H142--Fire Alarm and Sprinkler Systems Inspection (Bowling Campus) Lexington

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
36C24922Q0549
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Notice details come from SAM.gov. Updated .

Notice text

2 versions

Update #2 · Latest ·

Can you provide the fire alarm panel make and model number? Simplex TrueSite with 4000 series panels (4020, 4100, 4100ES)

Can you confirm that monthly fire extinguisher testing is included? Yes. They re inspected monthly

Can audio/visuals & Door holders be tested during normal hours? Yes

Can duct detectors be tested during normal working hours? Yes

Can elevators be tested during normal hours? Yes. Will VA coordinate for elevator contractor to be onsite during elevator recall and shunt trip testing? Yes.

Is there an incumbent contractor? Yes. Life Safety Systems. What is the previous contract number? VA249-18-C-10328

Update #1 ·

Fire Alarm and Sprinkler Systems Inspection (Bowling Campus) Lexington