00018334 Exhibit 6 Standard Drawings.pdf
PDF 442 KB Posted
- Attached to
- ESB Chiloquin & OR 58 Stockpile Site Fencing
- Solicitation number
- S-73000-00018334
- Issued by
- Jackson County, Cheshire CDP, Oregon
About this file
This file contains Oregon Standard Drawings (RD810 and RD820) that serve as technical specifications for fence and gate construction projects under Oregon Department of Transportation standards. The drawings provide detailed design specifications for barbed wire and woven wire fencing systems, as well as associated gate installations, applicable across state and local infrastructure projects within Oregon.
The technical specifications document covers three primary fence types (Type 1, Type 1-5W, and Type 2) with detailed dimensional requirements for posts, braces, wire configurations, and foundation details. Standard drawings include specifications for both wooden and metal posts, with post spacing ranging from 2'-2" to 5'-6" maximum intervals depending on fence type and terrain conditions. Gate specifications address single gate openings up to 20 feet and double gate openings up to 40 feet, with detailed component requirements for gate posts, truss rods, and bracing systems. Materials must comply with current Oregon Standard Specifications and ASTM standards, with all concrete foundations to be commercial grade. These standard drawings are effective from December 1, 2024 through May 31, 2025, and users are advised to consult a Registered Professional Engineer before implementation and to reference project-specific plans for details not shown on the standard drawings.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 00018334 Exhibit 5 Specifications.doc | DOC document | |
| 00018334 ESB_RFCQ_279C.docx | DOCX document | |
| 00018334 ESB Sample Contract.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RD810
FENCES
BARBED AND WOVEN WIRE
R D
.d g n
13-JAN-2020N/A
J U
L xxxxxxxxxxxx x x x x x xxxxx x x x x x xxxxxx x x xxx x xx x xx x x x x x x x x x x x x xxxxx x x x x x x x x x x x xxxxxxx x x x x x x x xxx xx x x x xx x xxx xxxxx x x x x x x x x x x x x x xxx x x x xx x x x x x x xx xx x x x x x x xx x x x x x x xx
B
C
WIRES
NO. OF
10"
14"
10"
12"
Type 1-5W
Type 1
1 1
SQUARE
SHAPE
a a a a b b
FENCE C SPACING
stake
1"x2"x12"
Lever metal posts)
(See wood or
Gate post from end of locking bar.
post and approx. 5" welded or bolted to gate
" short link coil chain4 line post material)
4'-4" (Metal
End bar Length
3" normal
Gate post
6 gauge thkn. wire loop wood line post material)
Length 4'-4" (Metal or
End bar
6 gauge thkn. wire loop
3" normal m in m in
Ground linewire loop
6 gauge thkn.
line post material) approx.2'-2" (Metal
Locking bar
Fence stays gauge wire2
6 gauge thkn. wire loop
30" (Type 2)
(33' max. for type 2 fence material)
Width as indicated on plan
5'-6" max. 5'-6" max. 5'-6" max.
3 For wooden stays, see Type 1 fence details.
2 For details not shown see fence type.
1 Match adjointing fence type.
Fence material Fence material Fence materialNOTES:
thkn. wire gauge2
Fence stays
4 or 5 barbed wires
2" min.
Ground line
Post
NOTE:
1 5'-6" 5'-6" ta b le b e lo w
F o r s p a c in g s e e for woven wire fabric.
Horizontal wires to be stapled are: single wires and a minimum of 4 wires on the ground.
Hemlock or Western Pine, spaced as shown for wire stays and to rest firmly
Stays to be 2"x2"x52" min. length, sound, untreated Douglas Fir, Western
Wooden Stays to be used in areas of heavy snowfall or snow drifts over 36".
wire fabric
Rectangular woven
832-6-12
Design number details see Type 1 fence
For wooden stays, NOTE:
Recommendation R9-47.
Simplified Practice
U.S. Dept. of Commerce
Post2
"Barbed wire
Ground line
Unit A required at gate post.
fence line at intersection with new fence line.
Either Unit A or Units A & B are required in existing
Over 330
20-330
20 or Less
Types
1-5W &
1, A & B
A
None
FENCE
R
(ft) REQUIRED
UNITS
TABLE 1 (For wood posts)
TABLE 2
TABLE 3
3" to 4"
All Types 660' 16'-6" 7'-6" 6'-6" 4'-4" 3'-2" 2'-2" 7'-8" 9"-22"
ASTM A-7021.33 lb or U-bar
Tee Channel 3"x3"3"Line Post
Brace Rail
Brace or
"2 to 5
"2
Other Post 4" to 7" 5"
4"
5"x5"
4"x4" Tubular
Angle
Tubular
Angle
3.19 lb b
4.1 lb "4
"x2
"x22
" O.D.8
"4
2"x2"x
" +/- O.D.2 min.-max. min. avg.
FENCE
max.
R P min.
L min.
L H min.
D min.
D min.
B min.-max.
X
MEMBER
SMALL END (in)
DIAMETER OF
ROUND
(in) nominal
SIZE
nominal
PER (ft)
WEIGHT
nominal
SIZE
WOOD METAL
Max. taper 1":48".
in each dimension.
Max. allowable size 1" additional
In accordance with ASTM A 702.
In accordance with AASHTO M 181.
corner post unit
End, gate or m in
12"
Brace min.
Concrete footing min.
nom. wt. 0.67 lbs
Anchor plate footing
Concrete
Brace
Line post
Intermediate end post line
Ground
Brace min.
18" min.
min.
2"
D H
L
X
B
P
R
B
X
H
L
D
12"
H D
L
22" round
20" sq. or
22" round
18" sq. or
22" round
20" sq. or
22" round
18" sq. or
2"
2"
8'-3"8'-3"
Wood brace rail steel dowel
"dia. x4"8
Wood post
Brace post thkn. wire
4 stands of 9 gauge
Brace guys Brace post
Brace rail Intermediate end post
3. For cross sectional dimensions of members see Table 3.
2. Line post spacing same as dimension P.
1. For dimensions indicated by letter see Table 2.
NOTES:
1"x2"x12" stake
Lever
8'-3" 8'-3"
R
P
H
L
D
D
L
H
Brace post
D
L
H
UNIT A UNIT B
For units required see Table 1 corner post unit(s)
End, gate or
Brace rail wire
9 gauge thkn.
4 strands of
Brace guy guy at gate posts
Additional brace line
Ground
Line post
21 21 21
GATEWAY
TYPES 1 , & 1-5W
BRACE RAIL CONNECTIONMETAL POSTS
WOOD POSTS
TYPE 2
TYPE 2TYPE 1-5WTYPE 1
7. Add fence grounding as required.
6. See project plans for details not shown.
5. See Std. Dwg. RD820 for fence gates.
4. All concrete shall be commercial grade concrete.
3. For shapes, weights and dimensions of members see Table 3.
2. Line post spacing same as dimension P.
1. For dimensions indicated by letter see Table 2.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
TABLE OF DIMENSIONS
the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2024 - May 31, 2025
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
Standard Drawing, while
The selection and use of this
RD820
FENCE GATES
R D
.d g n
13-JAN-2020N/A
J U
L
RODS
NUMBERDOUBLE GATESINGLE GATE
Min. Avg.(in)
NOM. DIA.
(in)
NOM. DIA.
DIA. OF SMALL END (in)
(in)
NOM. SIZE
(in)
NOM. DIA.
(lb/ft)
MIN. WT.
(lb/ft)
MIN. WT.
(lb/ft)
MIN. WT.
Max.Min.
17 thru 20
12 thru 16
7 thru 11
UP thru 6
33 thru 40
23 thru 32
13 thru 22
UP thru 12
3.65
2.72
2.27
1.68
2.27
2.27
1.68
10x10
8x8
6x6
6x6
18.97
18.97
9.11
5.79
1 2
Brace(s) to be equally spaced when required (See Table)
Schedule 40 galv. steel pipe brace (Typ.)
(See Table) steel pipe frame
Schedule 40 galv.
two are required)
Truss rod (Where
(See Table)
Gate post
(See Table)
" dia.8
Truss rod, or chain link fabric
Woven wire fabric
(See Table)
Gate post
Finish grade
Gate opening (as shown on plans)
20' single gate
Max. opening 40' double gate
For length, setting and bracing details see end posts, Std. Dwg. RD810.
to be as indicated for single gate installation of the wider gate width.
At a double gate installation with unequal width gates, size of both posts
Gate posts on each side of a gate opening to be the same size.
Max. taper 1" in 4'
4. Add fence grounding as required.
3. See project plans for details not shown.
2. See Std. Dwg. RD810 for details not shown.
1. Gates shown are for use with Fence Types 1, 1-5W and 2.
GENERAL NOTES FOR ALL DETAILS ON THIS SHEET:
GATE POSTS
GATE COMPONENTS
WOOD STEEL
STEEL PIPE BRACE
SCHEDULE 40 GALV.
STEEL PIPE FRAME
SCHEDULE 40 GALV.
(ft)
GATE OPENING ROUND SQUARE
STEEL PIPE
SCHEDULE 40 GALV.
TRUSS
the current Oregon Standard Specifications.
All materials shall be in accordance with
DATE REVISION DESCRIPTION
OREGON STANDARD DRAWINGS
DATE
SDR
BOOK NO.
CALC.
Effective Date: December 1, 2024 - May 31, 2025
Professional Engineer.
first consulting a Registered and should not be used without sole responsibility of the user principles and practices, is the generally accepted engineering designed in accordance with
Standard Drawing, while
The selection and use of this
| RD810_8 |
| RD820_6 |