J065--Annual Medical Gas Delivery Systems Testing and Inspection and Training (VA-26-00014193)

Closed Pre-Solicitation Posted

Solicitation number
36C24526Q0081
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Department of Veterans Affairs Vamc Baltimore MD 21201

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 5 is seeking qualified contractors to provide annual medical gas delivery systems testing, inspection, and training services for the Maryland Health Care System. The procurement encompasses three primary deliverables: instructor-led ASSE 6040 Medical Gas System Maintenance certification training courses for VAMC staff, testing and verification of medical air, vacuum, and HVAC compressor equipment, and preventative maintenance services. Key qualifications include certification as an ASSE 6030 Medical Gas Verifier and, for instructors, a minimum of ten years of experience in medical gas system design, testing, verification, and troubleshooting combined with current ASSE 6050 Instructor credentials. The evaluation will focus on the contractor's technical capability to meet specific inspection and maintenance requirements including testing master alarm panels, area alarm panels, zone valves, bulk oxygen systems, gas manifolds, and medical gas outlets. Interested vendors must submit a capability statement including business type, size, and SAM identification number to Keysha.Gorman74@va.gov by November 2, 2025 at 11:00 PM Eastern Time, with this submission representing the critical deadline for initial consideration.

This opportunity carries no set-aside designation and involves work at three VA medical facilities: Baltimore, Loch Raven, and Perry Point. The training component requires three 32-hour instructor-led courses delivered between October 2025 and February 2026, with each class limited to a maximum of 16 VA employees. All testing, verification, and certification work must be completed within 120 calendar days from the award date, and contractors must provide two preventative maintenance visits annually in accordance with manufacturer guidelines and detailed reporting requirements. While specific award values are not disclosed in this pre-solicitation notice, the scope of work, staffing requirements, and geographic coverage across three facilities suggest a moderate to substantial contract value. The pre-solicitation notice is classified under PSC J065 (Maintenance/Repair/Rebuild of Medical Equipment) and NAICS 333912 (Air and Gas Compressor Manufacturing).

Notice text

DISCLAIMER

This RFI is issued solely for information and planning purposes only and does not constitute a solicitation. All information received in response to this RFI that is marked as proprietary will be handled accordingly. In accordance with FAR 15.201(e), responses to this notice are not offers and cannot be accepted by the Government to form a binding contract. Responders are solely responsible for all expenses associated with responding to this RFI.

Submit Capability Statement to Keysha.Gorman74@va.gov by 11/2/2025 by 11pm. Include type of business size and SAM s identification number.

Page 7 of 7

Page 7 of 7

STATEMENT OF WORK

TITLE: Annual Medical Gas Delivery Systems Testing and Inspection and Training

I. SCOPE OF WORK

This Scope of Work encompasses the following 3 Task Items:

CLIN - (Contractor Line Item Number) #1 Instructor Led VAMC Staff Training Courses.

The contractor shall supply materials and an instructor to provide 3x 32-hour training class for ASSE 6040 Medical Gas System Maintenance for Staff personnel certification of VAMC employees. The instructor is required to have a minimum of 10 years experience in design, testing, verification, and troubleshooting of medical gas systems and a currently be credentialed an ASSE 6050 Instructor. The number of students (VA employees) for the class is not to exceed 16. The Training will need to be coordinated with the COR. The training will need to take place between October 2025 and February 2026 at least once at each site withing the Maryland Health Care System. Sites include those listed under Task Item #2, (Baltimore, Loch Raven, Perry Point.)

CLIN - (Contractor Line Item Number) #2 Medical Air, Vacuum, and HVAC Compressor equipment testing, verification, and certification.

The Contractor shall provide a certified ASSE 6030 Medical Gas Verifier(s), testing equipment, supplies and transportation. All work is to be completed within 120 calendar days from the award date. Contractor to submit a work schedule for each site for the COR for approval. The contractor will perform the inspection and testing of the medical gas delivery systems for the Department of Veterans Affairs, VA

Maryland Health Care System at these three locations:

1. Baltimore VA Medical Center

10 North Greene St.

Baltimore, MD 21201

2. Loch Raven Medical Center

3900 Loch Raven Blvd

Baltimore, MD 21228

3. Perry Point VA Medical Center

Perry Point, MD 21902-1000

II. MEDICAL GAS SYSTEMS FOR EACH SITE

A. Baltimore VA Medical Center

10 North Greene St,

Baltimore, MD 21201

1. Master alarm panels (3 ea.)

2. Master Alarm Signals (54 ea.)

3. Area Alarm Panel (19 ea.)

4. Alarm Signals (68 ea.)

5. Zone Value Boxes (36 ea.)

6. Zone Values (126 ea.)

7. Outlets (1,462 ea.) O2, MA, N2O, N2, VAC, WAGD

8. Bulk O2 with reserve tank, supplier/owner Air Products

9. Medical Air System 7th floor (3 ea.) 15-hp oil-less compressors

10. Dental Air System, room 1D-166, POWEREX (460v/3ph)

11. Dental Vacuum System, room 1D-166, ECO VAC, duplex 7.5hp

12. Dental Nitrogen manifold system (2 ea.) left side and (2 ea.) right side

13. Medical Vacuum System 7th floor (3 ea.) 15-hp oil-lubed rotary

14. Nitrogen manifold system (8 ea.) bottles left side and (8 ea.) bottles right

side

15. Nitrous oxide manifold system (8 ea.) bottles left side and (8 ea.) bottles right side

B. Loch Raven VA Medical Center

3900 Loch Raven Blvd

Baltimore, MD 21228

1. Master alarm panels (2 ea.)

2. Master Alarm Signals (24 ea.)

3. Area Alarm Panel (4 ea.)

4. Alarm Signals (12 ea.)

5. Zone Value Boxes (4 ea.)

6. Zone Values (12 ea.)

7. Outlets (240 ea.) O2, MA, VAC

8. Bulk O2 with reserve bottles, supplier/owner Air Products

9. Medical Air System duplex 5-hp oil-less compressors

10. Medical Vacuum System (2 ea.) 5-hp oil-lubed rotary

C. Perry Point VA Medical Center

Perry Point, MD 21902

1. Master alarm panels (total: 6 ea.)

a. Building 23H (2 ea.)

b. Building 19H (1 ea.) (NOTE: BLDG. Under Construction/ Subject to Change.)

c. Building 14H (2 ea.)

d. Building 361 (1 ea.)

2. Master Alarm Signals (98 ea.)

3. Area Alarm Panel (10 ea.)

4. Alarm Signals (98 ea.)

5. Zone Value Boxes (26 ea.)

6. Zone Values (70 ea.)

7. Outlets (263 ea.) O2, MA, VAC

8. Bulk O2 & reserve tank location 14H supplier/owner is Airgas (Air Liquide)

9. Bulk O2 & reserve tank location 19H supplier/owner is Airgas (Air Liquide)

10. Medical Air System location 14H, duplex 5-hp oil-less compressors

11. Medical Air System location 23H, duplex 5-hp oil-less compressors

12. Medical Vacuum System location 14H ,duplex 5-hp oil-lubed rotary

13. Medical Vacuum System location 23H ,duplex 5-hp oil-lubed rotary

14. Medical Vacuum System location 19H ,duplex 5-hp oil-lubed rotary

15. Medical Vacuum System location 24H ,duplex 1-hp oil-lubed rotary

(NOTE: BLDG. 24H Subject to Possible Demolition in Future.)

16. Dental Air and Dental Vacuum

III. SPECIFICATIONS:

The Contractor shall inspect and certify the medical gas delivery systems at each

site in accordance with most recent NFPA-99 Health Care Facilities, NFPA-55

Compressed Gases and Cryogenic Fluids, and NFPA-70 National Electrical Code.

Testing Master Alarm Panels

Function test of all signals from source and bulk systems to master alarm panels.

Simulate failures at all source field switches. Includes determination of trip setting

accuracy and correct bulk/source system labeling.

Testing Area Alarm Panels

Tests all audible and visual alarm signals for continuity, determine accuracy of trip

settings and readouts. Includes determination of proper area served signage.

Pressure transducers/pressure switches will be function tested to determine proper

operation of hi/lo pressure signals, proper communication with area panel, and

determination of hi/lo trip setting on alarm display.

Zone valves

Verify proper area served labeling, test for external leakage and validate accuracy of

pressure gauge. Particulate samples are taken in each zone to test for contamination.

Bulk Oxygen Supply Systems

Test operation of the reserve and reserve in use signaling devices, check proper

function of level activating switch. Inspect all cryogenic tanks for security, leaks,

control configuration and labeling. Inspect Emergency Oxygen Supply Connection

(EOSC).

Gas Manifold Source Systems

Leak test all manifold components including valves, pigtails, and regulators. Test for

proper reserve in use pressure switch activation. Test for proper operation of the

changeover for secondary supply.

Medical Air System

Verify compressor operating within manufacturer specifications. Check for

documented maintenance plan in place. Function test of automatic alternating

controls. Test audible and visual alarms. Test pressure across filters. Calibrate dew

point monitor and verify proper operation.

Medical Vacuum System

Verify maintenance conducted according to manufacturer specifications. Function

test automatic alternating controls. Test pressure/vacuum switch for proper operation.

Validate frequency of pump starts and duration of runs. Measure cut-in and cut-out

pressure/vacuum.

Medical Gas Outlets

Vacuum inlets and pressure gas outlets. Test flow of all vacuum inlets. Check

pressure and flow of all outlets: patient care areas, emergency rooms, intensive care,

procedure labs, operating rooms and recovery rooms. The surgical rooms testing is

performed after-hours. This testing includes coordination with the Baltimore site POC.

Manufactured Assemblies

Verify that each joint and DISS fitting is examined for leakage and that the flexible

assemblies are in a safe working condition.

CLIN - (Contractor Line Item Number) #3 Preventative Maintenance

Service Requirements:

Frequency: Two (2) preventative maintenance service visits per year and provide a detailed inspection report to the COR within 7 days after the inspections.

Comprehensive Inspection: During each visit, all equipment, including air compressors, vacuum systems, and associated accessories (filters, dryers, monitors, etc.), shall be thoroughly inspected, regardless of whether maintenance is immediately required.

Manufacturer Guidelines: All maintenance shall be performed in strict accordance with the equipment manufacturers' guidelines and recommended service intervals based on run-time hours.

Specific Service Tasks: The following tasks shall be performed, as applicable, for each piece of equipment:

Replace air intake filters.

Replace exhaust filter elements.

Clean aftercoolers and line filters.

Inspect Air Treatment Centers for proper operation.

Alternate Desiccant Dryers.

Calibrate CO monitors (where applicable).

Check DP monitors.

Check and adjust controls for proper operation.

Check motor, starter contacts, voltage, amp draw, control wiring, and

belts.

Drain and replace lubricants, including visual inspection for water and contamination.

Regrease components as needed.

Perform a general visual inspection of all components.

Perform a basic wipe-down of units.

Document all findings and submit a detailed service report.

Joint Commission Compliance: All service reports shall comply with Joint Commission standards for preventative maintenance documentation.

Equipment Tagging: All serviced units shall be tagged upon completion of maintenance.

Normal Business Hours: All work shall be conducted during normal business hours.

Scheduling: A strict schedule shall be developed and adhered to, ensuring maintenance is performed within the month scheduled to maintain Joint Commission compliance. Schedule shall be submitted to the COR 2 Weeks in advance of normal work start.

Emergency visits shall be exempted from the schedule requirements and may require off hour availability. Responding technicians are required to report on site within a 4 hour period from service call initiation.

END OF SCOPE OF WORK SECTION

Files

File Type Posted
36C24526Q0081_1.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
H365--annual medical gas testing POP: 11/20/2026 - 11/19/2031 VA Loma Linda Healthcare System 11201 Benton Street Loma Linda CA 92357 · NAICS 541380 Veterans Integrated Service Network 22 Service-Disabled Veteran-Owned Small Business
J065--Medical Gas Prevenative Maintenance and Service Albany VAMC Department of Veteran Affairs Albany Vamc Albany, New York 12208, United States · NAICS 811210 Veterans Integrated Service Network 2 No set-aside
6835--Med Gas Base Plus Four Department of Veterans Affairs Tucson VA Medical Center Tucson, Arizona 85723, United States · NAICS 325120 Veterans Integrated Service Network 22 Service-Disabled Veteran-Owned Small Business
J044--NOTICE OF INTENT TO SOLE SOURCE Baltimore VAMC Steam System Preventive Maintenance from Vicinity Energy Baltimore Corporation NAICS 561210 Veterans Integrated Service Network 5 No set-aside
Medical Gas System Activation and Bulk Oxygen Tank Services Louisville, Kentucky 40222, United States · NAICS 325120 Veterans Integrated Service Network 9 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors