Z1DA--RFQ - albany 3RD party witness annual elevator safety tests
Closed Solicitation Posted
- Solicitation number
- 36C24223Q0401
- Agency
-
Veterans Integrated Service Network 2
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 541350 Building Inspection Services
Notice details come from SAM.gov. Updated .
Notice text
4 versions
Update #4 · Latest ·
During the 5 Year testing, will the hydraulic elevators be required to have the rupture valve test performed? This test varies based on locations. Some VA locations require this test to be performed while other VA locations do not.
RESPONSE: Yes, the rupture valve test is required during the 5 year full load test.
In the Statement of Work (H) it states that the VA elevator maintenance contractor will operate the elevators during the annual inspection. Will they also operate the elevators, physically perform inspections, and provide the test weights for the Category 5 inspections?
RESPONSE: Yes. the maintenance contractor operates the elevators, physically performs inspections, and provides the test weights for the Category 5 inspections.
Update #3 ·
Amendment to Solicitation 36C24223Q0401
Update #2 ·
Elevator Inspection
Update #1 ·
Elevator Inspection
Files
| File | Type | Posted |
|---|---|---|
| 36C24223Q0401 0003.docx | DOCX document | |
| 36C24223Q0401 0002.docx | DOCX document | |
| 36C24223Q0401 0001.docx | DOCX document | |
| 36C24223Q0401.docx | DOCX document | |
| WAGE DETERMINATION 2015-4143 REV.23 12-27-2022.pdf |
Notice history
| Notice | Type | Posted |
|---|---|---|
| This notice | Solicitation | |
| Z1DA--RFQ - albany 3RD party witness annual elevator safety tests | Pre-Solicitation |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity