About this file

This request for quotes solicits firm fixed-price construction contract proposals for structural steel beam rust remediation at the National Cold-Water Marine Aquaculture Center in Franklin, Maine. The United States Department of Agriculture Agricultural Research Service seeks to award a single contract valued between $1-5 million, with a 365-day period of performance beginning at notice to proceed. As a total small business set-aside, the solicitation is only open to offers from small businesses. Evaluation will consider past performance, technical approach, and price using a best value determination. The technical approach will be evaluated based on similar laboratory experience, management and operations, and use of biobased products. The solicitation is posted on SAM.gov and questions must be submitted to the contracting officer by email.

View the file

Other files for this federal contract opportunity

Other files attached to NCWMAC Structural Steel Beam Rust Remediation, newest first.
File Type Posted
A0004 12305B22R0004.pdf PDF
A003 Panel P-D.pdf PDF
A003 Panel P-C.pdf PDF
12305B22R0004 A003.pdf PDF
A003 Site Visit Roster.jpg JPG image
A003 Questions regarding the referenced solicitation in Franklin JMc.docx DOCX document
A003 Panel P-B.pdf PDF
12305B22R0004 Amend 002 06292022.pdf PDF
12305B22R0004 Amend 001.pdf PDF
01.1 Drawings 2419-M USDA Franklin Final.pdf PDF
01.0 Specifications.pdf PDF
01.5 SOW 17FEB2022 Strl Stl Deteoration NCWMAC ME.docx DOCX document
12.0 1442 plus Prov Clauses - ME Steel.pdf PDF
10.0 DOL WD sme8.txt TXT text file
01.4 Calculations.pdf PDF
01.3 Lead Sampling.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CUT SHEETS

FINAL Design Submittal

STRUCTURAL STEEL BEAM

RUST REMEDIATION

USDA-ARS

NATIONAL COLD WATER MARINE

AQUACULTURE CENTER

FRANKLIN, MAINE

Prepared For:

U.S. DEPARTMENT OF AGRICULTURE

Agricultural Research Service

(Project Number: FY19 HPRL Project 09)

Prepared By:

THE JOHNSON-McADAMS FIRM, P.A.

Greenwood, Mississippi

May 18, 2021

Performance Quantity 8

Volume (CFM) 1,000 Total External SP (in. wg) 0.1

Total TP (in. wg) 0.192 Operating Power (hp) 0.07 Required Power (hp) 0.07

Fan RPM 1770 Elevation (ft) 331

Start-up Temp.(F) 70 Operating Temp.(F) 70

Fan Configuration Size 31

Arrangement 4 Discharge Position Horizontal

Mounting Base Mount Material Type Steel Casing Style Long

Impeller Material Aluminum

Equipment Weights Fan (LMD)(lb) 35

Motor/Drive (lb) 21 Accessories (lb) 16

Misc Fan Data Fan Eff. Index (FEI) -

Outlet Velocity (ft/min) 1,223 Static Efficiency (%) 23

Tip Speed (ft/min) 5,676

Motor and Drives Motor Included

Size (hp) 1/3

RPM 1770

Enclosure TEFC V/C/P 460/60/3

Frame Size 56 Max Frame Size 145

Model: AX-31-160-0422-A3 Medium Pressure Axial Direct Drive Tags: CF-1 CF-2 CF-3 CF-4 CF-5 CF-6 CF-7 CF-8

Operating Performance

Static Pressure Calculations External SP 0.1 in. wg Direct Drive RPM Static Adj 0 in. wg Total External SP 0.1 in. wg

Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA

Inlet 64 74 66 62 61 58 53 46 66 55 LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per octave band at 5 ft- dBA levels are not licensed by AMCA International

04/15/2021Printed Date:

Franklin Rust RemediationJob:

CF-1Mark:

AX-31-160-0422-A3Model:

Generated by: tom.lovelace@jmcfirm.com CAPS 4.34.1178 C:\Users\tlovelace\OneDrive - The Johnson McAdams Firm\Documents\CAPS\Jobs\Franklin Fans.gfcj Page 1 of 4

Model: AX-31-160-0422-A3 Medium Pressure Axial Direct Drive

Standard Construction Features:

CASING: Continuously welded heavy gauge steel coated with Permatector coating - Inlet and outlet flanges with mounting holes - Corrosion resistant fasteners - Motor support rigidly formed and welded to the casing

PROPELLER: Cast aluminum airfoil blade and hub - Manually adjustable blade pitch

Selected Options & Accessories:

Motor with Thermal Overload Motor with Class B or Greater Insulation Extended Motor Leads Motor Manufactured in USA Only Coating - Permatector, Concrete Gray-RAL 7023, Fan and Attached Accessories Switch - NEMA-4X, Toggle, For Indoor or Outdoor Use, Ship Separate UL/cUL-705 - "Power Ventilators" Mounting Support - Universal Unit Warranty: 1 Yr (Standard)

04/15/2021Printed Date:

Franklin Rust RemediationJob:

CF-1Mark:

AX-31-160-0422-A3Model:

CAPS 4.34.1178 C:\Users\tlovelace\OneDrive - The Johnson McAdams Firm\Documents\CAPS\Jobs\Franklin Fans.gfcj Page 2 of 4

Bolt Circle Ø 14 Flange Hole Ø 0.44 Quantity 8

END VIEW

0.56 DIA. MOUNTING HOLES

END VIEW SHOWS FROM OUTLET END OF UNIT

AIRFLOW

SIDE VIEW

11.13

13.25 15.25

18.63

12.25 15.00

17.00

12.38

Model: AX-31-160-0422-A3 Medium Pressure Axial Direct Drive

Notes: All dimensions shown are in units of in.

04/15/2021Printed Date:

Franklin Rust RemediationJob:

CF-1Mark:

AX-31-160-0422-A3Model:

CAPS 4.34.1178 C:\Users\tlovelace\OneDrive - The Johnson McAdams Firm\Documents\CAPS\Jobs\Franklin Fans.gfcj Page 3 of 4

AMCA

AMCA Licensed for Air Performance. Power rating (BHP/kW) does not include transmission losses.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW} does not include drive losses. Performance ratings do not include the effects of appurtenances in the airstream.

04/15/2021Printed Date:

Franklin Rust RemediationJob:

CF-1Mark:

AX-31-160-0422-A3Model:

CAPS 4.34.1178 C:\Users\tlovelace\OneDrive - The Johnson McAdams Firm\Documents\CAPS\Jobs\Franklin Fans.gfcj Page 4 of 4