Fluid chiller
Closed Solicitation Posted
- Solicitation number
- W912CH25QA017
- Agency
- Department of the Army Department of Defense
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 333413 Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing
- Place of performance
- W4GH Ccdc Ground Vehicle Sys.6501 E 11 Mile Road Shipping And Receiving Bldg 249WARREN, MI 48397
- Points of contact
-
- Judy-Ann Lawrence judy-ann.v.lawrence.civ@army.mil (520) 672-6507
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of the Army is soliciting procurement of a fluid chiller system with specific technical requirements including 61,000 BTU/hour capacity, 1¼" NPT inlet/outlet piping, and pump specifications of 18 GPM at 38 PSI. The chiller must operate on multiple voltage configurations (230/1, 230/3, 460/3 phases) with rated load amps at 11A@460/3, maintain a 50-degree Fahrenheit outlet temperature, and include a minimum 26-gallon reservoir with a continuous duty stainless steel pump rated for at least 5 GPM. Additional requirements include non-ferrous piping, digital temperature display and control, R407c refrigerant, highly efficient scroll compressor, and capability to operate outdoors year-round. The solicitation was posted on June 9, 2025, with responses due by June 24, 2025. No specific evaluation criteria are detailed in the notice provided.
This opportunity is designated as a Total Small Business set-aside under NAICS code 333413 for Industrial and Commercial Fan and Blower and Air Purification Equipment Manufacturing. The chiller must have maximum dimensions of 42" length by 28" width by 66" height with a dry weight of approximately 760 pounds, though the footprint cannot exceed 42" x 28" and height must be less than 80 inches. The equipment must include at least a one-year parts and labor warranty and be constructed to meet all specified technical parameters. Performance will take place in Warren, Michigan. No incumbent contractors, award values, or budget ranges are specified in the solicitation notice.
Notice text
2 versions
Update #2 · Latest ·
FLUID CHILLER:61,000 BTU?s / Hr Inlet /Outlet Piping needs to be 11/4? NPT. Pump Specifications must be 18 GMP at 38 PSI. Voltage / Phase must be 230/1, 230/3, 460/3Rated load amps at 11A@460/3. Dimensions must be 42?L X 28?W X 66?H. Dry Weight must be approximately 760 lbs. Chiller outlet temp should be 50 degrees Fahrenheit. Must have at least a 26-gallon reservoir. Chiller pump must be rated for no less than 5gpm. Pump must be continuous duty and of stainless-steel construction. All piping must be non-ferrous. Shall have a footprint no larger than 42? x 28? and less than 80? in height. Shall have a digital display for temperature display and control. Shall use R407c refrigerant. Shall have a highly efficient scroll compressor. Shall include at least a 1-year parts and labor warranty. Must be rated to operate outside all year.
Update #1 ·
FLUID CHILLER:61,000 BTU?s / HrInlet /Outlet Piping needs to be 11/4? NPTPump Specifications must be 18 GMP at 38 PSIVoltage / Phase must be 230/1, 230/3, 460/3Rated load amps at 11A@460/3Dimensions must be 42?L X 28?W X 66?HDry Weight must be approximately 760 lbs.Chiller outlet temp should be 50 degrees FahrenheitMust have at least a 26-gallon reservoirChiller pump must be rated for no less than 5gpmPump must be continuous duty and of stainless-steel constructionAll piping must be non-ferrousShall have a footprint no larger than 42? x 28? and less than 80? in heightShall have a digital display for temperature display and controlShall use R407c refrigerantShall have a highly efficient scroll compressorShall include at least a 1-year parts and labor warrantyMust be rated to operate outside all year