
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RECIRCULATING
DI DEIONIZED WATER
DOAS DEDICATED OUTDOOR AIR SYSTEM
DS DISTILLED WATER
DSA DUCT SOUND ATTENUATORS
DSCW DOMESTIC SOFT COLD WATER
DSHW DOMESTIC SOFT HOT WATER
DSHWR DOMESTIC SOFT HOT WATER
RECIRCULATING
DST DOMESTIC STORAGE TANK
DTW DOMESTIC TEPID WATER
DTWR DOMESTIC TEPID WATER
RECIRCULATING
EA. EACH
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EDH ELECTRIC DUCT HEATER
EEW EMERGENCY EYE WASH
EEWS EMERGENCY EYE
WASH/SHOWER
EF EXHAUST FAN
EFF EFFICIENCY
EFW EMERGENCY FACE WASH
EH EXHAUST HOOD
ERV ENERGY RECOVERY
VENTILATOR
ES EMERGENCY SHOWER
ESP EXTERNAL STATIC PRESSURE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER
TEMPERATURE
ET EXPANSION TANK
F FIRE SUPPRESSION PIPING
F-_ FURNACE
FCO FLOOR CLEANOUT
FC FLUID COOLER
FCU FAN COIL UNIT
FD FIRE DAMPER
FLA FULL LOAD AMPS
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOV FUEL OIL VENT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD FIRE/SMOKE DAMPER
FT FINNED TUBE
G GAS
GCWR GLYCOL CHILLED
WATER RETURN
GCWS GLYCOL CHILLED
WATER SUPPLY
GD GARBAGE DISPOSAL
GDH GAS DUCT HEATER
GHCR GLYCOL HOT/CHILLED
WATER RETURN
GHCS GLYCOL HOT/CHILLED
WATER SUPPLY
GHWR GLYCOL HOT WATER RETURN
GHWS GLYCOL HOT WATER SUPPLY
GI GREASE INTERCEPTOR
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GAS VENT
GWH GAS WATER HEATER
HB HOSE BIBB
HC HEATING COIL
HCR HOT/CHILLED WATER RETURN
HCS HOT/CHILLED WATER SUPPLY
DSS DUCTLESS SPLIT SYSTEM
H HUMIDIFIER
DHWP DOMESTIC HOT WATER RECIRCULATING PUMP
DWET DOMESTIC WATER EXPANSION
TANK
HP HORSEPOWER
HPR HIGH PRESSURE RETURN
HPS HIGH PRESURE STEAM
HRC HEAT RECOVERY COIL
HWR HOT WATER RETURN (HEATING)
HWS HOT WATER SUPPLY (HEATING)
HP-_ HEAT PUMP
HVLS HIGH VOLUME LOW SPEED
EUH ELECTRIC UNIT HEATER
HX HEAT EXCHANGER
HY HYDRANTS
IH INTAKE HOOD
IRH INFRARED RADIANT HEATER
KH KITCHEN HOOD
KW KILOWATT
KWH KILOWATT HOURS
L LAVATORY
LAT LEAVING AIR TEMPERATURE
LPR LOW PRESSURE RETURN
LPG LIQUIFIED PETROLEUM GAS
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPS
LS LAUNDRY SINK
LV LOUVER
LWT LEAVING WATER TEMPERATURE
HWP HOT WATER PUMP
BLV BALANCING VALVE
VRF VARIABLE REFRIGERANT FLOW
P 00 PLUMBING INFO SHEET
P001 DEMOLITION FLOOR PLAN - PLUMBING
P101 FLOOR PLAN - PLUMBING
P401 DETAILS & SCHEDULES - PLUMBING
8/12/26
P001
STORAGE /
LOCKERS
ASSEMBLY
ROOM / DRILL
FLOOR
MECHANICAL
ROOM
STORAGE /
OFFICE
STORAGE
116B
LOCKER / PT
MENS
WOMENS
ENTRY HALL
OFFICE
OFFICE
OFFICE
VEST.
OFFICE
LOBRARY /
CLASSROOM
IT
HALL
CLASSROOM
ARMS VAULT
UNIT STORAGE
/ SUPPLY
ROOM
KITCHEN
STORAGE
112B
KITCHEN
NBC NCO
OFFICE
SUPPLY
OFFICE
STORAGE
VAULT
110SUPPLY ENTRY
108A
MECHANICAL
ROOM
FD (E)
LS (E)MS (E)
WS (E)
WH (E) WH (E)
DWET(E)DWET(E)
SHELVING (E)
ELECTRICAL
HOUSEKEEPING PAD (E)
WATER/FIRE
SERVICE
2 2 3
BRANCH TO HEATING
WATER MAKEUP
7 (TYP.)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
TH
IS
D R
AW
IN
G
IS
B
EI
E
AV
AI
LA
BL
EM
M
ER
F O
R U
SE
O
N T
JE
C T
IN
A
C C
O R
D
AN
C E
W
IT
H S
C H
EM
M
EE
M
EN
T
FE
SS
IO
N
AL
S
ER
VI
C
ES
SC
H
EM
M
ER
A
SS
U M
ES
PO
N
SI
BI
LI
TY
O R
L
IA
BI
A N
Y U
SE
O
F
AW
IN
G O
R A
N Y
PA
R
T
TH
ER
EO
F
EX
C
EP
O
R D
AN
C
E W
IT
H
T H
E
TE
R M
S O
F
TH
E
AB
EE
M
EN
T.
DR
AW
N:
CH
EC
KE
D:
IS
SU
E
DA
TE
PROJECT NO.:
RE
VI
SI
ON
S:
No
DA
TE
BY
DE
SC
RI
PT
IO
N:
DE
SI
GN
ED
ar ch ite ct ur e
| e ng in ee rin g
C:
\U se rs
\aa ris te o\
Do cu m en ts \R ev it_ te m p\
1-
ME
CH
_R
_a ar ist eo
XZ
HQ
L.
rv t 8/9
/20
8:
:4 3 A
M
P001
SO
UT
H
DA
KO
TA
N
AT
IO
NA
L
GU
AR
D
DE
MO
LI
TI
ON
F
LO
OR
P
LA
N
- P
LU
MB
IN
G
W . 3
1S T
ST
YA
NK
TO
N, S
D
011152.001
JE
K
AM
A
AM
A
AU
GU
ST
, 2
RE
PL
AC
E
BO
IL
ER
S
- Y
AN
KT
ON
R
EA
DI
NE
SS
C
EN
TE
R
011152001-5-P001
W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota
8 |
5.3
.78
SO
UT
H
DA
KO
TA
DEMOLITION FLOOR PLAN - PLUMBING
REF. DEMO NOTES ( ):X
1 OWNER TO REMOVE SHELVING.
2 DEMO TANK TYPE WATER HEATER, EXPANSION TANK, AND ASSOCIATED PIPING AS
SHOWN.
3 DEMO HOT WATER RECIRC PUMP AND ASSOCIATED PIPING AS SHOWN.
4 DEMO FLOOR DRAIN, CUT FLOOR AS NEEDED TO FACILITATE THE REMOVAL OF
CORRODED FLOOR DRAIN. PREPARE BELOW GRADE SANITARY PIPE TO RECEIVE NEW
FLOOR DRAIN.
5 EXISTING HOUSEKEEPING PAD WILL NEED TO BE REMOVED. SAWCUT, REMOVE, AND
REPLACE FLOOR AS NEEDED. COORDINATE WITH ARCH.
6 DEMO DCW PIPE AS SHOWN. DEMO TUBING FROM PIPE TO BOILER CONDENSATE TRAP.
7 DEMOLISHED GAS PIPING AND PVC VENTING SHOWN ON MECHANICAL DEMO PLANS.
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR PLAN - DEMO PLUMBING
SCALE: 1/4" = 1'-0"
2 FIRST FLOOR PLAN - DEMO PLUMBING - ENLARGED MECH ROOM
NORTH
P101
STORAGE /
LOCKERS
ASSEMBLY
ROOM / DRILL
FLOOR
MECHANICAL
ROOM
STORAGE /
OFFICE
STORAGE
116B
LOCKER / PT
MENS
WOMENS
ENTRY HALL
OFFICE
OFFICE
VEST.
OFFICE
LOBRARY /
CLASSROOM
IT
HALL
CLASSROOM
ARMS VAULT
UNIT STORAGE
/ SUPPLY
ROOM
KITCHEN
STORAGE
112B
KITCHEN
NBC NCO
OFFICE
SUPPLY
OFFICE
STORAGE
VAULT
110SUPPLY ENTRY
108A
OFFICE
MECHANICAL
ROOM
GW
H-
GW
H-
GW
H-
DW
ET
-1
DH
W P-
WS (E)
LS (E)MS (E)
FD-1
ELECTRICAL
WATER/FIRE
SERVICE
HB-1
1 (TYP.)
P101
(REF.)
7'-3"
1/2 " D
CW
1 1 /4"
D
HW
1 1 /4"
D
CW
1 1 /4"
D
HW
1/2 " D
HW
R
WATER SOFTENER
SEE ISOMETIC VIEWS ON SHEET
M401 FOR MORE INFORMATION.
4 4
FIRST FLOOR
100' - 0"
LOWER ROOF
111' - 8 7/8"
F
F F
F
WATER SERVICE
AND METER
WATER
SOFTENER
GW
H-
GW
H-
GW
H-
DW
ET
-1
DHWP-1
G
1 1/4" DHW
1 1/4" DCW
1 1/4" DHW
1/2" DHWR
SEE WATER HEATER PIPING
DETAIL ON SHEET P401 FOR
MORE INFORMATION
3/4" DCW
3/4" DHW
G
(T
YP
2 Ø COMB. AIR
2 Ø FLUE GAS (T
YP
DC
WG
DH
W
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
TH
IS
D R
AW
IN
G
IS
B
EI
E
AV
AI
LA
BL
EM
M
ER
F O
R U
SE
O
N T
JE
C T
IN
A
C C
O R
D
AN
C E
W
IT
H S
C H
EM
M
EE
M
EN
T
FE
SS
IO
N
AL
S
ER
VI
C
ES
SC
H
EM
M
ER
A
SS
U M
ES
PO
N
SI
BI
LI
TY
O R
L
IA
BI
A N
Y U
SE
O
F
AW
IN
G O
R A
N Y
PA
R
T
TH
ER
EO
F
EX
C
EP
O
R D
AN
C
E W
IT
H
T H
E
TE
R M
S O
F
TH
E
AB
EE
M
EN
T.
DR
AW
N:
CH
EC
KE
D:
IS
SU
E
DA
TE
PROJECT NO.:
RE
VI
SI
ON
S:
No
DA
TE
BY
DE
SC
RI
PT
IO
N:
DE
SI
GN
ED
ar ch ite ct ur e
| e ng in ee rin g
C:
\U se rs
\aa ris te o\
Do cu m en ts \R ev it_ te m p\
1-
ME
CH
_R
_a ar ist eo
XZ
HQ
L.
rv t 8/9
/20
8:
:4 5 A
M
P101
SO
UT
H
DA
KO
TA
N
AT
IO
NA
L
GU
AR
D
FL
OO
R
PL
AN
PL
UM
BI
NG
W . 3
1S T
ST
YA
NK
TO
N, S
D
011152.001
JE
K
AM
A
AM
A
AU
GU
ST
, 2
RE
PL
AC
E
BO
IL
ER
S
- Y
AN
KT
ON
R
EA
DI
NE
SS
C
EN
TE
R
011152001-5-P101
W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota
8 |
5.3
.78
SO
UT
H
DA
KO
TA
FLOOR PLAN - PLUMBING
REF. NOTES ( ):X
1 GAS PIPING AND PVC VENTING SHOWN ON MECHANICAL PLANS.
2 CONNECT NEW FLOOR DRAIN TO EXISTING BELOW GRADE SANITARY PIPE. PATCH
CONCRETE FLOORING AROUND DRAIN. SLOPE AS REQUIRED.
3 SURFACE MOUNT PIPING TO NEW HOSE BIB. BIB TO BE 4' 6" AFF.
4 THIS SPACE IS RESERVED FOR ELECTRICAL EQUIPMENT. NO PIPING OR DUCTWORK
SHALL PASS BELOW, ABOVE, OR AROUND ELECTRICAL EQUIPMENT. PROVIDE CODE
REQUIRED MINIMUM CLEARANCE ABOVE ELECTRICAL EQUIPMENT ACCESS SPACE.
5 DOMESTIC HOT WATER RECIRCULATION PUMP SHALL BE ENABLED BASED ON THE
BUILDING AUTOMATION SYSTEM (BAS) OCCUPANCY SCHEDULE. THE DOMESTIC HOT
WATER RECIRCULATION LOOP TEMPERATURE SHALL BE MONITORED BY THE BAS. THE
BAS SHALL START THE RECIRCULATION PUMP WHENEVER THE LOOP TEMPERATURE
FALLS BELOW THE ADJUSTABLE LOOP TEMPERATURE SETPOINT AND STOP THE PUMP
WHEN THE LOOP TEMPERATURE RISES ABOVE THE SETPOINT (ADJUSTABLE DEADBAND
TO BE PROVIDED). ALL CONTROLS BY SCHNEIDER ELECTRIC.
SCALE: 1/8" = 1'-0"
1 FIRST FLOOR PLAN - PLUMBING
SCALE: 1/4" = 1'-0"
2 FIRST FLOOR PLAN - PLUMBING - ENLARGED MECH ROOM
NORTH
SCALE: 1/4" = 1'-0"
3 SECTION VIEW AT WATER HEATERS
INSULATION
THREADED ROD
INSULATION
THREADED ROD
HANGER NOT
SWALLOWED BY
INSULATION
PIPE, 1"Ø MAX
BAND
THREADED
ROD
HANGER
INSULATION
PIPE
SHIELD TO COVER 180°
OF PIPE, SEE CHART FOR
LENGTH
SEE CHART
SHIELD LENGTH
SEE CHART
SHIELD LENGTH,
SWIVEL
a.
b.
c.
d.
e.
SHIELD LENGTH FOR PIPE - NOT LESS THAN THE FOLLOWING:
NPS 1/4" TO 3-1/2" 12" LONG AND .048" THICK
NPS 4" 12" LONG AND .06" THICK
NPS 5" TO 6" 18" LONG AND .06" THICK
NPS 8" TO 14" 24" LONG AND .075" THICK
NPS 16" TO 24" 24" LONG AND .105" THICK
1.
2.
NOTE:
PIPES NPS 8" AND LARGER: INCLUDE WOOD OR REINFORCED CALCIUM-SILICATE-INSULATION INSERTS OF LENGTH AT LEAST AS LONG
AS PROTECTIVE SHIELD.
THERMAL-HANGER SHIELDS: INSTALL WITH INSULATION SAME THICKNESS AS PIPING INSULATION.
SHIELD TO COVER 180°
OF PIPE, SEE CHART FOR
LENGTH
SHIELD TO COVER 180°
OF PIPE, SEE CHART FOR
LENGTH
THREADED ROD
U-BOLT
UNISTRUT OR STEEL ANGLE
WITH LONG LEG DOWN
PIPE
ISOLATION
VALVE (TYP.)
PRESSURE
GAUGE
PUMP
SUPPORT PUMP
SEPARATE FROM
PIPING
CHECK
VALVE
STRAINER
UNION
(TYP.)
STRUCTURAL SLAB
FLOOR DRAIN
FLOOR DRAIN
STRUCTURAL SLAB
3'x3' WATERPROOF
MEMBRANE
2" FINISH SLAB BY
OTHERS
CHLORALOY MEMBRANE
SLAB ON-GRADE
APPLICATIONS
SLAB ABOVE GRADE
APPLICATIONS
DOMESTIC COLD
WATER IN
NATURAL GAS IN
DOMESTIC HOT WATER OUT
GWH-1GWH-2GWH-3
EXHAUST AND INTAKE
CONNECTION SIZES AND
LOCATIONS MAY VARY
BETWEEN MANUFACTURERS.
EXHAUST VENT
COMBUSTION AIR INTAKE
EXHAUST NON-RETURN VALVE WITH
MANUFACTURER RECOMMENDED
CONDENSATE TRAP (TYPICAL)
0.25":12"
CONNECTION SIZES AND
LOCATIONS MAY VARY
BETWEEN MANUFACTURERS.
RELIEF VALVE
(TYPICAL)
PIPE TO DRAIN
(TYPICAL)
DRAIN VALVE (TYPICAL)
CONDENSATE OUT
(TO FLOOR DRAIN)
SHUTOFF VALVE (TYPICAL)
CONDENSATE DRAIN
WITH MANUFACTURER
RECOMMENDED TRAP.
1.
2.
NOTE:
INSTALLATION SHALL COMPLY WITH ALL LOCAL CODES AND WITH MANUFACTURER RECOMMENDATIONS AND SPECIFICATIONS.
COLD AND HOT WATER PIPING TO BE ROUTED IN A "FIRST IN, LAST OUT" CONFIGURATION.
VENTING SIZES AND MATERIAL AS PER
MANUFACTURER RECOMMENDATIONS
1-1/4"
1-1/4"
1-1/4"
INLET TEE
WALL
CONDENSATE NEUTRALIZER,
CONFIGURE PER MANUFACTURER
RECOMMENDATIONS (TYPICAL)
EXPANSION
TANK
DW
ET
-1
DOMESTIC HOT WATER
RECIRCULATION
1/2
DHWP-1
CHECK VALVE
(TYPICAL)
1" 0.125":12"
1-1/4"
1-1/4"
1-1/4"
PROVIDE SEPARATION PER
CODE AND MANUFACTURER
REQUIREMENTS
TEMP GAUGE
TEMP GAUGE
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1-1/4" 1-1/4"1-1/4"
3/4
3/4
3/4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
TH
IS
D R
AW
IN
G
IS
B
EI
E
AV
AI
LA
BL
EM
M
ER
F O
R U
SE
O
N T
JE
C T
IN
A
C C
O R
D
AN
C E
W
IT
H S
C H
EM
M
EE
M
EN
T
FE
SS
IO
N
AL
S
ER
VI
C
ES
SC
H
EM
M
ER
A
SS
U M
ES
PO
N
SI
BI
LI
TY
O R
L
IA
BI
A N
Y U
SE
O
F
AW
IN
G O
R A
N Y
PA
R
T
TH
ER
EO
F
EX
C
EP
O
R D
AN
C
E W
IT
H
T H
E
TE
R M
S O
F
TH
E
AB
EE
M
EN
T.
DR
AW
N:
CH
EC
KE
D:
IS
SU
E
DA
TE
PROJECT NO.:
RE
VI
SI
ON
S:
No
DA
TE
BY
DE
SC
RI
PT
IO
N:
DE
SI
GN
ED
ar ch ite ct ur e
| e ng in ee rin g
C:
\U se rs
\aa ris te o\
Do cu m en ts \R ev it_ te m p\
1-
ME
CH
_R
_a ar ist eo
XZ
HQ
L.
rv t 8/9
/20
8:
:4 6 A
M
P401
SO
UT
H
DA
KO
TA
N
AT
IO
NA
L
GU
AR
D
DE
TA
IL
S
SC
HE
DU
LE
S
- P
LU
MB
IN
G
W . 3
1S T
ST
YA
NK
TO
N, S
D
011152.001
JE
K
AM
A
AM
A
AU
GU
ST
, 2
RE
PL
AC
E
BO
IL
ER
S
- Y
AN
KT
ON
R
EA
DI
NE
SS
C
EN
TE
R
011152001-5-P401
W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota
8 |
5.3
.78
SO
UT
H
DA
KO
TA
DETAILS & SCHEDULES - PLUMBING
2. PROVIDE WITH MPT (CP STYLE) INLET.
NOTES: 1. PROVIDE NICKEL BRONZE ROUND STRAINER, PROVIDE 3" OUTLET SIZE TO MATCH EXISTING - CONFIRM IN FIELD PRIOR TO ORDERING.
HB-1 HOSE BIBB -- 1/2" -- -- -- ~54" A.F.F. -- WOODFORD 24 -- -- -- 2
FD-1 FLOOR DRAIN -- -- 3" -- -- FLOOR -- ZURN Z415B -- -- -- 1
HOT
WATER
COLD
WATER WASTE VENT OTHER FIXTURE FAUCET/FLUSH VALVE ACCESSORY #1 ACCESSORY #2 REMARKSMARK DESCRIPTION
FIXTURE CONNECTIONS
MOUNTING
HEIGHT
FLOW
RATE
MANUFACTURER AND MODEL NUMBER
PLUMBING FIXTURE SCHEDULE
2. PROVIDE WITH 3/4" CONNECTION SIZE.
NOTES: 1. PUMP TO BE CONTROLLED BROM BAS BASED ON OCCUPANCY SCHEDULE AND LOOP TEMPERATURE.
DHWP-1 MECHANICAL 115 DHW INLINE HOT WATER 2.5 30 3250 1/8 115 1 60 BAS TACO 009-SF5 1, 2
TYPE RPM HP VOLTS PH HZ TYPEMARK LOCATION SERVES TYPE
FLUID FLOW
GPM
HEAD FT
WG
ELECTRICAL DATA CONTROL MANUFACTURER AND
MODEL NUMBER REMARKS
PUMP SCHEDULE
4. MANIFOLD AND LINK UNITS TOGTHER USING CASCADE MODE.
3. PROVIDE WITH WATER HEATER SERVICE VALVE KIT- WEBSTONE 4444 SERIES OR EQUIVALENT, 150 PSI RATED PRESSURE RELIEF VALVE.
2. PROVIDE UNIT WITH CONDENSATE NEUTRALIZATION KIT. PIPE CONDENSATE TO NEAREST FLOOR DRAIN.
NOTES: 1. PROVIDE COMMON VENT PER MANUFACTURER RECOMMENDATIONS. PROVIDE NON-RETURN VALVES ON VENTING AS REQUIRED.
GWH-3 MECH 115 NG 199 4.9 10 40 120 TANKLESS 120 1 2 BRADFORD WHITE RTGS199N1 1, 2, 3, 4 GWH-2 MECH 115 NG 199 4.9 10 40 120 TANKLESS 120 1 2 BRADFORD WHITE RTGS199N1 1, 2, 3, 4 GWH-1 MECH 115 NG 199 4.9 10 40 120 TANKLESS 120 1 2 BRADFORD WHITE RTGS199N1 1, 2, 3, 4
VOLT PHASE FLAMARK LOCATION
GAS
TYPE
INPUT
RATING
(MBH)
DESIGN
FLOW RATE
AT TEMP
RISE (GPM)
PRESSURE
DROP AT
DESIGN FLOW
RATE (PSI)
EWT
(°F)
LWT
(°F)
STORAGE
CAPACITY
(GALLONS)
ELECTRICAL DATA
BASIS OF DESIGN REMARKS
INSTANTANEOUS GAS-FIRED WATER HEATER SCHEDULE
2. SUPPORT INDEPENDENTLY FROM PIPING.
NOTES: 1. INSTALL AT COLD WATER INLET HEADER TO TANKLESS WATER HEATERS.
DWET-1 GWH-1 / 2 / 3 MECH 115 DIAPHRAGM 16 40 - 120 MATCH SYSTEM PRESSURE (~48 PSI) 150 2.0 AMTROL ST-5 1, 2
MARK SERVES LOCATION TYPE
TOTAL
SYSTEM
VOLUME
(GAL)
TEMP
RANGE (°F) FILL PRESSURE (PSIG)
MAX OPER.
PRESSURE
(PSIG)
TANK
VOLUME
(GAL) BASIS OF DESIGN REMARKS
EXPANSION TANK SCHEDULE
SCALE: NOT TO SCALE
2 PIPE HANGER DETAIL
SCALE: NOT TO SCALE
1 IN-LINE PUMP DETAIL
SCALE: NOT TO SCALE
3 FLOOR DRAIN DETAIL
SCALE: NOT TO SCALE
4 INSTANTANEOUS HOT WATER HEATER DETAIL
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
EXISTING CONDITIONS ARE BASED ON DRAWINGS PROVIDED BY THE OWNER AND LIMITED
FIELD VERIFICATION. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
AND DIMENSIONS AND NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR
VARIATIONS FROM THOSE SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL ADJUST
TO ACTUAL FIELD CONDITIONS AT NO ADDITIONAL EXPENSE TO THE OWNER.
ALL CONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF DOCUMENTS TO
DETERMINE THEIR FULL SCOPE OF WORK. CONTRACTOR SHALL NOT BE ALLOWED EXTRA
COSTS DUE TO FAILURE TO REVIEW ENTIRE SET OF DOCUMENTS.
CONTRACTOR SHALL TAKE ALL MEASUREMENTS FOR WORK AND BE RESPONSIBLE FOR
SAME. CONTRACTOR SHALL ADJUST FOR ACTUAL FIELD CONDITIONS AT NO ADDITIONAL
EXPENSE TO OWNER. COORDINATE THE WORK AND SHOP DRAWINGS WITH ALL OTHER
TRADES AFFECTED.
SCREENED HALF-TONE LINES INDICATE EXISTING CONSTRUCTION TO REMAIN. FULL-TONE
LINES INDICATED NEW OR RELOCATED CONSTRUCTION.
CONTRACTOR SHALL COORDINATE THE ROUTING OF ALL DUCTWORK WITH STRUCTURE,
CEILING, LIGHTING, AND PIPING.
MAINTAIN MANUFACTURER'S REQUIRED CLEARANCE AROUND ALL EQUIPMENT TO ALLOW
FOR MAINTENANCE ACCESS.
ALL PIPING IN CONCEALED LOCATIONS SHALL BE ROUTED AT RIGHT ANGLES AND PARALLEL
TO BUILDING WALLS UNLESS OTHERWISE INDICATED.
DO NOT ROUTE DUCTWORK OR PIPING ABOVE ELECTRICAL PANELS. MAINTAIN ALL CODE
REQUIRED CLEARANCES.
IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL REASONABLY
BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL
WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY
STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND
ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND CONTRACTOR.
ANY UTILITY OR SYSTEM DISRUPTIONS OR OUTAGES DURING CONSTRUCTION SHALL BE
COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.
A.
B.
C.
D.
E.
F.
G.
H.
THE DEMOLITION PLANS WERE PRODUCED BY DUPLICATING THE ORIGINAL DRAWINGS
PROVIDED BY THE OWNER AND LIMITED FIELD VERIFICATION. DIMENSIONS AND EXISTING
CONDITIONS ARE APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS. ITEMS WHICH ARE INTENDED TO BE REMOVED, RELOCATED, OR SALVAGED
ARE SHOWN AS FULL-TONE LINES. ALL OTHER ITEMS ARE INTENDED TO REMAIN IN PLACE
AND ARE SHOWN AS HALF-TONE.
DEMOLITION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE ITEMS LISTED BELOW OR HERE-
IN. THE CONTRACTOR SHALL COORDINATE ALL REQUIRED RENOVATION AND NEW
CONSTRUCTION WITH THE EXISTING BUILDING TO IDENTIFY THE TOTAL EXTENT OF THE
DEMOLITION REQUIRED AND AS LISTED BELOW.
THE REMOVAL OF FIRE PROTECTION, HVAC, AND PLUMBING EQUIPMENT FROM FINISHED
AREAS AND THROUGH WEATHER BARRIERS SHALL BE COORDINATED WITH ARCHITECTURAL
PLANS AND DETAILS AS WELL AS NOTES ON THE MECHANICAL DRAWING TO ENSURE
PROPER PATCHING AND REPAIR IS MADE TO THE BUILDING.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION AND REMOVAL OF ALL
EXISTING COMPONENTS, MATERIALS, EQUIPMENT, AND APPURTENANCES TO BUILD, ERECT,
INSTALL, OR ACCOMMODATE ALL NEW CONSTRUCTION WITH THE OWNER HAVING FIRST
RIGHT OF REFUSAL ON ALL ITEMS.
ITEMS NOTED TO BE REMOVED AND SALVAGED OR REINSTALLED SHALL BE CAREFULLY
REMOVED BY THE CONTRACTOR WITHOUT DAMAGE AND STORED OR REINSTALLED ON THE
SITE AS DIRECTED. REMOVED OR SALVAGED ITEMS SHALL REMAIN THE PROPERTY OF THE
OWNER.
COORDINATE THE DISCONNECTION OF ELECTRICAL MOTORS AND CONTROLS WITH
ELECTRICAL CONTRACTOR PRIOR TO MECHANICAL REMOVALS.
IN THE EVENT THE CONTRACTOR ENCOUNTERS ON THE SITE, MATERIAL REASONABLY
BELIEVED TO BE ASBESTOS, LEAD-BASED PAINT, OR ANY OTHER HAZARDOUS MATERIAL
WHICH HAS NOT BEEN RENDERED HARMLESS, THE CONTRACTOR SHALL IMMEDIATELY
STOP WORK IN THE AREA AFFECTED AND REPORT THE CONDITION TO THE OWNER AND
ARCHITECT IN WRITING. THE WORK IN THE AFFECTED AREA SHALL NOT THEREAFTER BE
RESUMED EXCEPT BY WRITTEN AGREEMENT OF THE OWNER AND ARCHITECT.
ANY UTILITY OR SYSTEMS DISRUPTION OR OUTAGES DURING DEMOLITION SHALL BE
COORDINATED WITH THE OWNER AND GENERAL CONTRACTOR.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
A
B
C
D
E
F
G
H
J
K
L
M
N
P
A
B
C
D
E
F
G
H
J
K
L
M
N
P
TH
IS
D R
AW
IN
G
IS
B
EI
E
AV
AI
LA
BL
EM
M
ER
F O
R U
SE
O
N T
JE
C T
IN
A
C C
O R
D
AN
C E
W
IT
H S
C H
EM
M
EE
M
EN
T
FE
SS
IO
N
AL
S
ER
VI
C
ES
SC
H
EM
M
ER
A
SS
U M
ES
PO
N
SI
BI
LI
TY
O R
L
IA
BI
A N
Y U
SE
O
F
AW
IN
G O
R A
N Y
PA
R
T
TH
ER
EO
F
EX
C
EP
O
R D
AN
C
E W
IT
H
T H
E
TE
R M
S O
F
TH
E
AB
EE
M
EN
T.
DR
AW
N:
CH
EC
KE
D:
IS
SU
E
DA
TE
PROJECT NO.:
RE
VI
SI
ON
S:
No
DA
TE
BY
DE
SC
RI
PT
IO
N:
DE
SI
GN
ED
ar ch ite ct ur e
| e ng in ee rin g
C:
\U se rs
\aa ris te o\
Do cu m en ts \R ev it_ te m p\
1-
ME
CH
_R
_a ar ist eo
XZ
HQ
L.
rv t 8/9
/20
8:
:4 7 A
M
M 00
SO
UT
H
DA
KO
TA
N
AT
IO
NA
L
GU
AR
D
ME
CH
AN
IC
AL
IN
FO
S
HE
ET
W . 3
1S T
ST
YA
NK
TO
N, S
D
011152.001
JE
K
AM
A
AM
A
AU
GU
ST
, 2
RE
PL
AC
E
BO
IL
ER
S
- Y
AN
KT
ON
R
EA
DI
NE
SS
C
EN
TE
R
011152001-6-M 00
W th St re et, S uit e # 2, Si ou x F all s, So uth D ak ota
8 |
5.3
.78
SO
UT
H
DA
KO
TA
MECHANICAL INFO SHEET
NORTH
ARROW
SYMBOL LEGEND ABBREVIATIONS
MATCHLINE AREA A
AREA B
EXISTING
COLUMN
NEW COLUMN
X
X
X
XXXX
SIM/OPP
X
XXXX
XX-1
X
X
SECTION/
DETAIL
PLAN
DETAIL
REFERENCE NOTE
REFERENCE
DEMOLITION NOTE
EQUIPMENT
NUMBER
ROOM NAME
ROOM / SPACE
NUMBER
LETTER/NUMBER INDICATES NEW
COLUMN LINE
LETTER/NUMBER INDICATES
EXISTING COLUMN LINE
SECTION/DETAIL NUMBER
SHEET NUMBER
INDICATES DIRECTION OF VIEW
DETAIL NUMBER
SHEET NUMBER
REFERENCE
DESIGNATION
DEMOLITION
DESIGNATION
EQUIPMENT
NUMBER
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION
REFERENCE LEGEND
NAME
ELEVATION
LEVEL
TITLE
MARKER 1
VIEW NAME
SCALE: 1/8" = 1'-0"
DRAWING/DETAIL NUMBER
LEVEL CALLOUT DESIGNATION
ELEVATION DESIGNATION
GRAPHIC AREA FOR DRAWING
TITLE
SCALE OF THE DRAWING
VOLUME DAMPER
DEMO TO EXISTING CONNECTION
SPRINKLER DRAIN
FIRE SUPPRESSION PIPING
ISOLATION VALVE
TAMPER SWITCH
MANUAL BALANCING VALVE
FLOW SWITCH
FIRE DEPARTMENT CONNECTION
CONTROL VALVE (3 WAY)
CONTROL VALVE (2 WAY)
HOSE END DRAIN VALVE
PRESSURE REDUCING VALVE
AUTO FLOW CONTROL VALVE
CHECK VALVE
HVAC DUCTWORK AND SPECIALTIES (CONT.)
MISCELLANEOUS SYMBOLS
RETURN DUCT DOWN
AIR TERMINAL (VERTICAL MOUNTING)
ROUND DUCT UP / DOUBLE LINE PIPE
ROUND DUCT DOWN / DOUBLE LINE
PIPE
RETURN DUCT UP
TURNING VANES
SUPPLY AND FRESH AIR DUCT DOWN
SUPPLY AND FRESH AIR DUCT UP
SIZE/TYPE
SIZE/TYPE
FLOW
FLOW
SIZE/TYPE
FLOW
SMOKE DAMPER
FIRE DAMPER-HORIZ FIRE SEPARATION
MOTORIZED DAMPER-OPPOSED BLADE
MOTORIZED DAMPER-PARALLEL BLADE
ROUND AIR TERMINAL
(HORIZONTAL MOUNTING)
GRAVITY DAMPER
(OR) SAFETY VALVE-STEAM
TEMP & PRESS RELIEF
FLOOR SINK
FLOOR DRAIN
GRADE CLEANOUT
PLUMBING VENT THRU ROOF
CLEANOUT / WALL CLEANOUT
THERMOSTATIC MIXING VALVE
M
M
MANHOLE
TRENCH DRAIN
OVERFLOW ROOF DRAIN
OXYGEN OUTLET
PIPE CAP
ELBOW UP
AIR OUTLET
TEE
ELBOW DOWN
VACUUM OUTLET
ROOF DRAIN
SIZE/TYPE
FLOW
HUMIDISTAT
THERMOSTAT
FLEXIBLE DUCT
S
H
T
TEMPERATURE SENSOR
UNION
TEE DOWN
STRAINER
EXPANSION JOINT
FLEXIBLE PIPE CONNECTION
AIR VENT
TEE UP
FIRE/SMOKE DAMPER
RECTANGULAR RETURN AIR TERMINAL
(HORIZONTAL MOUNTING)
RECTANGULAR SUPPLY AIR TERMINAL
(HORIZONTAL MOUNTING)
SOLENOID VALVE
F D
TS
VALVES
FS
M
M
S
LPR
HPS
MPR
MPS
LPS
HVAC PIPING
GHWR
GHWS
HWR
HWS
PC
HPR
ES
BBD BOILER BLOW DOWN
EXHAUST STEAM
PUMPED CONDENSATE
HIGH PRESSURE RETURN
HIGH PRESSURE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .