QA.docx
DOCX document 16 KB Posted
- Attached to
- Fiber Optic Cable & Wires
- Solicitation number
- WX03406Y2026T
- Issued by
-
Federal Emergency Management Agency
About this file
This is a Questions and Answers (Q&A) document that clarifies technical specifications for fiber optic cable and related communication equipment required under FEMA Region 1's solicitation for Fiber Optic Cable & Wires (WX03406Y2026T). The document addresses detailed requirements for a 24-fiber OM4 multimode armored cable with dual LC duplex connectors (UPC termination type, pre-terminated on both ends) that must be gel-filled, armored, and rated for underground/outdoor use. The cable requires a pulling eye with protective sock and must break out into 12 transmit and receive pairs at each end, connected to a standard LC 19-inch rack mountable patch panel, with specified fiber polarity ensuring pair-to-pair matching across termination points. Additionally, the Q&A specifies requirements for an 18/6C shielded communication cable with tinned copper stranded conductors, underground gel material insulation, white jacket color (or alternative options if unavailable), and a 300V voltage rating. The document also references DMP 3012 clip-on tamper switches (normally closed) as required components. These specifications support the delivery of supplies to 63 Old Marlboro Road, Maynard, MA 01754, with a proposal deadline of August 6, 2026 at 4:00 PM ET and a delivery requirement within 90 days of contract award.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2.2.1 RFQ - Fiber Optic Cables & Wires.pdf | ||
| SOW - Fiber Optic Cable - Wires.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question FEMA Response
| Delivery Zip Code |
| 01754. |
| Are LC connectors are required on both ends for the 24-fiber OM4 multimode armored cable? |
| LC connectors are required on both ends. |
| Are the required connectors LC simplex or LC duplex? |
| LC Duplex (must be compatible with standard Cisco SFP). |
| Is there a required fiber polarity or connector mapping for the 24-fiber cable? |
| Pair 1 TX/RX Pair 2 TX/RX etc… pair 1 should match to pair 1 on the opposite end pair 2 to pair 2 etc… |
| Does it need to be gel-filled? |
| Yes. Should be gel filled, armored, and underground/outdoor rated. |
| Is a pulling eye, protective pulling sock, or other pulling protection required for the pre-terminated fiber cable? |
| Yes, this should have a pulling eye with a protective sock. |
| is a required breakout or fan-out length at each terminated end? |
| Yes they must break out to the 12 transmit and receive pairs as answered in question 3 to standard LC 19-inch rack mountable patch panel. |
| Reference for the clip-on tamper switches |
| Reference DMP 3012 Clip On Tamper (normally closed). |
| What is LC the connector type for the 24-fiber OM4 Fiber Optic Cable? |
| UPC |
| Termination type |
| Dual-end pre-terminated |
| For the 18/6C Shielded Communication Cable, what is the Conductor Material? |
| Tinned Copper |
| Conductor Structure? |
| Stranded |
| Specific requirements for the insulation & Jacket material? |
| Color preferred to be white (if unable to provide white, please provide choices), Insulation = underground gel material |
| Voltage rating |
| 300v |