Generator and Fuel Tank Repair and Maintenance at USCG Station Destin, FL

Closed Solicitation Posted

Solicitation number
70Z02926QNEWO000003
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Destin, Florida 32540, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The U.S. Coast Guard seeks repair and maintenance of generator and fuel tank systems at USCG Station Destin, Florida, with quotes due May 15, 2026. The procurement is a Total Small Business set-aside, firm-fixed-price construction contract awarded on a Lowest Price Technically Acceptable basis.

Place of performance is USCG Station Destin, 2000 Miracle Strip Parkway, Destin, Florida 32540. The scope includes replacement of the emergency generator battery (Kohler model GM106373, 12-volt, minimum 650 cold crank amps), replacement of muffler exhaust insulation blankets with 3-inch thick Type 1 calcium silicate rated for 1200°F, removal and disposal of abandoned underground fuel lines, rust removal and painting of the existing 1,000-gallon fuel tank using state-approved primer and polyamide epoxy topcoat, furnishing and installation of OSHA-required placards, tank tightness testing by a Florida-registered precision tank tester, installation of two ground rods per NEC standards, installation of two galvanized fuel containment pans, connection of the generator to existing automatic transfer switch and electrical panels per NEC and Kohler specifications, one-hour operational testing of the Kohler 100REOZJF generator, and 20 minutes of operator training to station personnel.

The contractor must be a Florida-licensed electrician for electrical work, employ a factory-trained Kohler representative for generator testing, and use a licensed contractor with state-approved calibrated equipment for tank pressure testing. The performance period is 30 calendar days with normal working hours Monday through Friday, 7:00 a.m. to 4:00 p.m. The contractor must perform at least 50 percent of work with its own organization and comply with Davis-Bacon prevailing wage rates. The NAICS code is 238220, Plumbing, Heating, and Air-Conditioning Contractors; PSC code is Z2EZ. Evaluation factors are price, technical acceptability, and past performance. Performance and payment bonds are required. Sealed offers must be submitted to Daniel Galarza at DANIEL.GALARZA@uscg.mil.

Notice text

2 versions

Update #2 · Latest ·

This is a combined synopsis/solicitation for construction services prepared in accordance with the format in FAR Part 36, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and no other written solicitation will be issued.

Instructions to quoters, evaluation criteria, and all applicable FAR Provisions and Clauses are attached.

Solicitation Number: 70Z02926QNEWO000003
Type: Request for Quotation (RFQ)
NAICS Code: 238220
PSC Code: Z2EZ
Set Aside: 100% Small Business
Contract Type: Firm-Fixed Price Construction Contract
Award Basis: Lowest Price Technically Acceptable (LPTA)

This will be a firm-fixed priced purchase order awarded to the lowest priced technically acceptable offer. The evaluation factors are:

- Price

- Technical Acceptability

- Past Performance

Make sure to provide your price, technical approach, and past performance with your quote.

The Government will evaluate the past performance of each offeror to determine the degree of confidence that the offeror will successfully perform the contract requirements. Evaluation will consider the relevance, quality, and timeliness of prior work as demonstrated through submitted references and independent government sources. Offerors with no relevant past performance will receive a neutral rating. Past performance will be rated and factored into the overall evaluation as specified in the solicitation.

Offerors, if they wish, can also provide information on problems encountered on the identified contracts and the offeror’s corrective actions. The Government shall consider this information, as well as information obtained from any other sources, when evaluating the offeror’s past performance. The source selection authority shall determine the relevance of similar past performance information.

SAM.gov Registration: Active account required.

Project Location:
U.S. Coast Guard Station Destin
2000 Miracle Strip Pkwy
Destin, Florida 32540

Project Description:
The United States Coast Guard is seeking quotations from qualified contractors to perform comprehensive maintenance and repair services for the generator and fuel tank system at USCG Station Destin, Destin, Florida. Work includes, but is not limited to:

  • Replacement of emergency generator battery (Kohler 100REOZJF) with specified model and connection to charger.
  • Replacement of muffler exhaust insulation blankets with 3” thick Type 1 calcium silicate and aluminum jacket.
  • Removal and disposal of abandoned underground fuel lines; capping and sealing openings.
  • Modification of fuel trough-trench and installation of piping at ground level.
  • Removal of rust and painting of the 1,000-gallon fuel tank with state-approved coating system.
  • Installation of OSHA-required placards and electrical grounding per NEC.
  • Pressure testing of primary and secondary tanks by a Florida registered precision tank tester.
  • Sealing of concrete walls/dike with state-approved elastomeric polysulfide joint sealant.
  • Installation of fuel containment pans.
  • Electrical connections between generator, ATS, and panels per NEC and manufacturer requirements.
  • Generator operational testing and informal training for station personnel.
  • Compliance with all federal, state, and local environmental, safety, and security regulations.

Performance Period: 30 calendar days from Notice to Proceed.

Site Visit:
Site visits are required prior to submitting a quote and must be scheduled with the designated point of contact below.

Point of Contact for Site Visit and COR.
MKC Daniel Flanigan
Email: Daniel.P.Flanigan@uscg.mi
Telephone: (850) 244-7147,  (315) 406-2736

Submission Instructions:
All quotes are due by 1:00pm CST on May 15, 2026. Submit quotes to: Daniel.Galarza@uscg.mil
All questions regarding this solicitation and site visit shall be submitted to the COR:Daniel.P.Flanigan@uscg.mi, Phone: (850) 244-7147 and (315) 406-2736.

Applicable Wage Determination: Florida wage determination applies.

FAR Clauses Incorporated:

  • FAR 52.236-2 Differing Site Conditions (Apr 1984)
  • FAR 52.236-3 Site Investigation and Conditions Affecting the Work (Apr 1984)
  • FAR 52.236-27 Site Visit (Construction) (Feb 1995)

Site Visit (Construction) Provision:
(a) The clauses at 52.236-2 and 52.236-3 will be included in any contract awarded as a result of this solicitation. Accordingly, quoters are urged and expected to inspect the site where the work will be performed.
(b) Site visits may be arranged during normal duty hours by contacting the POC listed above.

Additional Requirements:

  • Contractor must be licensed in the State of Florida for electrical and tank testing work.
  • All personnel must be approved and carry valid government-issued identification.
  • Contractor responsible for safety, environmental compliance, and daily cleanup.
  • Submittals required for personnel roster, schedule, safety plan, product data, and operation/maintenance manuals.

FOB Destination:
USCG Station Destin
2000 Miracle Strip Pkwy
Destin, Florida 32540

All Proposal Bids sent to Daniel.Galarza@uscg.mil

Any questions related to the Scope of Work please reach out to: 

MKC Daniel Flanigan
Email: Daniel.P.Flanigan@uscg.mi
Telephone: (850) 244-7147, (315) 406-2736

Update #1 ·

This is a combined synopsis/solicitation for construction services prepared in accordance with the format in FAR Part 36, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and no other written solicitation will be issued.

Instructions to quoters, evaluation criteria, and all applicable FAR Provisions and Clauses are attached.

Solicitation Number: 70Z02926QNEWO000003
Type: Request for Quotation (RFQ)
NAICS Code: 238220
PSC Code: Z2EZ
Set Aside: 100% Small Business
Contract Type: Firm-Fixed Price Construction Contract
Award Basis: Lowest Price Technically Acceptable (LPTA)

This will be a firm-fixed priced purchase order awarded to the lowest priced technically acceptable offer. The evaluation factors are:

- Price

- Technical Acceptability

- Past Performance

Make sure to provide your price, technical approach, and past performance with your quote.

The Government will evaluate the past performance of each offeror to determine the degree of confidence that the offeror will successfully perform the contract requirements. Evaluation will consider the relevance, quality, and timeliness of prior work as demonstrated through submitted references and independent government sources. Offerors with no relevant past performance will receive a neutral rating. Past performance will be rated and factored into the overall evaluation as specified in the solicitation.

Offerors, if they wish, can also provide information on problems encountered on the identified contracts and the offeror’s corrective actions. The Government shall consider this information, as well as information obtained from any other sources, when evaluating the offeror’s past performance. The source selection authority shall determine the relevance of similar past performance information.

SAM.gov Registration: Active account required.

Project Location:
U.S. Coast Guard Station Destin
2000 Miracle Strip Pkwy
Destin, Florida 32540

Project Description:
The United States Coast Guard is seeking quotations from qualified contractors to perform comprehensive maintenance and repair services for the generator and fuel tank system at USCG Station Destin, Destin, Florida. Work includes, but is not limited to:

  • Replacement of emergency generator battery (Kohler 100REOZJF) with specified model and connection to charger.
  • Replacement of muffler exhaust insulation blankets with 3” thick Type 1 calcium silicate and aluminum jacket.
  • Removal and disposal of abandoned underground fuel lines; capping and sealing openings.
  • Modification of fuel trough-trench and installation of piping at ground level.
  • Removal of rust and painting of the 1,000-gallon fuel tank with state-approved coating system.
  • Installation of OSHA-required placards and electrical grounding per NEC.
  • Pressure testing of primary and secondary tanks by a Florida registered precision tank tester.
  • Sealing of concrete walls/dike with state-approved elastomeric polysulfide joint sealant.
  • Installation of fuel containment pans.
  • Electrical connections between generator, ATS, and panels per NEC and manufacturer requirements.
  • Generator operational testing and informal training for station personnel.
  • Compliance with all federal, state, and local environmental, safety, and security regulations.

Performance Period: 30 calendar days from Notice to Proceed.

Site Visit:
Site visits are required prior to submitting a quote and must be scheduled with the designated point of contact below.

Point of Contact for Site Visit and COR.
MKC Daniel Flanigan
Email: Daniel.P.Flanigan@uscg.mi
Telephone: (850) 244-7147

Submission Instructions:
All quotes are due by 1:00pm CST on May 15, 2026. Submit quotes to: Daniel.Galarza@uscg.mil
All questions regarding this solicitation and site visit shall be submitted to the COR:Daniel.P.Flanigan@uscg.mi, Phone:(850) 244-7147

Applicable Wage Determination: Florida wage determination applies.

FAR Clauses Incorporated:

  • FAR 52.236-2 Differing Site Conditions (Apr 1984)
  • FAR 52.236-3 Site Investigation and Conditions Affecting the Work (Apr 1984)
  • FAR 52.236-27 Site Visit (Construction) (Feb 1995)

Site Visit (Construction) Provision:
(a) The clauses at 52.236-2 and 52.236-3 will be included in any contract awarded as a result of this solicitation. Accordingly, quoters are urged and expected to inspect the site where the work will be performed.
(b) Site visits may be arranged during normal duty hours by contacting the POC listed above.

Additional Requirements:

  • Contractor must be licensed in the State of Florida for electrical and tank testing work.
  • All personnel must be approved and carry valid government-issued identification.
  • Contractor responsible for safety, environmental compliance, and daily cleanup.
  • Submittals required for personnel roster, schedule, safety plan, product data, and operation/maintenance manuals.

FOB Destination:
USCG Station Destin
2000 Miracle Strip Pkwy
Destin, Florida 32540

All Proposal Bids sent to Daniel.Galarza@uscg.mil

Any questions related to the Scope of Work please reach out to: 

MKC Daniel Flanigan
Email: Daniel.P.Flanigan@uscg.mi
Telephone: (850) 244-7147

Files

Similar open opportunities

Opportunity Agency Set-aside Responses due
STA Sand Key Repair Fuel Lines and Tank Clearwater Beach, Florida 33767, United States · NAICS 237120 — Total Small Business
USCGC dolphin fuel tank cleaning Mobile, Alabama 36615, United States · NAICS 336611 — Total Small Business
USCG Station Lake Worth Inlet HVAC Diagnostic and Repairs Riviera Beach, Florida 33404, United States · NAICS 238220 — Total Small Business
Gas Leak Repair, Valve Installation, and Asphalt Patching Services Birmingham, Alabama 35204, United States · NAICS 237120 — Total Small Business
Midgett #2 ssdg overhaul FY27 Honolulu, Hawaii 96819, United States · NAICS 336611 — Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors