About this opportunity
The Federal Bureau of Prisons is seeking a firm-fixed-price construction contract to upgrade the fire detection system at the Federal Correctional Institution Phoenix, located at 37900 N 45th Ave, Phoenix, Arizona. The project involves installing new addressable, automatic and manual fire alarm systems across all buildings at the facility, requiring detailed engineered shop drawings sealed by a qualified design professional with NICET Level 3 minimum certification or a Licensed Professional Engineer. The contractor must provide a new site fire alarm network using armored single-mode fiber optic cables, with significant expansion of the existing fiber optic system including new underground conduit systems. Two new UL listed central monitoring and control workstation desktop computers will be installed to monitor and control the system, with the Central Control Room serving as the primary workstation and on-premise proprietary monitoring station. This is a pre-solicitation notice posted on August 15, 2025, with the actual solicitation expected after a minimum 15-day posting period, and responses due by September 2, 2025.
This opportunity is designated as a Total Small Business set-aside under NAICS code 238210 for Electrical Contractors and Other Wiring Installation Contractors. The project scope encompasses all buildings on the correctional facility site, requiring Class A initiating circuits with combination manual pull stations and automatic detectors on each floor, and Class B notification circuits providing complete coverage throughout each building. The system will interface with mechanical units including rooftop units and fan coil units, though the description indicates additional technical requirements beyond what is fully detailed in this synopsis. No incumbent contractors or specific award values are mentioned in this pre-solicitation notice. The project falls under PSC category Z2FF for Repair or Alteration of Penal Facilities, indicating this is specialized work within a federal correctional environment.
Notice text
THIS IS A SYNOPSIS OF PROPOSED CONTRACT ACTION. THIS IS NOT A SOLICITATION OR INVITATION FOR OFFERORS TO SUBMIT BIDS. THIS NOTICE WILL BE POSTED FOR A MINIMUM OF 15 DAYS PRIOR TO POSTING OF THE SOLICITATION.
The Federal Bureau of Prisons (FBOP) anticipates issuance of a solicitation for the award of a firm-fixed-price construction contract for a project entitled Upgrade Fire Detection System at the Federal Correctional Institution Phoenix (FCI Phoenix), located in Phoenix, Arizona.
FCI Phoenix is a federal correctional facility located at 37900 N 45th Ave, Phoenix, Arizona 85086
The project consists of the following but not limited to:
- New addressable, automatic and manual fire alarm system for each building. All buildings on site are part of the Scope of Work. The Contractor will provide detailed, engineered shop drawings, prepared as a delegated-design submittal, and sealed and signed by a qualified design professional (NICET Level 3 minimum or Licensed Professional Engineer).
- The new fire alarm system will be monitored and controlled using two new UL listed central monitoring and control workstation desktop computer connected to the new fire alarm system network. The Central Control Room will be the location of the primary workstation and used as an on-premise proprietary monitoring station.
- Provide a new site Fire Alarm Network, using fiber optic cables. Fiberoptic cables shall be armored type (metallic protection), Single-Mode(SM). The existing SM fiber optic cable system on site will be used, however significant expansion is needed, including new underground conduit systems and new fiber optic cables to extend to new locations.
- Initiating circuits will be Class A. Each floor will have a combination of manual pull stations and automatic detectors.
- Notification circuits will be Class B. All areas must have complete notification appliance coverage throughout each building.
- Mechanical units, including roof top units and fan coil units, will be interfaced with fire alarm system for fan shut down.
- All fire sprinkler system risers flow and tamper switches will be interfaced with the fire alarm system.
- Post Indicator Valves (PIV) located on the exterior around the site will be interfaced with the fire alarm system. New underground conduit will be required for all PIV locations.
- Kitchen Fire Suppression (Ansul) systems will be interfaced with the Fire Alarm System.
- Programming and configuration of the fire alarm network, central monitoring and control workstation, fire alarm control units and all associated devices and equipment.
- Testing, inspection and commissioning of the entire system and all associated devices and equipment.
- New 20A, 120V circuit breakers and power branch circuits from existing power panelboards to supply FACU and NAC units in each building.
- While there are some ceiling and side access panels and hatches available, the ceiling space is congested with existing utilities in many locations. Contractor will be responsible for cutting/patching of ceilings and walls will be required to install new conduit and wiring in existing ceiling spaces.
- It is expected that hazardous material, including but not limited to, lead-based paints and asbestos will be present at the site. Contractor is responsible for avoiding disruptions to the hazardous material where possible. Where disruption is necessary, provide mitigation as required to complete the scope of work.
- Many of the walls are CMU/Concrete construction which will require core drilled penetrations to run the new conduit system.
- Certifications by Contractor’s design professional stating that the installation was completed based on the detailed shop drawings and meets all applicable Code requirements and regulations.
-
The NAICS code for this requirement is 238210 with a corresponding small business size standard of $19 million. Pursuant to Federal Acquisition Regulation (FAR) 36.204, the estimated magnitude of the project lies between $5,000,000 and $10,000,000 NOTE: This range is one of 8 available ranges from FAR 36.204 and is not meant to imply that the project has necessarily been estimated/budgeted to the maximum of the selected range. It merely conveys that the estimate/budget lies somewhere within that range.)
The solicitation will be available approximately on or about September 2, 2025. The solicitation will be distributed solely through the Contract Opportunity website at https://www.sam.gov. Hard copies of the solicitation will not be made available. The website provides download instructions.
-
The "Sensitive /Secure package Upload" option will be selected for this procurement. All secure/locked documents uploaded, to include the solicitation, will require an active www.sam.gov vendor registration to obtain access. In addition, only those vendors who have been issued a valid Marketing Partner Identification Number (MPIN) from www.sam.gov will be granted access. If your firm does not have the NAICS code listed in www.sam.gov required for this solicitation, an email may be forwarded to your firm requesting an explanation as to why your firm should be granted access.
If you encounter problems accessing these documents, please contact the Federal Service Desk at 866-606-8220. All future information about this solicitation, including any amendments, will also be distributed solely through this website. Interested parties are responsible for continuously monitoring this website to ensure that they have the most recent information about this proposed contract action.
IMPORTANT: Any contractor interested in obtaining a contract award with the Federal Bureau of Prisons must be registered in https://www.sam.gov. To qualify for award, your business size metrics information entered in your SAM registration must be less than or equal to the size standard specified above.
Each bidder's www.sam.gov registration will be reviewed by the Government to confirm that your business size meets the small business size standard requirement. All bidders are urged to double check their www.sam.gov registration and update as necessary, including the size metrics information.
This is a 100 percent small business set-aside. You must be registered in www.sam.gov as a small business (see FAR provision 52.219-1 in the Representations & Certifications section of your www.sam.gov registration).
Notice history
| Notice | Type | Posted |
|---|---|---|
| Upgrade Fire Detection System at FCI Phoenix | Award Notice | |
| Upgrade Fire Detection System at FCI Phoenix | Solicitation | |
| Upgrade Fire Detection System at FCI Phoenix | Pre-Solicitation | |
| Upgrade Fire Detection System at FCI Phoenix | Pre-Solicitation |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity