Bldg 5 Life Safety Code Project: 544-08-107

Awarded Award Notice Posted

Solicitation number
VA-247-09-RP-0165
Agency
Veterans Integrated Service Network 7 Veterans Health Administration, Department of Veterans Affairs
Awarded
to Tat Con Group
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Contract number
VA247C0549 Federal contract award
NAICS code
236220 Commercial and Institutional Building Construction
PSC
Not on record
Place of performance
Wjbd Va Medical Center 6439 Garners Ferry Road Columbia, South Carolina 29209 USA

Notice details come from SAM.gov. Updated .

Notice text

3 versions

Update #3 · Latest ·

Added: Mar 13, 2009 3:51 pm Modified: May 01, 2009 9:28 amTrack Changes Solicitation VA247-09-RP-0165, Bldg 5 Life Safety Code Project 544-08-107, WJBD VA Medical Center is amended to extend the date for RFIs from April 28, 2009 to May 6, 2009 - 3:00 p.m. The hour and date specified for receipt of proposals is extended from May 5, 2009 2:30 p.m. to May 13, 2009 3:30 p.m. Proposal may be hand delivered, mailed, in accordance with the solicitation

Update #2 ·

Added: Mar 13, 2009 3:51 pm Modified: Apr 28, 2009 3:51 pmTrack Changes Amendment No. 1Solicitation Number: VA247-09-RP-0165

April 28, 2009

Page 2 of 3



Bldg 5 Life Safety Code



A. Below is a list of several statement/questions discussed at the pre-bid conference and submitted Requesting Information up to the above date:



Is project advertised (publically opened bids) or negotiated? Project is RFP no public bid opening proposal shall be mailed or hand delivered to the address listed in the solicitation.

Will voice communication system requirement be deleted from the fire alarm system? YES, DO NOT INCLUDE IN YOUR PROPOSAL

All third floor work to be done on nights and weekends per note on sheet AS101? YES, PLAN ACCORDINGLY; however opportunities might arise to perform during normal working hours

The VA surveyed the building for lead paint and asbestos. If lead or asbestos is found, the VA will abate. YES, GC WILL MAKE AREAS ACCESSIBLE AND ALLOW FOR TIME TO PERFORM ABATEMENT SEE 010000-7 1.6 SPEC SECTION FOR ADDITIONAL DETAILS

Notes referring to mechanical work are to be deleted. There is no mechanical work. YES, NO HVAC WORK DISREGARD

No pneumatic tube rework or new work. CORRECT

Does the VA plan to deactivate/reactivate the fire alarm each work day? YES, IF THE SPECIFIC AREA CANNOT BE ISOLATED FROM MAIN SYSTEM. THE ENTIRE SYSTEM WILL NOT BE DEACTIVATED FOR LONG PERIODS; ESP. DURING INACTIVE PERIODS OF WORK

VA will allow use of temporary utilities (power, water and toilets). YES, CORRECT

Can you provide approximate location of construction dumpster. PLAN FOR LOCATION AT WATER TOWER ADJACENT TO ENGINEERING BLDG 20 WILL BE THE FURTHEREST.

No building permit will be required. YES, CORRECT

Re-painting of reworked walls will be from corner-to-corner, not the entire room. CORRECT, IF YOU CAN PROVIDE AN ACCURATE COLOR AND TEXTURE TO MATCH EXISTING ADJACENT WALLS

The fire sprinkler drawing requires dry system coverage on the balconies. Please specify location of the air compressor and related equipment and provide electrical design for same. THE DRY SYSTEM SHOWN IS THE PORCH CEILINGS. OPEN THE INTERNET LINK OF SPRINKLER HEADS FOR DETAILS.

(http://www.vikinggroupinc.com/databook/sprinklers/dry/qrstcov/031993.pdf).



B. DISREGARD THE FOLLOWING ITEMS FROM THE BID PACKAGE:



Item #1. https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=44055&FileName=VA-247-09-RP-0165-008.PDF





Item #2.

https://www.vendorportal.ecms.va.gov/FBODocumentServer/DocumentServer.aspx?DocumentId=44056&FileName=VA-247-09-RP-0165-009.PDF





C. Drawing AS101 A1 AS101. Partial plan shows note F 1/3. There is not a note F 1/3 in the door schedule on AS601. Please Advise.

Note is a typo. Should read F1 1 hour rating



Amendment No. 1

Solicitation Number: VA247-09-RP-0165

April 28, 2009

Page 3 of 3



2. Drawing AS-101. Key notes do not have a Note #4. Per A1 AS101 Partial Plan. Please Advise.

Key note #4 used to call for card reader access. No card reader required. Disregard keynote.



3. Drawing AS-101 C6 AS101. Partial plan Note #12 is clear at the door location, but is the window to the left to be removed and a wall installed or is a structural insulated panel to take up the complete space? Please Advise.

See photo E7/AS201. Clarification: Remove door, HM frame, and sidelights only. Maintain decorative pediment and upper window and provide SIP infill @ upper window per detail E4/AS101.





4. Drawing AS601. Jamb detail C shows sanitary stop on door frames this will not give you a fire rated frame. Please Advise.

This is a boiler plate VA detail. This is not a medical use, therefore disregard sanitary stop requirement at all new doors.



D. Drawing AS 100. Key Notes #9. There are no mechanical Plans for ventilation scope and no specifications for this work. Please Advise.

Leftover note from DD mechanical venting design in projection booth. Disregard



1. Drawing AS 100. Sign Detail F^-AS100 and Key Notes # 5; is Note 5 and sign detail one in the same? If they are, please provide wording, mounting location, and number of signs required. Please advise.

Key note #5 corresponds to detail F6/AS100. See drawing D2/AS100 for sign location to be placed in vicinity of door on the corridor side. Key note 11 corresponds to detail D6/AS100. See drawing A2/AS100 for sign location to be placed in clear view and close proximity to the base of the stairs. Both signs are to have the text shown in the detail. Total of 1 sign per each note/detail.

Update #1 ·

Added: Mar 13, 2009 3:51 pm Contractor shall provide all tools, labor, materials, permits, licenses, and supervision for demolition, renovation and new construction as indicated in drawings and specifications for project located at the VA Medical Center in Columbia, SC. Work includes but is not limited to general interior alterations and expansion of existing fire alarm and sprinkler system, and minor interior demolition as required to install all systems. New finishes include: Patching, repairing, and replacing existing finishes as required to install new systems adn localized new finishes at new wall systems and ceiling systems, and hollow metal frames and doors.

Solicitation posted to FedBiz on or about April 2, 2009

Attachments

Files attached to this notice, newest first
File Type Posted
VA-247-09-RP-0165-003003.PDF PDF
VA-247-09-RP-0165-003000.DOC DOC document
VA-247-09-RP-0165-003002.PDF PDF
VA-247-09-RP-0165-003001.PDF PDF
VA-247-09-RP-0165-002000.DOC DOC document
VA-247-09-RP-0165-001000.DOC DOC document
VA-247-09-RP-0165-001001.DOC DOC document
VA-247-09-RP-0165-002.PDF PDF
VA-247-09-RP-0165-003.PDF PDF
VA-247-09-RP-0165-005.PDF PDF
VA-247-09-RP-0165-009.PDF PDF
VA-247-09-RP-0165-001.DOC DOC document
VA-247-09-RP-0165-006.PDF PDF
VA-247-09-RP-0165-010.PDF PDF
VA-247-09-RP-0165-004.PDF PDF
VA-247-09-RP-0165-000.DOC DOC document
VA-247-09-RP-0165-011.PDF PDF
VA-247-09-RP-0165-007.PDF PDF
VA-247-09-RP-0165-008.PDF PDF
Show all 19

Notice history

Notices posted for this opportunity, newest first
Notice Type Posted
Bldg 5 Life Safety Code Project: 544-08-107 Latest Award Notice
Bldg 5 Life Safety Code Project: 544-08-107 This notice · Original Award Notice

On GovTribe

Work this opportunity on GovTribe

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity