Waddell Pumping Plant KW1A Transformer Repair

Closed State & local contract opportunity Posted

Solicitation number
C118278
State
Arizona
Responses due

Opportunity facts

Opportunity details come from constructionbidsource.com. Updated .

About this opportunity

Central Arizona Water Conservation District (CAWCD) is soliciting competitive sealed proposals for complete repair and re-gasket work on the Waddell Pumping Plant KW1A transformer, with proposals due October 8, 2026.

The scope is a comprehensive transformer re-gasket project addressing multiple oil leaks from primary bushings (H1, H2, H3), secondary bushings (X1, X2, X3), Buchholz Relay, and other connection points. The contractor must clean and prepare all sealing surfaces (faces, grooves, flanges, glands) and replace all sealing materials—gaskets, o-rings, packing, bolts, nuts, washers—at the main tank, oil preservation system, radiators, primary bushing gasketed flanges, and primary CT wells/turrets. The scope includes complete removal, processing, and vacuum re-filling of insulating mineral oil from the main tank, radiators, and conservator; removal, regasketing, and reinstallation of all bushings; replacement of the conservator bladder; and replacement of all associated gaskets, seals, vents, and drains on conservator system piping and devices. SF6 gas isolation, recovery, and refill will be performed by others. The work addresses equipment reliability, environmental compliance, and personnel safety concerns. Place of performance is the Waddell Pump & Generating Plant in Maricopa County / Phoenix area, Arizona.

Opportunity text

CAWCD is soliciting competitive sealed Proposals for Waddell Pumping Plant KW1A Transformer Repair. The Waddell Pump & Generating Plant transformer KW1A has multiple oil leaks including (but not necessarily limited to) Primary bushings (H1, H2, H3) Secondary bushings (X1, X2, X3), Buchholz Relay, and others. The oil leaks are reason for concern regarding equipment reliability, environmental compliance, and personnel safety. CAP proposes to clean and prep all sealing surfaces (faces/grooves/flanges/glands/ etc.) and replace the sealing materials (new gaskets/o-rings/packing/bolts/nuts/washers, etc.) at all main tank, oil preservation system/radiators, and primary bushing gasketed flanges (including SF6 gas side the Primary CT wells/ turrets), devices, connections on the KW1A transformer with new. This should be considered a complete transformer re-gasket project. This will require complete removal, processing, and vacuum re-filling of the insulating mineral oil from the main tank, radiators, and conservator. SF6 gas isolation, recovery, and refill will be performed by others. All bushings will be removed, regasketed, and re-installed by the contractor. Additionally, the conservator bladder will require replacement and all gaskets, seals, vents, drains, etc. associated with the conservator, system piping and devices will be included in the transformer leak repair and regasket.

Files

File Type Posted
WADDELL_KW1A_TRANSFORMER_REPAIR_SCOPE_OF_WORK_.pdf PDF

On GovTribe