The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8 is procuring air flow testing and pressure adjustment services for Operating Room #1 in Building 106 at Bay Pines VHA. The primary objective is to convert OR#1 from a positive pressure room to a negative pressure room with 100% fresh air and 100% exhausted air to accommodate bronchoscopy procedures, while ensuring that other rooms serviced by the same air handler system are not adversely affected by these modifications. The contractor must conduct pre-testing to establish baseline air flow measurements across 167 air distribution locations encompassing 37 rooms, 12 HELP grills, and 66 Phoenix air flow valves, and then perform post-adjustment testing to verify all spaces remain within specifications. The work must be completed during off-hours or weekends to minimize disruption to operating room operations. The response deadline for this Sources Sought Notice is November 7, 2025, at 2:00 PM Eastern Time.

This procurement is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses (SDVOSBC). Performance Air Balancing from Cape Coral, Florida, is identified as the sole-source contractor due to their specialized expertise with the proprietary air flow control system used in Building 106 and their prior experience conducting air flow testing and modifications in the OR suite. The specific scope involves testing 167 individual air distribution points across the second floor, requiring technical proficiency with Phoenix air flow valves and HELP grills. While no explicit award value or budget range is provided in the pre-solicitation notice, the complexity and scale of the testing work—involving multiple rooms and the requirement for both pre- and post-adjustment verification—indicates a moderately-sized facilities support services contract. The 60-day archive period for this notice suggests the procurement will move to formal solicitation following the response deadline.

Notice text

Statement of Work

Air flow testing for OR #1 in B106 at Bay Pines VHA

GENERAL

Overview

At the request of the medical service at Bay Pines there is a desired change to have Bronchoscopy procedures done in Operating Room #1 of Building 106 at Bay Pines VHA. In order to do this the room pressurization needs to be changed from being a positive pressure room to a negative pressure room, with 100% fresh air and 100% exhausted air.

It was determined by FMS staff that the infrastructure that supplies fresh air to the OR and exhaust air out of the OR can be adjusted to account for this desired change. However the valves that control the air flow that control room pressurization are a proprietary system that needs to have adjustments made by an authorized vendor for the company.

As these changes are made to one room, that is a part of an air handler system that supplies air to the entire second floor of B106, all rooms associated with that air handler need to be checked to ensure these changes did not impact other spaces.

This request is to have a pretest done to determine what the air flows (supply and return/exhaust air) are for each room before any changes are made. It will also check the air flow in each space after the change is made to this one room to ensure all rooms are still within spec.

This request is being made as a sole source to Performance Air Balancing out of Cape Coral FL. This is due the proprietary air flow system used in B106. Performance Air Balance has the knowledge to work with this system and has previous experience in the B106 OR suite testing air flows and making changes to this critical space.

Objective

To support the request to move the location where bronchoscopy procedures are done by ensuring the air pressurization of OR#1 in Building 106 at Bay Pines VHA is set properly. Also to ensure that all the other rooms in the OR suite that are serviced by the Air Handler that supports are not affected by this change.

Scope of Work

The Contractor shall

Complete a pretest and post adjustment test of 167 air distribution locations in Building 106 at Bay Pines in the OR suite on level 2. This will include the supply and return / exhaust air locations for associated with the Air handler for this floor. Included in this are at least 12 HELP grills, and 66 Phoenix air flow valves. 37 rooms will need air pressure readings taken. This work shall be done after hours or on weekends to not impact OR operations.

This phase of the testing will be completed prior to adjustments to the phoenix valves associated with OR #1. There is no order for doing these tests in terms of location or type of air flow device.

Post change testing will be immediately after phoenix representatives have completed making changes to the valves for OR#1, while they are still on site to allow for adjustments to be made if need be. The tests to be completed after the changes are made will be OR#1, supply and exhaust to confirm changes made are giving the proper results. Readings indicating that improper adjustment have been made will immediately be relayed to VHA staff to ensure feedback is given to Pheonix representatives while they are on site. Then other critical spaces in the OR suite will be checked to confirm no adverse effects as a result of the change to OR #1. Then all remaining spaces will be checked that are associated with the AHU.

Files

File Type Posted
36C24826Q0079.docx DOCX document

Similar open opportunities

Opportunity Agency Set-aside Responses due
Z2NZ--Turn Key Chiller Equipment (Purchase and Install) Pineville, Louisiana 71360, United States · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
H941--Chemical Hoods & HEPA PM Richard L. Roudebush VA Medical Center 1481 W. 10th Street Indianapolis, Indiana 46202, United States · NAICS 541620 Veterans Integrated Service Network 10 Service-Disabled Veteran-Owned Small Business
J048--NEW - Energy Center Steam Header& Boilers valves, gaskets, and vent replacement Department Of Veterans Affairs VA North Texas Health Care System Dallas TX 75216 · NAICS 238220 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business
VACCHCS Pharmacy Certification Fresno, California, United States · NAICS 541380 Veterans Integrated Service Network 21 No set-aside
Z1DA--Modernize Damen (Bldg. 1) Elevators Construction 537-24-101 Chicago, Illinois 60612, United States · NAICS 238290 Veterans Integrated Service Network 12 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors