RFQ - 12. 5-Ton Gas/Electric Rooftop Unit Package
Closed Solicitation Posted
- Solicitation number
- W911S226U3282
- Agency
-
MICC Fort Drum
Mission and Installation Contracting Command, Department of Defense
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 333415 Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
- PSC
- 4120 Air Conditioning Equipment
- Place of performance
- 9250 Amber Dr Frederick MD, 21702 21702
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of the Army Materiel Command Mission and Installation Contracting Command Fort Drum seeks a complete, like-for-like replacement 12.5-ton gas/electric rooftop unit package, with proposals due May 28. The procurement is set aside for Total Small Business.
Place of performance is Frederick, Maryland (9250 Amber Dr). The base unit must be a 12.5-ton gas heat and electric cooling rooftop unit rated for 208-volt, 3-phase power with single-circuit, two-stage cooling delivering a minimum 10.8 EER or 15.0 IEER, and two-stage medium gas heat with first-stage input of 180 MBH and second-stage input of 224 MBH. The unit must incorporate a high-static direct-drive vane axial fan such as a Carrier EcoBlue or equivalent, and use a modern, low-GWP refrigerant such as R-454b. The required accessory package includes one vertical economizer with controller, one enthalpy sensor and harness for the economizer, and one standalone, two-stage programmable thermostat. The NAICS code is 333415, Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing; the PSC is 4120, Air Conditioning Equipment.
Notice text
2 versions
Update #2 · Latest ·
Amended to change NAICS code. This requirement is for a complete, like-for-like replacement of an existing commercial rooftop unit, or RTU. The required equipment package must meet or exceed the following specifications. The base unit must be one 12.5-Ton Gas Heat and Electric Cooling Rooftop Unit with a 208-volt, 3-phase power supply. The unit must have single circuit, two-stage cooling with a minimum 10.8 EER or 15.0 IEER, and two-stage medium gas heat with a first stage of 180 MBH input and a second stage of 224 MBH input. It must also feature a high-static direct-drive vane axial fan, such as a Carrier EcoBlue or equivalent, and use a modern, low GWP refrigerant like R-454b. The package must also include the following compatible accessories: one Vertical Economizer with a controller, one Enthalpy sensor and harness for the economizer, and one standalone, two-stage programmable thermostat.
Update #1 ·
This requirement is for a complete, like-for-like replacement of an existing commercial rooftop unit, or RTU. The required equipment package must meet or exceed the following specifications. The base unit must be one 12.5-Ton Gas Heat and Electric Cooling Rooftop Unit with a 208-volt, 3-phase power supply. The unit must have single circuit, two-stage cooling with a minimum 10.8 EER or 15.0 IEER, and two-stage medium gas heat with a first stage of 180 MBH input and a second stage of 224 MBH input. It must also feature a high-static direct-drive vane axial fan, such as a Carrier EcoBlue or equivalent, and use a modern, low GWP refrigerant like R-454b. The package must also include the following compatible accessories: one Vertical Economizer with a controller, one Enthalpy sensor and harness for the economizer, and one standalone, two-stage programmable thermostat.
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Replacement of 10 Ton HVAC Unit, Bldg. 11, PR ANG | Army National Guard | Total Small Business | |
| Replace HVAC Rooftop Units at Building 2275 | Army National Guard | No set-aside | |
| Electrically Heated Tank | MICC Fort Drum | Total Small Business | |
| Two sets of HVAC units or Mobile Ground Control Station | Shared Services Center | Total Small Business | |
| 10th CAB Unit Maintained Equipment Maintenance | MICC Fort Drum | Competitive 8(a) |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity