WTE_ECONOMIZER_PARTIAL_PANELS_Tech_Description.doc

DOC document 55 KB Posted

Attached to
Waste To Energy (WTE) Facility Economizer Partial Panels
Solicitation number
25-P-00337
Issued by
Hillsborough County, Florida

About this file

This technical specification document is for the City of Tampa's McKay Bay Waste to Energy (WTE) Facility, detailing requirements for Super Heat/Economizer Partial Panels. The project involves procuring 120 partial panels for municipal solid waste incinerators, with specific fabrication requirements including 1" O.D. x .165" MWT SA210-A1 boiler tubes to be supplied by the bidder. The tubes must be fabricated in accordance with ASME Pressure Vessel Code Section - 1 (2019 Edition), with tube ends beveled, painted with Deoxyaluminate, and capped.

Delivery terms specify FOB delivery to the McKay Bay WTE Facility at 107 North 34th Street, Tampa, FL 33605, with deliveries permitted between 7:00 AM and 3:00 PM on normal working days. Bidders are required to provide manufacturer certifications, P4 forms, and include all applicable freight and fuel surcharges in their pricing. The bid response form allows vendors to quote a unit price for the 120 Super Heat/Economizer Partial Panels, with the expectation that all transportation charges will be prepaid by the supplier.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL SPECIFICATIONS

MCKAY BAY WASTE TO ENERGY (WTE) SUPER HEAT/ECONOMIZER PARTIAL PANELS

8.

GENERAL CONDITIONS

The material to be provided under this specification shall be Super Heat/Economizer Partial Panels for use in the McKay Bay WTE Facility, and shall meet the requirements contained within these specifications.

9.

PRODUCT SPECIFICATIONS

9.1 Fabricate Partial Panels (Long Leg) See Attached Drawing:

9.1.1 1 ½” O.D. X .165” MWT SA210-A1 Boiler Tube to be supplied by the bidder.

9.1.2 Fabricate super heat/economizer partial panels with tube supplied by the bidder.

9.1.3 Tube ends will be beveled 37-1/2 degrees, painted with Deoxyaluminate, and capped.

9.1.4 All materials will come with certifications per ASME code, all fabrication to be in accordance with ASME Pressure Vessel Code Section – 1 (Power Boilers), 2019 Edition

9.1.5 All required P4 forms will be supplied by the bidder.

10.

MANUFACTURER

The Bidder shall state, in its bid, the name of the manufacturer of the boiler tube the Bidder intends to supply.

11.

PURCHASE AND DELIVERY

11.1 Deliveries shall be made between 7:00 AM and 3:00 PM on normal working days (Monday through Friday) or as otherwise approved by the McKay Bay WTE Facility representative.

11.2 Delivery shall be made, FOB Tampa, to the City of Tampa McKay Bay WTE Facility, 107 North 34th Street, Tampa, FL 33605.

12.

BID PRICES

12.1 The price quoted must include all applicable freight charges and fuel surcharges.

BID RESPONSE FOR

MCKAY BAY WASTE TO ENERGY (WTE) SUPER HEAT/ECONOMIZER PARTIAL PANELS

Please Print or Type We the undersigned, as Bidders, hereby declare that we have carefully read this proposal or bid and the provisions, terms and conditions concerning the equipment, materials, supplies or services as called for, and with full knowledge and understanding of the requirements and conditions, do hereby agree to furnish and to deliver as indicated, FOB, McKay Bay WTE Facility, 107 North 34th Street, Tampa, FL, 33605, with all transportation charges prepaid, and for the prices quoted thereon as follows.

QTY

UNIT

DESCRIPTION

UNIT PRICE TOTAL PRICE

Each

Super Heat/Economizer Partial Panels

PAGE

File details come from the government source that posted it. Updated .