Presolicitation Notice for Prime Power Distribution Systems (PPDS)
Closed Pre-Solicitation Posted
- Solicitation number
- W909MY24R0005-Presol
- Agency
-
ACC Aberdeen Proving Ground
Army Contracting Command, Department of Defense
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 221121 Electric Bulk Power Transmission and Control
- Place of performance
- Fort Belvoir, Virginia 22060, United States
Notice details come from SAM.gov. Updated .
About this opportunity
Paragraph 1:
The U.S. Army Contracting Command-Aberdeen Proving Ground (ACC-APG) Belvoir Division intends to award an indefinite delivery/indefinite quantity (IDIQ) single award production contract for Prime Power Distribution Systems (PPDS). The PPDS will consist of four primary components: the Improved Primary Switching Center (iPSC), Improved Secondary Distribution Center Version 1 (iSDC-1), Improved Secondary Distribution Center Version 2 (iSDC-2), and the Tactical Prime Power Transformer (TPPT). The PPDS requirement is designed to modernize and standardize the Department of Defense's medium voltage power distribution capabilities. Responses to this presolicitation notice are due by April 22, 2024, and the anticipated contract award date is on or about September 13, 2024.
Paragraph 2:
This procurement will be a 100% small business set-aside. The NAICS code is 221121 - Electric Bulk Power Transmission and Control, and the PSC code is 61. The Government estimates the total contract value at $87 million. The contract will have a 4-year base period followed by six 1-year optional ordering periods.
Notice text
2 versions
Update #2 · Latest ·
This is a presolicitation notice only to gauge the interest of potential businesses.
AMEND 0001 simply updates the SOW which has changes concerning cybersecurity and the period of performance lengths for th3e periods.
-------------------------------
The U.S. Army Contracting Command-Aberdeen Proving Ground (ACC-APG) Belvoir Division, on behalf of Product Lead, Large Power Systems (PdL LPS), Project Manager Expeditionary Energy and Sustained Systems (PM E2S2) at Fort Belvoir, VA, the Government office intends to award an indefinite delivery/indefinite quantity (IDIQ) single award production contract for the Prime Power Distribution Systems (PPDS) requirements described in the two attached documents, the Statement of Work (SOW) and Purchase Description (PD) discussed later in this notice.
Description. This action is an IDIQ 4-Year Base and six (6) 1-Year optional ordering periods for a Firm Fixed-Price type Contract. The contract will be a single award contract for the PPDS. The PPDS enables the distribution and transformation of medium voltage (4160 VAC / 13.8 kVAC) prime power to standard user voltages (120/208 VAC or 277/480 VAC). This PPDS effort is designed to modernize the Department of Defense (DoD) medium voltage power distribution. PPDS will consist of the following four primary components: (1) the Improved Primary Switching Center (iPSC), model # MEPDS-1031; (2) a dual input voltage (4160 VAC or 13.8 kVAC) Improved Secondary Distribution Center Version 1 (iSDC-1), model # MEPDS-3131; (3) a fixed voltage (4160 VAC) Improved Secondary Distribution Center Version 2 (iSDC-2), model # MEPDS-3132; and (4) the Tactical Prime Power Transformer (TPPT), model # MEPDS-2131.
Set-aside Status. 100% Small Business Set-Aside.
SEE DRAFT SOW AND PURCHASE DESCRIPTION DOCUMENT FOR MORE INFORMATION ABOUT ALL THE PPDS REQUIREMENTS.
The PPDS will build on legacy prime power distribution capabilities to modernize, replace, and standardize legacy components fielded with the U.S. Army Deployable Power Generation and Distribution System (DPGDS) and the U.S. Air Force Basic Expeditionary Airfield Resources (BEAR) system; PPDS will replace commercial components and fulfill operational capability gaps of the 249th Engineer Battalion (Prime Power) and Force Provider Expeditionary (FPE) Prime Power Connection Kit (PPCK) to maintain standardization of power distribution at medium voltages. PPDS will add dual input voltage capabilities (4160 VAC and 13.8 kVAC) to enable versatility with host nation or contracted power systems; add output and auxiliary input capabilities lacking in legacy equipment; add metering and monitoring capabilities to increase the efficiency and reliability of prime power systems; and promote joint power system standardization to support combatant commanders or support disaster relief missions. See attached B01 SOW PPDS 29MAR2024 Final and B01 PPDS PD-6110-1036 PPDS 20240329_Final for further details of this requirement.
The following information is applicable to this pre-solicitation notice:
Action Code.
Date. 8 April
Year. 2024
Contracting Office ZIP Code. 22060
Product or Service Code: 61
NAICS: 221121 – Electric Bulk Power Transmission and Control
Subject. Pre-Solicitation for Prime Power Distribution Systems (PPDS)
Proposed Solicitation Number. W909MY-24-R-0005
Closing Response Date. 22 April 2024
Contact Point or Contracting Officer. Danny W. Lester
Contract Award Number. To be determined later.
Contract Award Dollar Amount. Estimated $87M
Line Item Number. Not-applicable during Pre-solicitation Phase.
Contract Award Date. Not-applicable during Pre-solicitation Phase, but award is estimated to be published on or about 13 September 2024.
Contractor. Not-applicable during Pre-solicitation Phase.
Delivery schedule. As specified above. For individual delivery orders, the exact requirements / units desired will be determined in the separate delivery orders to this IDIQ.
Duration of the contract period. As specified above. Orders period of performance will be a 4-year base for development, testing, and production of the first article units, then six (6) optional ordering periods with a 12-Month period of performance for each option year.
This acquisition will be solicited utilizing a 100% Small Business Set-Aside source selection process in determining the suitable contractor for the PPDS effort.
The anticipated IDIQ award date. Not Before 13 September 2024
NOTICE to Interested Parties. All responsible sources may submit a capability statement, proposal, or quotation, which shall be considered by the agency. Telephone requests for additional information will not be honored. Acknowledgement of receipt will be issued. A determination by the Government not to compete this proposed contract based upon responses to this notice is solely within the discretion of the Government. Information received will normally be considered solely for the purpose of determining whether to conduct a competitive procurement.
Contracting Office Address.
Army Contracting Command-APG-Belvoir Division
10205 Burbeck Road
Bldg 362, Suite 105
Fort Belvoir, VA 22060
United States
Place of Performance: To be determined by individual delivery orders.
Primary Point of Contact:
Tony D. Adams,
Contract Specialist
Tony.d.Adams10.civ@army.mil
Secondary Point of Contact:
Danny W. Lester,
Contracting Officer
danny.w.lester.civ@army.mil
Update #1 ·
This is a presolicitation notice only to gauge the interest of potential businesses.
The U.S. Army Contracting Command-Aberdeen Proving Ground (ACC-APG) Belvoir Division, on behalf of Product Lead, Large Power Systems (PdL LPS), Project Manager Expeditionary Energy and Sustained Systems (PM E2S2) at Fort Belvoir, VA, the Government office intends to award an indefinite delivery/indefinite quantity (IDIQ) single award production contract for the Prime Power Distribution Systems (PPDS) requirements described in the two attached documents, the Statement of Work (SOW) and Purchase Description (PD) discussed later in this notice.
Description. This action is an IDIQ 4-Year Base and six (6) 1-Year optional ordering periods for a Firm Fixed-Price type Contract. The contract will be a single award contract for the PPDS. The PPDS enables the distribution and transformation of medium voltage (4160 VAC / 13.8 kVAC) prime power to standard user voltages (120/208 VAC or 277/480 VAC). This PPDS effort is designed to modernize the Department of Defense (DoD) medium voltage power distribution. PPDS will consist of the following four primary components: (1) the Improved Primary Switching Center (iPSC), model # MEPDS-1031; (2) a dual input voltage (4160 VAC or 13.8 kVAC) Improved Secondary Distribution Center Version 1 (iSDC-1), model # MEPDS-3131; (3) a fixed voltage (4160 VAC) Improved Secondary Distribution Center Version 2 (iSDC-2), model # MEPDS-3132; and (4) the Tactical Prime Power Transformer (TPPT), model # MEPDS-2131.
Set-aside Status. 100% Small Business Set-Aside.
SEE DRAFT SOW AND PURCHASE DESCRIPTION DOCUMENT FOR MORE INFORMATION ABOUT ALL THE PPDS REQUIREMENTS.
The PPDS will build on legacy prime power distribution capabilities to modernize, replace, and standardize legacy components fielded with the U.S. Army Deployable Power Generation and Distribution System (DPGDS) and the U.S. Air Force Basic Expeditionary Airfield Resources (BEAR) system; PPDS will replace commercial components and fulfill operational capability gaps of the 249th Engineer Battalion (Prime Power) and Force Provider Expeditionary (FPE) Prime Power Connection Kit (PPCK) to maintain standardization of power distribution at medium voltages. PPDS will add dual input voltage capabilities (4160 VAC and 13.8 kVAC) to enable versatility with host nation or contracted power systems; add output and auxiliary input capabilities lacking in legacy equipment; add metering and monitoring capabilities to increase the efficiency and reliability of prime power systems; and promote joint power system standardization to support combatant commanders or support disaster relief missions. See attached B01 SOW PPDS 29MAR2024 Final and B01 PPDS PD-6110-1036 PPDS 20240329_Final for further details of this requirement.
The following information is applicable to this pre-solicitation notice:
Action Code.
Date. 8 April
Year. 2024
Contracting Office ZIP Code. 22060
Product or Service Code: 61
NAICS: 221121 – Electric Bulk Power Transmission and Control
Subject. Pre-Solicitation for Prime Power Distribution Systems (PPDS)
Proposed Solicitation Number. W909MY-24-R-0005
Closing Response Date. 22 April 2024
Contact Point or Contracting Officer. Danny W. Lester
Contract Award Number. To be determined later.
Contract Award Dollar Amount. Estimated $87M
Line Item Number. Not-applicable during Pre-solicitation Phase.
Contract Award Date. Not-applicable during Pre-solicitation Phase, but award is estimated to be published on or about 13 September 2024.
Contractor. Not-applicable during Pre-solicitation Phase.
Delivery schedule. As specified above. For individual delivery orders, the exact requirements / units desired will be determined in the separate delivery orders to this IDIQ.
Duration of the contract period. As specified above. Orders period of performance will be a 4-year base for development, testing, and production of the first article units, then six (6) optional ordering periods with a 12-Month period of performance for each option year.
This acquisition will be solicited utilizing a 100% Small Business Set-Aside source selection process in determining the suitable contractor for the PPDS effort.
The anticipated IDIQ award date. Not Before 13 September 2024
NOTICE to Interested Parties. All responsible sources may submit a capability statement, proposal, or quotation, which shall be considered by the agency. Telephone requests for additional information will not be honored. Acknowledgement of receipt will be issued. A determination by the Government not to compete this proposed contract based upon responses to this notice is solely within the discretion of the Government. Information received will normally be considered solely for the purpose of determining whether to conduct a competitive procurement.
Contracting Office Address.
Army Contracting Command-APG-Belvoir Division
10205 Burbeck Road
Bldg 362, Suite 105
Fort Belvoir, VA 22060
United States
Place of Performance: To be determined by individual delivery orders.
Primary Point of Contact:
Tony D. Adams,
Contract Specialist
Tony.d.Adams10.civ@army.mil
Secondary Point of Contact:
Danny W. Lester,
Contracting Officer
danny.w.lester.civ@army.mil
Files
| File | Type | Posted |
|---|---|---|
| A02 SOW PPDS 9APR2024 Final.docx | DOCX document | |
| B01 PPDS PD-6110-1036 PPDS 20240329_Final.pdf | ||
| B01 SOW PPDS 29MAR2024 Final.pdf |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Power Distribution and Illumination Systems, Electrical (PDISE) | ACC Aberdeen Proving Ground | No set-aside | |
| Power supply | Land and Maritime | No set-aside | |
| Power supply | Land and Maritime | No set-aside | |
| Power distribution | Land and Maritime | No set-aside | |
| Power distribution- | Land and Maritime | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity