The Department of Veterans Affairs has issued Amendment 0001 to solicitation 36C24W25Q0218 for a walk-in refrigerator project at the VA Medical Center in Tulsa, Oklahoma. This special notice serves as a request for quote amendment that provides answers to thirteen contractor questions submitted regarding the original solicitation. The procurement is set aside as a Service-Disabled Veteran-Owned Small Business sole source opportunity. The amendment clarifies critical technical specifications and project requirements while maintaining the original August 12, 2025 deadline for quote submissions. The solicitation seeks to procure a panel-by-panel walk-in medical laboratory refrigerator for the Eastern Oklahoma VA Healthcare System facility.

The amendment clarifies that the project requires an air-cooled condensing unit mounted above the ceiling, with a temperature set point of 2 degrees Celsius and volumetric temperature uniformity of +/- 2 degrees Celsius. Key technical requirements include 100% compressor redundancy, 208-volt electrical specifications, and stainless steel interior surfaces for all visible areas including floors, walls, and ceilings. The project will be subject to prevailing wage requirements for local labor, and building drawings will be made available to vendors who attend the mandatory site walk-through. Contractors must submit their quotes by August 12, 2025 at 12:00 PM Central Time, and the facility includes access to a freight elevator and loading dock for equipment delivery and installation. Only Service-Disabled Veteran-Owned Small Businesses are eligible to participate in this sole source procurement opportunity.

Notice text

NOTICE FOR REQUEST FOR QUOTE AMENDMENT

SOLICITATION NUMBER: 36C24W05Q0218

AMENDMENT NUMBER: 0001

DATE: July 10, 2025

PROJECT NUMBER: N/A

PROJECT TITLE: Walk-in Refrigerator

LOCATION: VA Medical Center, Tulsa, OK, 74127

REASON FOR AMENDMENT:  Answer Questions 1 – 13, Condensing Unit Type – Missing Division

______________________________________________________________________________ AMENDMENT: 0001

Question: 1 - Condensing Unit Type: I see both air-cooled and water-cooled listed in the RFQ and specifications.

VA Response: An air-cooled type condensing unit is required.

Question: 2 - Condensing Unit Location: Can you find out where the condensing units are located and I need to know the total horizontal and vertical feet of pipe too.

VA Response: The condensing unit will be mounted above the ceiling on top of the cooler. The precise location will have to be determined by the contractor base on access, and position of other MEP (mechanical, electrical, piping) in the space.

Question: 3 - Chamber temperature set point: Can you confirm if this is a 2-8C° Cold Room.

VA Response: The set point will be 2 degrees Celsius.

Question: 4 - Temperature uniformity: Is this required for this type of “Lab Grade Chamber”? I typically +/-2.0°C volumetric temperature uniformity in Pharma applications.

VA Response: Correct, volumetric temperature uniformity should be +/- 2 degrees Celsius.

Question: 5 - Relative Humidity and Uniformity: Neither of these are listed.

VA Response: I am unaware of any humidity uniformity requirement.

Question: 6 - 100% Mechanical Redundancy: Are they looking for an “A” and “B” systems that are identical to each other for system switchover? Or are they looking for dual circuited evaporators with redundant condensing units?

VA Response: The exact solution is up to your discretion. The only requirement that we have is 100% redundancy for the compressor.

Question: 7 - Labor: Would this be a Prevailing Wage Job?

VA Response: Yes, local labor would apply because there are labor qualifications specified.

Question: 8 - Freight Elevator and Size: Is one available and can we get the size.

VA Response:

    1. 69” W x 102” D x 102”H
    2. Door opening 54” W x 96”H

Question: 9 - Building Drawings: Are these available?

VA Response: Drawings will be made available to all vendors that attend the site walk-through.

Question: 10 - Loading Dock: Is a loading dock available?

VA Response: The loading dock can be made available for scheduled loading and unloading. The delivery time and location can be worked out post award.

Question: 11 - Condensing Unit Voltage: Will this be 208/230V or 460V?

VA Response: 208v.

Question: 12 - Chamber Interior Finish: Would this be 304 stainless steel walls floors and ceilings?

VA Response: Stainless steel is the required surface for all visible surfaces, including floors, walls and ceilings.

Question: 13 - Missing Divisions:

VA Response:All VA Master Construction Specifications can be obtained here:

https://vatilms.va.gov/vatilms/reports/PG-18-1

Please give it a minute to load and click “VA Specs”.

THE DUE DATE FOR OFFERS REMAINS AUGUST 12, 2025 @ 12:00PM.

_____________________________________________________________________________________

All other terms and conditions remain unchanged.

Files

File Type Posted
S02 36C24W25Q0218 Amendment Opportunties.pdf PDF

Notice history

Notice Type Posted
This notice Latest special notice Special Notice
Walk-in Refrigerator Original Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
Remove and Replace Walkin Cooler and Freezer NAICS 333415 — Total Small Business
4120--rental of two chillers for one year Asheville, North Carolina 28805, United States · NAICS 238220 Veterans Integrated Service Network 6 Service-Disabled Veteran-Owned Small Business
Refrigerator-freezer, s NAICS 335210 Medical Supply Chain Total Small Business
J041--PMI ICE Machine Service Contract -w/wd, B+4, POP 1/1/2027 - 12/31/2027 Department of Veteran Affairs Phoenix VA Healthcare System Phoenix AZ 85012 U.S.A · NAICS 811310 Veterans Integrated Service Network 22 Service-Disabled Veteran-Owned Small Business
Amendment CTX Steam Humidifier Temple, Texas 76504, United States · NAICS 238220 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity