Z1MG--SOLAR PV SYSTEM PMIR - Base 4 OY [605] | POP: (05/01/2025 - 09/30/2025)
Closed Pre-Solicitation Posted
This opportunity was awarded. See the award notice from , or the latest solicitation from .
- Solicitation number
- 36C26225Q0849
- Agency
-
Veterans Integrated Service Network 22
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- Service-Disabled Veteran-Owned Small Business
Opportunity facts
- NAICS code
- 221114 Solar Electric Power Generation
- Place of performance
- Department of Veterans Affairs VA Loma Linda Healthcare System (Vallhcs) Loma Linda CA 92357, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Veterans Health Administration (VA) is seeking solar photovoltaic (PV) system maintenance services for the Loma Linda Healthcare System's existing solar array infrastructure. The solicitation requires a contractor to provide comprehensive maintenance for a 1.421 MW-DC solar system, including system management, performance monitoring, preventative maintenance, repairs, and training. Key contract requirements include a site manager with at least three years of solar PV experience and NABCEP certification, technicians with electrical and solar PV experience, and OSHA safety training. Potential contractors must submit a detailed capability statement demonstrating technical expertise by April 30, 2025, as part of this sources sought announcement. The evaluation will focus on the contractor's ability to monitor the Data Acquisition System, provide monthly and annual energy production reports, and perform system maintenance to manufacturer standards.
This pre-solicitation notice is specifically set aside for Service-Disabled Veteran-Owned Small Businesses, with potential opportunities for other small business classifications including Veteran-Owned, 8(a), HubZone, and Women-Owned Small Businesses. The contract will cover one base year from May 1, 2025, to September 30, 2025, with potential for up to four additional option years. The solar array consists of five separate installations across parking lots and a garage structure, utilizing Samsung solar modules and various inverter manufacturers. Contractors will be responsible for managing a system with 1,420 kW-AC rated capacity, including monitoring, maintenance, repair, and cleaning services. While no specific award value is mentioned, the comprehensive maintenance requirements suggest a substantial contract scope for the selected vendor.
Notice text
This is a SOURCES SOUGHT ANNOUNCEMENT ONLY. It is neither a solicitation announcement nor a request for proposals or quotes and does not obligate the Government to award a contract. Requests for a solicitation will not receive a response. Responses to this Sources Sought must be in writing. The purpose of this sources sought announcement is for market research to make appropriate acquisition decisions and to gain knowledge of potential qualified Service-Disabled Veteran Owned Small Businesses, Veteran Owned Small Businesses, 8(a), HubZone and other Small Businesses interested and capable of providing the services described below.
Documentation of technical expertise must be presented in sufficient detail for the Government to determine that your company possesses the necessary functional area expertise and experience to compete for this acquisition. Responses to this notice shall include the following: (a) company name (b) address (c) point of contact (d) phone, fax, and email (e) SAM UEI number (f) Cage Code (g) Tax ID Number (h) Type of small business, e.g. Services Disabled Veteran Owned small Business, Veteran-owned small business, 8(a), HUBZone, Women Owned Small Business, Small disadvantaged business, or Small Business HUBZone business and (i) must provide a capability statement that addresses the organizations qualifications and ability to perform as a contractor for the work described below.
GENERAL
Introduction: The VA Loma Linda Healthcare System (VALLHCS) located at 11201 Benson Street Loma Linda, CA 92357 requires Solar Photovoltaic (PV) Maintenance services for one base and up to four option years.
Background: The VALLHCS currently has five solar arrays and metered inverters on-site; four arrays mounted on the carports in the parking lots and one on the garage structure. The total capacity of the solar PV arrays is 1.421 MW-DC.
Table 1 Solar PV System Information
Array
Location
Inverter Manufacturer
Inverter Size (kW-AC)
Array Size (kW-DC)
Module Quantity
4
Parking Lot (carport)
Solaron
500
580.944
2,352
5
Parking Lot (carport)
Solaron
333
359.632
1,456
7
Parking Lot (carport)
Satcon
135
148.694
602
8
Parking Lot (carport)
Satcon
75
82.992
336
9
Parking Garage Structure
Solaron
250
248.976
1,008
OBJECTIVE
Description: The VALLHCS installed a grid-tied solar PV system that is connected to the facility s 480V service bays with no energy storage or backup feature in November 2013. The solar modules are Samsung model LPC247M-08. The inverters are metered and monitored from the Data Acquisition System (DAS), using Athea platform. The inverter was rated at 1,420 kW-AC. The system was rated at 1,701 kW-DC STC and 1,490 kW-AC CEC. The system has downsized when the rooftop arrays were removed in September 2024. The VALLHCS had solar PV maintenance services from April 2020 to March 2025 and requires renewal of full maintenance services.
Scope of Work: The contractor shall provide all labor, materials, tools, equipment, engineering, transportation, qualified personnel, supervision and other services necessary for performing solar PV system management, maintenance, repair, cleaning, and training to the manufacturer and industrial standards. The purpose is to manage system performance for optimum solar generation.
System Management: The contractor shall provide system management services to include monitoring the DAS, responding to alarms, tracking work orders/services, administrating warranty/utility, and reporting performance.
System Production Report: The contractor shall provide, via DAS, a monthly and annual energy production reports showing the actual system performance within first two weeks of the month.
Preventative Maintenance: The contractor shall provide inspections, testing, cleaning, and preventative maintenance (PM) services in accordance with manufacturers recommendations.
Preventative Maintenance Report: The contractor shall provide a completed maintenance checklist/log, list of issues discovered, resolution, and appliable photos as appropriate within two weeks of each visit.
System Repair and Training: The contractor shall provide repairs and training as needed to maintain the solar PV system.
Specific Requirements:
Conference Meetings: The contractor agrees to attend any post award conference convened by the contracting activity or contract administration office. The contractor shall facilitate monthly meetings on Microsoft Teams with meeting minutes to discuss reports, services, and any agenda that will optimize the performance of the solar PV system.
Quality Control Program: The contractor shall develop and maintain an effective Quality Control Program (QCP) to ensure services are performed in accordance with the Scope of Work. The contractor implements procedures to assure their work complies with the requirements of the contract. The QCP shall be delivered within 21 days after contract award and revised annually for Contracting Officer Representative (COR) review/approval.
Site-Specific Safety Plan: The contractor shall develop and maintain an effective Site-Specific Safety Plan to ensure safe services are performed in accordance with standard electrical and PV safety practices. The contractor implements procedures to identify, prevent, and train contractor personnel in event of medical or site emergency. The plan shall be delivered within 21 days after contract award and revised annually for COR review/approval.
Applicable Publications: The contractor shall abide by all latest applicable regulations, publications, manuals, and local policies/procedures to include but not limited to OSHA, NFPA, IEEE, NEC, and VA/VHA Directives.
Qualifications: The contractor site manager shall have at least three years of solar PV experience, possess an OSHA 30-Hour Occupational Safety and Health Training Course card, and preferably obtain a North American Board of Certified Energy Practitioners (NABCEP) Board Certification. The contractor solar PV technician(s) shall have at least two years of electrician experience, one year of solar PV experience, possess at lease an OSHA 10-Hour Occupational Safety and Health Training Course card, and preferably obtain a NABCEP Associate Credential. The resumes and copy of the OSHA cards shall be delivered within 21 days after contract award for COR review/approval.
Adequate Workforce: The contractor shall maintain stability and continuity of an adequate workforce for uninterrupted performance of all services.
Background Check: The contractor personnel performing work must have a general employment background check at the time of the proposed submission and must maintain the level of security required for the life of the contract.
Physical Security: The contractor shall be responsible for safeguarding all government equipment, information, and property provided for contractor use. At the close of each work period, government facilities, equipment, and materials shall be secured.
Access Control: The contractor shall establish and implement methods of ensuring all badges and keys issued to the contractor by the government are not lost, misplaced, duplicated and are not used by unauthorized persons.
Government Responsibilities:
Furnished Items and Services: The COR or facility personnel will provide site access to the solar PV system to perform the services or will allow the contractor to check-out a key and temporary badge from the Facilities Management Service.
Technical Documents: The COR will provide Operation & Maintenance (O&M) manuals, as-builds, and any technical documents on file. The contractor is responsible for the accuracy of the technical documents.
Water Source: The government will provide access to water spigot for use in module washing. The contractor is responsible for water conservation practices.
Quality Assurance: The COR will evaluate the contractor s performance on the deliverables and services.
General Maintenance Services
Furnished Items and Services: The contractor shall provide compatible software/hardware parts or equipment with the existing PV system/design. The cost of labor, materials, equipment, and other services shall be submitted to the COR for review/approval prior to any work.
Site Visits: The contractor shall notify the COR at least one month of any site visits or services to discuss and coordinate the best course of action with the VA Police, Facility, Safety, and any other departments involved. The contractor shall check-in and check-out with the COR for each site visit.
System Management: The contractor shall provide system management services to include monitoring the DAS, responding to alarms, tracking work orders/services, administrating warranty/utility, and reporting performance. The contractor shall respond and notify the COR for discussion/decision on the path forward to resolve/repair the issue to the alarms from the DAS as follows in Table 2.
Table 2 Alarm Response Level
Response Level
General
Description
Remote Response
Field Response
1
Emergency (Safety related issues and/or complete site outages)
½ Day
1 Day
2
Critical System Production Issues (Inverter Loss or Weather Adjusted Performance
Files
| File | Type | Posted |
|---|---|---|
| 36C26225Q0849.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| Z1MG--SOLAR PV SYSTEM PMIR - Base ($4, 200. 00) [605] | POP: (06/01/2025 - 09/30/2025) | Award Notice | |
| Z1MG--SOLAR PV SYSTEM PMIR - Base Period + 4 OY [605] | POP: (06/01/2025 - 09/30/2029) | Solicitation | |
| This notice | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| J061--SOURCES SOUGHT NOTICE - Triennial Electrical Inspection Testing and Maintenance Services Requirement - Louis A Johnson VA Medical Center 36C24527Q0039 | Veterans Integrated Service Network 5 | No set-aside | |
| J061--triennial electrical maintenance - amendment 4 POP: 12/01/2026 - 11/30/2027 plus 4 option years | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| Water system Maintenance | Veterans Integrated Service Network 20 | Total Small Business | |
| 657A5-26-111, Triennial Electrical Testing | Veterans Integrated Service Network 15 | Service-Disabled Veteran-Owned Small Business Sole Source | |
| J065 | Viewpoint Software Support and Maintenance | Veterans Integrated Service Network 21 | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity