500 KVA Pad-Mounted Transformer - Seymour Johnson AFB, NC

Closed Pre-Solicitation Posted

Solicitation number
FA480926Q1829
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Goldsboro, North Carolina 27531, United States

Notice details come from SAM.gov. Updated .

About this opportunity

Air Combat Command's 4th Contracting Squadron intends to solicit a 500 KVA pad-mounted transformer for Seymour Johnson Air Force Base, North Carolina, under a total small business set-aside, with responses due by August 20, 2026.

The transformer must be three-phase oil-filled with radial feed configuration and meet detailed technical specifications provided in the attached salient characteristics document. Primary voltage is specified at 12470/7200-volt DELTA with 15 KV, 200-amp loadbreak bushing wells equipped with 15 KV 200-amp inserts, one on-off loadbreak switch, and Bay-O-Net fuses. Secondary voltage is 208/120-volt WYE with 8-hole spade terminals. Windings must be aluminum or copper if remanufactured, or aluminum if newly manufactured. The transformer must include standard operational and safety features: upper fill plug, drain valve, liquid level gauge, pressure/vacuum gauge, and automatic pressure relief valve, along with grounding provisions, three-point latching door with padlock provision, and standard ANSI green paint finish. These specifications establish minimum compliance requirements.

Performance location is Seymour Johnson Air Force Base, North Carolina. The procurement is classified under NAICS 335999 (All Other Miscellaneous Electrical Equipment and Component Manufacturing) and PSC 6120 (Transformers: Distribution and Power Station).

Notice text

4 CONS, Seymour Johnson AFB, NC, intends to post a solicitation for a 500 KVA Pad-Mounted Transformer. For specific salient characteristics, please see Attach 1 - TRANSFORMER SALIENT CHARACTERISTICS. 

Files

File Type Posted
Attach 1 - TRANSFORMER SALIENT CHARACTERISTICS.pdf PDF

Similar open opportunities

Opportunity Agency Set-aside Responses due
Switchgear Transformer Replacement 57330 Mustang Dr Bldg 42 Mcconnellafb, KS 67221, United States · NAICS 335311 Army National Guard Total Small Business
Transformer, power NAICS 334416 Naval Supply Systems Command No set-aside
Transformer, power Naval Supply Systems Command Total Small Business
CSSC Utility Feed Transformer Replacement 790 East Old Romeo Road, Lockport, IL 60441 60441 · NAICS 237130 ENDIST Chicago No set-aside
Transformer, power NAICS 333992 Aviation No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity