Super-Silent 56kW Generator Rental & Installation
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 140P6026Q0050
- Agency
-
Midwest Region
National Park Service, Department of the Interior
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- Place of performance
- 24290 Doane Mountain Road Keystone, South Dakota 57751, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of the Interior National Park Service Midwest Region seeks rental and installation of a super-silent 56kW diesel generator at Mount Rushmore National Memorial, Keystone, South Dakota, with quotations due June 5 at 12:00 PM Central Daylight Time. This is a total small business set-aside under NAICS 532490 with a $40 million size standard; questions are due June 3.
Place of performance is 24290 Doane Mountain Road, Keystone, South Dakota 57751. The generator must be UL-listed, diesel-powered with minimum 56kW rated output, acoustic-enclosed for noise-sensitive public environments, and rated as manufacturer-certified super-silent or whisper-rated. The unit shall operate at most 14 hours per day with at least 16 continuous hours of run time on June 2nd, 3rd, and 4th during the June 24–July 7 period of performance. Delivery, installation, and utility connection occur during the afternoon of June 24; complete removal and demobilization occur by close of business July 7. The contractor connects to existing trailer panels approximately 50 feet or less from each trailer, with cables routed through a parking lot area. Refueling may occur any day except July 2nd, 3rd, and 4th.
The contractor furnishes all labor, transportation, fuel, grounding systems with minimum 1-inch diameter 24-inch copper-clad rod, EPA-compliant spill containment, electrical distribution, temporary cabling, startup, testing, monitoring, maintenance, and restoration. The generator must maintain minimum 10-foot clearance from trees, vegetation, tents, and flammable materials; exhaust oriented away from trailers; air intakes at least 5 feet from any obstruction. Post-award submittals including Accident Prevention Plan are due at least 8 days prior to mobilization. The contractor must maintain liability insurance of $100,000 per person, $500,000 per occurrence, and $500,000 property damage. Evaluation criteria are technical capability, past performance, and price. Award is anticipated by June 9.
Notice text
Super-Silent 56kW Generator Rental including Installation and Utility Connection at Mount Rushmore National Memorial, Keystone, South Dakota
The purpose of this amendment (0001) is to provide answers to questions asked thus far and two additional attachments - location map and trailer electrical requirements.
Q1. Please confirm the expected generator operating schedule during the June 24, 2026, through July 7, 2026, period. Should the contractor assume continuous 24/7 operation, daily event/business-hour operation, or another defined operating schedule?
A1. At most 14 hours per day with at least 16 hours run times on the 2nd, 3rd, and 4th.
Q2. Please confirm the intended connection point for each trailer. Will the contractor connect to existing trailer panels, receptacles, disconnects, or another Government-provided connection point?
A2. Existing Trailer Panels
Q3. Please provide the approximate distance between the proposed generator placement area and each trailer, including whether temporary cables are expected to cross pedestrian-accessible areas.
A3. Approximately 50 foot or less from each trailer to generator. Cables will run through a parking lot area
Q4. Please confirm whether there is a specific maximum acceptable noise level in dB(A), including the measurement distance, or whether a manufacturer-rated super-silent / whisper-rated sound-attenuated generator is acceptable.
A4. Manufacturer-rated super-silent / whisper-rated sound-attenuated generator is acceptable.
Q5. Please confirm whether fuel/refueling should be priced for the full period of performance and whether there are any site access restrictions or preferred refueling windows.
A5. Refueling can occur any day other than July 2nd, 3rd, and 4th
Q6. Please confirm whether the Government will provide known utility information or utility locating support prior to any grounding rod installation or ground penetration.
A6. Government will provide Information upon request
Q7. Please confirm whether the attached Technical Questionnaire is the correct questionnaire for this solicitation, as the title appears to reference a different project, while the solicitation number shown is 140P6026Q0050.
A7. The title/heading is in error, but the questions are correct.
Q9. Please provide the electrical specifications for each of the two mobile trailers including voltage (120V/240V), phase (single or three-phase), amperage rating, panel size, and estimated total load in kilowatts. This is required to verify generator compatibility and select appropriate distribution equipment. Would this be available at pre-bid site visit?
A9. Please see attached document for electrical requirements
Q10. Will the government provide a site plan or sketch showing the approximate generator placement area, cable routing to each trailer, and proximity to pedestrian pathways? Are there known underground utilities in the grounding rod installation area, and what is the process for utility locating at this National Park Service (NPS) site? If not, is a pre-bid site visit available before the June 5 deadline?
A10. See attached document for approximate location. Exact placement is unknown but will be in the Red box. Underground utilities are unknown. Contractors must call 811 or fill out a utility-locate ticket online at least two business days before starting any digging project in South Dakota.
Q11. The SOW requires certain item submittals 15 days prior to mobilization (June 9, 2026), but the quote deadline is June 5. Please confirm: does the 15-day submittal requirement still apply post-award?
A11. Award is anticipated by June 9, 2026. Submittal requirement changed from 15 days to no less than 8 days prior to mobilization.
Q12. What are the required hours of generator operation during the June 24 ¿ July 7 period of performance? (24/7, daytime only, or event-driven hours?) This directly affects fuel consumption and maintenance scheduling.
A12. At most 14 hours per day with at least 16 hours of run time on the 2nd, 3rd, and 4th.
Q13. Does NPS have a specific maximum decibel threshold for generator operation at this site (measured at a defined distance), or is compliance with the manufacturer's "super-silent/whisper-rated" designation sufficient?
A13. Manufacturer's "super-silent/whisper-rated" designation is sufficient.
Q14. Are there NPS-specific access requirements for contractor personnel at Mount Rushmore like background checks, vehicle passes, badging, or check-in procedures?
A14. No additional background checks are needed at this time, but this is subject to change for any unforeseen circumstances.
Q15. Is there a designated contractor staging and parking area on NPS grounds for delivery vehicles and equipment? Are there vehicle height or weight restrictions for accessing the site?
A15. Lot 7 as indicated on the map in the Yellow box. Contractor responsible for verifying height and weight restrictions for route.
Q16. Desired fuel: diesel or propane?
A16. Diesel
Q17. Runtime requirement: continuous or standby?
A17. Continuous
Q18. Site location for installation?
A18. See attached Map. Loading and unloading in the Yellow box. Installation in the Red box.
Submit all questions via email to adam_kircher@ios.doi.gov and james_bissaillon@ios.doi.gov by June 3, 2026, to ensure enough time to provide answers.
Reminder to monitor the solicitation posting for any amendments posted until the solicitation closes. All amendments must be acknowledged by the quote due date and time.
Files
Notice history
| Notice | Type | Posted |
|---|---|---|
| MORU Super-Silent 56kW Generator Rental including | Award Notice | |
| This notice | Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Johnston Ridge Observatory Backup Generator Repairs Gifford Pinchot National Forest | Region 6 - Pacific Northwest Region | Total Small Business | |
| GAOA Grizzly Bear Campground | Region 2 - Rocky Mountain Region | Total Small Business | |
| Emergency Generator Preventive Maintenance, Repair, Emergency Callout & Rental Services | Indian Health Service | Buy Indian | |
| 750kW Emergency Diesel Generator (EDG) Rental (PSNS&IMF) | Naval Supply Systems Command | Total Small Business | |
| Request for Information (RFI) - CONUS Generator Maintenance | Federal Emergency Management Agency | Total Small Business |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity