19GV1024Q0011 PMS-Kitchen Hood Fire Suppression System

Closed Solicitation Posted

Solicitation number
19GV1024Q0011
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
Conakry Conakry 603 Guinea

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of State is seeking contractor proposals to provide annual preventive maintenance and servicing of the kitchen hood fire suppression system at the United States Embassy in Conakry, Guinea. The contractor will be responsible for performing quarterly maintenance tasks on the ANSUL R-102 wet chemical fire suppression system, including activating detectors, verifying system operation, inspecting components, and compiling an inspection report. The work must comply with NFPA 17 standards, and the technician performing the services must be trained and certified by the manufacturer or a testing organization. Offers are due by June 13, 2024 at 10:00am local time, and the government intends to award a one-year firm-fixed-price contract based on the lowest priced, technically acceptable offer. The contract includes four one-year option periods.

This solicitation is not set-aside for any specific business category. The incumbent contractor is not identified. The government has not provided an estimated award value or budget range, but the contract is for annual preventive maintenance services at the U.S. Embassy in Conakry, Guinea.

Notice text

Preventive Maintenance Contract

Scope of Work

For

Kitchen hood fire suppression system

United States Embassy

Conakry -Guinea

2024

Exhibit A - - STATEMENT OF WORK

I.         GENERAL INFORMATION:

The United States Embassy in Conakry requires professional services and contractor cost proposals to perform annual preventive maintenance and servicing of the kitchen hood fire suppression system installed at recreation facility, NOX AID ANNEX cafeteria.

II.        PROJECT REQUIREMENTS:

                          DESCRIPTION OF EQUIPMENT: The kitchen hood fire suppression system and its equipment are*:

                                *Please see attachment at the end of this sheet for more details

  1. ANSUL wet Chemical fire suppression system

III.           GENERAL REQUIREMENTS:

The Contractor under this SOW will be responsible for labor, tools, and materials required to carry out all preventive maintenance as outlined in this SOW. Embassy staff has service manuals for kitchen hood suppression system on-site.

IV.          SCOPE OF WORK - - KITCHEN HOOD SUPPRESSION SYSTEM- PREVENTIVE MAINTENANCE

Contractor shall provide all materials, supervision, labor, tools, and equipment to perform preventive maintenance.   All personnel working in the vicinity shall wear and /or use safety protection while all work is performed.  Any questions or injuries shall be brought to the attention of the Post Occupation Safety and Health Officer (POSHO).  Material Safety Data Sheets (MSDS) shall be provided by the Contractor for all HAZMAT materials.  Copies will be provided to the COR for approval.

If any discrepancies are found with the system that are NOT covered under this scope of work, then the contractor must provide the following:

  1. Detailed report noting the discrepancy found.
  2. Bill of Materials (BOM) to include component name, quantity, part #, and price for any repair material required and material lead time.
  3. Price quote for repair labor.

SPECIFIC REQUIREMENTS:

All work shall be in conformance with NFPA 17 Wet Chemical Extinguishing Systems or NFPA 17A Dry Chemical Extinguishing Systems

At a minimum, the following work must be completed: (All tasks are to be performed quarterly unless otherwise noted)

  1. Activate one detector for each system.
  2. Verify mechanical system operation.
  3. Verify condition and operability of gas shutoff valve.
  4. Verify electrical shutoff.
  5. Inspect piping condition.
  6. Check all piping supports.
  7. Check all nozzles.
  8. Install record tags.
  9. Verify owner’s manual on site.
  10. Inspect for any changes to the cooking equipment or kitchen layout that may affect the performance and reliability of the system.
  11. Inspect and determine if hood and ducts are clean and free of grease.
  12. Inspect condition of filters
  13. Inspect and verify all detectors and nozzles are properly located.
  14. Check nozzles are correctly aimed at equipment.
  15. Compile a complete report of inspection.
  16. Clean and lubricate all mechanical linkages and accessories.
  17. The manual actuators are unobstructed.
  18. The tamper indicators and seals are intact.
  19. No obvious physical damage or condition exists that might prevent operation.
  20. The pressure gauge(s), if provided, has been inspected physically or electronically to ensure it is in the operable range.
  21. The nozzle blows off caps, where provided, are intact and undamaged.
  22. During the inspection of the hoods, grease-removal devices, fans, ducts, or other appurtenances have an accumulation of grease, such components shall be cleaned.

V. TECHNICIAN REQUIREMENTS

Technician who performs maintenance on an extinguishing system shall be trained and shall have passed a written or online test. The certificate shall be issued by the manufacturer or testing organization.







 

EQUIPMENT

MANUFACTURER

MAKE

MODEL

SPECIFICATION

LOCATION

Fire suppression system

wet chemical

Korun.com

Professional- Turkey

ANSUL

R-102

3 Gallons Liquid Agent Restaurant Fire Suppression System. Wet Chemical Extinguishing System unit 16S6.

NOX USADI Cafeteria





 






 

Files

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity