UPS Maintenance Agreement - NWI Base Year: DOA to 10/31/2017 +4
Award Notice Posted
- Solicitation number
- VA26317Q0006
- Agency
-
Veterans Integrated Service Network 23
Veterans Health Administration, Department of Veterans Affairs
- Awarded
- to J & S Power Solutions Inc.
- Set-aside
- No set-aside
Opportunity facts
- Contract number
- VA263-17-C-0005 Federal contract award
- NAICS code
- 238220 Plumbing, Heating, and Air-Conditioning Contractors
- PSC
- Not on record
Notice details come from SAM.gov. Updated .
Notice text
2 versions
Update #2 · Latest ·
Five year requirement (1 base year and 4 one year options) to provide preventive maintenance coverage (PM) with battery replacement coverage (BR) as indicated on Uninterruptible Power Supplies (UPS) and Rectifiers located at various sites in the NWIHCS as listed in paragraph 2.1.
Provide all tools, parts, transportation and labor to complete the following semi-annual PM:
Electronics Preventive Maintenance: Rectifier Power Module Preventive Maintenance/Calibration of all metering and protective features. Functional testing of all transfer conditions. Inspection of online performance and equipment history. Examination of interfaces to other Power-train equipment. Visual check on batteries and battery environment. Written evaluation providing a record of equipment performance. The Vendor will perform the Preventive Maintenance at a mutually accepted date.
Battery Preventive Maintenance: VR battery system or flooded lead acid battery preventive maintenance visits during the term of the service agreement. NOTE: Due to the size and type of battery, testing and work procedures vary between battery jars above and below 100 watts per battery; work procedures may vary by UPS or related device and battery type and may be limited by safety requirements.
Performed During Semi-Annual Preventive Maintenance Visit:
Measure and Record the following:
Individual cell/battery float voltages and overall float voltage
Charger output current and voltage
AC ripple current and voltage imposed on the battery
Internal ohmic values of each cell/battery or perform a continuity test of each cell/battery
Connection Resistance of 10% of the inter cell/battery connection
Ambient temperature
Negative terminal temperature of one cell/battery per battery cabinet shelf or rack tier
Visually inspect conditions and appearance of the following:
Connection terminals inter cell/battery connectors, cables and associated hardware
Cell/battery covers, containers, and post seals
Battery racks or cabinets and associated components and hardware
Cell/battery jar or cover, noting any excessive distortion
Perform cleaning of all accessible surfaces as required
Perform the following:
Measure and record the connection resistance of 100% of the inter cell/battery connections.
Re-torque any connection where the resistance is above 20% of the average.
E. Reporting Each Preventive Maintenance Visit:
The technician(s) will issue the VA a verbal report summarizing the condition of the battery and identifying any critical issues before leaving the customer's site.
A detailed report containing all readings and observations will be sent to the VA within five business days.
Electronics (UPS Power Module, DC, PDU, Flywheel) Preventive Maintenance
The following is an outline of general checks required to be perfonned during a Preventive Maintenance. All checks should be designed to be performed during off line operation, in the bypass mode. All checks or processes may not be applicable to all equipment types or models.
Visual Inspection
Inspect all printed circuit board connections for cleanliness, swab contacts if necessary.
Inspect all power connections for signs of overheating
Inspect all subassemblies, bridges and legs for signs of component defects or stress
Inspect all DC capacitors for signs of leakage
Inspect all AC capacitors for signs of leakage
Inspect and inventory all customer-owned spare parts
Inspect for, and perform as required, any open engineering changes
Internal Operating Parameters
DC Ground Detection Offset (if applicable)
Inverter leg current average balance (if applicable)
Output filter current average phase balance
Rectifier bridge current average leg balance
AC Protection settings are checked
DC Protection settings are checked
Input and Output Frequency and Voltage Bandwidth settings are checked
Verify DC filter capacitance
i. Verify AC tank and trap filter capacitance
j. Power Supply voltages and waveforms
External Operating Parameters
System Input Voltages (all phases)
System Input Currents (all phases)
DC Charging Voltages (float and equalize), record settings, adjust to nominal
Rectifier phase on and walk up
Inverter phase on and walk up
Adjust all panel meters to measured values
System Bypass Voltages (all phases)
Manual and UV Transfer Testing, verify uninterrupted transfer waveform (if applicable)
i. Outage simulation, and battery capability testing, and verify charger current limit
j. Generator operation and interface verification (if applicable)
Environmental Parameters
UPS area ambient temperature and condition of ventilating equipment
General Cleanliness of UPS Power Module
General Cleanliness of UPS area
Replace all air filters
Clean control panel/CRT screen
Battery Cabinet Checks
General appearance of Battery System (all types)
General cleanliness of Battery System area (all types)
Inspect cells for physical abnormalities
Inspect all DC connections for abnormalities
Battery System area ambient temperature and condition of ventilating equipment
For internal batteries only, measure and record:
Overall battery float voltage
Charger output current and voltage
Negative terminal temperature of one cell/battery per battery cabinet shelf or rack tier
Monitoring System Parameters
Alarm archive review and printing
Alarm lamp test-local and remote (if applicable)
Replace all open monitor bulbs
Review Battery Test in history (if applicable)
General
Customer Consultation
Verbal Recommendations
General Observations
Following the Preventive Maintenance inspection, a written report will be provided detailing the results of the inspection, and making specific recommendations toward future remedial action.
Battery Replacement: Provide all parts, tools, labor and transportation to replace all batteries with equal or better batteries once during the duration of the agreement. Preferred year of replacement is listed in para. 2.1. under BR Year The VA reserves the right to request earlier replacement if the need is identified. It is the responsibility of the vendor to arrange delivery of the new batteries to coincide with the mutually agreed upon scheduled replacement date. Batteries shall not arrive any earlier than 2 business days before replacement. It is also the vendor's responsibility to arrange for pick-up and proper disposal of all used/old batteries within 2 business days of the replacement. All 3 NWIHCS locations have dock access to the facility, but do not have fork-lifts available. Rectifier battery replacement shall be done after 1800 hours on weekdays or on the weekend, unless the contractor can provide a system to keep the PBX/telephone system operational when they replace the batteries.
1.3. Provide all tools, parts, transportation and labor to provide Full Service Repair coverage as follows:
1.3.1. 4-Hour Response 1.3.2 Unlimited Service Calls
Free 24 Hour Tech Support
24 x 7 Contracted Service Coverage (Including Holidays)
Provide unlimited continuous effort service response within the contracted period, provide free parts, and fund all travel and labor costs.
Update #1 ·
UPS Maintenance Agreement - VA NWI Health Care System
This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in FAR Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation, quotes are being requested.
Solicitation number VA263-17-Q-0006 is issued as a request for quotes (RFQ).
The solicitation document and incorporated provisions and clauses are those in effect through Federal Acquisition Circular 2005-87-2.
The VA anticipates one firm fixed price contract award for all resources and labor necessary to complete the UPS Maintenance Agreement for the VA NWI Health Care System. Additional requirements are listed within the attached solicitation document.
This procurement is a total set-aside for a Small Busines. Prospective offerors must be registered and current in the System for Award Management (SAM) database prior to contract award (www.sam.gov). Quotes will only be accepted from responsible contractors. The NAICS code for the solicitation is 238220 with a size standard of $20.5 Million.
A list of the contract line items, quantity, and unit of measure are listed within the attached solicitation documentation.
Quotes are due to the Contracting Office by October 19, 2016 at 2:00 PM CDT. Quotes are required to be emailed to Travis.Johnson2@va.gov prior to the solicitation closing date and time. It is the responsibility of the offeror to ensure their quote is received in its entirety by the Contracting Officer before the solicitation closing.
Files
| File | Type | Posted |
|---|---|---|
| VA263-17-C-0005-000.docx | DOCX document | |
| VA263-17-Q-0006-001.pdf | ||
| VA263-17-Q-0006-000.docx | DOCX document |